HomeMy WebLinkAboutFile Documents.122 W Main St.0032.2018.ACBK0032-2018-ACBK_BuildingComment2
Subject: PlanCheck
Page Label: A0.1 cOCCUPANCY/•50MEANS OF:gress
plansh<QcLiU1h
Author: justinh
File Name: Permit Drawing Set_Architecture.122 West
Main.2018.4_ Addendum 1.pdf
Please revise this number to be
the correct common path travel
distance as this appears to be a
typo.
Permit Drawing Set_Architecture.122 West Main.2018.4_ Addendum 1.pdf (4)
Subject: PlanCheck
Page Label: A2.1 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set_Architecture.122 West
Main.2018.4_ Addendum 1.pdf
Show the proposed venting
termination for the new DV
fireplace that was not in the
original submittal to demonstrate
compliance with the unit's
installation instructions.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set_Architecture.122 West
Main.2018.4_ Addendum 1.pdf
Now that you are proposing a
parallel approach at the sink
then it cannot overlap into the
space that the dishwasher door
would occupy when in the open
position. The edge of the
dishwasher would need to be a
minimum of 24" inches from the
centerline of the sink in order to
provide a compliant parallel
approach centered on the sink
that does not obstruct the
dishwasher door. Please revise.
Subject: PlanCheck
Page Label: A8.1 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set_Architecture.122 West
Main.2018.4_ Addendum 1.pdf
Show maneuvering clearances
at all doors in the commercial
spaces as well as all doors
within the fully accessible lodge
unit. This previous comment
was not addressed and still
stands. See ANSI figure
404.2.3.2 for examples of the
required maneuvering
clearances.
¶´¶´Please revise this
number to be the
correct common path
travel distance as this
appears to be a typo.
Show the proposed
venting termination for
the new DV fireplace
that was not in the
original submittal to
demonstrate
compliance with the
unit's installation
instructions.
Now that you are proposing a parallelapproach at the sink then it cannot
overlap into the space that the dishwasherdoor would occupy when in the openposition. The edge of the dishwasher
would need to be a minimum of 24"inches from the centerline of the sink inorder to provide a compliant parallel
approach centered on the sink that doesnot obstruct the dishwasher door. Pleaserevise.
Show maneuvering clearances at all
doors in the commercial spaces as
well as all doors within the fully
accessible lodge unit. This previous
comment was not addressed and still
stands. See ANSI figure 404.2.3.2
for examples of the required
maneuvering clearances.
Typo corrected. Sheet A0.1
resubmitted.
GSA 9/17/28
See elevation 2 on
resubmitted A3.0
GSA 9/17/28
See plan 3 on resubmitted
A8.0.
GSA 9/17/28
See resubmitted Sheet
A8.1. Clearances are
omitted at doors in
inaccessible areas (the
mechanical room, the
inaccessible lodge unit) and
in the existing stair, elevator
+ toilet cores that maintain
existing openings.
GSA 9/17/28