HomeMy WebLinkAboutFile Documents.124 W Hallam St.0025.2017.ARBK00025-2017-ARBK_BuildingComments_3
Page: 1
File Name: PERMIT REVISIONS
02-ARCHITECTURAL.2017.08.31.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide stamped design
drawings of the permanent
micropiles. Minimum factor of
safety is 2. Your response says
it is forthcoming. I cannot sign off
until it is submitted.
PERMIT REVISIONS 02-ARCHITECTURAL.2017.08.31.pdf (4)
Page: 7
File Name: PERMIT REVISIONS
02-ARCHITECTURAL.2017.08.31.pdf
Subject: PlanCheck
Author: nickt
Color:
The window fall
protection/opening limiting
devices must be listed to ASTM
F2090. Provide a spec
demonstrating that they have
that listing.
Page: 31
File Name: PERMIT REVISIONS
02-ARCHITECTURAL.2017.08.31.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a new REScheck
showing the new insulation at
the window well
Page: 46
File Name: PERMIT REVISIONS
02-ARCHITECTURAL.2017.08.31.pdf
Subject: PlanCheck
Author: nickt
Color:
Skylight on flat roof requires 4"
curb above roof surface unless
permitted by manufacturer's
instructions (2009 IRC R308.6.8)
Provide stamped design
drawings of the permanent
micropiles. Minimum factor of
safety is 2. Your response says
it is forthcoming. I cannot sign off
until it is submitted.
The window fall
protection/opening limitingdevices must be listed to
ASTM F2090. Provide a
spec demonstrating that they
have that listing.
Provide a newREScheck showing thenew insulation at the
window well
09/14/2017
Skylight on flat roofrequires 4" curb aboveroof surface unlesspermitted bymanufacturer'sinstructions (2009 IRCR308.6.8)