HomeMy WebLinkAboutFile Documents.520 W Hallam St.0041.2018 (22).ARBK0041.2018.ARBK_BuildingComment1
Subject: PlanCheck
Page Label: A1.07 PROPOSED PLANS
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
Provide a cutsheet on the
skylight showing compliance
with IRC 308.6 for material and
required curb height.
520 W HALLAM ARCHITECTURAL SET.pdf (8)
Subject: PlanCheck
Page Label: A1.10 PROPOSED ELEVATIONS
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
Provide the installation manual
for this DV fireplace to show you
are allowed to vent this close to
operable windows (scales at 2'4"
from the awning window).
Subject: PlanCheck
Page Label: A1.10 PROPOSED ELEVATIONS
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
Please clarify what is intended at
this guardrail. Is it 1' wide metal
panels with 2" spacing between
them? If it is the other way
around it will not comply with
IRC 312.1.3 but it is hard for me
to tell as the panels appear to be
transparent as drawn.
Subject: PlanCheck
Page Label: A1.10 PROPOSED ELEVATIONS
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
Window fall protection required
per IRC 312.2 req'd. Note this
requirement on the window
schedule.
Subject: PlanCheck
Page Label: A1.12 WINDOW SCHEDULE
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
This window is required to be
safety glazed per its proximity to
the bathtub. Please identify it as
such.
206
ROOF SKYLIGHT
E
K
4'-9 1/4"5'-2 3/4"
CL
5 U
Provide a cutsheet on the skylight
showing compliance with IRC 308.6
for material and required curb
height.
T.O. F.F. @ MAIN LEVEL (E)
ELEV. 100'-0"
T.O. F.F. @ UPPER LEVEL (E)
ELEV. 108'-10 3/4" V.I.F.
T.O. F.P. MONTIGO PL52
2'-6"ELEV. 33.25" + 26" = 59 1/4"1'-0"6'-4"10 3/4"1'-0"VERIFY W/FIREPLACE MFG.5'-10"EXTERNAL POWER
VENT- REF.
FIREPLACE MFG.
FRAMING
ALLOWANCE - REF.FIREPLACE MFG.
AND STRUCTURAL
1
11
2 2
3
9
DASHED LINE OF
FOUNDATIONBEYOND
12 Provide the installation
manual for this DV fireplace
to show you are allowed to
vent this close to operable
windows (scales at 2'4" from
the awning window).2'-6"T.O. F.F. @ MAIN LEVEL (E)
T.O. F.F. @ UPPER LEVEL (E)
ELEV. 108'-10 3/4" V.I.F.
NEW SIDING TO
MATCH EXISTING
1
14
6
8
8
10
11
11
V
Please clarify what is intended at
this guardrail. Is it 1' wide metal
panels with 2" spacing between
them? If it is the other way around it
will not comply with IRC 312.1.3 but
it is hard for me to tell as the panels
appear to be transparent as drawn.
T.O. F
ELEV
T.O. F
ELEV 1'-0"10 3/4"1'-0"VERIFY W/FIREPLACE MFG.5'-10"EXTERNAL POWER
VENT- REF.
FIREPLACE MFG.
FRAM
ALLO
FIREP
AND
1
2
2
3
4
3
8
12
Window fall protection
required per IRC
312.2 req'd. Note this
requirement on the
window schedule.1'-0"K
CURB MOUNTED FIXED SKYLIGHT
VERIFY SIZE AND STYLE
WITH MFG.
VERIFY
4'-0"VERIFY5'-0"L
3 UNITS MULLED TOGETHER
(1) FIXED AND (2) AWNING
W/ INT. SCREEN FOR OPERABLE UNIT
REF. ELEV. FOR SWING
NOTE: REPLACEMENT WDW. WITHIN
6'-0"3'-6"1'-6"5'-0"3'-0"3'-0"F THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. 520 W HA 520 W. HA BLOCK PARCE
This window is
required to be safety
glazed per its
proximity to the
bathtub. Please
identify it as such.
04/06/2018
Subject: PlanCheck
Page Label: A1.13 DOOR SCHEDULE
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
Verify that the custom door will
be NFRC labeled at inspection in
order to verify U value.
Subject: PlanCheck
Page Label: A1.14 ROPOSED LIGHTING & ELECTRICAL
PLAN
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
This is a commercial code
requirement/reference, please
remove it from all lighting
schedules.
Subject: PlanCheck
Page Label: A1.17 DETAILS
Author: justinh
File Name: 520 W HALLAM ARCHITECTURAL SET.pdf
Provide an assembly detail for
the new flat roof that is
proposed. Provide
documentation that this new
assembly is class A (UL listing,
ESR report, etc).
Subject: PlanCheck
Page Label: 5
Author: justinh
File Name: 520 W HALLAM STRUCTURAL SET.pdf
A signed special inspection
agreement is required for the
welding shown in the structural
details.
520 W HALLAM STRUCTURAL SET.pdf (1)
3'-0"2'-6"
OWNER SPECIFIED
CUSTOM DOOR
Verify that the custom
door will be NFRC
labeled at inspection in
order to verify U value.
TOTAL FIXTURES
GENERAL NOTES:
ALL LIGHTING SHALL COMPLY WITH 2014 NEC, 2015 IECC,
PROVIDE LIGHT REDUCTION CONTROLS PER 2015 IECC C405.2.2.2
ALL BULBS ARE TO BE 12W LED ONMIDIRECTIONAL BULBS, UNLESS NOTED OTHERWISE
TOTAL PERCENTAGE HIGH EFFICIENCY PER 2015 IECC R404.1 :
G
H
J
K
L
M
N
P
R
Q
S
SUBTOTAL
T
U
TBD TBD LED CABLE LIGHTING TBD
LED TRACK LIGHTING TBDTBDTBD
This is a commercial code
requirement/reference,
please remove it from all
lighting schedules.
Provide an assembly detail for the new flat roof
that is proposed. Provide documentation that
this new assembly is class A (UL listing, ESR
report, etc).
COAT PO
BASEPLATE &
GRADE W/
EXIST
B
A signed special inspection agreement is required for the welding
shown in the structural details.