HomeMy WebLinkAboutFile Documents.122 W Main St.0032.2018 (31).ACBKMarkup Summary Permit Drawing Set.122 West Main.2018.4 7-27-2018
Page Label: 2(.Q<Z3.0hU2C<02JQ cROOF
DEMO•50CALCULATIONSh<0cuu3h
Page Index: 6
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 8:23:30 AM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Permit Drawing Set.122 West Main.2018.4.pdf (9)
Page Label: 2<_a<Z4.0rvu2C2<1hQLia 2CWALL
DEMO•50ALCULATIONSi->acT12LiII-
Page Index: 7
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:23:21 PM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please correct the
measurements and re-tally the
Wall Demo table, and the Roof
Demo table.
Page Label: 2Ca<Z5.0rvu2C2<1VhQLia 2CFLOOR
AREA•50ALCULATIONS•50EXISTINGi-<acLL2Li1I-
Page Index: 8
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:25:14 PM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please provide Floor Area
calculations for the entire
building for both existing and
proposed. Please also include
all non-unit allocation numbers
to the permit because there are
two uses in the other building.
Non unit allocations need to be
created for each building.
Page Label: 2Ca<Z5.0rvu2C2<1VhQLia 2CFLOOR
AREA•50ALCULATIONS•50EXISTINGi-<acLL2Li1I-
Page Index: 8
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:15:53 PM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please label as 'Existing'.
Page Label: 2Ca<Z5.1rvu2C2<1VhQLia 2CFLOOR
AREA•50ALCULATIONS•50PROPOSEDi-<acLL2Li1I-
Page Index: 9
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:20:15 PM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
This area is commercial floor
area.
Roof Demolition
Roof Label Roof Area in Plan (SF)Roof Slope Adjustment Factor
Area of Roof Used for Demo Calc (SF)Area of Roof to be Removed (SF)A 217.0 12:12 1.414 306.8B 217.0 12:12 1.414 306.8C 293.4 12:12 1.414 414.9C1 155.2 12:12 1.414 219.5 219.5D 293.4 12:12 1.414 414.9D1 155.2 12:12 1.414 219.5 219.5E 5.8 12:12 1.414 8.2F 5.8 12:12 1.414 8.2G 110.3 12:12 1.414 156.0G1 25.5 12:12 1.414 36.1 36.1H 110.3 12:12 1.414 156.0I 5.8 12:12 1.414 8.2J 5.8 12:12 1.414 8.2K 16.6 3:12 1.035 17.2L 13.6 3:12 1.035 14.1M 13.6 3:12 1.035 14.1N 49.0 3:12 1.035 50.7O 45.7 3:12 1.035 47.3P 13.7 3:12 1.035 14.2Q13.7 12:12 1.414 19.4R32.1 12:12 1.414 45.4S5.8 12:12 1.414 8.2T5.8 12:12 1.414 8.2U76.6 12:12 1.414 108.3V76.6 12:12 1.414 108.3V125.5 12:12 1.414 36.1 36.1W5.8 3:12 1.035 6.0X5.8
Roof Surface Total (SF)2000.4 2760.5
Roof Surface Area to be Removed (SF)511.0
Demolition TotalsRoof + Wall Area Used for Demo Calculation (SF)2760.5 + 2725.6 5486.1Surface Area to be Removed (SF)511.0 + 205.8 716.8
Total 13.07%
3.12 1.035 6.0
2,766.80
511.20
Please add in the missing measurements and re-tally the RoofDemo table, and the Wall Demo table.
2,766.80 + 3,071.90
511.20 + 205.80
5,838.70
717
12.28
Wall Demolition
Wall Label Individual Wall Area (SF)Area Reduced for Fenestration (SF)Area of Wall to be Removed (SF)A 457.6 131.4 171.5B 322.4 103.4 19.2C 28.3 0.0D 387.1 111.4E 28.3 0.0F 449.7 112.0G 582.9 84.9 15.1H 533.7 494.2I 141.1 13.0J 527.4 38.7K 140.6 34.4L 364.8 114.9
Wall Surface Area Total (SF) 3963.9Area Reduced for Fenestration (SF) 1238.3Area Used for Demo Calculation (SF) 2725.6
Wall Surface Area to be Removed (SF)205.8
Demolition TotalsRoof + Wall Area Used for Demo Calculation (SF)2760.5 + 2725.6 5486.1Surface Area to be Removed (SF) 511.0 + 205.8 716.8
Total 13.07%
Please correct the measurements and re-tally the Wall Demo table, and the Roof Demo table.
147.90
892
2,766.80 + 3,071.90 5,838.70
511.20 + 205.80 717
3,071.90
12.28
Total GSF 3,597.00
Please provide Floor Area calculations for the entire building for both
existing and proposed. Please also include all non-unit allocation numbers
to the permit because there are two uses in the other building. Non unit
allocations need to be created for each building.
Top Level of Elevator
Countable Floor Area (SF)
Total Second Level Countable Floor Area (SF)
Basement Level (SF)
First Level (SF)
Second Level (SF)
Total Proposed Floor Area (SF)
Total GSF
Total Proposed Floor Area Calculation
Please label as
'Existing'.
This area is
commercial floor
area.
SHEET Z3.0 REVISED
GSA
SHEET Z4.0 REVISED
GSA
CALCULATIONS ADDED TO SHEET Z5.1
GSA
SHEET Z5.0 REVISED
GSA
SHEET Z5.1 REVISED
GSA
08/23/2018
Page Label: 2Ca<Z5.1rvu2C2<1VhQLia 2CFLOOR
AREA•50ALCULATIONS•50PROPOSEDi-<acLL2Li1I-
Page Index: 9
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:35:55 PM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please show how these areas
underneath the eaves are less
than 30" in height.
Page Label: 2Ca<Z5.1rvu2C2<1VhQLia 2CFLOOR
AREA•50ALCULATIONS•50PROPOSEDi-<acLL2Li1I-
Page Index: 9
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:25:41 PM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please provide Floor Area
calculations for the entire
building for both existing and
proposed. Please also include
all non-unit allocation numbers
to the permit because there are
two uses in the other building.
Non unit allocations need to be
created for each building.
Page Label: NO)RPRT SAMrWF7 ARPHI 2CJET
LEASABLE•50ALCULATIONS•50PROPOSEDi-<aCLL2LiTI-
Page Index: 11
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 11:32:59 AM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Numbers in diagrams do not
match numbers in table.
Page Label: NO)RPRT SAMrWF7 ARPHI 2CJET
LEASABLE•50ALCULATIONS•50PROPOSEDi-<aCLL2LiTI-
Page Index: 11
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 11:29:14 AM
Color:
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
This area is part of Net Leasable
space.
Total First Level Countable Floor Area (SF)1,2
Gross Floor Area (SF)1,199.00Top Level of Stair -113.00Top Level of Elevator -48.00Countable Floor Area (SF)1,0
Total Second Level Countable Floor Area (SF)1,0
Gross Floor Area (SF)523.00Top Level of Stair -30.00Countable Floor Area (SF)4
Total Loft Level Countable Floor Area (SF)4
Basement Level (SF)3 First Level (SF)1,2 Second Level (SF)1,0 Loft Level (SF)4
Total Proposed Floor Area (SF)3,1
Second Level Floor Area Calculation
Loft LevelLoft Level Floor Area Calculation
Total Proposed Floor Area Calculation
Second Floor
Please show howthese areasunderneath theeaves are less than30" in height.
Total Loft Level Countable Floor Area (SF)493.00
Basement Level (SF)387.25First Level (SF)1,202.00Second Level (SF)1,038.00
Loft Level (SF)493.00
Total Proposed Floor Area (SF)3,120.25
Total Proposed Floor Area Calculation
Please provide Floor Area calculations for the entire building for both
existing and proposed. Please also include all non-unit allocation numbers
to the permit because there are two uses in the other building. Non unit
allocations need to be created for each building.
PROPOSED NET LEASABLE AREA
122 West Main Non-Unit Area Net Leasable Area Net LivableBasement Level (SF)252.00 837.00 0.00First Level (SF)277.50 861.50 0.00Second Level (SF)152.00 0.00 976.22Loft Level (SF)0.00 0.00 467.63
Subtotal for 122 West Main (SF)681.50 1,698.50 1,443.85 Total Proposed Non-unit + Leasable Area + Livable 3,823.85
122 Proposed Net Leasable AreaNumbers in diagramsdo not matchnumbers in table.
This area is part of
Net Leasable space.
CALCULATIONS ADDED TO SHEET Z5.1
GSA
SHEET Z6.1 REVISED
GSA
SHEET Z6.1 REVISED
GSA
SHEET Z5.1 REVISED
GSA
08/23/2018
Markup Summary Building Permit Application.122 West Main.2018.4
7-27-2018
Page Label: 9
Page Index: 9
Checkmark: Unchecked
Author: bobn
Date: 7/27/2018 3:40:02 PM
Color:
File Name: Building Permit Application.122 West
Main.2018.4.pdf
Please have the contractor sign
prior to permit issuance.
Building Permit Application.122 West Main.2018.4.pdf (1)
Please have the
contractor sign prior
to permit issuance.
FORM SUBMITTED.
GSA
08/23/2018
0038.2018.acbk_HPC Round 1
Page: E-201
Author: amyg
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Exterior lighting plan and fixtures
require review and approval by
HPC staff and monitor.
Permit Drawing Set.122 West Main.2018.4.pdf (2)
Page: L400
Author: amyg
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Landscape plan, changes to
ramp and walkway, and paver
selection require review and
approval by HPC staff and
monitor.
Exterior lighting plan and fixtures require review and
approval by HPC staff and monitor.
Landscape plan, changes to ramp and walkway, and
paver selection require review and approval by HPC
staff and monitor.
SUBMITTED TO STAFF
GSA
SUBMITTED TO STAFF
GSA
08/23/2018
Markup Summary
Subject: Callout
Page: 1.0 OL PLAN
Page Index: 27
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 4:41:36 PM
Creation Date: 4/30/2018 4:29:42 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
A stabilization plan is required
for the size of excavation
needed for the drywell
installation this close to City
ROW. Please provide. If project
plans to use ROW for layback
additional permit will be required.
Callout (1)
Subject: Engineer
Page: 1.0 OL PLAN
Page Index: 27
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 1:36:14 PM
Creation Date: 4/30/2018 1:29:52 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
No utilities have been shown on
the plans. Please provide in both
the survey and civil sheets.
Utilities need to be shown to
ensure there are no conflicts and
proper separations with
proposed drainage
improvements.
Engineer (6)
Subject: Engineer
Page: 1.0 OL PLAN
Page Index: 27
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 1:37:25 PM
Creation Date: 4/30/2018 1:36:24 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
There appears to be 2 trees that
will require removal with the
improvements. The project team
should confirm with Parks
Department to ensure removal is
acceptable and any other
permits or special considerations
required.
Subject: Engineer
Page: 1.0 OL PLAN
Page Index: 27
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 1:33:35 PM
Creation Date: 4/30/2018 1:32:08 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Curb & gutter along the property
is in poor condition and needs
replaced. Please update
drawings with new curb & gutter
and appropriate CDOT standard
t-top asphalt patch. Work along
Main Street will require a CDOT
and CoA ROW permit.
OSED WATERTY DRYWELL
PROPOSED
P
E
R
M
E
A
B
L
E
PAVER PA
R
K
I
N
G
20.5'0.4%.6%RMEABLETER BANDD EQUAL.
ITERNE20.4' ALLEYROWA stabilization plan is
required for the size
of excavation needed
for the drywell
installation this close
to City ROW. Please
provide. If project
plans to use ROW for
layback additional
permit will be
required.
DS
DS
DS
DS
DS
DS
DS
DS
HOTEL ASPEN
MAIN STREET
ST MAIN STREETART OF PROJECT)
PROPOSED WATERQUALITY DRYWELL
ROPOSED PE
R
M
E
A
B
L
E
PAVER PARKI
N
G
PROPOSED EDGE OF ROOF
PROPOSED FULL INFILTRATIONPERMEABLE PAVER ENTRY WALKWAY20.5'PROJECT BENCHMARKELEV: 7896.04'5.0%8.3%4.3%0.4%RE-GRADE EXISTINGWALKWAY. INSTALLGROUT SET PAVERS
122 WESTMAIN STREET 0.6%THREE (3) STEPS12" TREAD7.5" RISE
SCL
SCL
SCL2.0%PROPOSED TRASHENCLOSURE. SEE ARCH.
PROPOSED DECK(MAIN LEVEL)PROPOSED DECK(UPPER LEVEL)
PROPOSED EDGE OFDECK (UPPER LEVEL)
APPROXIMATE LIMITOF PERMEABLE PAVERGEOMEMBRANE
MATCH EXISTINGGRADES ALONG EDGEOF EXISTING STAIRLANDING
EXISTING LOWER LEVEL COURTYARD(NO PROPOSED IMPROVEMENTS)EXISTING STAIRSEXISTING STAIRSEXISTING BRIC
KSIDEWALK -3.0:1-3.0:1-3.0:1
TRIM EXISTING STAIRWALL TO FACILITATENEW RAMP
2.0%
MATCH EXISTINGGRADES ALONG FACEOF BUILDING.
INSTALL 4' PERMEABLE PAVERWALKWAY w/ UNDERDRAIN SLOPEFINISHED GRADE 2% AWAY FROMBUILDING. RE: DETAIL ON SHEET C-2.0
INSTALL 4"PERFORATED PVCUNDERDRAIN PIPE.
TRANSITION FROM 4"PERFORATED PVC TO4" SOLID PVCUNDERDRAIN PIPE.ROOF DOWNSPOUT ALONGFACE OF BUILDING. SEEARCHITECTURAL PLANS FORFURTHER INFORMATION.
PROPOSED FULL INFILTRATIONPERMEABLE PAVER BENEATH BIKERACK PAD. SEE ARCH PLANS FORFURTHER INFORMATION.
2.0%
WITHOUT THE PRIOR CONSENT OF THE PROPERTY OWNER INVOL
9. ALL MANHOLE COVERS MUST BE ADJUSTED SUCH THAT THE TOP
10. COMPACTION IN EXCAVATED AREAS SHALL BE 95% MODIFIED PR
11. CONTRACTOR SHALL PROTECT ALL EXISTING TREES THAT ARE
PRIOR TO COMMENCING CONSTRUCTION.
12. ALL SPOT ELEVATIONS AND GRADING CONCEPTS SHALL BE FIE LANDSCAPE ARCHITECT.
SCALE: N.T.S.
PERMEABLE
30 MIL. PVC LINER PLACED ON PREPPED SUBGRAD (SLOPED TO DRAIN AWAY FROM BUILDING @ 2 TYPICAL SLOPE FOR 10'. PROVIDE SEPARATO FABRIC BELOW LINER ONLY IF SUBGRADE CONTAIN ANGULAR ROCK OR OTHER MATERIAL THAT MA PUNCTURE THE GEOMEMBRANE LINE
ATTACH FABRICTO FOUNDATION WALLAND/OR CONCRETE BARRIER WALL; RE.TO PLANS AND ATTACHMENT DETAIL
CDOT #8 OR #9 STONE IN APPROVED
SCALE: N.T.S.
PERMEABLE P
30 MIL. PVC LINER PLACED ON PREPPED SUBGR (SLOPED TO DRAIN TOWARDS 4" P UNDERDRAIN); PROVIDE SEPARATOR FABRIC BE LINER ONLY IF SUBGRADE CONTAINS ANGULAR R OR OTHER MATERIAL THAT MAY PUNCTURE GEOMEMBRANE L
EXISTING SUBGRADE PREPPED T SLOPE TOWARDS UNDERDRAIN 0.5% MIN SLOP 4" PERFORATED SLOPED @ MIN. 0.5% W/ FRAME &
ECO-STONE PER OR A
CDOT # 8
FOUNDATION WALL AND/O REINFORCED CONCRET
18" MIN.6" WIDE REINFORCED CONCRETEBARRIER CURB 18" MIN. DEPTH
No utilities
have beenshown on theplans. Please
provide in boththe survey andcivil sheets.Utilities need tobe shown toensure thereare no conflictsand properseparationswith proposed
drainageimprovements.
DS
DS
DS
DS
DS
DS
DS
DS
HOTEL ASPEN
PROPOSED EDGE OF ROOF
PROJECT BENCHMARKELEV: 7896.04'8.3%4.3%122 WESTMAIN STREET
THREE (3) STEPS12" TREAD7.5" RISE
SCL
SCL
SCL
PROPOSED TRASHENCLOSURE. SEE ARCH.
PROPOSED DECK(MAIN LEVEL)
PROPOSED DECK(UPPER LEVEL)
PROPOSED EDGE OFDECK (UPPER LEVEL)
MATCH EXISTINGGRADES ALONG EDGEOF EXISTING STAIRLANDING
EXISTING LOWER LEVEL COURTYARD(NO PROPOSED IMPROVEMENTS)EXISTING STAIRS STAIRS-3.0:1-3.0:10:1
2.0%
MATCH EXISTINGGRADES ALONG FACEOF BUILDING.
INSTALL 4' PERMEABLE PAVERWALKWAY w/ UNDERDRAIN SLOPEFINISHED GRADE 2% AWAY FROMBUILDING. RE: DETAIL ON SHEET C-2.0
INSTALL 4"PERFORATED PVCUNDERDRAIN PIPE.
TRANSITION FROM 4"PERFORATED PVC TO4" SOLID PVCUNDERDRAIN PIPE.WNSPOUT ALONGOF BUILDING. SEETURAL PLANS FORER INFORMATION.
PROPOSED FULL INFILTRATIONPERMEABLE PAVER BENEATH BIKERACK PAD. SEE ARCH PLANS FORFURTHER INFORMATION.
2.0%
12. ALL SPOT ELEVATIONS AND GRADING CONCEPTS SHAL LANDSCAPE ARCHITECT.
SCALE: N
PERMEA
30 MIL. PVC LINER PLACED ON PREPPED S (SLOPED TO DRAIN AWAY FROM BUILD TYPICAL SLOPE FOR 10'. PROVIDE SE FABRIC BELOW LINER ONLY IF SUBGRADE ANGULAR ROCK OR OTHER MATERIAL PUNCTURE THE GEOMEMBRA
ATTACH FABRICTO FOUNDATION WALLAND/OR CONCRETE BARRIER WALL; RE.TO PLANS AND ATTACHMENT DETAIL
CDOT #8 OR #9 A
SCALE: N.
PERMEAB
30 MIL. PVC LINER PLACED ON PREPPED (SLOPED TO DRAIN TOWA UNDERDRAIN); PROVIDE SEPARATOR FA LINER ONLY IF SUBGRADE CONTAINS AN OR OTHER MATERIAL THAT MAY PU GEOMEM
EXISTING SUBGRADE PR SLOPE TOWARDS UNDE 0.5% M
4" PERF SLOPED @ M W/ F
ECO-S
18 6" WIDE REINFORCED CONCRETEBARRIER CURB 18" MIN. DEPTH
There appears to be 2 trees
that will require removal with
the improvements. The projectteam should confirm with Parks
Department to ensure removal
is acceptable and any otherpermits or special
considerations required.
PROPOSED FULL INFILTRA PERMEABLE PAVER ENTRY
RACK PAD. SEE ARCH FURTHER INFORMAT
Curb & gutter along the property is in
poor condition and needs replaced.
Please update drawings with new curb
& gutter and appropriate CDOT standard
t-top asphalt patch. Work along Main
Street will require a CDOT and CoA
ROW permit.
SE: Noted. The contractor is planning on utilizing manhole trench
boxes for drywell installation to avoid layback within the alley ROW.
SE: The revised plan set has been updated to reflect utility
extensions to the proposed remodel. Please see sheet C4.0 for utility
routing.
SE: The project team has coordinated the removal of the southern
tree with the Parks Department to facilitate the installation of a new
water service.
SE: The plan set has been updated to reflect curb and gutter replacement to match
existing TBC/FL elevations. Please additionally see the curb detail on Sheet C1.0 and
the City's t-top detail on Sheet C4.0. A CDOT Special Use Permit has been submitted
for the water service installation.
08/23/2018
Subject: Engineer
Page: 1.0 OL PLAN
Page Index: 27
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 1:32:00 PM
Creation Date: 4/30/2018 1:31:01 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
The brick sidewalk in the ROW
does not meet current ADA
standards. Rework of this
sidewalk is required to meet
current standards. Please
update drawings.
Subject: Engineer
Page: 2
Page Index: 2
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 1:34:54 PM
Creation Date: 4/30/2018 1:34:07 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Provide existing utilities on both
plan set and survey.
Subject: Engineer
Page: 9
Page Index: 9
Lock: Unlocked
Checkmark: Unchecked
Author: justinf
Date: 4/30/2018 2:08:51 PM
Creation Date: 4/30/2018 2:08:06 PM
Color:
Unit: Count
Measurement: 1
Capture: No
File Name: Drainage Report.122 West Main.2018.4.pdf
Report claims to fully retain 100
year runoff. Please supply
volume calculations that
demonstrate the detention.
MAIN STRE
E
T 5.0%8.3%
RE-GRADE EXISTINGWALKWAY. INSTALLGROUT SET PAVERS
SCL
SCL2.0%E
EXISTING B
R
I
C
K
SIDEWALK -3.0:1-3.0:1-3.0:1
The brick sidewalk in the ROW does not
meet current ADA standards. Rework of
this sidewalk is required to meet current
standards. Please update drawings.
Provideexisting utilitieson both plan
set and survey.
reatment capacity, the 10’ minimum drywell depth as
des adequate storage volume to fully retain the runoff
nt. The required storage volume for this design storm was
ults in a required 35.1 cubic feet of storage based on the
usness. The proposed 10’ deep, 4’ diameter drywell
olume within the drywell chamber alone, with additional
ckfill.
5 in/hr was estimated by the Geotechnical Engineer,
used for this analysis. Table 4 summarizes the water
ons are provide within Appendix E.
as designed to capture and filter or infiltrate the water
ed zones within landscaping and incorporate the required
P. The water quality drainage basins for the proposed
sed building ridgelines to ensure the proposed receiving
Report claims to fully
retain 100 year runoff.
Please supply volume
calculations that
demonstrate the
detention.
SE: Please see the existing cross slope labels on C2.0. The existing
brick walkway appears to meet ADA standards within reasonable
construction tolerances.
SE: Please see the revised existing conditions survey provided by
Aspen Survey Engineers depicting existing utility locations. The
existing utilities are additionally reflected on C4.0 Utility Plan.
SE: Please see Table 4 in the revised Drainage Report summarizing the required
100-yr full retention volume as well as the volume provided in excess of the
required amount.
REVISED SURVEY INCLUDES EXISTING
UTILITIES.
GSA
08/23/2018
0032-2018-ACBK_BuildingComment1
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Lighting COMcheck.122 West Main.2018.4.pdf
Provide cutsheets for all lighting
fixtures (both exterior and
interior) that give maximum
fixture wattage (not lamp
wattage) and NRTL listing.
Lighting COMcheck.122 West Main.2018.4.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: Mechanical COMcheck.122 West Main.2018.4.pdf
Please revise your Mechanical
ComCheck to match what is
shown on M-002, I am seeing
many inconsistencies between
what is shown here and what is
shown on the equipment
schedules.
Mechanical COMcheck.122 West Main.2018.4.pdf (1)
Subject: PlanCheck
Page Label: >DCDT CAMrUC7 ADPUI
2CDCCUPANCY/•50MEANS OF•50GRESS PLANSi-<Qcu2u3I-
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Provide an area sheet that
shows gross floor area as
defined in the IBC (this is
different than the gross floor
area provided for zoning).
Permit Drawing Set.122 West Main.2018.4.pdf (25)
Subject: PlanCheck
Page Label: >DCDT CAMrUC7 ADPUI
2CDCCUPANCY/•50MEANS OF•50GRESS PLANSi-<Qcu2u3I-
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Travel distances need to be
drawn rectilinearly, not crossing
spaces diagonally or through
furniture. Please revise for the
basement and main level.
Subject: PlanCheck
Page Label: A2.0 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
You are referencing a listed 1
hour assembly in multiple
locations that do not require fire
resistance rated construction.
Please provide an unlisted typ.
assembly for your non-rated
partitions and revise the wall
type references on all floor plans
as applicable.
Proposed Interior Lighting Power
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballas
1-Bank (Office)
LED 1: UC1: Other:
LED 2: C1: Other:
LED 3: D1: Other:
LED 11: D1A: Other:
LED 4: D1E: Other:
LED 10: D2: Other:
LED 5: S1: Other:
LED 6: A1: Other:
LED 7: A2: Other:
LED 8: A3: Other:
LED 9: R1: Other:
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented
specifications, and other calculations submitted with this permit applicatio
Interior Lighting PASSES: Design 1% better than code
Provide cutsheets for
all lighting fixtures
(both exterior and
interior) that give
maximum fixture
wattage (not lamp
wattage) and NRTL
listing.
ner/Agent:
bert Sanchez
0 South Spring Street
202
pen, CO 81611
0-948-0597
sanchezaia@gmail.com
Designer/Contractor:
BG Buildingworks
222 Chapel Place
Unit AC-201
Avon, CO 81620
970-949-6108
erformance requirement will be identified in the mechanical requirements checklist
pacity = 8 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
lies
otor nameplate HP method) : Passes
M, 0.1 motor nameplate hp, 0.0 fan efficiency grade
Please revise your Mechanical
ComCheck to match what is shown
on M-002, I am seeing many
inconsistencies between what is
shown here and what is shown on
the equipment schedules.
Provide an area sheet that shows gross floor
area as defined in the IBC (this is different than
the gross floor area provided for zoning).
-0”43’-10”60’-4”Travel distances need to be
drawn rectilinearly, not
crossing spaces diagonally
or through furniture.
Please revise for the
basement and main level.
You are referencing a listed 1 hour
assembly in multiple locations that do
not require fire resistance rated
construction. Please provide an
unlisted typ. assembly for your
non-rated partitions and revise the
wall type references on all floor plans
as applicable.
1
2
Mechanical COMcheck has been updated to reflect
current system types and capacities.
Dylan Friday
BG Buildingworks
Lighting spec sheets are being provided to show
NRTL listings and max fixture wattage.
Brent Schumacher
BG Buildingworks
SHEET A0.2 ADDED
GSA
SHEET A0.1 REVISED
GSA
PARTITIONS REVISED ON SHEET A2.0
GSA
08/23/2018
Subject: PlanCheck
Page Label: A2.0 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Show your 36' wide accessible
route throughout the all
commercial spaces and the
accessible lodge unit.
Subject: PlanCheck
Page Label: A2.0 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Show complaint maneuvering
clearances at all doors in the
commercial spaces as well as
the fully accessible lodge unit
per ANSI 404.2.3.2.
Subject: PlanCheck
Page Label: A2.0 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
These assemblies work for the
1 hour fire resistance
requirement of a dwelling
separation but do not provide
any sound test information.
Dwelling separations are
required to have a STC rating of
50 or greater. Provide listed
assemblies for your dwelling
separation assemblies that meet
this STC requirement as well as
the fire rating requirement.
Subject: PlanCheck
Page Label: A2.1 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
The planning approvals make
reference to two separate lodge
units. Clearly identify your
dwelling separation between the
two units on all applicable floor
plans and sections. Doors
separating units shall be 20
minute fire rated doors per IBC
table 716.5 and need to be
identified as such on the floor
plan and schedule. Be sure the
assembly you are referencing for
the dwelling separation walls has
a compliant fire rating and STC
rating.
Subject: PlanCheck
Page Label: A2.1 FLOORPLANS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please note the requirement for
a minimum of 1/2" gwb on the
interior of this entire exterior wall
per IEBC 1012.5.3. An exterior
exit stairway would normally be
required to be separated from
the interior of a building by a 1
hour fire barrier (IBC
1027/1023), but the existing
building code allows existing
wood lath and plaster or 1/2"
thick gwb to satisfy that
requirement. Please make this
note on all floor plans.
Show your 36' wide
accessible route throughout
the all commercial spaces and
the accessible lodge unit.
Show complaint
maneuvering clearances at
all doors in the commercial
spaces as well as the fully
accessible lodge unit per
ANSI 404.2.3.2.
These assemblieswork for the 1 hour fire
resistance requirementof a dwelling
separation but do notprovide any sound testinformation. Dwelling
separations arerequired to have a
STC rating of 50 orgreater. Provide listedassemblies for your
dwelling separationassemblies that meetthis STC requirement
as well as the firerating requirement.
The planning approvals makereference to two separate lodgeunits. Clearly identify yourdwelling separation between thetwo units on all applicable floorplans and sections. Doorsseparating units shall be 20 minutefire rated doors per IBC table716.5 and need to be identified assuch on the floor plan andschedule. Be sure the assemblyyou are referencing for thedwelling separation walls has acompliant fire rating and STCrating.
Please note the requirement for a
minimum of 1/2" gwb on the interior
of this entire exterior wall per IEBC1012.5.3. An exterior exit stairway
would normally be required to be
separated from the interior of abuilding by a 1 hour fire barrier (IBC
1027/1023), but the existing building
code allows existing wood lath andplaster or 1/2" thick gwb to satisfy
that requirement. Please make this
note on all floor plans.
SHEET A8.1 ADDED
GSA
SHEET A8.1 ADDED
GSA
ASSEMBLIES REVISED ON SHEET A2.0
GSA
SEPARATIONS + DOOR INDICATED ON SHEET
A2.1. DOOR INDICATED ON SHEET A5.0.
GSA
NOTE ADDED TO PLANS ON SHEETS A2.0 + A2.1
GSA
08/23/2018
Subject: PlanCheck
Page Label: A2.2 ROOFPLAN
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Provide documentation that your
roof assemblies are class A (UL
listing, ESR report, etc) and
details for your roof assembly
that match these class A
assemblies.
Subject: PlanCheck
Page Label: A3.0 ELEVATIONS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Provide a typ. detail for the new
metal guard rail showing
compliant height and opening
limitations per IBC 1015 or call
out/dimension compliant height
and size of openings on all
applicable elevations.
Subject: PlanCheck
Page Label: A3.0 ELEVATIONS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Provide details showing
compliant riser height, tread
depth, guards and handrails for
all new stairways (both exterior
and interior) that show
compliance with IBC 1011, 1014
and 1015.
Subject: PlanCheck
Page Label: A4.0 BUILDINGSECTIONS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Per the floor plan I've made the
assumption that bedroom 209
and bath 208 are intended to be
their own lodge unit. If that is
the case then this assembly is
also a dwelling separation and
must be a listed/tested assembly
with a compliant fire and STC
rating. I do not see a location
where this floor/ceiling assembly
could terminate at another fire
rated wall assembly and
therefore the entire floor for the
loft level would be required to be
built as a dwelling separation to
provide the required continuity
for a horizontal fire partition.
Subject: PlanCheck
Page Label: A5.0 ROOM FINISH•50+ DOOR•50SCHEDULE
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Identify all exterior doors as such
and provide U values for all
new/replacement exterior doors.
Entrance doors on the
basement and first floor can be
up to .77 U value (commercial
requirement) and the second
floor will need to be .28 or less
(COA amendment to the
residential requirement). Please
revise.
Provide documentation that your roof
assemblies are class A (UL listing, ESRreport, etc) and details for your roof assemblythat match these class A assemblies.
Provide a typ. detailfor the new metal
guard rail showing
compliant height and
opening limitations per
IBC 1015 or callout/dimension
compliant height andsize of openings on all
applicable elevations.
Provide details
showing compliant
riser height, tread
depth, guards and
handrails for all new
stairways (both
exterior and interior)
that show compliance
with IBC 1011, 1014
and 1015.
Per the floor plan I've made the assumption thatbedroom 209 and bath 208 are intended to betheir own lodge unit. If that is the case then this
assembly is also a dwelling separation and
must be a listed/tested assembly with a
compliant fire and STC rating. I do not see alocation where this floor/ceiling assembly couldterminate at another fire rated wall assemblyand therefore the entire floor for the loft levelwould be required to be built as a dwelling
separation to provide the required continuity for
a horizontal fire partition.
Identify all exterior doors as such andprovide U values for all new/replacementexterior doors. Entrance doors on thebasement and first floor can be up to .77U value (commercial requirement) and thesecond floor will need to be .28 or less(COA amendment to the residentialrequirement). Please revise.
DETAILS ADDED ON SHEET A2.2
GSA
DETAILS ADDED TO SHEET A2.1 + NOTES
ADDED TO SHEET A3.0
GSA
DETAILS ADDED TO SHEET A2.1
GSA
SEPARATIONS INDICATED ON SHEET A4.0
GSA
DOOR SCHEDULE REVISED ON SHEET A5.0
GSA
08/23/2018
Subject: PlanCheck
Page Label: A5.1 WINDOWSCHEDULE
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
IEBC 1012.6.3 does not require
existing openings in buildings to
be protected unless the sum of
the opening areas exceeds 50%
of the total area of the wall, you
are not required by code to
replace this glazing with fire
rated glazing. Energy code
requirements are triggered if
these windows are replaced for
any reason, so a compliant U
value will need to be provided.
Subject: PlanCheck
Page Label: A5.1 WINDOWSCHEDULE
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
U values for all new or
replacement glazing on the
second floor and loft levels is
required to be .28 or better per
COA amendment to the IECC.
Fixed windows on the basement
and ground levels must be .29
and operable windows must be
.37 or better. Please revise your
schedule for all new windows or
existing windows being repaired
or altered.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
You dimensions shown for the
water closet are wrong, it should
be 60" wide and 56" deep, this is
reversed from that. Please
revise to comply, required
clearances will not fit into this
space as currently drawn.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please provide a side elevation
or section through all fixtures
where you are proposing knee
and toe clearance to
demonstrate proper clearance
per ANSI figures 306.2 and
306.3.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Where a forward approach/clear
space is provided it should be
drawn tucked into the fixture 17"
to demonstrate proper knee and
toe clearances. If knee and toe
clearances are not being
provided then a parallel
approach/clear space centered
on the fixture shall be provided.
Please revise all applicable floor
plans.
IEBC 1012.6.3 does not require existing
openings in buildings to be protected unless
the sum of the opening areas exceeds 50%of the total area of the wall, you are not
required by code to replace this glazing with
fire rated glazing. Energy code
requirements are triggered if these windows
are replaced for any reason, so a compliantU value will need to be provided.
U values for all new or replacement glazing on thesecond floor and loft levels is required to be .28 orbetter per COA amendment to the IECC. Fixedwindows on the basement and ground levels must be.29 and operable windows must be .37 or better. Please revise your schedule for all new windows orexisting windows being repaired or altered.
You dimensions
shown for the water
closet are wrong, it
should be 60" wide
and 56" deep, this is
reversed from that.
Please revise to
comply, required
clearances will not fit
into this space as
currently drawn.
Please provide a side elevation or
section through all fixtures where you
are proposing knee and toe clearance
to demonstrate proper clearance per
ANSI figures 306.2 and 306.3.
Where a forward approach/clear space isprovided it should be drawn tucked into thefixture 17" to demonstrate proper knee and toe
clearances. If knee and toe clearances are notbeing provided then a parallel approach/clearspace centered on the fixture shall be provided. Please revise all applicable floor plans.
WINDOW SCHEDULE REVISED ON SHEET A5.1
GSA
WINDOW SCHEDULE REVISED ON SHEET A5.1
GSA
SHEET A8.0 REVISED
GSA
SHEET A8.0 REVISED
GSA
SHEET A8.0 REVISED
GSA
08/23/2018
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Are garbage disposals being
proposed under the kitchen or
breakroom sinks? If so please
clearly show them to clearly
demonstrate that they will not
interfere with the required knee
and toe clearances.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
The sink cannot overlap into the
required clear space for the
water closet. Please revise.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
You are showing a front
approach to the range which
implies you have the required
knee and toe clearance. I do not
believe this is the case based on
elevation #10 which shows an
oven under the range cooktop.
You need to have a parallel
approach centered on the oven
for the cooktop, but also a
parallel approach adjacent to the
range for the oven per ANSI
804. You should also show a
forward facing approach at the
required workspace that is
tucked under the counter 17".
The width of the work space
under counter clearance should
be clearly dimensioned.
Subject: PlanCheck
Page Label: A8.0 ACCESSIBILITY•50PLANS +•50DETAILS
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Please dimension the distance
from toilet centerline to the
adjacent wall either on an
elevation or the floor plan for all
restrooms.
Subject: PlanCheck
Page Label: E-201 FIRST LEVEL LIGHTING PLAN
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Show compliant lighting controls
for the basement and ground
levels. This includes occupant
sensors per IECC C405.2.1,
time-switch controls per
C405.2.2.1, manual light
reduction controls per
C405.2.2.2, and daylight
responsive controls per
C405.2.3 (daylight zones should
be shown on the plan).
Are garbage disposals
being proposed under
the kitchen or
breakroom sinks? If
so please clearly show
them to clearly
demonstrate that they
will not interfere with
the required knee and
toe clearances.
The sink cannot
overlap into the
required clear space
for the water closet.
Please revise.
You are showing a front approach to the range
which implies you have the required knee and
toe clearance. I do not believe this is the case
based on elevation #10 which shows an ovenunder the range cooktop. You need to have
a parallel approach centered on the oven for
the cooktop, but also a parallel approach
adjacent to the range for the oven per ANSI804. You should also show a forward facing
approach at the required workspace that is
tucked under the counter 17". The width of
the work space under counter clearanceshould be clearly dimensioned.
Please dimension the
distance from toilet
centerline to the
adjacent wall either on
an elevation or the
floor plan for all
restrooms.
SENSO
PROVID TECHN SENSO
3
Show compliant lighting controls for the basement and ground levels. This includes
occupant sensors per IECC C405.2.1, time-switch controls per C405.2.2.1, manual
light reduction controls per C405.2.2.2, and daylight responsive controls per
C405.2.3 (daylight zones should be shown on the plan).
3
Daylighting zones shown on ground level plan.
Brent Schumacher
BG Buildingworks
GARBAGE DISPOSAL INTENDED FOR
BREAKROOM 010 WITH PARALLEL APPROACH.
NO DISPOSAL IN ACCESSIBLE LODGE KITCHEN
204
GSA
THE EXISTING CORE + RESTROOM
DIMENSIONS ARE UNCHANGED. EXISTING
RESTROOM FIXTURES ARE BEING REPLACE.
GSA
SHEET A8.0 REVISED
GSA
SHEET A8.0 REVISED
GSA
08/23/2018
Subject: PlanCheck
Page Label: E-202 SECOND LEVEL LIGHTING PLAN
Author: justinh
File Name: Permit Drawing Set.122 West Main.2018.4.pdf
Both the second level and loft
level are under the residential
IECC code provisions. Please
note the requirement for at least
75% of lamps in permanently
installed fixtures to be high
efficacy. Please also note the
requirement for all recessed
fixtures installed in the building
thermal envelope (loft ceiling) to
be IC rated and air sealed.
Subject: PlanCheck
Page Label: S.6.01
Author: justinh
File Name: Permit Drawing Set.122
West Main.2018.4.pdf
A signed special inspection
agreement is required for the
structural welding and bolting
shown in the structural details.
This is be required to be
submitted before full building
department approval and permit
issuance, but you may submit all
other responses without it if you
have not selected your welding
contractor, etc. at that point.
Both the second level and loft level are under the
residential IECC code provisions. Please note the
requirement for at least 75% of lamps in permanently
installed fixtures to be high efficacy. Please also note the
requirement for all recessed fixtures installed in the building
thermal envelope (loft ceiling) to be IC rated and air sealed.
WF BE
58" DIA
STAGGERED F
A signed special inspection agreement is required for the
structural welding and bolting shown in the structural
details. This is be required to be submitted before full
building department approval and permit issuance, but
you may submit all other responses without it if you have
not selected your welding contractor, etc. at that point.
4
Added a note on residential unit plans that indicate
75% of lighting fixtures are high-efficacy fixtures.
Added a note that fixtures in building thermal
envelope shall be in an IC-rated housing.
Brent Schumacher
BG Buildingworks
FORM SUBMITTED.
GSA
08/23/2018
WELS Markup 1.1 RM
Page: 4
Author: rickma
Date: 8/6/2018 1:28:25 PM
File Name: Water Efficiency Completeness.122 West
Main.2018.4.pdf
Please include the language of WELS Section 6.1.6 -Sensors
4 (1)
Page: 5
Author: rickma
Date: 8/6/2018 1:13:57 PM
File Name: Water Efficiency Completeness.122 West
Main.2018.4.pdf
If possible, insert the water budget calculation worksheet here. The copy of the worksheet received on 4/3/18 is not entirely legible.
5 (2)
Page: 5
Author: rickma
Date: 8/6/2018 1:16:59 PM
File Name: Water Efficiency Completeness.122 West
Main.2018.4.pdf
Of these species all but Aquilegia and Deschampssia are listed as Low water-requiring plants in Appendix E of the WELS. The
water budget calculation worksheet indicates Medium water use plants.
Please include the language of
WELS Section 6.1.6 -Sensors
If possible, insert the water budget calculation worksheet here. The copy of the worksheet received on 4/3/18 is notentirely legible.
Of these species allbut Aquilegia and
Deschampssia arelisted as Lowwater-requiring plants
in Appendix E of theWELS. The waterbudget calculation
worksheet indicatesMedium water use
plants.
HINES: SPECIFICATION AND INSTALLATION NOTES FOR RAIN/
FREEZE SENSOR INTEGRATED INTO CONSTRUCTION NOTE #2
HINES: ZONE 1 ( STATION A4) CHANGED TO LOW WATER USE PLANTING
HINES: WATER BUDGET CALCULATION UPDATED
08/23/2018
Page: 11
Author: rickma
Date: 8/6/2018 1:10:44 PM
File Name: Water Efficiency Completeness.122 West
Main.2018.4.pdf
The ROW must be in the calculations
11 (2)
Page: 11
Author: rickma
Date: 8/6/2018 1:10:50 PM
File Name: Water Efficiency Completeness.122 West
Main.2018.4.pdf
The rain garden is labeled as Low
water on L400
The ROW must be in
the calculations
The rain garden is
labeled as Low
water on L400
HINES: ROW CALCULATION INCORPORATED
HINES: ZONE 1 ( STATION A4) CHANGED TO LOW WATER USE PLANTING
08/23/2018