HomeMy WebLinkAboutFile Documents.122 W Main St.0032.2018 (28).ACBKCOMcheck Software Version 4.0.8.2
Mechanical Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Location:Aspen, Colorado
Climate Zone:7
Construction Site:
122 West Main Street
Aspen, CO 81611
Owner/Agent:
Gilbert Sanchez
300 South Spring Street
#202
Aspen, CO 81611
970-948-0597
grsanchezaia@gmail.com
Designer/Contractor:
BG Buildingworks
222 Chapel Place
Unit AC-201
Avon, CO 81620
970-949-6108
Project Information
Energy Code:
122 West Main Street
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Cooling: 10 each - VRF Zone Fan Unit (FC-1,2,4-7,9-12), Capacity = 7 kBtu/h, No Economizer, Economizer exception: Heat Recovery
System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
10 FXZQ07MVJU9 (Single Zone):
Cooling: 2 each - VRF Zone Fan Unit (FC-3,20), Capacity = 8 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
2 FXAQ07PVJU (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit (FC-8), Capacity = 15 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 FXFQ15TVJU (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit (FC-13), Capacity = 24 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 FXFQ24TVJU (Single Zone):
Cooling: 2 each - VRF Zone Fan Unit (FC-15,16), Capacity = 18 kBtu/h, No Economizer, Economizer exception: Heat Recovery
2 FXAQ18PVJU (Single Zone):
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
211 ofPage08/23/2018
09/12/2018
justinh
Quantity System Type & Description
System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
Cooling: 1 each - VRF Zone Fan Unit (FC-17), Capacity = 12 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 FXAQ12TVJU (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit (FC-18), Capacity = 30 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: FC-18 | Living/Dining -- Compliance (Motor nameplate HP method) : Passes
Fans:
FC18 Supply, Single-Zone VAV, 1400 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 FXMQ30PBVJU (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit (FC-19), Capacity = 12 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 FXAQ12PVJU (Single Zone):
Heating: 1 each - Radiant Heater, Electric, Capacity = 2 kBtu/h
No minimum efficiency requirement applies
Fan System: Cassettes -- Compliance (Motor nameplate HP method) : Passes
Fans:
VRF Supply, Single-Zone VAV, 500 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
13 BB-1 (Single Zone w/ PerimeterSystem):
Heating: 1 each - Unit Heater, Electric, Capacity = 4 kBtu/h
No minimum efficiency requirement applies
Fan System: TH-1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Single-Zone VAV, 260 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 TH-1 (Unknown):
VRF, Air Cooled w/ Heat Recovery Heat Pump
Heating Mode: Capacity = 144 kBtu/h,
No minimum efficiency requirement applies
Cooling Mode: Capacity = 130 kBtu/h,
No minimum efficiency requirement applies
Fan System: None
1 CU-1 (Multiple-Zone):
VRF, Air Cooled w/ Heat Recovery Heat Pump
Heating Mode: Capacity = 87 kBtu/h,
No minimum efficiency requirement applies
Cooling Mode: Capacity = 76 kBtu/h,
No minimum efficiency requirement applies
Fan System: None
1 CU-2 (Multiple-Zone):
Gas Storage Water Heater, Capacity: 50 gallons, Input Rating: 75 kBtu/h w/ Circulation Pump
Proposed Efficiency: 0.95 EF, Required Efficiency: 0.58 EF
1 WH-1:
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
212 ofPage08/23/2018
09/12/2018
justinh
08/23/2018
09/12/2018
justinh
Inspection Checklist
Requirements: 89.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.8.2
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
214 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.2.4.
5,
C403.2.4.
6
[FO9]3
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
215 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
216 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M001
C404.6.1,
C404.6.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
217 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
218 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
219 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2110 ofPage08/23/2018
09/12/2018
justinh
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2111 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Location on plans/spec: Just refrigerant piping
See the Mechanical Systems list for values.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Location on plans/spec: Just refrigerant piping
See the Mechanical Systems list for values.
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Only fans are in terminal units
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Only fans are in terminal units
C403.2.13
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.4.
4
[ME112]3
Zone isolation devices and controls
installed where applicable.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
4
[ME112]3
Zone isolation devices and controls
installed where applicable.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2112 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Location on plans/spec: M102
C403.2.9
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M001
C403.2.9
[ME10]2
Ducts and plenums sealed based on
static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M001
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2113 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.1.
1
[ME75]2
Hydronic and multizone HVAC system
controls areVAV fans driven by
mechanical or electrical variable
speed drive per Table C403.4.1.1.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: VRF has all ECM motors
C403.4.1.
1
[ME75]2
Hydronic and multizone HVAC system
controls areVAV fans driven by
mechanical or electrical variable
speed drive per Table C403.4.1.1.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: VRF has all ECM motors
C403.4.1.
2
[ME67]2
VAV fans have static pressure sensors
located so controller setpoint <=1.2
w.c..
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.1.
2
[ME67]2
VAV fans have static pressure sensors
located so controller setpoint <=1.2
w.c..
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.1.
3
[ME24]2
Reset static pressure setpoint for DDC
controlled VAV boxes reporting to
central controller based on the zones
requiring the most pressure.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.1.
3
[ME24]2
Reset static pressure setpoint for DDC
controlled VAV boxes reporting to
central controller based on the zones
requiring the most pressure.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2.
3.2.2
[ME122]3
Open- or closed circuit cooling towers
have a separate heat exchanger to
isolate the cooling tower from the
heat pump loop, and heat loss is
controlled by shutting down the
circulation pump on the cooling tower
loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2.
3.2.2
[ME122]3
Open- or closed circuit cooling towers
have a separate heat exchanger to
isolate the cooling tower from the
heat pump loop, and heat loss is
controlled by shutting down the
circulation pump on the cooling tower
loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2114 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C404.2.1
[ME111]2
Gas-fired water-heating equipment
installed in new buildings: where a
singular piece of water-heating
equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency
>= 90 Et. Where multiple pieces of
water-heating equipment serve the
building with combined rating >=
1,000 kBtu/h, the combined input-
capacity-weighted-average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <= 100
kBtu/h.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2115 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2116 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
Exception: Required standby equipment with proper controls
per code.
Location on plans/spec: M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2117 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M100-103, M300
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M 100-103
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M 100-103
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2118 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: P300
C404.4
[FI25]2
All piping insulated in accordance with
section details and Table C403.2.10.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M001
C404.6.1
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: M300
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2119 ofPage08/23/2018
09/12/2018
justinh
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2120 ofPage08/23/2018
09/12/2018
justinh
Project Title:
Data filename:
122 West Main Street
S:\BGProjects\9867.00 122 West Main Street Remodel\Engineering\Energy\Calcs\COMcheck.cck
06/29/18Report date:
2121 ofPage08/23/2018
09/12/2018
justinh