HomeMy WebLinkAboutFile Documents.108 Maple Ln.0035.2017.ARBK108 Maple Ln Building Markup Summary Round 1 5-5-2017
Page: 1
Page Index: 1
Checkmark: Checked
Author: bonniem
Date: 5/1/2017 3:06:11 PM
File Name: A. Index.2017.01.pdf
The City of Aspen has amended
the maximum U-factor to .28;
Correct Energy Compliance
Notes.
A. Index.2017.01.pdf (1)
Page: 1
Page Index: 1
Checkmark: Checked
Author: bonniem
Date: 5/4/2017 11:06:46 AM
File Name: E. Architectural.2017.01.pdf
A whole house balanced
mechanical ventilation system is
required for new houses per
Ordinance 40, 2016. Provide
mechanical plans from either a
licensed mechanical contractor
or mechanical engineer
demonstrating compliance. The
minimum continuous outdoor
airflow rate shall be determined
in accordance with the following
equation:
Qr = ((0.01 x Afloor) + [7.5 x
(Nbr + 1)]) x Sc
where:
Qr = ventilation flow rate, cubic
feet per minute (cfm)
Afloor = floor area in square feet
(ft2)
Nbr = number of bedrooms, not
less than one
Sc = 0.75 (system coefficient for
balanced systems)
Exception: The outdoor air
ventilation system is not required
to operate continuously where
the system has controls that
enable operation for not less
than 1 hour of each 4-hour
period. The average outdoor air
flow rate over the 4-hour period
shall be not less than that
prescribed by the equation.
E. Architectural.2017.01.pdf (8)
Page: 6
Page Index: 6
Checkmark: Checked
Author: bonniem
Date: 5/5/2017 12:14:18 PM
File Name: E. Architectural.2017.01.pdf
Snow stops required at barrel
roof to prevent snow and ice
shed on potentially occupied
areas per City of Aspen
ordinance 40, 2016.
2 3
2015 INTERNATIONAL PLUMBING CODE
2015 INTERNATIONAL FUEL & GAS CODE
2015 INTERNATIONAL ENERGY CONSERVATION CODE
2015 NATIONAL ELECTRICAL CODE
2016 ASPEN LAND USE CODE
ROOF VENTILATION
ALL ROOFS OVER CONDITIONED SPACES TO CONTAIN MINIMUM7" SPRAY IN POLYURETHANE INSULATION (SEE WALL SECTIONS).CONDENSATION CANNOT OCCUR WITHIN THIS INSULATINGSYSTEM, THEREFORE 'COLD ROOF' AND VENTING TECHNIQUES
ARE NOT REQUIRED.
ENERGY COMPLIANCE
PER 2015 IECC, SECTION 402.1-402.3 (PRESCRIPTIVE METHOD):
ASPEN CLIMATE ZONE: 7 CODE MINIMUM
FENESTRATION U-FACTOR .32(MAX)CEILING R-VALUE 49WOOD FRAME WALL R-VALUE 20+5FLOOR R-VALUE 30CRAWL WALL R-VALUE 15/19 or R-13 CAVITY
R-5 CONTINUOUSUNDER SLAB R-10
SEE MECHANICAL DOCUMENTS FOR MORE INFORMATION.
9. NO DEVELOPMENT ACTIVITY, INCLUDING
LANDSCAPING OR VEGETATION REMOVAL, SOUTSIDE OF THE PROPERTY LINES WITHOUT
10. SURFACE AND SUBSURFACE DRAINAGE ACIVIL ENGINEER DRAWINGS
11. COORDINATE JOIST PLACEMENT W/ PLUMLAYOUT
12. COMBINE AND PLACE ALL PLUMBING VENROOF AND TO BACK SIDE OF HOUSE. AVOID VMINIMUM
13. CONTRACTOR TO VERIFY THAT ALL GLASVALUE REQUIREMENTS
14. CONTRACTOR TO REVIEW PERMIT SET WITHIMMEDIATELY UPON ISSUING OF PERMIT
15. CONTRACTOR IS RESPONSIBLE FOR SAFETY, METHODS, PROCESS & SEQUENCING. ARCHITRESPONSIBLE FOR SAFETY ON THE JOB SITE
The City of Aspen
has amended themaximum U-factor to.28; Correct Energy
Compliance Notes.
A
B
4
C
532X2
X2.2
X5
A.2
B.2
63.69 sq ft
86.00 sq ft
710.38 sq ft
T3
T2
T1
T
Z
PLANNORTH2A-301 1A-3024A-301
1A-303
2A-303
3A-301 2A-302
1A-203 2A-203
1A-202
1A-201 23'-113/4"65'-9"6'-5"2'-1"1'-111/4"1'-63/8"1'-81/2"105/8"1'-51/2"
3/12PITCH
1/4/12PITCHBARRELPITCH 22'-3" RBARRELPITCH 22'-3" RFLAT ROOF
GUTTER
GUTTER
NG SEAM METAL STANDING SEAM METALROOF
STANDING SEAM METALBARREL ROOF
Flat Roof
Snow stops requiredat barrel roof toprevent snow and iceshed on potentiallyoccupied areas perCity of Aspenordinance 40, 2016.
Change Made
Bighorn Consulting Drawing
Note added and spoke with Dave
Page: 13
Page Index: 13
Checkmark: Checked
Author: bonniem
Date: 5/3/2017 3:58:54 PM
File Name: E. Architectural.2017.01.pdf
3'-10"
Page: 13
Page Index: 13
Checkmark: Checked
Author: bonniem
Date: 5/5/2017 12:01:58 PM
File Name: E. Architectural.2017.01.pdf
Foundation drains required per
R405.1
Page: 13
Page Index: 13
Checkmark: Checked
Author: bonniem
Date: 5/3/2017 4:01:42 PM
File Name: E. Architectural.2017.01.pdf
Revise so grade is 6” or more
below the top of each foundation
wall per R404.1.6.
Page: 15
Page Index: 15
Checkmark: Checked
Author: bonniem
Date: 5/3/2017 4:21:27 PM
File Name: E. Architectural.2017.01.pdf
Maximum U-Value amended to
.28 per City of Aspen Ordinance
40, 2016
Page: 17
Page Index: 17
Checkmark: Checked
Author: bonniem
Date: 5/3/2017 4:30:25 PM
File Name: E. Architectural.2017.01.pdf
Provide additional information on
the material of the skylight and
thickness of the polyvinyl butyral
interlayer to comply with R308.6;
Maximum U-Value for skylight is
.55 per Prescriptive Table
R402.1.2 in the 2015 IECC 3'-10"3
HYDRODUCT COIL 600 AT
FOOTING
Section Foundation drains
required per R405.1
MICRO PILES- ON PROPERTY
LINE OR LESS THAN 18" ON
NEIGHBORS PROPERTY
HARDIEPANEL SIDING
BACKFILL WITH CLEAN SOIL
HORIZON COAT ON
THERMOPANEL ABOVE
GRADE
Revise so grade is 6”
or more below the top
of each foundation
wall per R404.1.6.
WINDOW WITH U-.32 MAX
RATING
MANUFACTURERS
INSTRUCTION
Maximum U-Value
amended to .28 per
City of Aspen
Ordinance 40, 2016
2 3
Garage Storage T
T1
T2
T3
Z
3'-6"
3'-6"
3'-6"
3'-6"
---
1'-4"
1'-4"
1'-4"
1'-4"
---Skylight ---
Clerestory
Clerestory
Clerestory
Clerestory
3'-0" x 6'-10"
Provide additional information on the material of the skylight and thickness of the polyvinyl butyral interlayer to complywith R308.6; Maximum U-Value for skylight is .55 per Prescriptive Table R402.1.2 in the 2015 IECC
Scale of Dimension Off 1’-3” See A-401
Detail Revised to Call Out and Match Civil C-6.0
Dimension note added to call out and match Detail 1 S-3.1
Window Removed per Zoning See Lower Level Plan A-101
Information added to schedule
Page: 17
Page Index: 17
Checkmark: Checked
Author: bonniem
Date: 5/3/2017 4:36:56 PM
File Name: E. Architectural.2017.01.pdf
Windows A3, A2, A1 and D2 are
required to be safety glazed
because of their proximity to the
exterior stairs. R308.4.6
Page: 4
Page Index: 4
Checkmark: Checked
Author: bonniem
Date: 5/4/2017 8:44:50 AM
File Name: F. Structural.2017.01.pdf
A Special Inspection Agreement
is required for the high strength
bolting and structural steel
welding. Provide a special
inspection agreement signed by
all required parties.
F. Structural.2017.01.pdf (2)
Page: 4
Page Index: 4
Checkmark: Checked
Author: bonniem
Date: 5/4/2017 8:38:09 AM
File Name: F. Structural.2017.01.pdf
Ground snow load is 100 per
City of Aspen Ordinance 40,
2016.
om
om
om
om
om
J1
K
L
M
M1
2'
9'
3'
3'
3'
Windows A3, A2, A1
and D2 are required
to be safety glazed
because of their
proximity to the
exterior stairs.
R308.4.6
2x WALLSEE PLAN
2x STRANDGUARD PLATE
CURLEY RESIDENCE
01/17/17
A.DESIGN LIVE LOADS1. GROUND SNOW 90 psfROOF SNOW LOAD 75 psf2. RESIDENTIAL 40 psf3. WIND: BASIC WIND SPEED 115 mphEXPOSURE B .4. SEISMIC CATEGORY C .
B.DESIGN CODES1. INTERNATIONAL RESIDENTIAL CODE (2015)2. ACI BUILDING CODE (ACI 318-14)
3. AISC STEEL CONSTRUCTION MANUAL (14th EDITION)4. AITC TIMBER CONSTRUCTION MANUAL (4th EDITION)
C.SPECIAL INSPECTIONSPECIAL INSPECTION REQUIREMENTS LISTED BELOW ARE BASED ON THEREQUIREMENTS OF THE 2015 INTERNATIONAL BUILDING CODE. THE REQUIREMEARE TO BE ENFORCED BY THE LOCAL BUILDING OFFICIAL. THE OWNER SHALL RTHE "INDEPENDENT INSPECTOR" AS REQUIRED BY CHAPTER 17 OF THE IBC AND TLOCAL BUILDING OFFICIAL. THE REQUIREMENTS LISTED BELOW ARE BASED ON STRICT INTERPRETATION OF THE IBC AND MAY NOT BE REQUIRED BY THE LOCALBUILDING OFFICIAL BASED ON EXCEPTIONS LISTED IN IBC SECTION 1704.2.
CONCRETE - SHALL BE IN ACCORDANCE WITH TABLE 1705.3, EXCEPT SPECIALINSPECTION IS NOT REQUIRED FOR TYPICAL FOUNDATIONS FOR BUILDINGS LESS
Ground snow load is
100 per City of Aspen
Ordinance 40, 2016.
D1 & D2 Already Noted, A3, A2, A1 Deleted per
Zoning B & V Added and Noted as Tempered
Signed Document Ready
Albright Issued Letter in Folder
PLEASE NOTE REVISED SHEETS A-101 LOWER LEVEL PLAN,
A-102 ENTRY LEVEL PLAN, A-202 NORTH AND SOUTH
ELEVATIONS, A-601 DOOR AND WINDOW SCHEDULES FOR
REMOVAL OF SOUTH LIGHTWELL WINDOWS PER ZONING