HomeMy WebLinkAboutFile Documents.108 Maple Ln.0035.2017 (8).ARBK11FOR THE MOST COMPLETE AND CURRENT INFORMATION VISIT RENEWAIRE.COM EV-SERIES & GRSpecifications may be subject to change without notice.
INDOOR UNIT
EV 300
SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 150-300 CFM
Standard Features:
Painted cabinet
Line-cord power supply
Low-voltage circuit for controls
Unit may be mounted in any orientation
Controls:
On board 24 VAC transformer/relay package
with switched dry contacts
Filters:
Total qty. 2, MERV 8, spun-polyester media:
10 1/2" x 21 3/4" x 1"
Unit Dimensions & Weight:
33 3/4" L x 24" W x 20" H
72 lbs.
Max. Shipping Dimensions & Weight (on pallet):
34" L x 44" W x 34" H
115 lbs.
Motor(s):
Qty. 1, Double-shaft standard motor
Accessories:
Backdraft damper 8"
Wall cap 8" - taupe plastic, galvanized,
paintable galvanneal
Louver with 8" round duct connection -
12" (W) x 8" (H)
Percentage timer control (PTL)
Push-button point-of-use controls (PBL), PTL req'd.
Percentage timer control with
furnace interlock (FM)
Electric duct heater - EK series (1–60 kW)
ELECTRICAL DATA
HP Volts HZ Phase Input Watts FLA
0.2 120 60 Single 315 @ 297 CFM 3.3
UNIT PERFORMANCE CORE PERFORMANCE
Airflow CFM ESP in H20 Temp EFF%Total EFF%
Winter/Summer*
170 1.0 78 73/59
191 0.9 77 71/57
215 0.8 75 69/55
256 0.7 73 66/51
277 0.6 71 65/49
295 0.5 70 63/47
311 0.4 69 62/46
5 1/2" 9 1/8" 5 3/8" 9 1/4" OA EA
RA FA
34" Line Cord 9 3/4"Typ. 28 3/4" Case
33 5/8" Overall
2 1/2" Typ. 24" Overall(with HangingBracket)10"Typ.18 5/8"Case 5/8" Typ. 2 3/8" 21 3/4" Overall(with Hanging Bracket)To Fit
8" Duct
Typ.20"Overall 23 7/8" Case
22 1/4" MinimumService Area
(Door can beRemoved from
Hinges.)18 1/2"MinimumService AreaDoor
Swing
24V AC
Control
Terminal
LEFT VIEW FRONT VIEW RIGHT VIEW
TOP VIEW
Model: EV300Drawing Type: Unit DimensionVersion: MAR16
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit may be installed in any orientation.
NOTE1.UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THENEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
UNIT DIMENSIONS EV-SERIES & GRAIRFLOW CONFIGURATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream
can be switched with OA/FA airstream.
STANDARD