Page: [1] A-103X
File Name: 1419 Crystal Lake Drawings.pdf
These numbers should match
1419 Crystal Lake Drawings.pdf (27)
Subject: PlanCheck
Page: [1] A-103X
File Name: 1419 Crystal Lake Drawings.pdf
Total should be 1450 SF
Subject: PlanCheck
Page: [4] C1D-Crystal Lake-LandscapeSheetset-L1.03
File Name: 1419 Crystal Lake Drawings.pdf
Will these water features be
heated? If so they will be
treated as a pool/spa for REMP.
What is the depth of the water
features?
Subject: PlanCheck
Page: 18
File Name: 1419 Crystal Lake Drawings.pdf
What are you showing here?
Please clarify.
Subject: PlanCheck
Page: 19
File Name: 1419 Crystal Lake Drawings.pdf
Req'd to be a solid door or have
20 min fire rating IRC 302.5.1,
show on door schedule
HEFG
5
6
4.5
E.5
DECK
PROPOSED
UPPER LEVEL FLOOR PLAN
3/16" = 1'-0"
1A-103.1
948 sf
MELT PLAN UPPER LEVEL - 949 SQFT
These numbers shouldmatch
F G
EXIST
UPPER
3/16" = 1'-0"
1
A-103X
ER LEVEL - 1430 SQFT
Total should be 1450
SF
6" ABOVE-GROUND
WATER FEATURE
KITCHEN
AUTOCOURT
ENTRY
ONCRETE-
WMELTED;
RE: 1/L.5.01
TILE OVER CONCRETE-
SNOWMELTED;
RE: 1/L.5.01
ISOLATION JO
RE: 2/L.5.01
Will these waterfeatures be heated? If
so they will be treated
as a pool/spa forREMP. What is thedepth of the water
features?
What are you showing
here? Please clarify.
Req'd to be a solid
door or have 20 min
fire rating IRC 302.5.1,
show on door
schedule
This has been corrected on the sheets.
This has been corrected on the sheets.
These water features are not heated
and drained in the winter. The
features will be approximately 6" deep.
This door has been changed to a two
direction "barn" door as shown on
lower level plans.
Door type updated in dwg, as well as added to door schedule.
Door to follow IRC 302.5.1
Subject: PlanCheck
Page: 19
File Name: 1419 Crystal Lake Drawings.pdf
Fill out a COA fireplace
registration form for all existing
and new fireplaces
Subject: PlanCheck
Page: 19
File Name: 1419 Crystal Lake Drawings.pdf
Label all windows on the floor
plans to correspond with the
labeling on the window schedule
Subject: PlanCheck
Page: 19
File Name: 1419 Crystal Lake Drawings.pdf
What is this? Please clarify.
Subject: PlanCheck
Page: 19
File Name: 1419 Crystal Lake Drawings.pdf
Include all new interior doors on
the door schedule
Subject: PlanCheck
Page: 21
File Name: 1419 Crystal Lake Drawings.pdf
Two solar proposals were
included in the submission.
Please select one and include it
on the roof plan if you intend to
use it to mitigate REMP fees
with it. The REMP worksheet
you submitted is an old form,
please fill out our new REMP
worksheet including the PV
worksheet tab to correspond
with the selected solar proposal.
Fill out a COA fireplace
registration form for allexisting and newfireplaces
Label all windows on
the floor plans to
correspond with the
labeling on the window
schedule
What is this? Please clarify.
Include all new interior
doors on the door
schedule
Two solar proposals were included in the
submission. Please select one and
include it on the roof plan if you intend to
use it to mitigate REMP fees with it. The
REMP worksheet you submitted is an
old form, please fill out our new REMP
worksheet including the PV worksheet
tab to correspond with the selected solar
proposal.
These will be sealed gas appliances,
cutsheets and manufacturer
information have been provided.
All windows have been labeled on the
plans to correspond to the window
schedule.
This will be a bifold door system from
NanaWall, La Cantina, Pacific
Millworks, or similar manufacturer.
The door will meet exterior door
requirements per IRC Climate zone 7.
All interior doors have been added to
the Door Schedule. See sheet A-602
The new form has been filled out. At
this time the snowmelt between
existing and new will zero out with
regards to area. The shown exterior
spa will be offset with REMP fee at this
time. No Solar PV will be used to
offset.
Subject: PlanCheck
Page: 24
File Name: 1419 Crystal Lake Drawings.pdf
Show the gas meter location on
your proposed elevations.
Subject: PlanCheck
Page: 25
File Name: 1419 Crystal Lake Drawings.pdf
Showing a window here on the
floor plans
Subject: PlanCheck
Page: 25
File Name: 1419 Crystal Lake Drawings.pdf
Safety glazing req'd, shown as
such on the schedule but not
here, please revise.
Subject: PlanCheck
Page: 25
File Name: 1419 Crystal Lake Drawings.pdf
Door 112D is shown here on the
floor plan.
Subject: PlanCheck
Page: 25
File Name: 1419 Crystal Lake Drawings.pdf
Safety glazing req'd per 308.4
(2)
Show the gas meter location on your
proposed elevations.
Showing a window
here on the floor plans
Safety glazing req'd,
shown as such on the
schedule but not here,
please revise.
Door 112D is shown
here on the floor plan.
Safety glazing req'd
per 308.4 (2)
Gas Meter has been shown on
elevations and noted. Existing location
to remain.
Bathroom window has been added to
elevations as well as window
schedule.
Window has been noted as 'Tempered'
on the elevations.
Door 112D has been updated on the
elevations.
Tempered window has been noted on
the elevations.
Subject: PlanCheck
Page: 29
File Name: 1419 Crystal Lake Drawings.pdf
This does not meet prescriptive
req's if I am reading your
insulation schedule correctly.
Either provide insulation values
on the detail or provide more
detail on the schedule. As I read
it your flat roof rigid insulation
give you 24.2 average R value
with a 4" average thickness. In
order to have the req'd R 49 for
the ceiling you would need to
have the full 4" of rigid insulation
which is not what this detail
shows.
Subject: PlanCheck
Page: 32
File Name: 1419 Crystal Lake Drawings.pdf
Safety glazing req'd IRC 308.4
(shown on elevation but not
here)
Subject: PlanCheck
Page: 32
File Name: 1419 Crystal Lake Drawings.pdf
Interior doors should also be
included in your door schedule,
make sure to note any safety
glazing or fire rating.
Subject: PlanCheck
Page: 32
File Name: 1419 Crystal Lake Drawings.pdf
Safety glazing req'd per 308.4
Subject: PlanCheck
Page: 32
File Name: 1419 Crystal Lake Drawings.pdf
Identify emergency egress
windows as such
This does not meet prescriptive req's if I am reading your insulation schedule
correctly. Either provide insulation values on the detail or provide more detail on the
schedule. As I read it your flat roof rigid insulation give you 24.2 average R value
with a 4" average thickness. In order to have the req'd R 49 for the ceiling you wouldneed to have the full 4" of rigid insulation which is not what this detail shows.
Safety glazing req'd
IRC 308.4 (shown on
elevation but not here)
Interior doors should also be included
in your door schedule, make sure to
note any safety glazing or fire rating.
Safety glazing req'd
per 308.4
Identify emergency
egress windows as
such
Tempered window has been noted on
the window schedule.
The intent is that the R-49 is met with
both continuous insulation above deck
as well as cavity spray foam insulation.
The insulation schedule indicates two
different categories for this insulation.
We have adjusted the detail to indicate
4" of rigid insulation above deck at the
minimum point.
Interior doors have been added to
door schedule. See sheet A-602
Tempered window has been noted on
the window schedule.
All emergency door and window
egress locations have been updated
on the elevations and schedules.
Subject: PlanCheck
Page: 32
File Name: 1419 Crystal Lake Drawings.pdf
Safety glazing req'd IRC 308.4
(shown on elevation but not
here)
Subject: PlanCheck
Page: 32
File Name: 1419 Crystal Lake Drawings.pdf
Safety glazing req'd IRC 308.4
(shown on elevation but not
here)
Subject: PlanCheck
Page: 40
File Name: 1419 Crystal Lake Drawings.pdf
No ventilation information is
shown in either the mechanical
plans or RCP, compliant
ventilation must be
demonstrated hor the entire
home (2009 IMC 403).
Subject: PlanCheck
Page: 40
File Name: 1419 Crystal Lake Drawings.pdf
A minimum of 50% of all lamps
installed in permanent light
fixtures must be high efficacy
(2009 IECC 404.1), note this on
your plans.
Subject: PlanCheck
Page: 42
File Name: 1419 Crystal Lake Drawings.pdf
RCP directs you to reference
lighting plans for specific
fixtures, location, etc. - no
lighting plan was submitted.
Please provide more detail
regarding new lighting to be
installed. Any recessed lighting
in the thermal envelope must be
sealed and IC rated (IECC
402.5), if recessed lighting is
proposed in the upper level
provide a cutsheet
demonstrating compliance.
Safety glazing req'd
IRC 308.4 (shown on
elevation but not here)
Safety glazing req'd
IRC 308.4 (shown on
elevation but not here)
No ventilation information is shown in either the mechanical
plans or RCP, compliant ventilation must be demonstrated hor
the entire home (2009 IMC 403).
A minimum of 50% of all lamps installed in permanent
light fixtures must be high efficacy (2009 IECC 404.1),
note this on your plans.
RCP directs you to reference lighting plans for specific
fixtures, location, etc. - no lighting plan was submitted.
Please provide more detail regarding new lighting to be
installed. Any recessed lighting in the thermal envelope
must be sealed and IC rated (IECC 402.5), if recessed
lighting is proposed in the upper level provide a cutsheet
demonstrating compliance.
Tempered window has been noted on
the window schedule.
Tempered window has been noted on
the window schedule.
On page 3 of the Mechanical Design Assist file the ventilation system
equipment is laid out. Each bathroom exhaust fan will exceed the 50 cfm
intermittent flow requirement, the garage fan will be sized at 100
cfm/vehicle, and the kitchen make-up air system will be automatic and
balanced. The remaining house will have operable windows in all bedrooms
as well as (2) Energy Recovery Ventilators (ERVs); these are sized
according to ASHRAE 62.2 for a minimum size of 280 cfm, which exceeds
the IMC requirement of 90 cfm.
RCP's have included IECC 404.1 note,
referencing at least 50% of all lamps
must be high efficacy.
RCP's have included IECC 402.5,
showing all recessed cans are sealed
and IC rated. A cut sheet and graphic
has been supplied as well.
Mechanical ventilation is required throughout the home per
COA 8.16.020(k). Show the locations of the ventilation
equipment/supply and return air throughout the home in
your plans to demonstrate compliance with this. Operable
windows do not help meet this requirement.
Subject: PlanCheck
Page: 89
File Name: 1419 Crystal Lake Drawings.pdf
This total should be 8168 SF
Subject: PlanCheck
Page: 91
File Name: 1419 Crystal Lake Drawings.pdf
Note the temperature and
moisture controls req's per IECC
403.8 on your snowmelt plan.
Subject: PlanCheck
Page: 2
File Name: Energy Code Compliance.pdf
Provide a cutsheet on the boiler
that corresponds with this and
the efficiency noted on the
REMP worksheet.
Energy Code Compliance.pdf (2)
Subject: PlanCheck
Page: 3
File Name: Energy Code Compliance.pdf
This REMP worksheet does not
appear to match what is shown
in the plans, please remove.
Subject: PlanCheck
Page: 1
File Name: REMP 1419 Crystal Lake - 2017-0208.pdf
Two other REMP worksheets
were submitted with this permit
set (one in the "energy code
compliance" and another titled
"REMP docs"), they both appear
to be incorrect. Please fill out
the new 2017 REMP worksheet
including the PV worksheet tab
to correspond with the selected
solar proposal.
REMP 1419 Crystal Lake - 2017-0208.pdf (2)
\General CADD 12\Gxd\19050A.gxd -- 08/22/2016 -- 02:10 PM -- Scale 1 : 240.000000
ELT PLAN MAIN LEVEL - 6718 SQFT
MELT - 8148 SQFT This total should be
8168 SF
PROPERTY LINE
10' SIDE YARD SE
T
B
A
C
K
TOW8003.0
5,328 sf
Note the temperatureand moisture controlsreq's per IECC 403.8on your snowmelt plan.
016 Game Room 1 12.3 Jul 1500 769 4.9 800.0 0.96
101 Entry 1 7.8 Jul 1700 486 8.5 395.0 1.23
102 Powder 1 1.4 Jul 1700 85 1.4 75.0 1.13 104 Living Room 1 15.2 Jul 1500 945 18.9 500.0 1.89
105 Dining Room 1 8.7 Nov 1400 544 8.2 380.0 1.43
107 Family Room 1 15.7 Aug 1600 976 14.3 395.0 2.47 108 Kitchen 1 14.9 Jul 1700 930 4.5 425.0 2.19
110 Mud Room 1 1.8 Jul 1100 110 1.7 200.0 0.55
112 Garage 1 3.6 Aug 1600 874 17.5 765.0 1.14 113 Diesels Room 1 0.7 Jul 1500 101 2.0 55.0 1.84
201 Her Closet 1 3.5 Jul 1500 286 5.7 190.0 1.51
202 His Closet 1 1.8 Jul 1500 132 2.6 130.0 1.01 204 Master Bath 1 8.8 Oct 1400 550 6.9 370.0 1.49
206 Master Bedroom 1 7.9 Sep 1400 492 8.6 455.0 1.08 207 Bedroom 3 1 7.0 Aug 1600 438 8.4 300.0 1.46
208 Bathroom 3 1 0.9 Jul 1700 58 0.5 60.0 0.96
209 Office 1 3.3 Jul 1700 207 1.6 135.0 1.53 211 Stairs 1 4.9 Jul 1700 308 4.4 225.0 1.37
212 Bathroom 4 1 2.1 Aug 1700 132 1.6 115.0 1.15
213 Bedroom 4 1 5.7 Jul 1600 376 7.6 335.0 1.12
Hourly Analysis Program v4.50 Page 1 of 1
Provide a cutsheet on
the boiler that
corresponds with this
and the efficiency
noted on the REMP
worksheet.
Permit Number:
City:Pon
State:
Zip Code:
NERGY MITIGATION PROGRAM
pen
611
TBDThis REMP worksheet
does not appear to
match what is shown
in the plans, please
remove.
ESS:Version 10
Permit Number:
ON :
City:Ponte Vedra Beach
State:FL
Zip Code:32082
Cell Phone:
e :
City:Aspen
State:CO
Zip Code:81611
911 Ponte Vedra Blvd
Thunderbowl Architects - Matthew Smith
200 Spring Street, Suite 20
matthew@thunderbowlarchitects.com
09 IECC RESIDENTIAL RENEWABLE ENERGY MITIGATION PROGRAM
City of Aspen
1419 Crystal Lake Rd, Aspen, CO, 81611
2737-181-32-017 TBD
Big Dog LLC - Joe Jangro
Two other REMP worksheets were submitted with this permit
set (one in the "energy code compliance" and another titled
"REMP docs"), they both appear to be incorrect. Please fill out
the new 2017 REMP worksheet including the PV worksheet tab
to correspond with the selected solar proposal.
This has been updated.
Page 2 of the Mechanical Design Assist file
has the Snowmelt sequence of operations. This
sequence calls for outdoor temperature
sensors and slab snow/ice sensors which in
conjunction with a Tekmar controller will
operate the snowmelt system in compliance of
IECC 403.8.
The Manual J design conditions do not reference any
boiler efficiency, they show the results of the heat loss and
gain modelling. The snowmelt boilers referenced in the
REMP worksheet are existing and the cutsheet is
attached. The pool boiler efficiency is based off a Raypak
R206-406 pool heater which is 82% efficient, but is subject
to change by the pool contractor.
This has been updated.
This has been updated.
Subject: PlanCheck
Page: 1
File Name: REMP 1419 Crystal Lake - 2017-0208.pdf
Per the plans this should be
8313 SF
Email:
Phone:
RESIDENTIAL RENEWABLE ENER
Total New Sq Ft Existing to b
ro Snowmelt 8333
ic Snowmelt 0
Pool 0
Spa 127
matthew@t
Per the plans this
should be 8313 SF
This has been updated.