Provide a minimum 40" clear
between the new wall/door and
the refrigerator/counertop per
A117.1-2009 section 804.2
exception 1.
PLANS.pdf (5)
Page: PROPOSED
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Is this a supply register or an
exhaust fan? Demonstrate that
adequate ventilation is provided
per 2015 IMC 401.2.
Page: PROPOSED
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Door opening with leaf at 90
degrees must be 32" clear in
width minimum. (2015 IBC
1010.1.1)
Page: PROPOSED
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
If the lighting will change,
provide an interior lighting
COMcheck. If the switching will
change, provide an occupant
sensor for the new office. 2015
IECC C405.
Page: PROPOSED
File Name: PLANS.pdf
Subject: PlanCheck
Author: nickt
Color:
Show and dimension accessible
door maneuvering clearances on
both sides of the new door (ICC
A117.1-2009 section 404.2.3).
Kitchenette appears to
encroach.
Provide a minimum
40" clear between thenew wall/door and therefrigerator/counertopper A117.1-2009section 804.2exception 1.
Is this a supplyregister or an exhaustfan? Demonstrate that
adequate ventilation isprovided per 2015
IMC 401.2.
Door opening with leaf
at 90 degrees must be32" clear in width
minimum. (2015 IBC
1010.1.1)
If the lighting willchange, provide aninterior lightingCOMcheck. If theswitching will change,provide an occupantsensor for the newoffice. 2015 IECCC405.
Show and dimensionaccessible doormaneuveringclearances on bothsides of the new door(ICC A117.1-2009section 404.2.3).Kitchenette appears toencroach.
04/12/2018