HomeMy WebLinkAboutordinance.council.037-11 ORDINANCE NO. 37
(Series of 2011)
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF ASPEN,
COLORADO, AMENDING SECTIONS 11.04.020 AND 11.04.030 OF
THE ASPEN MUNICIPAL CODE, ADOPTING BY REFERENCE THE
INTERNATIONAL FIRE CODE, 2009 EDITION, AMENDING CERTAIN
SECTIONS OF SAID CODE, AND REPEALING SECTIONS OF THE
MUNICIPAL CODE INCONSISTENT THEREWITH.
WHEREAS, the City Council desires to adopt, for the benefit of the City of Aspen, the
2010 edition of the International Fire Code, to repeal existing fire code provisions, and
implement recommended changes to the 2090 edition.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF
THE CITY OF ASPEN, COLORADO, THAT:
Section 1
That Section 11.04.020 of the Municipal Code of the City of Aspen, Colorado, is hereby repealed and
reenacted to read as follows:
11.04.020 Adoption of the International Fire Code.
Pursuant to the power and authority conferred by the laws of the State of Colorado and the
Charter of the City of Aspen, Colorado, it is hereby adopted as the fire code of the City of Aspen,
Colorado, by reference thereto, the International Fire Code, 2009 edition, including the appendix,
except Sections A, E, F and G of said appendix of such code published by the International Code
Council Inc. 4051 West Flossmoor Road, Country Club Hills, Illinois, 60478 -5795 all to have the
same force and effect as though set forth herein in every particular.
Section 2
That Section 11.04.030 of the Municipal Code of the City of Aspen, Colorado, is hereby
repealed and reenacted to read as follows:
Sec.11.04.030 Amendments.
The International Fire Code herein adopted shall be amended as follows:
Sec.. 101.1 Title.
These regulations shall be known as the Fire Code of the Aspen Fire Protection District,
hereinafter referred to as "this code."
Sec. 102.8 Subjects not regulated by this code.
Where no applicable standards or requirements are set forth in this code, or are contained
within other laws, codes, regulations, ordinances or bylaws adopted by the jurisdiction,
compliance with the most current applicable standards of the National Fire Protection Association
or other nationally recognized fire safety standards, as approved, shall be deemed as prima facie
evidence of compliance with the intent of this code. Nothing herein shall derogate from the
authority of the fire code official to determine compliance with codes or standards for those
activities or installations within the fire code official's jurisdiction or responsibility.
Exception: When that current cycle is less than a year from the previous cycle, the
previous cycle may be used with the approval of the fire code official.
Sec.102.9 Matters not provided for.
Requirements that are essential for the public safety of an existing or proposed activity,
building or structure, or for the safety of the occupants thereof, which are not specifically
provided for by this code shall be determined by the fire code official. The most current NFPA
code cycle or other nationally recognized fire safety standards, as approved shall be utilized.
Exception: When that current cycle is less than a year from the previous cycle, the
previous cycle may be used with the approval of the fire code official.
Sec. 103.2 Appointment.
The fire code official shall be appointed by the chief appointing authority of the
jurisdiction; and the fire code official shall not be removed from office except for cause and after
full opportunity to be heard on specific and relevant charges by and before the appointing
authority. For the purposes of this code the term fire code official there may be inserted fire
marshal.
Sec. 104.6.3 Fire records.
The fire department shall keep a record of fires occurring within its jurisdiction and of facts
concerning the same, including statistics as to the extent of such fires and the damage caused
thereby, together with other information as required by the fire code official. Copies of all such
records shall be forwarded to the office of the fire marshal.
Sec. 104.10 Fire investigations.
The fire code official, the fire chief or other responsible authority shall have the authority
to investigate the cause, origin and circumstances of any fire, explosion or other hazardous
condition. Information that could be related to trade secrets or processes shall not be made part of
the public record except as directed by a court of law.
Sec.108.1 Board of appeals.
Appeals shall be in accordance with Section 8.08 of the Municipal Code of the City of
Aspen or Section Title 11 sec 04.040.112.1 of the Pitkin County Code.
2
Sec. 109.2.2 Compliance with orders and notices.
A notice of violation issued or served as provided by this code shall be complied with by the
owner, operator, occupant or other person responsible for the condition or violation to which the notice of
violation pertains.
(1) If the building or other premises is owned by one person and occupied by another, under
lease or otherwise, and the notice of violation requires additions to or changes in the
building or premises such as would be considered real estate and become the property of
the owner, said notice and order shall be directed to such owner of the building or
premises.
(2) Every notice of violation pursuant to this chapter shall set forth a time by which
compliance with the notice violation is required. The time specified shall be reasonable
according to the circumstances of the particular hazards or condition to which the notice
and order pertains. Immediate compliance may be required in any case which represents
extreme or imminent danger to persons or property.
(3) Except for cases where immediate compliance is required, violations pursuant to this
chapter may be appealed as set forth in Section 108.1.
(4) In cases where immediate compliance is required, the notice of violation so stating shall
be final and conclusive.
(Sec. 202 General Definitions.
"Guest" shall mean any person hiring or occupying a room or bed for living or
sleeping purposes.
Section 202 General Definitions.
"Street" shall mean any thoroughfare, alley or public space not less than sixteen (16) feet
in width which has been dedicated or deeded to the public for public use.
Sec. 307.1.1 Prohibited open burning.
Open burning that is offensive or objectionable because of smoke emissions or when atmospheric
conditions or local circumstances make such fires hazardous shall be prohibited. from May 31 to
October 1.
Exception:
Open burning may be permitted or prohibited at any time when in the opinion
of the fire code official the atmospheric conditions are conducive for safe
burning.
Sec. 308.3 Group A occupancies.
Open -flame devices shall not be used in a Group A occupancy.
Exceptions:
I. Open -flame devices are allowed to be used in the following situations, provided
approved precautions are taken to prevent ignition of a combustible material or injury to
occupants:
1.1. Where necessary for ceremonial or religious purposes in accordance with
Section 308.1.7.
1.2. On stages and platforms as a necessary part of a performance in accordance
with Section 308.3.2.
3
1.3. Where candles on tables are securely supported on substantial
noncombustible bases and the candle flames are protected.
2. Heat - producing equipment complying with Chapter 6 and the International
Mechanical Code.
3. Gas lights are allowed to be used provided adequate precautions satisfactory to the fire
code official are taken to prevent ignition of combustible materials.
4. The use of indoor pyrotechnic displays in a Group A occupancy shall be
prohibited.
Exceptions:
Indoor pyrotechnics shall be permitted if all the following
conditions are met:
(1) A permit shall be issued for each display.
(2) The building is fully equipped with an approved fire sprinkler
system.
(3) The building is fully equipped with an approved and
monitored fire alarm system.
(4) The display is handled and performed by a certified
pyrotechnician, possessing a valid certificate issued by the State
of Colorado.
(5) There are at least two standby personnel equipped with the
appropriate fire extinguisher and familiar in the use of that fire
extinguisher.
(6) A safety plan is filed and approved by the Fire Marshal's
office.
(7) In accordance with NFPA 160 and NFPA 1126
Sec. 308.3.2 Theatrical performances.
Where approved, openflame devices and pyrotechnic devices used in conjunction with theatrical
performances are allowed to be used when the following conditions are met:
(1) A permit shall be issued for each display.
(2) The building is fully equipped with an approved fire sprinkler system
(3) The building is fully equipped with an approved and monitored fire alarm
system
(4) The display is handled and performed by a certified pyrotechnician,
possessing a valid certificate issued by the State of Colorado
(5) There are at least two standby personnel equipped with the appropriate fire
extinguishers and familiar in the use of that fire extinguisher.
(6) A safety plan is filed and approved by the Fire Marshal: s office.
(7) In accordance with NFPA 160 and NFPA 1 126
Sec. 310.9 Hotels, motels, rooming or lodging houses.
It shall be unlawful for any person to cause a fire through the use or misuse of tobacco in
any form or of matches or lighters used in connection therewith, in any hotel, motel, rooming
or lodging house. All managers or operators of hotels, motels, rooming or lodging houses
shall post in a conspicuous place within such hotel, motel, rooming or lodging house a copy
of Section 310.9 along with the penalty imposed for such violation. Any person violating said
4
section shall be guilty of a misdemeanor. Such posting shall be done at no expense to the
City.
Sec. 507.5.4.1 Snow removal.
Snow removal operations shall not prevent fire hydrants from being immediately
discernible or hinder gaining immediate access.
Sec. 903.2 Where required.
Approved automatic sprinkler systems in new buildings and structures shall be provided in the
locations described in Sections 903.2.1 through 903.2.14.
Exception:
Spaces or areas in telecommunications buildings used exclusively for
telecommunications equipment, associated electrical power distribution equipment,
batteries
and standby engines, provided those spaces or areas are equipped throughout with an
automatic smoke detection system in accordance with Section 907.2 and are separated
from the remainder of the building by not less than 1 -hour fire barriers constructed in
accordance with Section 707 of the International Building Code or not less than 2 -hour
horizontal assemblies constructed in accordance with Section 712 of the International
Building Code, or both.
Sec. 903.2.13 R -1, R -2.
Every apartment house, town house, lodging house, dormitory, convent, monastery,
rooming house, condominium or hotel two stories or more in height and containing four or more
dwelling units shall have installed therein an approved automatic sprinkler system throughout the
premises. Fire separations shall not constitute separate buildings for this purpose. This includes
all R -3 occupancies.
Sec. 903.2.14 One and two family dwellings and auxiliary buildings.
Any residential occupancy or auxiliary building, including attached garages, in excess of
5,000 square feet or in a location that is difficult to access as determined by the fire code official,
shall be equipped with an approved automatic fire sprinkler system including the installation of a
fire department connection.
For residential automatic fire sprinkler systems a minimum of a three sprinkler head hydraulic
calculation shall be submitted for approval, a larger number of sprinkler head calculation may be
required depending on the structural design. Fire separations shall not constitute separate
buildings for this purpose. This is includes all R -3 occupancies
Sec. 903.4 Sprinkler system supervision and alarms.
All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water
levels and temperatures, critical air pressures and water -flow switches on all sprinkler systems shall be
electrically supervised by a listed fire alarm control unit.
Automatic sprinkler systems protecting one, two or multiple family dwellings that are not
monitored shall operate in the following manner:
(1) All water flow activations shall be capable of sounding an interior audible alarm
notifying all occupants simultaneously.
5
(2) All water flow activations shall be capable of activating an exterior audible /visual
alarm. This alarm shall be located so as to be visible from the nearest fire department
access road. A second visual device may be required to delineate the fire department
connection.
(3) The activation of any water control device shall be capable of activating the light
portion only of the exterior audible /visual signal.
Exceptions:
1. Limited area systems serving fewer than 20 sprinklers.
3. Jockey pump control valves that are sealed or locked in the open position.
3. Control valves to commercial kitchen hoods, paint spray booths or dip tanks
that are sealed or locked in the open position.
4. Valves controlling the fuel supply to fire pump engines that are sealed or
locked in the open position.
5. Trim valves to pressure switches in dry, pre- action and deluge sprinkler
systems that are sealed or locked in the open position.
Sec. 903.4.2 Alarms.
Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler
water -flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the
smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building
in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system
shall actuate the building fire alarm system.
For one and two family dwelling and R -3 occupancies: Interior audible water flow
signals capable of notifying all occupants simultaneously shall be provided. A visual and audible
water flow alarm shall be installed on the exterior of the building. This alarm shall be located so
as to be visible from the nearest fire department access road. A second visual device may be
required to delineate the fire department connection. Where the R -3 occupancy is a duplex,
triplex or greater, audible alarms shall notify all of the occupants simultaneously upon a water
flow activation. Exterior visual and audible alarms shall activate on the unit of origin only.
Sec. 906.1 Where required.
Portable fire extinguishers shall be installed in the following locations.
I . In new and existing Group A, B, E, F, 1-I, I , M, R -1, R -2, R -4 and S occupancies.
2. Within 30 feet (9144 mm) of commercial cooking equipment.
3. In areas where flammable or combustible liquids are stored, used or dispensed.
4. On each floor of structures under construction, except Group R -3 occupancies, in
accordance with Section 1415.1.
5. Where required by the sections indicated in Table 906.1.
6. Special - hazard areas, including but not limited to laboratories, computer rooms and
generator rooms, where required by the fire code official.
Sec. 907.1.4 Designer requirements.
All plans for fire alarm systems submitted for approval shall have affixed the signature of
a NICET Level 3 or higher in the field of fire alarm design.
Exception:
Where the fire alarm system designer has the equivalent of NICET Level 3
training, all certificates and documentation shall be presented for compliance.
Sec. 907.1.5 Installer requirements.
6
All fire alarm system installations shall be supervised by a person having a NICET Level
2 or higher in the field of fire alarm installation.
Exception:
Where the fire alarm system installer has the equivalent of NICET Level
2 training, all certificates and documentation shall be presented for compliance.
Sec. 907.1.6 Required types of systems.
All fire alarm systems required by this code shall be addressable, analog systems.
Exception:
With the approval of the Fire Marshal a conventional system may be
used if that system is used only to monitor a fire sprinkler system.
Sec. 907.2.1 Group A.
A manual and automatic fire alarm system that activates the occupant notification system in
accordance with Section 907.6 shall be installed in Group A occupancies having an occupant load of 100
or more. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire
alarm system as required for the Group E occupancy
Sec. 907.2.2 Group B.
A manual and automatic fire alarm system shall be installed in Group B occupancies where one of
the following conditions exists:
1. The combined Group B occupant load of all floors is 100 or more.
2. The Group B occupant load is more than 50 persons above or below the lowest
level of exit discharge.
3. The Group B fire area contains a Group B ambulatory health care facility
Sec. 907.2.3 Group E.
A manual and automatic fire alarm system that activates the occupant notification system in
accordance with Section 907.6 shall be installed in Group E occupancies. When automatic sprinkler
systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire
alarm system.
Exceptions:
1. A manual fire alarm system is not required in Group E occupancies with an occupant
load of less than 50.
2. Manual fire alarm boxes are not required in Group E occupancies where all of the
following apply:
2.1. Interior corridors are protected by smoke detectors.
2.2. Auditoriums, cafeterias, gymnasiums and similar areas are protected by heat
detectors or other approved detection devices.
2.3. Shops and laboratories involving dusts or vapors are protected by heat detectors or
other approved detection devices.
2.4. The capability to activate the evacuation signal from a central point is provided.
2.5. In buildings where normally occupied spaces are provided with a two -way
communication system between such spaces and a constantly attended receiving station
7
from where a general evacuation alarm can be sounded, except in locations specifically
designated by the fire code official.
2.6 Where the building is equipped throughout with an approved automatic
sprinkler system and the alarm notification devices will activate upon sprinkler
water flow. Where the building is equipped throughout with an approved
automatic sprinkler system and the alarm notification devices will activate upon
sprinkler water flow and manual activation is provided from a normally occupied
location.
Sec. 907.2.7 Group M.
A manual and automatic fire alarm system that activates the occupant notification system in accordance
with Section 907.6 shall be installed in Group M occupancies where one of the following conditions exists:
1. The combined Group M occupant load of all floors is
500 or more persons.
2. The Group M occupant load is more than 100 persons
above or below the lowest level of exit discharge.
Exceptions:
I. A manual fire alarm system is not required in covered mall buildings
complying with Section 402 of the International Building Code
Sec. 907.2.8.1 Manual fire alarm system.
A manual fire alarm system that activates the occupant notification system in accordance with
Section 907.6 shall be installed in Group R -I occupancies.
Sec. 907.2.8.2 Automatic smoke detection system.
An automatic smoke detection system that activates the occupant notification system in
accordance with Section 907.6 shall be installed throughout all interior corridors serving sleeping
units.and in all common areas, laundry rooms, and mechanical rooms.
Sec. 907.2.9 Where required.
Every apartment house, town house, lodging house, dormitory, convent, monastery,
rooming house, condominium or hotel two stories or more in height and containing four or more
dwelling units shall have installed therein an approved automatic and manually operated fire
alarm system so designed that all occupants of the building may be warned simultaneously. Fire
alarm systems shall be installed in accordance with I.F.C. Section 907.2 and nationally
recognized standards. Fire separations shall not constitute separate buildings for this purpose.
This includes all R - occupancies other than single family dwellings.
Sec. 907.2.9.1 Manual fire alarm system.
A manual fire alarm system that activates the occupant notification system in accordance with
Section 907.6 shall be installed in Group R - occupancies where they are two stories or more in
height and containing four or more dwelling units
8
Sec. 907.6.2.2.5 Interior alarms.
An inside audible alarm is to be installed whenever an alarm is required by Chapter 9 of
the International Fire Code and Chapter 9 of the International Building Codes. In the case of
public assembly areas with an occupant load of one hundred (100) or more persons or where, in
the opinion of the Building Official or the Fire Marshal, the installation of an inside alarm may
result in creating panic, the alarm signal shall be installed in an attended area (e.g. projection
booth, manager's office) from where there can be effectuated an orderly evacuation of the
assembly area pursuant to the system approved by the Building Official or Fire Marshal.
Sec. 907.6.2.3.1.2 Exterior visual requirements.
The exterior visual signals shall meet the following requirements:
(l) The light used shall be of the strobe type producing at least one million candle power,
or incandescent flashing type which can be plainly seen for at least 1,500 feet in all
directions of approach.
(2) Lights are to be red in color for systems equipped with a fire department connection
and yellow in color for systems not having a fire department connection.
(3) In systems with fire department connections the light is to be located at least 12ft.
above and as directly vertical to the fire department connection as possible. In systems
without fire department connections the light is to be located so as to be visible from the
nearest street.
(4) A sign with the words "Fire, Call Fire Department" (black on a white background and
large enough to be visible from the center of the adjacent street) shall be mounted
directly above the Tight.
(5) The light shall not replace the audible alarms but is to be used in conjunction with it.
(6) The visual and audio signal shall be together on a circuit separate from all others
except exit signs.
Sec. 913.4 Valve supervision.
Where provided, the fire pump suction, discharge and bypass valves, and the isolation valves on
the backflow prevention device or assembly shall be supervised open by one of the following methods:
1. Central- station, proprietary or remote - station signaling service.
2. Local signaling service that will cause the sounding of an audible signal at a constantly attended
location.
3. Sealing of valves and approved weekly recorded inspection where valves are located within
fenced enclosures under the control of the owner.
Sec. 1008.1.9.10 Stairway doors.
Interior stairway means of egress doors shall be openable from both sides without the use of a key
or special knowledge or effort.
Exceptions:
I. Stairway discharge doors shall be openable from the egress side and shall
only be locked from the opposite side.
2. This section shall not apply to doors arranged in accordance with Section
403.5.3 of the International Building Code.
3.In stairways serving not more than two stories, doors are permitted to
be locked from the side opposite the egress side, provided they are
openable from the egress side and capable of being unlocked
simultaneously without unlatching upon a signal from the fire command
9
center, if present, or a signal by emergency personnel from a single
location inside the main entrance to the building.
Sec. 1028.12 Seat stability.
In places of assembly, the seats shall be securely fastened to the floor.
Exceptions:
1. In places of assembly or portions thereof without ramped or tiered floors for
seating and with 75 or fewer seats, the seats shall not be required to be fastened
to the floor.
2. In places of assembly or portions thereof with seating
at tables and without ramped or tiered floors for seating,
the seats shall not be required to be fastened to the floor.
3. In places of assembly or portions thereof without ramped or tiered floors for
seating and with greater than 75 seats, the seats shall be fastened together in
groups of not less than three or the seats shall be securely fastened to the floor.
4. In places of assembly where flexibility of the seating arrangement is an
integral part of the design and function of the space and seating is on tiered
levels, a maximum of 75 seats shall not be required to be fastened to the floor.
Plans showing seating, tiers and aisles shall be submitted for approval.
5. Groups of seats within a place of assembly separated from other seating by
railings, guards, partial height walls or similar barriers with level floors and
having no more than 14 seats per group shall not be required to be fastened to
the floor.
6. Seats intended for musicians or other performers and separated by railings,
guards, partial height walls or similar barriers shall not be required to be
fastened to the floor.
Sec. 2204.3 Unattended self - service motor fuel dispensing facilities.
Unattended self - service motor fuel dispensing facilities shall comply with Sections 2204.3.1
through 2204.3.7. A safety plan and safety equipment technical data shall be submitted for review
prior to approval. Unsupervised private dispensing shall be by permit only.
Sec. 3301.1.3 Fireworks.
The possession, manufacture, storage, sale, handling and use of fireworks are prohibited.
Exceptions:
I . Storage and handling of fireworks as allowed in Section 3304.
2. Manufacture, assembly and testing of fireworks as allowed in Section 3305.
3. The use of fireworks for fireworks displays as allowed in Section 3308.
4. The possession, storage, sale, handling and use of specific types of Division
1.4G fireworks where allowed by applicable laws, ordinances and regulations,
provided such fireworks comply with CPSC 16 CFR, Parts 1500 and 1507, and
DOTn 49 CFR, Parts 100 -185, for consumer fireworks.
5. The storage, sale, use and handling of toy caps, sparklers and smoke
snakes shall be permitted.
Sec. 3301.2.4 Financial responsibility.
Before a permit is issued, as required by Section 3301.2, the applicant shall file with the
City of Aspen or Pitkin County a corporate surety bond in a principal sum equal to the amount
required by the Colorado state statutes, Pitkin County, or the City of Aspen, of persons engaging
10
in similar activities, or a public liability insurance policy for the same amount, for the purpose of
the payment of all damages to persons or property which arise from, or are caused by, the conduct
of any act authorized by the permit upon which any legal judgment results. The fire code official
may specify a greater or lesser amount when, in his opinion, conditions at the location of use
indicate a greater or lesser amount is required. Public agencies shall be exempt from this bond
requirement
Sec. 3301.4 Qualifications.
Persons in charge of magazines, blasting, fireworks display or pyrotechnic special effect
operations shall not be under the influence of alcohol or drugs which impair sensory or motor
skills, shall be at least 21 years of age and shall demonstrate knowledge of all safety precautions
related to the storage, handling or use of explosives, explosive materials or fireworks.
The handling and firing of explosives shall only be performed by the person possessing a valid
explosives certificate issued by the State of Colorado.
Sec. 3304.10.8 Storage exceeding 50 lbs.
Storage of explosives in quantities exceeding fifty (50) pounds shall be in a Type I
magazine, except that a Type 3 magazine may be used for temporary storage of a larger quantity
of explosives at the site of blasting operations where such amount constitutes not more than one
day's supply for use in current operations. At the end of the day's operations any remaining
explosives shall be safely destroyed or returned to a Type 1 magazine.
Sec. 3304.10.9 Storage less than 50 lbs.
Storage of explosives in quantities of fifty (50) pounds or less shall be in Type I or Type
II magazine, except that explosives in any quantity when stored in remote locations shall be in
Type I, bullet resistant magazines.
Sec. 3308.1.2 Indoor pyrotechnic displays
The use of indoor pyrotechnic displays shall be prohibited.
Exception:
Indoor pyrotechnics shall be permitted if all the following conditions
are met:
(1) A permit shall be issued for each display.
(2) The building is fully equipped with an approved fire sprinkler system
(3) The building is fully equipped with an approved and monitored fire
alarm system
(4) The display is handled and performed by a certified pyrotechnician
and possessing a valid certificate issued by the State of Colorado
(5) There are at least two standby personnel equipped with the
appropriate fire extinguisher and familiar in the use of that fire
extinguisher.
(6) A safety plan is filed and approved by the Fire Marshal's office
(7) In accordance with NFPA 160 and NFPA 1126.
11
Sec. 3404.2.13.2.4 Above - ground tanks.
Hereafter no tank for the storage of flammable fluid in excess of ten (10) gallons shall be
erected, repaired, renewed or replaced either wholly or partially above ground. Where in the
opinion of the fire code official an existing tank constitutes a fire hazard through neglect or
disrepair, he shall order such tank removed; however, tanks or other facilities for the storage of
Class 6 fuel oil may be installed above ground if approved by the fire code official and in
accordance with existing codes and regulations pertaining to above ground storage.
Sec. 3406.2.4 Capacity limits.
The capacity of permanent above - ground tanks containing Class I or 11 liquids shall not
exceed 1,100 gallons (4164 L). The capacity of temporary above -tanks containing Class I or 11 liquids
shall not exceed 500 gallons (1892 L). Tanks shall be of the single - compartment design.
A permit shall be obtained from the Fire Marshal for the storage or keeping of volatile inflammable
fluids in excess of five (5) gallons in any building and often (10) gallons on any premises. The Fire
Marshal is further authorized to issue temporary permits for the above ground storage of such fluids
in tanks which shall not exceed a five hundred (500) gallon capacity for the purpose of providing fuel
for heavy equipment used in building construction, earth moving, earth grading or similar operations
and such permits may be issued only for sites where there are not close hazards. Such temporary
permits shall be issued with the time limits set which shall conform to the reasonably necessary time
for completion of the individual job for which the permit is issued.
Sec. 3406.6.1.12 Delivery hose length.
The maximum length of the delivery hose used to connect the tank vehicles being filled
shall not exceed twenty (20) feet.
Sec. 3406.6.1.13Delivery vehicle capacity.
Tank delivery vehicles used for the delivery of flammable liquids as defined in this
article, having an aggregate capacity in excess of one thousand five hundred (1,500) gallons shall
be equipped with a single cargo tank mounted thereon, self - propelled and of the diesel powered
type.
Sec. 3406.6.1.14 Delivery vehicle single compartment capacities.
It shall be unlawful for any motor vehicle having a tank capacity in excess of five
thousand (5,000) gallons aggregate, or with any one compartment thereof in excess of two
thousand five hundred (2,500) gallon individual capacity, to deliver flammable liquids to any
place of storage within the corporate limits of the city.
Sec. 3406.6.1.15 Delivery periods.
It shall be unlawful for any motor vehicle transporting flammable liquids in excess of
five thousand (5,000) gallons, or any motor vehicle transporting LP gas in excess of two
thousand five hundred (2,500) gallons liquid, or any vehicle transporting explosives and other
12
dangerous articles, to remain within the city for a period exceeding one hour, unless as provided
herein.
Sec. 3406.6.1.16 Noncompliant motor vehicles.
It shall be unlawful for any motor vehicle other than a tank delivery vehicle as
defined herein to deliver flammable liquids, LP gas, or other dangerous articles to any place of
storage within the corporate limits of the city
Sec. 3803.4 Multiple LP -gas container installations.
Multiple LP -gas container installations with a total water storage capacity of more
than 180,000 gallons (681 300 L) [150,000- gallon (567 750 L) LP -gas capacity] shall be subdivided into
groups containing not more than 180,000 gallons (681 300 L) in each group. Such groups shall be separated
by a distance of not less than 50 feet (15 240 mm), unless the containers are protected in accordance with
one of the following:
1. Mounded in an approved manner.
2. Protected with approved insulation on areas that are subject to impingement of ignited
gas from pipelines or other leakage.
3. Protected by firewalls of approved construction.
4. Protected by an approved system for application of water as specified in Table 6.4.2 of
NFPA 58.
5. Protected by other approved means.
Where one of these forms of protection is provided, the separation shall not be less than 25 feet (7620 mm)
between LP - gas container groups It shall be unlawful for any motor vehicle having a tank capacity
in excess of two thousand five hundred (2,500) gallons liquid capacity to deliver LP gas to any
place of storage within the corporate limits of the city.
Sec. 3803.5 Noncompliant vehicles.
It shall be unlawful for any motor vehicle other than a tank delivery vehicle as defined
herein to deliver flammable liquids, LP gas, or other dangerous articles to any place of storage
within the corporate limits of the city.
Sec. 4603.6 Fire alarm systems.
An approved fire alarm system shall be installed in existing buildings and structures in
accordance with Sections 4603.6.1 through 4603.6.7 and provide occupant notification in
accordance with Section 907.6 unless other requirements are provided by other sections of this
code. All fire alarm systems shall be installed and in operation within one year of notification by
the fire prevention bureau.
Sec. 4603.6.5.1 Group R - hotel and motel manual fire alarm system.
A manual fire alarm system that activates the occupant notification system in
accordance with Section 907.6 shall be installed in existing Group R -1 hotels and motels two
stories or more in height and with four or more dwelling units.
Sec. 4603.6.5.1.1 Group R -1 hotel and motel automatic smoke detection system.
13
An automatic smoke detection system that activates the occupant notification system in
accordance with Section 907.6 shall be installed in existing Group R -1 hotels and motels
throughout all interior corridors serving sleeping rooms.
4603.6.6 Group R - 2.
An automatic and manual fire alarm system that activates the occupant notification system
in accordance with Section 907.6 shall be installed in existing Group R - a occupancies two
stories or more in height and containing four or more dwelling or sleeping units. Fire alarm
systems shall be installed in accordance with I.F.C. Section 907.2 and nationally recognized
standards. Fire separations shall not constitute separate buildings for this purpose.
Sec. 4604.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises'
electrical supply. In the event of power supply failure, illumination shall be automatically provided from an
emergency system for the following occupancies where such occupancies require two or more means of
egress:
1. Group A having 50 or more occupants.
Exception: Assembly occupancies used exclusively as a place of worship and having an
occupant load of less than 300.
2. Group B occupancies with 100 or more total occupants. For high -rise buildings and
smoke proof enclosures, see the Building Code. Emergency systems shall be supplied
from storage batteries or an on -site generator set and the system shall be installed in
accordance with the requirements of the Electrical Code
3. Group E in interior stairs, corridors, windowless areas with student occupancy, shops and
laboratories.
4. Group F having more than 100 occupants.
Exception: Buildings used only during daylight hours
which are provided with windows for natural light in
accordance with the International Building Code.
5. Group 1.
6. Group M.
Exception:
Buildings less than 3,000 square feet (279m2) in gross sales area on one story
only, excluding mezzanines.
7. Group R -1.
Exception:
Where each sleeping unit has direct access to the outside of the building at
grade.
8. Group R -2.
Exception:
Where each dwelling unit or sleeping unit has direct access to the outside of the
building at grade.
9. Group R -4.
Exception:
Where each sleeping unit has direct access to the outside of the building at
ground level.
14
Section 3
That the International Fire Code, 2009 edition, hereinabove adopted by reference is to govern the
maintenance of buildings and premises; to safeguard life, health, property and public welfare by
regulating the storage, use and handling of dangerous and hazardous materials, substances and
processes and by regulating the maintenance of adequate egress facilities.
Section 4
That three copies of the primary code and secondary code being considered for adoption by this
ordinance, all certified to be true copies by the Mayor and City Council, shall be on file with the
City Clerk and shall be open for public inspection in her office at the Aspen City Hall, Aspen,
Colorado, any weekday between the hours of 9 a.m. and 5 p.m., at least fifteen days preceding the
public hearing on this ordinance.
Section 5
That on passage of this ordinance and adoption of this code by reference, one copy of the Code
may be kept in the office of the chief enforcement officer instead of in the office of the City
Clerk. Following the adoption of this code, the City Clerk shall at all times maintain a reasonable
supply of copies of the code available for purchase by the public.
Section 6
Existing ordinances or parts of ordinances covering the same matters as embraced in this
ordinance are hereby repealed and all ordinances or parts of ordinances inconsistent with the
provisions of this ordinance are hereby repealed, except that this repeal shall not affect or prevent
the prosecution or punishment of any person for any act done or committed in violation of any
ordinance hereby repealed prior to the taking effect of this ordinance.
Section 7
If any section, subsection, sentence, clause, phrase or portion of this ordinance is for any reason
held invalid or unconstitutional in a court of competent jurisdiction, such portion shall be deemed
a separate, distinct and independent provision and shall not affect the validity of the remaining
portions thereof.
Section 8
A public hearing on the ordinance shall be held on the 12 day of December, 2011, in the City
Council Chambers, Aspen City Hall, Aspen, Colorado. Pursuant to the provisions of Section 31-
12 -403, C.R.S., as amended, notice of the hearing shall be published at least twice, once at least
eight (8) days preceding the hearing and once at least fifteen (15) days preceding it.
INTRODUCED, READ, AND ORDERED PUBLISHED as provided by law by the City Council of
the City of Aspen on the 28 day of November 2011
Mick Ireland, Mayor
A TTEST:
Kathryn S. Koch, City Clerk
FINALLY adopted, passed and approved this day of , 2011.
Mick Ireland, Mayor
A TTEST:
15
Section 3
That the International Fire Code, 2009 edition, hereinabove adopted by reference is to govern the
maintenance of buildings and premises; to safeguard life, health, property and public welfare by
regulating the storage, use and handling of dangerous and hazardous materials, substances and
processes and by regulating the maintenance of adequate egress facilities.
Section 4
That three copies of the primary code and secondary code being considered for adoption by this
ordinance, all certified to be true copies by the Mayor and City Council, shall be on file with the
City Clerk and shall be open for public inspection in her office at the Aspen City Hall, Aspen,
Colorado, any weekday between the hours of 9 a.m. and 5 p.m., at least fifteen days preceding the
public hearing on this ordinance.
Section 5
That on passage of this ordinance and adoption of this code by reference, one copy of the Code
may be kept in the office of the chief enforcement officer instead of in the office of the City
Clerk. Following the adoption of this code, the City Clerk shall at all times maintain a reasonable
supply of copies of the code available for purchase by the public.
Section 6
Existing ordinances or parts of ordinances covering the same matters as embraced in this
ordinance are hereby repealed and all ordinances or parts of ordinances inconsistent with the
provisions of this ordinance are hereby repealed, except that this repeal shall not affect or prevent
the prosecution or punishment of any person for any act done or committed in violation of any
ordinance hereby repealed prior to the taking effect of this ordinance.
Section 7
If any section, subsection, sentence, clause, phrase or portion of this ordinance is for any reason
held invalid or unconstitutional in a court of competent jurisdiction, such portion shall be deemed
a separate, distinct and independent provision and shall not affect the validity of the remaining
portions thereof.
Section 8
A public hearing on the ordinance shall be held on the 12 day of December, 2011, in the City
Council Chambers, Aspen City Hall, Aspen, Colorado. Pursuant to the provisions of Section 31-
12 -403, C.R.S., as amended, notice of the hearing shall be published at least twice, once at least
eight (8) days preceding the hearing and once at least fifteen (15) days preceding it.
INTRODUCED, READ, AND ORDERED PUBLISHED as provided by law by the City Council of
the City of Aspen on the 28 day of November 2011.
ZiP 11./
Michael C. Ireland, Mayor
ATTEST:
15
athryn S. Kochi / ity Clerk
FINALLY adopted, passed and approved this 12 day of December 2011.
r2 4W
Michael C. Ireland, Mayor
ATTEST:
Kathryn S. Kocs; City Clerk
16
0
J
N
M
L.
81,2r. 8 • r @ E @
m &
'�.� °
E .g O oic ci w o
8 m - € 0
r7 E u • 1,
00111111 N �
g� .m 0 §
Fiz $
i '.E oa a� F
N�m O U'$ ��LL F
_° 2Q , C p
V ,-SO@ l.. , s .2N
iiitgioi: OPA oS c A i$ X1\ \11111111// / ///
\ •,.�`��P,G E N 10 . , /, s
p . "o
N
=m. O m 6
1v '. z 4 ' U y •
/ / "/11111' n��G ,§
0 .• O
ft ft'
v,4 ci a o,0 v C dp E 7 • � ro �a
N 74 - 0 _o u
C v .� P. ,u u O - 'b 0 +' 3 :".-2
v b O A y. w v F. C u u 2
111CO211 H y O a � „_' 4 O. ...„,,,,„m Q' " a ∎ `n N N Li °
• M E ° a° C H 3 0 c L a C d
d Z G 9,- Vi aa'° 3 c y° a c ° c
H 3 0 v> y v a M o
U O ro v E c U x E ro' w , C a U. c ry
..J �' i .-o ad v . 7 E. O T v LL, v N
pci • w Q x N v N .b fl.0 G E L. \ vs O O O N
ill ni 0 v v O `O c v Ei > to (.'" N .. . `�
t O G
v v
O > 3 c L � v v u b Y 5••o C CI
Q 3 v rn U d p,, a '0 - E N u — O et
v ni a 'b • N v u V)
a r • $ �x v u. o c c c v 0 o o v w
p• w ° �.� 0- C �N n.� c u a o 0
E
O co° CC ',00 —. o-E'-'
x
vy 'ro� 3 °° v c ° 3 0 0 . V .
cc .C� rc T x ,, 0 ti v
H 3 W c e L t c .® 'v w 3 G ° ¢
°�a� � .n.o 0 v� w
vl c u y 'u N v h v N
3 T v
0 4n ht N
n