HomeMy WebLinkAboutFile Documents.1130 Black Birch Dr.0096.2018 (22).ARBKSPARK MODERN FIRES WITH ELECTRONIC IGNITION SYSTEM Version française de ce manuel est disponible à partir du site WEB : www.sparkfires.com French version of this Owner's Manual is available at www.sparkfires.com DIRECT VENT GAS FIREPLACE MODELS: 87NE, 87PE INSTALLATION AND OPERATING INSTRUCTIONS Report # 0321GF003S – Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. – WHAT TO DO IF YOU SMELL GAS department. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only)or mobile home where not prohibited by local codes. WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. •Do not try to light any appliance. WARNING: Improper installation, adjustment, alteration, services or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE. YOUNG CHILDREN SHOULD BE SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE. CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION. DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES. KEEP THE ROOM AREA CLEARAND FREE FROM COMBUSTIBLE MATERIALS, GASO- LINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS. •Leave the building immediately. •Immediately call your gas supplier from a neighbor's •Do not touch any electrical switch; do not use any phone in your building. phone. Follow the gas supplier's instructions. •If you cannot reach your gas supplier, call the fire –Installation and service must be performed by a qualified installer, service agency or the gas supplier. 04/20/2018 2 L100001 3 CONTENTS Important Safety Information .......................... 3 Product Features............................................ 5 Code Approval................................................ 5 Pre-Installation Information............................. 6 Installing Above 2000 Feet .......................... 6 Orifice Sizes, P essures and BTUs ................ 6 Before You Install ........................................ 6 Fireplace Framing ........................................ 7 Fireplace Dimensions .................................. 8 Fireplace Location ....................................... 9 Securing Fireplace to Floor or Framing .......... 10 Clearances................................................... 11 Installation Information................................. 12 Installation Pr ecautions ............................. 13 Installation Planning .................................. 14 Rear Wall Vent Installation ......................... 17 Horizontal T ermination Configuratio ........... 19 Below Grade Installation ............................ 21 Ver tical Thr ough-the-Roof Installation .......... 22 Installation for V er tical Termination ..............23 Cathedral Ceiling Installation ...................... 24 Fireplace Installation .................................... 25 Check Gas Type ........................................ 25 Installing Gas Piping to Fir eplace/Bur ner Checking Gas Pressure................................. 27 Electrical Installation.................................... 28 Electrical Wiring ........................................ 28 Wall Switch ............................................... 28 Glass Removal ............................................. 29 Final Installation........................................... 30 Vent Installation......................................................... 12 Gas Connection .......................................... 26 Bur ner Troubleshooting ............................................ 43 V What To Do If You Smell Gas ................ ... 33 Lighting Pilot for the First Time ............. ... 33 Lighting Pilot ......................................... . 34 Lighting Burner......................................... 35 To Turn Of f Gas ................................... ..... 35 .Media Tray Placement ...................... ...... 30 Safety Screen Installation ........................... 31 Operating Instructions ................................. 33 Cleaning and Maintenance ............................ 37 .......................................... 38 Fan Assembly................................................ 38 , Pilot and Cont r ol Compa r tment ..... 37 Pilot Flam e .............................................. 37 Bur ner Flam e ...........................................37 Air Shutter Assembl y ................................37 Vent Syste m ........................................... 38 Glass Panel..............................................38 Stones, Media Replacement Par ts ....................................... 39 ent Components .................................... 39 Fir ebox Components ........................ ..... ..... 40 SIT Proflame Wiring Diagram....................... 41 Warranty.......................................... Back Cover 04/20/2018 2L100001 3 4. Never install the fireplace • in a recreational vehicle • where curtains, furniture, clothing, or other flammable objects are less than 42" from the front, top, or sides of the fireplace • in high traffic areas • in windy or drafty areas 5. This fireplace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching. 6. Carefully supervise young children when they are in the room with fireplace. 7. Do not modify fireplace under any circumstances. Any parts removed for servicing must be replaced prior to operating fireplace. 8. Turn fireplace off and let cool before servicing, installing, or repairing. Only a qualified service person should install, service, or repair the fireplace. Have burner system inspected annually by a qualified service person. 9. You must keep control compartments, burners, and cir- culating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, pet hair, etc. Turn off the gas valve and pilot light before cleaning fireplace. 10. Have venting system inspected annually by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 37. 11. Keep the area around your fireplace clear of combustible materials, gasoline, and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace. INSTALLER Please leave these instructions with the owner. OWNER Please retain these instructions for future reference. IMPORTANT SAFETY INFORMATION properly seated and sealed. If this unit is not properly installed by a qualified service person with glass panel properly seated and sealed, combustion leakage can occur. CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu with headaches, diz- ziness and/or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have the fireplace inspected and serviced by a qualified service person. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung dis- ease or anemia, those under the influence of alcohol, and those at high altitudes. Propane/LP gas and natural gas are both odorless. An odor- making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper opera- tion of this fireplace. 1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used. 2. For propane/LP fireplace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity. 3. If you smell gas • shut off gas supply. • do not try to light any appliance. • do not touch any electrical switch; do not use any phone in your building . • immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. Continued on page 4 • Read this owner’s manual carefully and completely before trying to assemble, operate, or service this fireplace. • Any change to this fireplace or its controls can be dangerous. • Improper installation or use of this fireplace can cause serious injury or death from fire, burns, explosions, electrical shock and carbon monoxide poisoning. WARNING installed by a qualified service person. The glass panel must be This fireplace is a vented product. This fireplace must be properly 04/20/2018 4 L100001 5 IMPORTANT SAFETY INFORMATION Continued from page 3 IMPORTANT: PLEASE READ THE FOLLOWING CAREFULLY It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. IMPORTANT: PLEASE READ THE FOLLOWING CAREFULLY odor the first time it is burned. This is due to the manufacturing process. Please ensure that your room is well ventilated during burn off — open all windows. It is recommended that you burn your fireplace for at least ten (10) hours the first time you use it. Place the fan switch in the “OFF” position during this time. It is not unusual for a gas fireplace to give off some cracked, or broken. 20.Do not operate the fireplace with glass panel removed, other accessory not approved for use with this fireplace. 19.Do not use a blower insert, heat exchanger insert, or any person to arrange for replacement of the unit. has been under water. Immediately call a qualified service 18.Do not use fireplace if any part has been exposed to or pad extending the full width and depth of the appliance. you must set appliance on a metal or wood panel or hearth or other combustible material other than wood flooring, 17.When the appliance is installed directly on carpetin accessibility clearance for servicing and proper operation. ings into the combustion chamber along with adequate in any way. Provide adequate clearances around air open- 16.Do not obstruct the flow of combustion and ventilation air NFPA 70, or the Canadian Electrical Code, CSA C22.1. of local codes, with the National Electrical Code, ANSI/ grounded in accordance with local codes or in the absence 15.This appliance, when installed, must be electrically rating plate. etc.) in this fireplace. Use only the gas type indicated on 14.Do not use any solid fuels (wood, coal, paper, cardboard, 13.Never place anything on top of fireplace. other objects. 12.Do not use this fireplace to cook food or burn paper or 21. Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children, and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children, and other at risk individuals out of the room and away from hot surfaces. 22. Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance. Handle glass door with care to avoid striking or scratching it on hard objects. WARNING: Do not operate appliance with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person. 23. 24. Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a profesional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments,burners and circulating air passageway of the appliance be kept clean. 04/20/2018 5 PRODUCT FEATURES AND CODE APPROVAL Figure 1 - Fireplace controls PRODUCT SPECIFICATIONS FIREPLACE CONTROLS (see Figure 1) 1 1 2 2 3 3 4 5 6 7 1- Remote Control Receiver 2- Blower Speed Control with Manual On/Off Switch 3- Power Outlet to Connect Blower or Optional AUX Block 4- Gas Manual Shut-Off Valve 5- Main Gas Control Valve 7- Thermostat Blower 6- Electronic Control DFC Board •This appliance has been certified for use with either natural or propane gas. See appropriate data plates. •This appliance is not for use with solid fuels. •The appliance is approved for bed- room or bedsitting room installa- tions. •The appliance must be properly connected to a venting system. CSA B149.1 in Canada. Gas and Propane Installation Code, NFPA54 in U.S.A., or the Natural Fuel Gas Code, ANSI Z223.1/ of local codes, with the National with local codes or, in the absence •The installation must conform •The appliance is not approved for closet or recessed installations. TESTED TO: ANSI Z21.88-2014/CSA 2.33-2014, CGA 2.17-M91 (R2009), CSA P.4.1-09 STANDARDS LISTED VENTED GAS FIREPLACE HEATER Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe. CODE APPROVAL These appliances have been listed by OMNI and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows: This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. 04/20/2018 6 L100001 7 PRE-INSTALLATION INFORMATION INSTALLING ABOVE 2000 FEET • In Canada, these appliances are certified for altitudes of 0 – 4,500 ft. ORIFICE SIZES, PRESSURES AND BTUs NATURAL GAS PROPANE GAS Manifold Press: (W.C.) 3.5" Manifold Press: (W.C.) 10" Maximum Supply Pressure 10.5" Maximum Supply Pressure 13" Minimum Supply Pressure 4.5" Minimum Supply Pressure 11" BEFORE YOU START ITEMS REQUIRED FOR INSTALLATION Tools:Building Supplies: • Phillips Screwdriver • Framing Materials • Hammer • Wall Finishing Materials • Saw and/or saber saw • Caulking Material (Noncombustible) • Level • Fireplace Surround Material (Noncombustible) • Measuring Tape • Piping Complying with Local Codes • Electric Drill and Bits • Tee Joint • Pliers • Pipe Sealant Approved for use with Propane/LPG • Square (Resistant to Sulfur Compounds) • Pipe Wrench Model Gas Orifce Size Input Rate, Btu/hr Number Type As Shipped Max Min • In the USA, the appliance must be derated 4% for every 1,000 ft above 2,000 ft elevations (at the factory). Read this homeowner'smanual thoroughly and follow all instructions carefully. Inspect all contents for shipping damage and immediately. Do not install any unit with damaged, incomplete, or substituted parts. Check your packing list to verify that all listed parts have been received. 87N -E Natural #37 28,000 19,000 87P-E Propane #52 28,000 19,000 04/20/2018 PLANING FIREPLACE FRAMING AND COVERING FACE Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following Figure 2 and the chart below for your specific installation requirements. See Figure 3 on Page 8 for firebox dimensions. The framing headers may rest on the top of the firebox standoff. The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the firebox is installed directly on carpeting, tile, or other combustible material, other than wood flooring, the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure. Figure 2 - Framing Dimensions WARNING NON COMBUSTIBLE NON COMBUSTIBLE COMBUSTIBLE 46" 36.25" 7" 11.25" COVERING FIREPLACE FACE COMBUSTIBLE COMBUSTIBLE NON COMBUSTIBLE NON COMBUSTIBLE INSIDE CHASE INSTALLATION 36.5" RECESSED INSTALLATION ______________________________ _______________ _______________ IMPORTANT: The following must be taken into consideration if you decide to cover over the fireplace face: 1. The covering material must be non combustible, maximum 3/4" thick. 2. Minimum outside dimensions of the material over the facing are 46" x 36-1/4" (see Figure 2). 3. The inner opening in covering material must be minimum 36-1/2" wide, 18" tall and centered over the fireplace opening to allow for glass door removal. 4. The cover should maintain an air gap of at least 1/8" between covering material and fireplace to allow for metal fireplace front to expand and contract during operation. 5. PLEASE NOTE: Natural stone products may react to heat by discoloring or cracking. Spark Modern Fires is not resposible for any damages due to covering materials used. If tiles are to be applied covering the fireplace face, a layer of cement board must 23" 46"46" 46" 23" 36.25" Do not fill spaces around firebox with insulation or other materials. This could cause a fire. be used as a substrate. 7 04/20/2018 16" 45" 10" 22.5" FIREPLACE DIMENSIONS 32" TOP VIEW FRONT VIEW 36" 7.25" 17.5" 7.25" 36" 45" RIGHT SIDE VIEW WITH 30 DEGREE ELBOW 22.5" 32" 24.9" 36.0" 16.5" 36.0" PRE-INSTALLATION INFORMATION Figure 3 - Fireplace Dimensions VENT ELBOW GAS AND ELECTRICAL ACCESS HOLES (BOTH SIDES) 8 9 (BOTH SIDES) ACCESS HOLES GAS AND ELECTRICAL ELBOW VENT 0.5" 37.0"36.0" RIGHT SIDE VIEW WITH 60 DEGREE ELBOW 22.5" 32" 24.9" 04/20/2018 � ��� � � � � � PRE-INSTALLATION INFORMATION FIREPLACE LOCATION Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent configuration to be used, framing and finishing details, and whether any optional accessories (i.e. wall switch, or remote control) are desired. Consult your local building code agency to ensure compliance with local codes, including permits and inspections. The following factors should be taken into consideration: • Clearance to side-wall, ceiling, woodwork, and windows. Minimum clearances to combustibles must be maintained. • This fireplace may be installed along a wall, across a corner, or use an exterior chase. See Figure 4 for suggested locations. • Location should be out of high traffic areas and away from furniture and draperies due to heat from appliance. • Never obstruct the front opening of the fireplace. • Do not install in the vicinity where gasoline or other flammable liquids may be stored. • Vent pipe routing. See Venting section found in this manual for allowable venting configurations. •These units can be installed in a bedroom or bathroom . See National Fuel Gas Code ANSI Z233.1/NFPA 54 (current edition), the Uniform Mechanical Code — (current edition), and Local Building Codes for specific installation requirements. Figure 4 - Locating Gas Fireplace A Flat on Wall B Cross Corner C Island** D Room Divider* E Flat on Wall Corner* F Chase Installation Y 7" Minimum ** Island (C) and room divider (D) installation is possible as long as the horizontal portion of vent system (X) does not exceed 15'. See Installing Horizontal Termination Configuration on pages 18 and 19. * When you install your fireplace in (D) room divider or (E) flat on wall corner positions (Y), a minimum of 7" clearance must be maintained from perpendicular wall and front of fireplace. ________________________________ 9 04/20/2018 10 L100001 11 The fireplace must be secured to the floor and/or to framing studs as shown in Figure 5. Use two (2) wood screws or masonry/ concrete screws to secure fireplace to the floor. Use four (4) screws to attach fireplace to framing. The side brackets are adjustable from 1/2" to 5/8" to accommodate different thickness of material. SECURING FIREPLACE TO FLOOR OR FRAMING Figure 5 - Securing Fireplace to Floor and Framing Studs Framing Screws Side adjustable bracket Screws Screws Side adjustable bracket Side adjustable bracketSide adjustable bracket _ _ _ __ _ _ __ _ _ __ _ _ __ _ _ __ _ _ _NOTE: If installed in mobile home, fireplace must be bolted securely to floor. 04/20/2018 10L100001 11 CLEARANCES CLEARANCES TO COMBUSTIBLES MANTEL CLEARANCES NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual. Figure 6 - Clearances Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard. The appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending full width and depth of the appliance. WARNING The fireplace face may be completely covered with any non-combustible ma- terial. Allow clearance for removal of front air panel 66 6 666 6 614" minimum 90" minimum Minimum 7" from both side walls 12" maximum depth COMBU S T I B L E M A N T E L and glass door. Clearance to Combustibles Sides 0" (0 mm) Floor 0" (0 mm) Back 0.5" (13 mm) Standoff 0" (0 mm) (915 mm) Front 36" 04/20/2018 12 L100001 13 INSTALLATION PRECAUTIONS Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions. Only a qualified installer/service person should install venting system. The installer must follow these safety rules: •Wear gloves and safety glasses for protection. •Use extreme caution when using ladders or when on rooftops. •Be aware of electrical wiring locations in walls and ceilings. The following actions will void the warranty on your fireplace: •Installation of any damaged venting component. •Unauthorized modification of the venting system. •Installation of any component part not manufactured or approved by Spark Modern Fires. •Installation other than permitted by these instructions. FINISHING MATERIAL NOTE: Any remote wiring (i.e. remote control, wall switch, and optional fan) must be done prior to final finishing to avoid costly reconstruction. INSTALLATION INFORMATION VENT INSTALLATION Never obstruct or modify the air inlet or outlet. This may create a fire hazard. WARNING Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life. Failure to follow these instructions will void the warranty. NOTICE WARNING State of Massachusetts: The installation must be done by a licensed plumber or gas fitter in the Commonwealth of Massachusetts. 04/20/2018 12L100001 13 VENT INSTALLATION Figure 7 - Combustible Clearances for Vent Pipe WARNINGThis fireplace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems. WARNING Horizontal sections of this vent system require a minimum clearance of 3" from the top of the pipe and 1" minimum to the sides and bottom. Vertical sections of this system require a minimum of 1" clearance to combustible materials on all sides of the pipe. WARNING 3 ���� " A Minimum of 3" Clearance to the Top Is Required Along Horizontal Length of Pipe until Flue Pipe Goes Through Nearest Wall. 1" Clearance Is Acceptable at the Outside Wall. 04/20/2018 14 L100001 15 VENT INSTALLATION INSTALLATION PLANNING There are two basic types of direct-vent installation: • Horizontal Termination • Vertical Termination It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness. FOR HORIZONTAL TERMINATION Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 12" of run towards the termination. You may use up to three 90° elbows in this vent configuration. See Horizontal Termination Configurations on pages 19 and 20. FOR VERTICAL TERMINATION Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roof line. NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a maximum of 270°. For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required. You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed. It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed. INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required for such venting. Never run the vent pipe level or downward. This may cause excessive temperatures which could cause a fire. WARNING When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible material. Maintain proper clearances to all combustible materials. NOTICE Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes. NOTICE 04/20/2018 14L100001 15 � � � � � � � � � � � � � � � � � � � � � � � � � � � �������� ������������������������������� � � � � � VENT INSTALLATION Figure 8 - Horizontal Vent Termination Location Vent Terminal Air Supply Inlet Area Where Terminals Not Permitted Inside Corner Detail FOR HORIZONTAL TERMINATION MINIMUM DISTANCES A = Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305mm) minimum]. B = Clearance to window or door that may be opened [*12" (305mm) minimum]. C = Clearance to permanently closed window [*minimum 12" (305mm) recommended to prevent condensation on window] D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2) feet (610mm) from the centerline of the terminal [18" (457mm) minimum]. E = Clearance to unventilated soffits [12" (305mm) minimum]. Clearance to vinyl soffit [30" (762mm)]. F = Clearance to an outside corner [*6" (152mm) minimum]. G = Clearance to an inside corner [*6" (152mm) minimum]. H = *Not to be installed above a gas meter/regulator assembly within three (3) feet (914mm) horizontally from the centerline of the regulator. I = Clearance to service regulator vent outlet [*3' (914mm) minimum]. J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12" (305mm)minimum]. K = Clearance to a mechanical air supply inlet [*6' (1829mm) minimum]. L = Clearance above a paved sidewalk or paved driveway located on public property [**7' (2133mm) minimum]. M = Clearance under veranda, porch, deck, or balcony [*12" (305mm) minimum***]. N = Clearance above a roof shall extend a minimum of 24" (610mm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (457mm). * As specified in CAN/CGA B149 Installation Codes. Note: Local codes or regulations may require different clearances. ** A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-family dwellings and serves both dwellings. *** Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. Always maintain minimum clearances around vent systems. The minimum clearances to combustibles for horizontal vent pipe are 3" at the top and 1" at the sides and bottom of the vent system until the pipe penetrates the nearest vertical wall. A 1" minimum clearance all around the pipe must be maintained. Do not pack the open air spaces with insulation or other materials. This could cause high temperatures and may present a fire hazard. WARNING 04/20/2018 16 L100001 17 � ����� ������� ����� ������� � � � �������������12��305��� ���������������2��305��� ����������� � �������������� ��12��305��� � � ��� ������� � � � � �������� ����� �� ��� �������� ��� ������ �������� � �������� ����� ��� ���� ���� �� ������ �������� ����������� � ��� ������� �������������� � ��� ������� � ���������� ���� ������ �� ������ �������� ����������� � �� ������� �������������� � �� ������ � � ��� ������ ������ ������ �������� ������� ������ ������� ���� �� ���� ����������� ���� ������������� ���� ���� VENT INSTALLATION TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE AND NONCOMBUSTIBLE EXTERIORS Figure 9 - Allowable Venting Chart HOW TO USE THE VENT GRAPH The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimensions of the vent system. 1. Determine the height of the center of the horizontal vent pipe exit- ing through the outer wall. Using this dimension on the Sidewall Vent Graph below, locate the point intersecting with the slanted graph line. 2. From the point of this intersection, draw a vertical line to the bottom of the graph. 3. Select the indicated dimension, and position the fireplace in accordance with same. Example: If the vertical dimension from the floor of the fireplace is 11' (3.4m) the horizontal run to the face of the outer wall must not exceed 18'. Example: If the vertical dimension from the floor of the unit is 7’ (2.14m), the horizontal run to the face of the outer wall must not exceed 20 '. Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system.Figure 10 - Rear Wall Venting Graph Horizontal Dimension (Ft) From the Outside of Termination to the Back of the FireplaceVertical Dimension (Ft) From the Floor of Unit to the Center of the Horizontal Vent PipeDimensions in Feet 50 48 46 44 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 2 4 6 8 16141210 18 20 04/20/2018 16L100001 17 ����� ������� Figure 12 - Vent Opening Requirements Note: Horizontal runs of vent must be supported every three feet (914mm). Use wall straps for this purpose. Figure 13 - Rigid Vent Pipe Connections Female Locking Lugs Male Slots REAR WALL VENT INSTALLATION When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance • The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See Figure 11. • Only one 60° elbow is allowed in these installations. VENTING INSTALLATION 1. Locate and cut the vent opening in the wall. For com- bustible walls first frame in opening. See Figure 11. Combustible Walls: Cut a 9 Noncombustible Walls: Hole opening should be 71⁄2" (190mm) in diameter. 2. Rigid vent pipes and fittings have special twist-lock connections. Assemble the desired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor. Twist-lock Procedure: The female ends of the pipes and fittings have three locking lugs (indentations). These lugs will slide straight into matching slots on the male end of adjacent pipes and fittings. Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. See Figure 13. 1 Figure 11 - Rear Vent Application, Maximum Horizontal Distance 66Maximum 20" "H x 9 " W (229mm x 229 mm) hole through the exterior wall and frame as shown. See Figure 12. �� �229��� �� �229��� "W (229mm x 229mm ) rectangle hole (fo r noncombustible material such as masonry block or concrete, a 7 (229mm X 229mm) rectangle hole through combustible exterior wall (7 "H x 9 3. Attach vent pipe assembly to the fireplace. Set fire- place in front of its permanent location to insure minimum clearances. Mark the wall for a 9 vent pipe end. Be sure to allow for 1/2" [190mm] diameter hole is acceptable). See Figure 11. The center of the hole should line up with the center line of the horizontal rigid minimum rise. Cut a 9"x9" /2" [190mm] diameter hole if noncombustible). Frame as necessary. Allow 1/4" minimum rise per foot. See Figure 12. 04/20/2018 18 L100001 19 HOT HOT VENT INSTALLATION 4. Apply a bead of non-hardening mastic around the outside edge of vent cap. Position the vent cap in the center of hole on the exterior wall with the word “UP” on the vent cap facing up. Insure proper clearance of 1" to combustibles is maintained. Attach the vent cap with four wood screws sup- plied. See Figure 14. NOTE: Replace the wood screws with appropriate fasteners for stucco, brick, concrete, or other types of siding. For vinyl siding, stucco, or wood exterior use vinyl siding stand- offs between vent cap and exterior wall. The vinyl siding standoff prevents excessive heat from melting the vinyl siding material. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of the standoff instead of the vent cap assembly. Use wood screws provided to attach the standoff. See Figure 15. 5. Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap. See Figure 16. 6. Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 11/4". Apply silicone to the outer pipe connection. Fasten all vent connections with screws provided. 7. Slide the wall thimble against the interior wall surface and attach with srews. See Figure 16. Figure 14 - Installing Horizontal Vent Cap REAR WALL VENT INSTALLATION (continued) Figure 15 - Installing Vinyl Siding Standoff Apply Mastic to All Four Sides Vent Cap Wood Screw Cut Vinyl Siding Away to Fit Standoff Wood Screw Vent Cap Bolt Apply Mastic to All Four Sides Nut Standoff Figure 16 - Connecting Vent Cap with Horizontal Vent Pipe Interior Wall Surface Decorative Wall Thimble Horizontal Vent PipeScrew Vent Cap (Horizontal Termination) Deflecting Shield Do not recess vent termination into any wall. This will cause a fire hazard. WARNING 04/20/2018 18L100001 19 VENT INSTALLATION HORIZONTAL TERMINATION CONFIGURATIONS — RIGID VENTING Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust exhaust, certain limitations as to vent configurations apply and must be strictly adhered to. The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the various dimensions allowable. See page 16. Minimum clearance between vent pipes and combustible materials is 3" on top and 1" from bottom and sides unless otherwise noted. When vent termination exits through foundations less than 20" below siding outcrop, the vent pipe must flush up with the sid- ing. It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length. The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition Elbow) to the face of the outer wall. Figure 18 - Maximum Three (3) 90 Elbows Per Installation • The maximum number of 90° elbows per side wall installation is three (3), the maximum horizontal run is 20" (Figures 18, 19). Figure 19 - Maximum Horizontal Run 3 x 90° Elbows 20" Max. 20" Max. The Commonwealth of Massachusetts requires the installation and USE of Carbon Monoxide detectors in the rooms of ALL direct vent units which utilize a SIDE WALL VENTING TERMINATION FOR STATE OF MASSACHUSETTS: / / 04/20/2018 20 L100001 21 VENT INSTALLATION 7'6" A B•If a 90° elbow is used in the horizontal vent run (level height maintained) the horizontal vent length is reduced by 36" (914 mm) (Fig. 21 A and B) This does not apply if the 90° elbows are used to increase or redirect a vertical rise. See Figure 19. Example: According to the vent graph (page 16) the maximum horizontal vent length in a system with a 7.5' vertical rise is 20’ (6m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17' (5.2 m). In Figures 20 and 21, Dimension A plus B must not be greater than 17' (5.2m). •The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run. •For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system. •The maximum number of elbow degrees in a system is 270°. See Figure 22. Figure 21 - Maximum Vent Run with Elbows Figure 20 - Horizontal Run Reduction Figure 22 - Maximum Elbow Usage 90° A + B = 17' Maximum 90° Elbow = 3' 1 + 2 + 3 + 4 = 270° 1 2 3 1 2 3 4 7'6" 10'A 7'B HORIZONTAL TERMINATION CONFIGURATION — RIGID VENTING (Continued) Example: Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total Angular Variation = 270° 04/20/2018 20L100001 21 VENT INSTALLATION BELOW GRADE INSTALLATIONS — RIGID VENTING When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall. Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area. If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24". 1. Establish vent hole through the wall. See Figure 12, page 17. 2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Figure 21. 3. Install vent system. 4. Ensure a watertight seal is made around the vent pipe coming through the wall. 5. Apply high temperature sealant caulking (supplied) around the 4" and 7" snorkel collars. 6. Slide the snorkel into the vent pipes and secure to the wall. 7. Level the soil so as to maintain a 4" clearance below snorkel. See Figure 23. Figure 24 - Snorkel Installation, Recessed FoundationFigure 23 - Below Grade Installation Ground Window Well Gravel Foundation Wall Firestop 36" Minimum Foundation Recess Watertight Seal Around Pipe Sheet Metal Screws Wall Screws Snorkel • Do not back fill around snorkel. • A clearance of at least 4" must be maintained between the snorkel and the soil. IMPORTANT: For below grade installations IMPORTANT: If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8x1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. See Figure 24. a 12" minimum clearance above grade for the ter- mination vent must be maintained for all termina- tions including the snorkel vent application for basements. 4" Minimum 12" Minimum Drain 12" Minimum Screws CLEARANCES 04/20/2018 22 L100001 23 Restrictor Disk VERTICAL THROUGH-THE-ROOF APPLICATIONS — RIGID VENTING ONLY using a maximum of two 90° elbows. See Figure 25. Figure 25- Support Straps for Horizontal Runs VENT INSTALLATION Figure 26 - Maximum Elbow Usage • Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450mm). Example: Maximum horizontal length No elbows = 10’ (3m) 1x45° elbows = 8.5’ (2.6m) 2x45° elbows = 7’ (2.1m) • A minimum of an 8' (2.5m) vertical rise is required. • Two sets of 45°elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows. See Figure 26. •88 Series fireplaces allow for offsets. This application will require that you first determine the roof pitch and use the appropriate starter kit. • The maximum angular variation allowed in the system is 270°. See Figure 26. • The minimum height of the vent above the high- est point of penetration through the roof is 2' (610mm). 40' Maximum Height 8' Minimum Height 40' Maximum Height 8' Minimum Height 10'Maximum 10'Maximum 1 2 3 4 1 2 3 4 Support Straps Every 3' Support Straps Every 3' Example: Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total Angular Variation = 270° Support Straps Every 5'Vertical Restrictor Disk Restrictor Disk Restrictor Disk RESTRICTOR DISC NOTE: The restrictor disc included with the installation instructions should be used on vertically terminating installations only. Install the restrictor disc into the flue collar of the appliance with the bar horizontal. This Gas Fireplace has been approved for, •Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system 04/20/2018 22L100001 23 ����� VENT INSTALLATION INSTALLATION FOR VERTICAL TERMINATION 1. Determine the route your vertical venting will take. If ceiling joist, roof rafters or other framing will obstruct the venting system, consider an offset. See Figure 27 to avoid cutting load bearing members. NOTE: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shows in Figure 10, page 16. 2. Set fireplace in desired location. Drop a line plumb down from the ceiling to the position of the flue exit. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole a this point. Drop a plumb line from the inside of the roof to the ceiling locat- ing hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point. 2. Assemble the desired lengths of pipe and elbows necessary to reach from the burner system flue up through the firestop. Be sure pipe and elbow connections are fully twist-locked. See Figure 13, page 17. Figure 27 - Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45° Elbows Ceiling Firstop Figure 28- If area above is a room, install firestop above framed hole as shown Figure 29 - If area above is not a room, install firestop below framed hole as shown Continued on next page Firestop Nails Nails Firestop FLAT CEILING INSTALLATION 1. Cut a 9 " (229mm) square hole in the ceiling using the page 17 using framing lumber the same size as the ceiling joist. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. See Figure 28. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side. See Figure 29. 3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof). The 9" x 9" Figure 12 on page 17. locating hole as a center point The opening should be framed to 9" (229mm x 229mm) inside dimensions as shown in Figure 12, (229mm x 229mm) hole must be measured on the horizontal. Actual length may be larger depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials. (Insulation should be considered a combustible material) Frame the opening as shown in 04/20/2018 24 L100001 25 VENT INSTALLATION 4. Connect a section of pipe and extend up through the hole. NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet. Use wall straps for this purpose. See Figure 25, page 22. Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the ue gases and intake air. 5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance from the vent pipe to combustible materials. 6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements. NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem. NOTE: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure to meet the minimum allowable clearances to combustibles. Do not fill any of the required clearance spaces with insulation. Figure 30 - Cathedral Ceiling Support Box Installation Figure 31 - Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT: Review all information on previous page before planning this installation. Cathedral ceiling installations can be very tricky. 1. Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box. Mark the outline of the cathedral ceiling support box on the roof sheathing using the locating hole as a center point. 2. Cut the hole 1/8" larger than the support box outline. See Figure 30. 3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" ( 50 mm) below ceiling. See Figure 30. Align the support box vertically and horizontally using a level. Temporarily tack the support box in place through the inside walls and into the roof sheet- ing. 4. Using tin snips, cut the support box from the top corners down to the roofline and fold the resulting flaps over the roof sheeting. See Figure 31. Apply a bead of non-hardening mastic around the top edges of the support box to make a seal between the box and the roof. Nail in place with roof- ing nails. Remove any combustible material that might be inside the support box. 5. Complete the cathedral ceiling installation by following the same procedures outlines in steps 2 through 6 for Flat Ceiling Installation, page 23 and above. Level Cathedral Ceiling Support Box 2" Minimum Below Finished Ceiling Cut Hole 1/8" Larger than Support Box when Projected onto Roofline Apply Non-hardening Mastic Under all Edges of Support Box before Nailing 04/20/2018 24L100001 25 Figure 32 - External Regulator with Vent Pointing Down (Propane/LP Only) FIREPLACE INSTALLATION CHECK GAS TYPE Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or conversion kit. INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION INSTALLATION ITEMS NEEDED Before installing fireplace and burner system, make sure you have the items listed below. • External regulator (supplied by installer) • Piping (check local codes) • Sealant (resistant to propane/LP gas) • Equipment shutoff valve*• Test gauge connection* • Sediment trap (recommended) • Tee joint • Pipe wrench • approved flexible gas line with gas connector (if allowed by local codes — not provided) * A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer. For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 32.Pointing the vent down protects it from freezing rain or sleet. External Regulator 100 lb. (min) Propane/LP Supply Tank Vent Pointing Down When using copper or flex connectors use only fittings approved for gas connections. The gas control inlet is 3/8" NPT. A qualified installer or service person must connect appliance to gas supply. Follow all local codes. WARNING For propane/LP units, never connect fireplace directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP supply. CAUTION Use only new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (listed on data plate) at the maximum flow rate (BTU/hr). Undue pressure loss will occur if the pipe is too small. CAUTION 04/20/2018 26 L100001 27 �� � � � � � � � FIREPLACE INSTALLATION A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. See Figure 33. IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the fireplace. Check your building codes for any special requirements for locat- ing equipment shutoff valve to fireplaces. Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves. We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 33. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly. Figure 33 - Gas Connection Tee Joint Pipe Nipple Cap Approved Flexible Gas Line CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap* Sediment Trap/Drip Leg Natural Gas From Gas Meter (5" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 13" W.C. Pressure) NOTE : The gas line connection may be made using 1/2" rigid tubing or an approved flex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CAN/CGA-B149 (1 or 2) Installation Code. Only persons licensed to work with gas piping may make the necessary gas connections to this appliance. WARNING A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. See Figure 33. CAUTION Use pipe joint sealant that is resistant to liquid petroleum (LP) gas. CAUTION 04/20/2018 26L100001 27 CHECKING GAS PRESSURE 1. Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately. gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a solution of 50/50 water and soap or a gas sniffer. 4. To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. See Figure 34. After taking pressure reading, be sure and turn captured screw clockwise firmly to reseal. Do not over torque. Check test points for gas leaks. Figure 34 - Gas Pressure Check at Gas Valve Do not use open flame to check for gas leaks. WARNING FAN ASSEMBLY DIAGRAMS Speed Control Control Shaft Control Knob Switch Bracket Blower Plug-In Duplex Outlet (Located underneath firebox floor agains Blower LocationSide View Strips Exhaust Port Screw Green Ground Wire Spade Terminals Lower Firebox CavityFRONT BACK(see page 5) BLOWER/FAN LOCATION Outlet Pressure Tap Pilot Adjustment Inlet Pressure Tap lower right outside wall, as shown on page 5) Velcro 2. The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa). . After completing gas line connection, purge air from 5. Install and attach 1/2" gas line onto shut-off valve. 3.To ease installation, a 24" fex line with manual shut-off valve has been provided with on this appliance. 04/20/2018 28 L100001 29 ELECTRICAL INSTALLATION ELECTRICAL WIRING Electrical connections should only be performed by a qualified, licensed electrician. Main power must be off when connecting to main electrical power supply or performing service. All wiring shall be in compliance with all local, city, and state codes. The appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code ANSI/ NFPA 70 (latest edition) and Canadian Electrical Code, CSA C22.1. WARNING Label all wires before disconnecting when servicing controls. Wiring errors can cause improper and dangerous operation. CAUTION This fireplace requires 110V AC electrical supply for normal operation in order to power up blower and 7V DC adapter which is required to operate Remote Control. However, during power outage situation, its electronic system (DFC board) can be temporarily powered with 6V DC battery pack (4 AA batteries). 04/20/2018 28L100001 29 GLASS REMOVAL GLASS REMOVAL 3.Loosen and remove the three nuts at the top of the glass door frame. 4.Carefully lift the glass door assembly out of the lower channel and remove by angling the frame down to the left GLASS FRAME REMOVAL 1.Remove the front air panel using a screwdriver to lift from center if necessary. 2.Remove the left and right side panels by lifting up and moving to the center. and tilting out the upper right corner. Figure 36 - Removing Glass Frame Front air panel Left side panel Right side panel Glass door Nuts and Washers NOTE: Avoid contacting the glass to any surface and be carefull to not damage any of the controls in the lower cavity. 04/20/2018 30 L100001 31 FINAL INSTALLATION MEDIA TRAY PLACEMENT (optional) 1.Place media tray (see figure 37) on the support brackets as shown on figure 38. 2.Fill the tray with media supplied. Do not place media on burner or block air flow between burner and tray (see figure 39). Figure 37 - One piece media tray Figure 38 - Placing media tray Figure 39 - Filling the tray with media 04/20/2018 SAFETY SCREEN INSTALLATION WARNING: A barrier (safety screen) designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shell be installed for the protection of children and other at-risk individuals. IMPORTANT: Safety Screen must be in place when the fireplace is in operation. If the barrier becomes damaged, the barrier shall be replaced with the manufacturer's barrier for this appliance. Any safety screen, guard, or barrier removed for servicing the appliance, must be replaced prior to operating the appliance. STEP 4: Center screen door screen door over 31 the small studs and secure the screen in place. Using the nuts provided attach the screen firmly. STEP 3: Position the safety screen inside of the fireplace in front of the glass door. Locate the two small vertical studs along the glass door frame bracket. STEP 2: Angle the safety screen as shown on the picture and carefully bring into the fireplace opening. STEP 1: Remove front air panel and both side panels. 04/20/2018 32 SAFETY SCREEN INSTALLATION (continued) STEP 5: Insert the right side panel into the STEP 6: Match up the tabs in the panel with opening angling in at the top.the slots in the face and slide downward. Make sure the side panel is secured properly. Repeat Steps 5 and 6 for the Left Side Panel. STEP 7: Angle the Air Front Panel beneath the bottom of the screen. Support the Air panel on the left and right Side Panels. STEP 8: Tilt the Panel down to rest on the face support. 04/20/2018 OPERATING FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTING A. This appliance is equipped with an ignition device which automatically lights the pilot. Do Not try to light the pilot by hand. use any phone in your building. • Immediately call your gas supplier from a neigh- bor's phone. Follow the gas supplier's instruc- tions. •If you cannot reach your gas supplier, call the fire department. C. Main gas valve in this appliance is not serviceable and does not have any control knobs or switches to operate. Do not remove heat shields covering the valve and electronic devices; do not try to repair or modify the valve as it may result in a fire or explo- sion. Call a qualified service technician if you have any safety concerns. D. Do not use this appliance if any part has been under water. Immediately call a qualified service techni- cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water. OPERATING INSTRUCTIONS 1.STOP! Read the safety information, starting on page 2. Remove media tray from the appliance (see Illustrated parts list), 3. Turn off all electric power to the appliance. Unplug DC adapter from the power outlet. 4. Do not attempt to light the pilot by hand. 5.Lift and remove heat shield covering electronic com- ponents inside of the unit (see illustrated parts list). If you don't smell gas, go to the next step. Note:Before applying any power supply to the DFC board, please verify that the electrical connections illustrated parts list), or mounted in adjacent wall. Make sure that the remote receiver switch is in "REMOTE" (middle) position. Initializing the System for the First Time 1.Set the remote receiver switch to the OFF position. WARNING:If you do not follow these instructions exactly,a fire or explosion may result causing property damage, personal injury or loss of life. REMOTE 5. Turn main shutoff valve counterclockwise to ON position. 6. Set remote receiver switch to OFF position. 7. Wait five (5)minutes to clear out any gas. Then smell for gas, including near the floor.If you smell gas, STOP! Follow "B"in the safety information. 9. Connect the wire to the DC input plug at the unit. 10. Locate remote receiver either inside the unit (see B. BEFORE LIGHTING:smell all around the appli- ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS: • Do not try to light any appliance. • Do not touch any electric switch; do not are in accordance to Wiring Diagram. 8.Plug supplied DC adapter into 110V power outlet. 11.Replace access panel (i.e inner cover or optional media tray). 2.Make sure that fresh set of AA batteries are installed into the battery holder and verify the polarity indicated on the battery holder.If necessary, connect the battery holder to the DFC's main wiring harness. OPERA TING INSTRUCTIONS Figure 43 - Remote Receiver Switch in OFF Position Figure 42a w Remote Receiver Switch in OFF Position Fiqure 42b - Remote Receiver Switch in REMOTE Position 3304/20/2018 26 If pilot does not stay lit, contact a qualified service person or gas supplier for repairs. Figure 9d - Remote Receiver Switch in ON Position 1.Slide the remote receiver switch to the ON position. This will allow the main burner to ignite. 1.Slide the remote receiver switch to the OFF position. This will turn off the main burner. levels by using the equipment shutoff valve. from home for long periods of time. Heater may come on automatically with remote receiver switch in the "REMOTE" position. TO TURN OFF GAS TO APPLIANCE 1.Tum off all electric power to the appliance if service is to be performed.Unplug DC adapter from the power outlet. 2.If necessary, remove access panel from the appliance to access manual shutoff valve on gas line. 3.Turn the gas control manual valve clockwise to the full OFF position. 4.If necessary, replace media tray or access panel REMOTE CONTROL OPERATION Proflame G-Fire System Operation Initializing the System for the First Time 1.Install the 4 AA batteries into the receiver batter bay. Note the polarity of the batteries and insert into the battery bay as indicated on the battery covel'(+/-). 2. Place the 3-posilion slider switch in the REMOTE position. 3. Insert the end of a paper clip into the hole marked PRG on the receiver front cover. The receiver will beep three times to indicate that it is ready to syn- chronize with a transmitter. 4.Install the 3 AAA batteries in the transmitter battery bay located on the base of the transmitter. 5.Press the ON button on the transmitter. The receiver will beep four times to indicate the transmitters Temperature Indication Display 1.With the system in the OFF position, press the THERMOSTAT key and the MODE key at the same time. CAUTION: Do not try to adjust heating WARNING: Make sure the remote receiver switch is in the OFF position when you are away Blue LCD display ON/OFF Key THERMOSTAT Key UP/DOWN Arrow KeyMODE Key Manually Turning ON the Appliance Manually Turning OFFthe Appliance command is accepted. The system is now initial- ized. 2. Look at the LCD screen on the transmitter to verify that a °C or °F is visible next to the room temperature. Figure 44 - Remote Receiver Switch in OFF Position Figure 45 - Remote Receiver OPERA TING INSTRUCTIONS (continued) 34 04/20/2018 T Turning ON the Appliance 1.Press the ON/OFF button on the transmitter. The transmitter screen will display all active icons. The receiver will command the DFC board to start the ignition process, Once the pilot flame is lit,the DFC 1.With the system ON and the flame level at maximum height, press the down-arrow key once to reduce the flame height by one step. Continue pressing down- arrow key until flame is turned OFF. 2. Press the up-arrow key to increase the flame hcight. Flame Levell Flame Level 5 Flame Level Max. Room Thermostat (Transmitter Operation) The remote control can operate as a room thermostat. The thermostat can be set to a desired temperature to control the comfort level in the room. 1.To activate this function, press the Thermostat key. The LCD display on the transmitter will change to show that the room thermostat is ON and the set Room Temperature Set Temperature board will open the main valve outlet and the main burner will ignite. A single "beep"from the receiver will confirm the command. Turning OFF the Appliance 1.Press the ON/OFF button 011 the transmitter, The A single "beep" from the receiverwill confirm the command. Proflame GTM the receiver will confirm the command. Note:If you press the up-arrow key while the remote system is ON but the flame is OFF, the flame will come on in the high position, A single "beep" from Flame Height Control transmitter LCD display will only show the room temperature and icon (see Figure 48b). The receiver disconnects and will command the DFC board to turn off the burner. Figure 50 - Remote Control Displaying Room Temperature and Set Temperature temperature is now displayed (see Figure 50). 2. Adjust the set temperature by pressing the up or down-arrow keys until the desired set temperatureis displayed on the LCD screen (see Figure 50). These units have six flame levels (see Figure 49). Figure 46 -Remote Control Display in Farenheit and Celsius Figure 47 - Remote Control Displaying Room Temperature Figure 48 - Remote Control Displaying Flame Levels Figure 49 -Remote Control Displaying Split Flow Mode OPERA TING INSTRUCTIONS (continued) 3504/20/2018 2648D0139 Smart Thermostat The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actual room temperature. As the room temperature gets closer to the set point, the Smart Function will modulate the flame down. 2. To adjust the set temperature, press the up or down-arrow keys until the desired set temperature is displayed on the LCD screen. Key Lock This function will lock the keys to avoid unsupervised operation. 2.To deactivate this function, press the MODE and UP keys at the same time. The lock icon will disappear from the LCD screen. Low Battery Power Detection Receiver The life span of the receiver batteries depends upon various factors: battery quality, Humber of appliance ig- nitions, number of thermostat set point changes, etc. 'Vhen the receiver batteries are low, no "beep" will sound from the receiver when a transmitter command is sent. Replace batteries when this happens, Transmitter The life span of the transmitter batteries depends upon various factors: battery quality, number of appliance ig- nitions, number of thermostat set point changes, etc. Manual Override If the receiver or transmitter batteries are low or de- pleted, the appliance can still be turned on manually. 1.Move the receivers three-position slider to the ON position. This will bypass the remote control feature of the system and the appliance main burner will turn on. Command Definitions Pilot IPI / CPI switch Position of the receiver slider switch Command reference name Commanded Fireplace State Opened, IPI “OFF” “REMOTE” and “OFF received” Turn-OFF Flames OFF Opened, IPI “ON” “REMOTE” and “ON received” Turn-ON Pilot + Main burner flames ON Closed, CPI “OFF” “REMOTE” and “OFF received” Pilot-ON Pilot flame ON Closed, CPI “ON” “REMOTE” and “ON received” Turn-ON Pilot + Main burner flames ON (Transmitter Operation" Proflame GTM ) 1.To activate this function, press the MODE and UP Control Displaying SmartFigure 45d- RemotH Thermostat Function Figure 45e - RemotH Control Displaying Key Lock Mode Figure 45f- Remote Control Displaying Low Battery 1. To activate this function, press the Thermostat key until the word "SMART" appears to the right of the temperature bulb on the LCD screen. keys at the same time. A lock icon will appear on the LCD screen. When the transmitter batteries arc low, an icon will appeal' on the LCD display, Replace batteries when this icon appears. OPERA TING INSTRUCTIONS (continued) 36 04/20/2018 BURNER FLAME The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation. In normal operation, at full rate, and after operat- ing for about 15 to 30 minutes, the flame should be yellow and up to 6 inches high. See Figure 46. If the flame is blue and only in the center, turn off unit and let cool. After unit is cool, remove trays and check to make sure the holes in the burner are not covered with media particles. configuration, and wind effects may cause the flame patterns to vary. AIR SHUTTER ASSEMBLY Air shutter is adjusted at factory: 1/8" for natural gas and 1/4" for propane gas. If necessary, change this by loosening nut and opening or closing the air shutter more. See Figure 47. Figure 46 - Burner Flame Appearance CLEANING AND MAINTENANCE BURNER, PILOT AND CONTROL COMPARTMENT Keep the control compartment and burner areas clean by vacuuming or brushing at least twice a year. Make sure the burner porting, pilot air opening and burner air opening are free of obstructions at all times. PILOT FLAME The flames from the pilot should be visually checked as soon as the heater is installed and periodically during normal operation. The pilot flame must always be present when the fireplace is in operation. See Figure 45. The pilot flame has two distinct flames, one engulfing the flame sensor, and the other reaching to the main burner. BURNER Inspect area around the injector. Remove any lint or foreign material with a brush or vacuum. Turn off gas before servicing fireplace. It is recommended that a qualified service technician perform these check-ups at the beginning of each heating season. WARNING Figure 47 - Adjusting Air Shutter Nut Shutter Opening Figure 45 - Pilot Flame NOTE: The type of installation, vent system 37 04/20/2018 CLEANING AND MAINTENANCE More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageway of the appliance be kept clean. If the vent system is disassembled for any reason, it must be reassembled and secured before the appliance can be used. Thoroughly clean the inside of the glass panel after using the fireplace for ten hours. Periodically clean the glass panel as neces- operation after servicing. gerous operation. Verify proper can cause improper and dan- servicing controls. Wiring errors prior to disconnection when CAUTION: Label all wires Fan Wiring Diagram blower start up and shut off timing. Replace or add media as required following unstallation instructions in the Final Installation section of this manual. MEDIA amount to the glass and wipe off with a damp cloth. After all maintenance has been completed, re-install glass door. the glass should be cleaned off using a nontoxic, non-corrosive, non-abrasive, mild-cleaning solution. Simply apply an adequate To clean glass door, follow “Glass Removal” procedure outlined in the Final Installation section. Film deposit on the inside of •Handle glass door with care to avoid striking or scratching it on hard objects. manufacturer – No substitute materials may be used. •Replace any glass that is chipped, cracked, or broken. Replacement glass door assemblies MUST be supplied by the fireplace •Never operate the fireplace if the glass is broken. •Never operate the fireplace without the glass door properly secured. •Keep children and pets a safe distance away. •NEVER use abrasive materials. •Do not remove the glass when hot. Allow glass to cool before removal. When cleaning the glass, remember: GLASS PANEL system to ensure proper function. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow. Inspect entire venting The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service person. VENT SYSTEM Blue VariableFan Switch Fan Switch(N.O.) Green White On 110/115 V.A.C. BlowerMotor Black Off 1 2 Black BLOWER/FAN ASSEMBLY The fan assembly has an automatic temperature control which will turn the fan on as the fireplace heats up. The fan will turn off as the fireplace cools down. The control knob can be used to turn the fan off or control the fan speed. The heat up time and cool down time is controlled by the temperature disc magnetically mounted under the fireplace bottom. This disc can be moved to adjust the 38 04/20/2018 RIGID VENT COMPONENTS (not supplied with fireplace) ��� 1 3 4 5 6 7 8 9 10 2 ILLUSTRATED PARTS LIST Direct Vent Pro or Item Qty/Box Description Spark Modern Part # Simpson Duravent — 1 30° Starter Elbow for Vertical from Firebox '9$( — 1 60° Starter Elbow for Horizontal from Firebox '9$( 1 1 Simpson Horizontal High Wind Horizontal Termination Cap'9$+& 2 1 High Wind Vertical Termination '9$9&+ 3 6 6” Pipe Length'9$ 3 6 9” Pipe Length'9$ 3 6 12” Pipe Length '9$ 3 6 24” Pipe Length '9$ 3 6 36” Pipe Length '9$ 3 6 48” Pipe Length '9$ 4 6 11” To 14 5/8” Pipe, Adjustable 11 4 6 17” To 24” Pipe, Adjustable 17 5 6 45° Elbow '9$ 6 6 90° Elbow '9$90 7 6 Flashing, 0/12 To 6/12 Roof Pitch '9$) 8 6 Storm Collar '9$6& 9 6 Firestop '9$)6 10 1 Vinyl Siding Standoff '9$966 NOTE: This model is also approved for use with Metal Fab and Selkirk Direct Vent systems. 39 04/20/2018 ILLUSTRATED PARTS LISTS (continued) 15 17 18 19 20 CONTROL COMPARTMENT BURNER COMPARTMENT FIREBOX COMPONENTS ACCESS AND MEDIA COMPONENTS 12 3 4 5 6 7 8 9 10 11 12 21 16 16A 13 14 40 04/20/2018 Proflame Wiring Diagram ILLUSTRATED PARTS LISTS (continued) REMOTE REMOTE Receiver 14 Pin Connector Pilot CPI / IPI MODE 120 Vac INPUT 7 Vdc STABILIZED SUPPLY OUTPUT MOTORIPI/CPI RECEIVER DC SUPPLY SPLIT FLOW ON / OFFTHTPTHDFC SUPPLYDC SUPPLYGROUND 885 PROFLAME Orange Green Chassis connection Remote control GTM This diagram shows replaceable SIT Proflame parts used in your fireplace. 2511 24 22 23 1 5 6 41 04/20/2018 PARTS LIST ILLUSTRATED PARTS LISTS (continued) PART NUMBER KEY No. 87N-E 87P-E DESCRIPTION QTY 10 W100071 W100071 BURNER 1 11 C200003 C200004 PILOT ASSEMBLY 1 12 D100019 D100019 PILOT BRACKET 1 13 F200100 F200100 3/8” NPT X 5/16” COMPRESSION CONNECTOR 1 15 D100015 D100015 INNER FRONT COVER 1 18 D100017 D100017 LEFT SIDE PANEL 1 19 D100030 D100030 GLASS DOOR WITH GASKET 1 20 XXXXXX XXXXXX VARIOUS TRAY MEDIA (“M” MODELS ONLY) SET 22 H200001 H200001 GTM REMOTE CONTROL 1 - D100018 D100018 RIGHT SIDE PANEL (NOT SHOWN) 1 23 H200011 H200011 GTMFS WIRE HARNESS 1 24 H200012 H200012 DFC TO CPI WIRE HARNESS 1 25 H100140 H100140 7V 10mA DC ADAPTER 1 1 H200010....H200010...REMOTE CONTROL RECEIVER 1 5 C200001 C200002 MAIN GAS VALVE 1 7 A100010 A100010 THERMOSTAT, BLOWER WITH SPEED CONTROL 1 6 H100142 H100142 ELECTRONIC CONTROL DFC BOARD 1 8 D200020 D200020 VALVE BRACKET 1 3 C100020 C100020 DUPLEX OUTLET 1 2 D100027 D100027 FAN CONTROL FACE PLATE 1 9 D300017 D300018 ORIFICE 1 - W100075 W100075 SAFETY SCREEN (NOT SHOWN) 1 42 4 C100009 C100009 FLEX CONNECTOR WITH SHUTOFF VALVE 1 14 C100084 C100084 3/8” NPT X 3/8” FLARE CONNECTION 1 16 W100023 W100023 INNER REAR COVER 1 16A W100059 W100059 MEDIA TRAY (OPTIONAL)1 21 C100031 C100031 BURNER CONNECTOR 1 17 W100014 W100014 FRONT AIR PANEL 1 This list contains replaceable parts used in your fireplace.All replacement parts should be ordered from your installer or from Spark Modern Fires at 1-866-938-3846 or on-line at www.sparkfires.com 04/20/2018 TROUBLESHOOTING TROUBLESHOOTING 43 WARNING: Turn off the unit and let cool before servicing. Only a qualified service person should service and repair this appliance. Note: All troubleshooting items are listed in order of operation. SYMPTOM POSSIBLE CAUSE ACTION light pilot after repeated triggering of piezo. after carefully following lighting instructions. A. Wire disconnected. B. Defective ignitor. C. No gas or low gas pressure. D. No Propane/LPG in tank B. Check for spark at electrode and pilot. If no spark and electrode wire is properly connected, replace pilot assembly. C. Check remote/manual shut off valve from fireplace. Low pressure can be caused by bent lines, restricted lines, low pressure line pres- sure. Consult with plumber or gas supplier. D. Check Propane/LPG tank. Refill tank. problem. burner extinguish while in operation too low, causing pilot safety to drop out gases back into system B. Horizontal vent improperly pitched on thermocouple. B. Check horizontal-venting piping is running upward 1/4" per foot. Do not run the pipe level or downward. lifts off burner (ghost- ing) the vent system joints are tight and have no leaks. Ensure that no debris has been blocking the inner air intake at the bottom back of the combustion chamber. Ensure that the glass is properly secure and latch. . Frequent pilot outage A. Pilot flame may be too high or A. Clean and adjust the pilot flame for maximum flame impingement . The pilot and main A. Inner vent pipe leaking exhaust A. Check for flue product leak. Replace defective pipe section. . Flame burn blue and A. Insufficient oxygen being supplied A. Ensure that the vent cap is installed properly and free of debris. Ensure that 3 4 5 . Pilot will not stay lit . Spark ignitor will not 2 1 A. Defective pilot sensor.A. Check that pilot flame impinges on flame sensor. Clean and/or adjust pilot for maximum flame impingement. Ensure sensor is clean. Ensure that the sensor wiring connected to DFC module. If no success, replace pilot assembly. B. Defective DFC module. B. If ignitor continues to spark after pilot is lit, replace the module. A. Open door and check to make sure wire is connected to ignitor. Check wiring connections at the DFC module and gas valve. B. Low gas pressure. B. Check that inlet pressure meets requirements. C. Improper vent cap installation. D. Weak batteries in remote C. Check for proper installation and freedom from debris or blockage. D. Replace AA batteries in remote receiver and AAA batteries in control and receiver. hand held unit. Re-program receiver making sure the battery cover C. Pilot flame wavering off pilot sensor. is properly closed. C. Clean pilot head, make sure sensor is clean. 04/20/2018 NOTES 04/20/2018 Date Purchased: Purchaser/Dealer: Installer: Fireplace S/N on product ID tag: Date Installed: FUEL:◯◯Natural Gas ◯◯L.P. Propane Inlet Pressure Measured After Installation:In. W.C. Manifold Pressure Measured After Installation: High Fire:In. W.C.Low Fire:In. W.C. VENTING: Please Verify The Brand And Model Of Venting Used: Vent Termination (Cap):◯◯Horizontal ◯◯Vertical ◯◯Snorkel Vent Cap Model No: CONFIGURATION:Vent Configuration Sketch Required Below: Total Horizontal Run:Feet/Inches Total Vertical Run:Feet/Inches Quantity 90° Elbows: Quantity 45° Elbows: ALTITUDE:Feet Above Sea Level Was Stove Derated? ◯◯Yes ◯ ◯ No If Yes To What Orifice Size? Unusual Structure Near Vent? ◯◯Inside Corner ◯◯Trees/Shrubs ◯◯Other Termination:(Please Describe) Prevalent Wind Conditions? Other Installation Notes: INSTALLATION RECORDINSTALLATION RECORD The installer should complete the form below that describes the details of the installation. Having this written record of installation information available will greatly expedite trouble-shooting should any problem arise with your fireplace. The installer should keep a duplicate of this form for their records. Accurate com- pletion of this form is required for warranty coverage and for any technical support by Spark Modern Fires. 04/20/2018 LIMITED LIFETIME WARRANTY The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion Chamber, and Steel Burner. BASIC WARRANTYSpark Modern Fires warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of two years from date of instal- lation. After installation, if any of the components manufactured by Spark Modern Fires in the appliance are found to be defective in materials or workmanship, Spark Modern Fires will, at its option, replace or repair the defective components at no charge to the original owner. Spark Modern Fires will also pay for reasonable labor cost incurred in replacing or repairing such components for a period of two years from date of installation. Any products presented for warranty repair must be accompanied by a dated proof of purchase. This Limited Lifetime Warranty will be void if the appliance is not installed by a qualified installer in accordance with installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating in- structions supplied with the appliance, and does not extend to (1) firebox/burner assembly damaged by accident, neglect, misuse, abuse, alterations, negligence of others, including the installation thereof by unqualified installers, (2) the costs of removal, re-installation or transportation of defective parts on the appliance, or (3) identical or consequential damage. All service work must be performed by an authorized service representative. This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness for purpose and of all other obligations or liabilities. Spark Modern Fires does not assume for it any other obligations or liabilities in connection with sale or use of the appliance. In states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional right not covered in the Limited Lifetime Warranty. Spark Modern Fires reserves the right to investigate any and all the claims against this Warranty and decide upon method of settlement. For information about this warranty contact: SPARK MODERN FIRES 99B Greenwood Ave Bethel, CT 06801 USA P. 203.791.2725 F. 203.798.8661 WWW.SPARKFIRES.COM Rev. No: 2/2017 WARRANTY INFORMATION Model: Serial No.: Date Purchased: Date Installed: Always specify model and serial numbers when communicating with the factory. 04/20/2018