Page: 16
Author: claudes
Date: 6/11/2017 3:31:45 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning Comment 10:
2.Provide Site plan with details.
Sheet LS-10.0 Landscape layout
plan and A-100.00 Site Plan,
each provide some detail. Either
add to one of the existing sheets
or provide a Zoning specific site
plan. Please a zoning include:
•Setbacks: front, side, rear,
provide unique line weights in
order to distinguish between grid
lines, setbacks and property
lines.
•Property lines
•Setback chart; ZCV policy: all
items in setbacks shall comply
with Section 26.575.020(E)(5)
Allowed Projections into
Setbacks. Note: veneer is not
permitted in the any yards.
These plans illustrate several
place where veneer is proposed
for the front and side yards.
•Fence locations, heights,
materials
•Mechanical equipment: utilities
listed on LS-10.0 provide height
information
•Outdoor lighting
•Trash enclosure: see policy
attached
•Provide dimension for parking,
8.5’ wide x 18’ length.
•Window well to fitness room, is
not an exception for location in
a setback
A. PERMIT DRAWINGS-ARCHITECTURAL.2017.03.08.pdf (14)
Page: 17
Author: claudes
Date: 6/11/2017 3:34:24 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning comment 11:
3.Sheet A-110.00 Lower Level
Floor Plan:
•Provide consistent grid line
labels on all sheets.
•Foundation wall is not permitted
in a setback. Please amend this
sheet, the South/ front
foundation wall is in the setback.
Page: 18
Author: claudes
Date: 6/11/2017 1:09:34 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning Comment 10:2.Provide Site plan with details. Sheet LS-10.0 Landscape layout plan and A-100.00 Site Plan, each
provide some detail. Either add to one of the existing sheets or provide a Zoning specific site plan.
Please a zoning include:
•Setbacks: front, side, rear, provide unique line weights in order to distinguish between grid lines,
setbacks and property lines.
•Property lines
•Setback chart; ZCV policy: all items in setbacks shall comply with Section 26.575.020(E)(5) Allowed Projections into Setbacks. Note: veneer is not permitted in the any yards. These plans illustrateseveral place where veneer is proposed for the front and side yards.
•Fence locations, heights, materials
•Mechanical equipment: utilities listed on LS-10.0 provide height information
•Outdoor lighting
•Trash enclosure: see policy attached
•Provide dimension for parking, 8.5’ wide x 18’ length.
•Window well to fitness room, is not an exception for location in a setback
Zoning comment 11:
3.Sheet A-110.00 Lower Level Floor Plan:
•Provide consistent grid line labels on all sheets.•Foundation wall is not permitted in a setback. Pleaseamend this sheet, the South/ front foundation wall is in the
setback.
-SITE PLAN SHEET A100 HAS BEEN UPDATED TO INCLUDE MORE
SETBACK AND PROPERTY LINE NOTES
-PLANS/ELEVATIONS/SECTIONS HAVE BEEN ADJUSTED SO THAT THE EXTERIOR WOOD CLADDING IS
WITHIN THE SETBACKS. WALL FRAMING AND WALL ASSEMBLIES HAVE BEEN REVISED THROUGH-OUT
THE SET.
SETBACK CHART: ALL FACADE CLADDING AND SIDING TO BE 1/4"
WITHIN SETBACK LINES
-FENCE LOCATIONS/HEIGHTS INCLUDED ON LANDSCAPE PLANS
-MECH. EQUIPMENT IS WITHIN SETBACKS: CU-1 AND CU-2 = 25" HEIGHT; CU-3 = 43" HEIGHT
CU-4 (LG UNIT) = 26" HEIGHT
-OUTDOOR LIGHTING IS INCLUDED ON RCP PLANS AND FRONT YARD (HALLAM FACING) STONE
WALK-WAY HAS PIN LIGHT PENDING APPROVAL FROM HPC
-TRASH ENCLOSURE TO BE DETERMINED. WILL COMPLY WITH CITY POLICY IF IT IS DECIDED THAT
GARABAGE WILL NOT BE KEPT IN THE GARAGE
-PARKING DIMENSIONS COMPLY AND ARE RECENTLY DIMENSIONED
-FITNESS ROOM HAS BEEN CHANGED TO A BEDROOM, WHICH
IS ALLOWED TO HAVE AN EGRESS WELL PER CODE
-GRID LINES ARE UPDATED
-FOUNDATION WALL MOVED TO BE WITHIN SETBACK
City of Aspen
Received
06/23/17
Building Department
Page: 18
Author: claudes
Date: 6/11/2017 3:35:49 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning Comment 12:
4.Sheet A-111.00 Main Level
Floor Plan:
•Veneer and structure are not
permitted in a setbacks. Please
amend every façade. Amend
Structural, Architectural and Civil
sheets as necessary. The only
exception is the historic bay
window
West Yard:
•Wing wall around the
mechanical equipment
•Veneer on the garage
North yard/rear:
•See sheet A-404.00 Sections;
please explain how the house is
at the property line?
•Garage veneer at 5’ setback
•House veneer at 10’ setback
East yard:
•House veneer at 10’ setback
South yard/ front:
•Front wall, porch and veneer
appear to be in the setback. As
previously stated, please provide
a chart to verify the distance the
wall is outside the required
setback. This is required for ZCV
policy.
Page: 18
Author: claudes
Date: 6/11/2017 1:00:44 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Page: 18
Author: claudes
Date: 6/11/2017 2:40:16 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Page: 18
Author: claudes
Date: 6/11/2017 3:36:06 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning Comment 12:
4.Sheet A-111.00 Main Level Floor Plan:
•Veneer and structure are not permitted in a setbacks. Please amend every façade. AmendStructural, Architectural and Civil sheets as necessary. The only exception is the historic bay
window
West Yard:
•Wing wall around the mechanical equipment
•Veneer on the garage
North yard/rear:
•See sheet A-404.00 Sections; please explain how the house is at the property line?
•Garage veneer at 5’ setback
•House veneer at 10’ setbackEast yard:
•House veneer at 10’ setback
South yard/ front:
•Front wall, porch and veneer appear to be in the setback. As previously stated, please
provide a chart to verify the distance the wall is outside the required setback. This is required
for ZCV policy.
Received
4/12/2017 10:39:47 AM
-BUILDING DESIGN REVISED TO ALLOW EXTERIOR WOOD
CLADDING SYSTEM TO STAY WITHIN SETBACKS; SEE PLANS,
SECTIONS, ELEVATIONS, DETAILS, ASSEMBLIES
-SETBACK LINE MISLABELED AS PROP LINE
-FRONT PORCH HAS BEEN REVISED AND IS WITHIN SETBACKS
AND HPC DIRECTED DESIGN/PROPORTIONS/MATERIALS
-ALL VENEER/CLADDING WILL RESIDE WITHIN SETBACK TO A
SURVEY VERIFIABLE DIMENSION. 1/4" FROM SETBACK LINE WILL
BE OUR STATED VALUE FOR "SETBACK CHART"
City of Aspen
Received
06/23/17
Building Department
Page: 18
Author: claudes
Date: 6/11/2017 1:04:00 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Page: 18
Author: claudes
Date: 6/11/2017 1:07:58 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Page: 19
Author: claudes
Date: 6/11/2017 3:38:19 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning Comment 13:
5.Sheet A112.00 Upper Level
Floor Plan:
•Provide details of window called
out as ‘Fixed Glazing’ in
bathroom, room #23. The
window does not appear on
window schedule.
Page: 24
Author: claudes
Date: 6/11/2017 3:41:42 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning Comment 14:
6.Sheet A-300.00 – A-302.00
Exterior Elevations;
•For zoning purposes height is
measured from the most
restrictive of natural or finished
grade. Please section
26.575.020(F) Measuring
Building Height. Please label the
grade, provide unique line
weights.
•Please provide a height chart as
well as drop down lines on the
Elevation sheets. The drop down
lines shall be from the most
restrictive of natural or finished
grade to a point specified by the
roof form. The chart will provide
perimeter measurements and a
roof points for roof over
topography points.
•The chart shall also provide
exceptions to height for
proposed chimneys and any
other element on the roof, such
as solar, guards, etc. The chart
will be used in the ZCV policy,
see attached.
Zoning Comment 13:
5.Sheet A112.00 Upper LevelFloor Plan:
•Provide details of window calledout as ‘Fixed Glazing’ in bathroom,
room #23. The window does notappear on window schedule.
Zoning Comment 14:
6.Sheet A-300.00 – A-302.00 Exterior Elevations;•For zoning purposes height is measured from the most restrictive of natural or finished grade. Please section
26.575.020(F) Measuring Building Height. Please label the grade, provide unique line weights.
•Please provide a height chart as well as drop down lines on the Elevation sheets. The drop down lines shall be fromthe most restrictive of natural or finished grade to a point specified by the roof form. The chart will provide perimeter
measurements and a roof points for roof over topography points.•The chart shall also provide exceptions to height for proposed chimneys and any other element on the roof, such as
solar, guards, etc. The chart will be used in the ZCV policy, see attached.
INTERIOR FIXED GLAZING AT UPPER LEVEL BATH, OVER-LOOKS
OPEN TO BELOW SPACE (KITCHEN). WINDOW TO BE TEMPERED;
NO EXPOSURE TO BLDG. EXTERIOR; TO BE FIELD GLAZED AND
NOT A WINDOW PER SE TO BE INCLUDED ON WINDOW SCHED.
-BUILDING HEIGHT IS AT 25'-0" ABOVE FINISHED GRADE, WHICH IS GENERALLY MORE RESTRICTIVE.
SEE DASHED LINE FOR NATURAL GRADE HEIGHT LIMIT.
-HPC REQUIRED PROJECT PARAPETS TO BE PULLED BACK AND BELOW MAX. HEIGHT LIMIT; GLASS
GUARDRAILS ARE THEREFORE AT THE MAX. HEIGHT LIMIT.
-DIMENSIONS HAVE BEEN ADDED TO EXTERIOR ELEVATIONS AND SITE PLAN A100,
VICTORIAN ROOF VARIES AND IS EXEMPT AS WE ARE PRESERVING EXISTING STRUCTURE
WHICH DOES NOT COMPLY
ROOF HEIGHTS
-CHIMNEYS, FLUES, VENTING APPARATUS, PV PANELS, AND VENTS MAY EXTEND BEYOND
HEIGHT LIMIT AND WILL DO SO AT MINIMUM REQUIREMENT TO FUNCTION. CHIMNEYS AND CAPS
WILL NOT EXTEND ABOVE REQUIRED CODE ALLOWANCES
City of Aspen
Received
06/23/17
Building Department
Page: 27
Author: claudes
Date: 6/11/2017 3:42:39 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Zoning comment 15:
7.Please note section
26.575.020(D)(8)Subgrade
requires compliance;
a.Single-family and duplex
structures shall contain no more
than one floor level below
finished grade. A basement with
a stepped floor is allowed. The
finished floor level shall be no
more than 15 feet below finished
grade. A crawl space below the
basement, compliant with the
limitations of Section
26.575.020.D.3, shall be exempt
from this depth limitation.
•On what sheet has this
information been illustrated?
Page: 30
Author: claudes
Date: 6/11/2017 2:45:46 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Page: 31
Author: claudes
Date: 6/11/2017 2:48:05 PM
File Name: A. PERMIT
DRAWINGS-ARCHITECTURAL.2017.03.08.pdf
Page: 7
Author: claudes
Date: 6/11/2017 3:13:21 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning Comment 2:
•Wall 2.the egress window well
permitted width is 6’. The plans
illustrate 6’7.5” please amend
the width of the window well to
be 6’. On Sheet A-200 and
S-120 the window well is
illustrated a non-compliant width
of 7’. Please amend all the
sheets, architectural, zoning,
and structural to be compliant at
6’.
C. ZONING DRAWINGS.2017.03.08.pdf (7)
Zoning comment 15:
7.Please note section 26.575.020(D)(8)Subgrade requires compliance;
a.Single-family and duplex structures shall contain no more than one floor level below finished grade. A
basement with a stepped floor is allowed. The finished floor level shall be no more than 15 feet below finished
grade. A crawl space below the basement, compliant with the limitations of Section 26.575.020.D.3, shall beexempt from this depth limitation.•On what sheet has this information been illustrated?
Zoning Comment 2:
•Wall 2.the egress window well permitted width is 6’. The plans
illustrate 6’7.5” please amend the width of the window well to be 6’. On
Sheet A-200 and S-120 the window well is illustrated a non-compliant
width of 7’. Please amend all the sheets, architectural, zoning, and
structural to be compliant at 6’.
-SUBGRADE LIMIT (15'-0") HAS BEEN ADDED TO BUILDING
SECTIONS. (A400-405.00) IN MOST CASES, FINISHED
BASEMENT/LOWER LEVEL FLOOR HEIGHT IS 3'-0" ABOVE THE
SUBGRADE LIMIT
-EGRESS WELL HAS BEEN REVISED. SEE SHEET A113.00
City of Aspen
Received
06/23/17
Building Department
Page: 7
Author: claudes
Date: 6/11/2017 3:12:05 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning Comment 1:
1.Sheets: Z-103.00 – Z-105.00
Floor Area Calculations and
Sheet A-112.00 Upper Level
Floor Plan:
•Subgrade wall totals are not
accurate. For example wall 5.
4’x10’ should be 40’,it is listed as
45’.
•And wall 7. 32’10” x 10’ should
be 325.33 and is listed as 330’.
Please review all math and
correct the sheet.
•The wall segments at ¼” are not
scaling correctly for example
wall 5. States 4’ wide but scales
at 4’3”. Please correct the scale
or the walls segments.
Page: 8
Author: claudes
Date: 6/11/2017 3:21:43 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning comment 4:
•Add the stone patio at bedroom
28 in deck totals.
•Add outdoor stair at kitchen
deck totals.
Page: 8
Author: claudes
Date: 6/11/2017 3:16:34 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning comment 3:
•Remove the window well for the
fitness room, room #10. The
exceptions for window wells in a
setback is for bedrooms only.
Amend the subgrade wall
calculations as necessary,
amend all sheets, structural,
architectural, civil, etc.
Page: 8
Author: claudes
Date: 6/11/2017 3:24:00 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning comment 6:
•Add floor area at stair,
exemption is for, “not counted as
floor area on the top-most
interior floor served by the
element.” As drawn, the whole
stair has been exempted. Only
half this feature is exempt.
Page: 9
Author: claudes
Date: 6/11/2017 3:27:48 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning comment 7:
•Count the outdoor stair, at roof
access in deck totals. Detail
provided on sheet A-700.00
Enlarged Stair Plan
Zoning Comment 1:
1.Sheets: Z-103.00 – Z-105.00 Floor Area Calculations and Sheet A-112.00 Upper
Level Floor Plan:
•Subgrade wall totals are not accurate. For example wall 5. 4’x10’ should be 40’,it is
listed as 45’.
•And wall 7. 32’10” x 10’ should be 325.33 and is listed as 330’. Please review all math
and correct the sheet.
•The wall segments at ¼” are not scaling correctly for example wall 5. States 4’ wide
but scales at 4’3”. Please correct the scale or the walls segments.
Zoning comment 4:
•Add the stone patio at bedroom 28 in deck totals. •Add outdoor stair at kitchen deck totals.
Zoning comment 3:
•Remove the window well for
the fitness room, room #10.
The exceptions for window
wells in a setback is for
bedrooms only. Amend the
subgrade wall calculations as
necessary, amend all sheets,
structural, architectural, civil,
etc.
Zoning comment 6:
•Add floor area at stair,
exemption is for, “not counted as
floor area on the top-most interior
floor served by the element.” As
drawn, the whole stair has been
exempted. Only half this feature
is exempt.
Zoning comment 7:
•Count the outdoor stair, at roof access
in deck totals. Detail provided on sheet
A-700.00 Enlarged Stair Plan
-FITNESS ROOM 10 HAS BEEN REVISED TO BE BEDROOM.
EGRESS WELL ALLOWED
ROOF STAIR IS AN EXTERIOR STAIR AND HAS BEEN INCLUDED
IN DECK TOTALS - DOES NOT GET COUNTED AS INTERIOR
FLOOR AREA - SEE COMMENT 4 RESPONSE ABOVE
-HALF OF STAIR SF WAS COUNTED ORIGINALLY BUT HATCH WAS MISSING ON Z-104.00
SUBGRADE WALL TOTALS HAVE BEEN REVISED. SEE SHEET
Z-103.00
ROOF DECK (W/ STAIR) - 352 SF
BALCONY - 55 SF
DECK (W/ STEPS) - 78 SF
TOTAL = 485 SF (486 SF ALLOWED)
ROOF STAIR IS AN EXTERIOR STAIR AND HAS BEEN INCLUDED
IN DECK TOTALS - DOES NOT GET COUNTED AS INTERIOR
FLOOR AREA - SEE COMMENT 4 RESPONSE ABOVE
City of Aspen
Received
06/23/17
Building Department
Page: 9
Author: claudes
Date: 6/11/2017 3:29:19 PM
File Name: C. ZONING DRAWINGS.2017.03.08.pdf
Zoning Comment 8:
•Please provide math to illustrate
totals. For example, main floor
total 1755 (1031 + 724 + 120
(garage) = 1875. The total for
the main floor is listed as 1752,
and 1755, how was this number
derived?
Zoning Comment 8:
•Please provide math to illustrate totals. For example, main floor total 1755 (1031
+ 724 + 120 (garage) = 1875. The total for the main floor is listed as 1752, and
1755, how was this number derived?
SEE AREA CALCULATION SHEETS:
MAIN LEVEL - 724 SF
1,031 SF
TOTAL= 1,755 SF
UPPER LEVEL - 921 SF
1866 SF
TOTAL= 1,787 SF
LOWER - 3,375 SF
GARAGE - 120 SF (485-250--118)
City of Aspen
Received
06/23/17