HomeMy WebLinkAboutFile Documents.210 E Cooper Ave.0316.2017.ARBKBuildingComment1
Subject: PlanCheck
Page Label: 6
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Provide structural verification
that the walls being demolished
are not structural and that this
remodel will have no negative
affect on the building's structure.
This can be in the form of a
stamped and signed letter from
an engineer or a note in your
plans specific to that on a sheet
that you have stamped and
signed.
210 Cooper Permit Set_120817.pdf (8)
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Note the requirement for a
minimum of 75% of lamps in
permanently installed fixtures to
be high efficacy on your RCP.
Also note that recessed
luminaries installed in the
building's thermal envelope shall
be IC rated and air sealed.
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Show bath exhaust fans on your
RCP.
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Show required smoke and CO
detectors on the RCP
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
The permit application made
reference to new flooring, but
this is not shown or mentioned in
the plans. Provide a spec for an
underlayment product that
achieves an IIC and STC rating
of 50 or greater when used with
your existing floor assembly.
2
FIREPLACE TO BEREMOVED; MAINTAINVERTICAL CHASE/FLUEFOR NEW GAS APPLIANCE UNIT
REMOVE PLUMBING FIXTURES TYP.
BATHROOM106 MASTERBATHROOM108
MECH104
NITF
CLOSET
Provide structural verification that the walls being
demolished are not structural and that this
remodel will have no negative affect on the
building's structure. This can be in the form of a
stamped and signed letter from an engineer or a
note in your plans specific to that on a sheet that
you have stamped and signed.
3
A
2
D COVE
Note the requirement for a minimum
of 75% of lamps in permanently
installed fixtures to be high efficacy
on your RCP. Also note that
recessed luminaries installed in the
building's thermal envelope shall be
IC rated and air sealed.
2
OM LIGHTING TO
REMAIN
BATHROOM106 MASTERBATHROOM108
CLOSET
Show bath exhaust
fans on your RCP.
C
CCC
103
Show required smoke and
CO detectors on the RCP
The permit application made reference to
new flooring, but this is not shown or
mentioned in the plans. Provide a spec
for an underlayment product that
achieves an IIC and STC rating of 50 or
greater when used with your existing
floor assembly.
NOTE INCLUDED ON SHEET 3.1 DEMO
PLAN
BOTH NOTES ARE INCLUDED IN
GENERAL NOTES ON SHEET 1.2
SHOWN ON RCP
SHOWN ON RCP
THE NEW FLOORING IS SHOWN ON
SHEET 3.2 FURNITURE PLAN. I'VE
INCLUDED A SICA PRODUCT SPEC
FOR THE STC RATING
02/06/2018
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Asbestos abatement
documentation and clean air
report is required before the
building department can approve
this permit as asbestos testing
was positive in multiple
locations.
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Provide more information on the
millwork paneled surround. If
this surround is floor to ceiling
and creating concealed space
behind it it must meet the
requirements of IBC
803.13.2-803.13.2.1 for set out
construction.
Subject: PlanCheck
Page Label: 8
Author: justinh
File Name: 210 Cooper Permit Set_120817.pdf
Provide a listed/tested assembly
for the demising wall that has a
1 hour fire rating and STC of 50
or greater. This detail does not
work because you are disturbing
the existing rated wall with the
connection of the new interior
wall. With this assembly you no
longer have a 1 hour rated
assembly where the demising
wall and the new interior wall
meet.
1
B
EXISTRAILIN
SCALE: 1/4" = 1'-0"1 FLOOR PLAN
Asbestos abatement documentation and
clean air report is required before the
building department can approve this
permit as asbestos testing was positive in
multiple locations.
RELOCATE DOOR
NEW FIREPLACEAPPLIANCE
W1 WALL TYPE TYP.
MILLWORK PANELED SURROUND
BAT MECH104
ORAY
ADJACENT UNITOUTSIDE OFSCOPE
CLOSET
F
Provide more information on the
millwork paneled surround. If this
surround is floor to ceiling and
creating concealed space behind it
it must meet the requirements of
IBC 803.13.2-803.13.2.1 for set out
construction.
3" = 1'-0"1 DEMISING WALL:1 HOUR RATED WALL CONNECTION
EXIST. WALL
NEW BLOCKING FOR FIRE RATINGNEW TYPE X 5/8" SHEET ROCK BACKER FORFIRE RATING
EXIST. WALL
NEW BLOCKING FOR FIRE RATINGNEW TYPE X 5/8" SHEET ROCK BACKER FORFIRE RATING
5/8"SEE PLAN
1 ½" = 1'-0"INTERIOR WALLW1
GL
Provide a listed/tested assembly for the demising wall thathas a 1 hour fire rating and STC of 50 or greater. Thisdetail does not work because you are disturbing theexisting rated wall with the connection of the new interiorwall. With this assembly you no longer have a 1 hour ratedassembly where the demising wall and the new interior wallmeet.
THE MITIGATION AND REMOVAL IS
BEING CONDUCTED AND A CLEAN
AIR REPORT WILL BE PROVIDED
ONCE COMPLETED
THE MILLWORK PANEL WILL NOT
CREATE AIR SPACE; IT IS SIMPLY A
WALL TREATMENT THAT WILL BE
FASTENED DIRECTLY TO THE
DRYWALL
ASSEMBLIES UPDATED WITH A
LISTED ASSEMBLY.
02/06/2018