HomeMy WebLinkAboutFile Documents.700 Gillespie St.0129.2018.ACBK0129-2018-ACBK_BuildingComments_1
Page: A100 rennovation plan
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
Provide one Van accessible
parking space 1106.1- 1106.5
ARCHITECTURAL PLANS.pdf (8)
Page: A100 rennovation plan
File Name: ARCHITECTURAL PLANS.pdf
Subject: Group
Author: denism
Color:
provide at two accessible
means of egress IBC1009.1
Page: A100 rennovation plan
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
Provide an accessible route from
parking to the outdoor classroom
and from the classroom to an
accessible toilet facility and
drinking fountain IBC 1104.2-3
Page: A101 main level plan
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
Provide a seating plan IBC
section 1029 that includes four
accessible wheelchair spaces
1108.2.2.1. A spec for how the
seats connect to each other per
the IFC 1029.14 as amended by
AFPD.
Page: A101 main level plan
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
If audible communication is
provided assivtive listening
systems are required per
1108.2.716/18 11:23 AMACP_Patio_10122018_permit.pln, /Users/jeffrey/Documents/ACP/ACP_Patio_10122018_permit.plnexisting structure and canopy to be remove
all existingconcretemasonrywalls toremain. typ.
existing slab to be demolished existing slab to be demolished
existing structure and canopy to be remove 146
'
-
8
3
/
4
"
160'-11"365'-5 1/2"338'-9 1/2"
100'-0" T.O. CONC SLAB
OutdoorClassroom
Bethe Hall
Staging AreaArea of Disturbance, perimeterArea of Disturb
a
n
c
e
,
p
e
ri
m
e
t
e
r
GGas Meter
SetbacksOutdoor Classroom Distance to Aspen Centerfor Physics property line:146'- 8 3/4" to East Lot Line338'-9 1/2" to South Lot Line365'- 5 1/2" to West Lot Line
Stranahan Hall
GillespieAvenue
SixthStreet
Aspen Center forPhysics Parking
Aspen Center forPhysics
site plan
Construction Management Plan notesOutdoor ClassroomExisting (Wood and cloth) Outdoor Classroom to be demolished. Existing CMU walls to erected (same impervious area); improved drainage.ParkingParking for construction at the Aspen Center for Physics parking lot. All parking is off st Site AccessAccess to construction site from Gravel Parking LotOff Street Construction Parking on Aspen Center for Physics propertyStranahan HallStone treads outside of Stranahan Hall to be moved temporarily for construction.Water closets and lavatories for construction to utilize Stranahan Hall.Construction office in Stranahan Hall
Provide one Vanaccessible parkingspace 1106.1- 1106.5
PRINT DATE: 10/16/18 11:23 AMACP_Patio_10122018_permit.pln, /Users/jeffrey/Documents/ACP/ACP_Patio_10122018_permit.plnexisting structure and c
existing sl existing sl
existing structure and c
146
'
-
8
3
/
4
"
160'-11"365'-5 1/2"338'-9 1/2"
100'-0" T.O. CONC SLAB
OutdoorClassroom
Bethe Hall
Staging AreaArea of Disturbance, perimeterArea of Disturban
c
e
,
p
e
r
i
m
e
t
e
r
GGas Meter
SetbacksOutdoor Classroom Distance to Aspen Centerfor Physics property line:146'- 8 3/4" to East Lot Line338'-9 1/2" to South Lot Line365'- 5 1/2" to West Lot Line
Stranahan Hall
GillespieAvenue
SixthStreet
Aspen Center forPhysics Parking
Aspen Center forPhysics
SCALE: 1" = 40'3 site plan
Construction Management Plan notesOutdoor ClassroomExisting (Wood and cloth) Outdoor Classroom to be demolished. E erected (same impervious area); improved drainage.ParkingParking for construction at the Aspen Center for Physics parking lot Site AccessAccess to construction site from Gravel Parking LotOff Street Construction Parking on Aspen Center for Physics prope Stranahan HallStone treads outside of Stranahan Hall to be moved temporarily for Water closets and lavatories for construction to utilize Stranahan H Construction office in Stranahan Hall
provide at two accessible means ofegress IBC1009.1
PRINT DATE: 10/16/18 11:23 AMACP_Patio_10122018_permit.pln, /Users/jeffrey/Documents/ACP/ACP_Patio_10122018_permit.pln146
'
-8
3
/
4
"
160'-11"365'-5 1/2"338'-9 1/2"
100'-0" T.O. CONC SLAB
OutdoorClassroom
Bethe Hall
Staging AreaArea of Disturbance, perimeterArea of Disturb
a
n
c
e
,
p
e
r
i
m
e
t
e
r
GGas Meter
SetbacksOutdoor Classroom Distance to Aspen Centerfor Physics property line:146'- 8 3/4" to East Lot Line338'-9 1/2" to South Lot Line365'- 5 1/2" to West Lot Line
Stranahan Hall
GillespieAvenue
SixthStreet
Aspen Center forPhysics Parking
Aspen Center forPhysics
SCALE: 1" = 40'3 site plan
Construction Management Pl Outdoor ClassroomExisting (Wood and cloth) Ou erected (same impervious are ParkingParking for construction at th Site AccessAccess to construction site fr Off Street Construction Parki Stranahan HallStone treads outside of Stran Water closets and lavatories Construction office in Stranah
Provide an accessibleroute from parking tothe outdoor classroomand from theclassroom to anaccessible toilet facilityand drinking fountainIBC 1104.2-3
Aspen Center for Physics129 Emma Rd. Suite ABasalt, CO 81621970 927 4862 info@teaguearch.comwww.harryteaguearchitects.com
700 Gillespie AvenueAspen, CO 81611JOB NO.: 1803
10/12/2018 Permit Set
A101
main level plan
HARRY TEAGUE ARCHITECTS
issuedate
wet stamp
consultant information
3
3
4
4
5
5
6
6
7
7
8
8
2
2
1
1
A A
B B
C C
D D
E E
1A301
1A301
2A301 2A301
5'-11"5'-9"8'8'8'5'-9"5'-11"47'-4"7'-11 3/4"7'-9 1/2"7'-9 1/2"7'-11 3/4"31'-6 1/2"12" typ.12" typ.12" typ.12" typ.Crown at Center T.O. CONC SLAB
100'-0" T.O. EDGE OF CONC SLAB
3A401
1A402
1A401
3A301
6A301
5A301
4A301
New Gravel Fill @entry, to slab New Gravel Fill @entry, to slab
New 4"concrete slabwith 3/8"aggregate
New 4"concrete slabwith 3/8"aggregate
New slabextends tostone treads
Control jointsat grid linesControl jointsat grid lines
existing stonetreads
slope 1/8":1'slope 1/8":1'slope 1/8":1'slope 1/8":1'GENERAL NOTES -
1. REFER TO STRUCTURAL FOR OVERALL GRID DIMENSIONS2. REFER TO STRUCTURAL FOR FOUNDATION DIMENSIONS3. (2) NEW INTERIOR CHALKBOARDS, 14' X 4' x 1/2", OWNERSUPPLIED, FRAMED IN 4" X 4" X1/4" STEEL FRAME
SCALE: 1/4" = 1'-0"1 1st FLOOR PLAN
Provide a seating planIBC section 1029 thatincludes fouraccessible wheelchairspaces 1108.2.2.1. Aspec for how the seatsconnect to each otherper the IFC 1029.14 asamended by AFPD. Aspen Center for Physics129 Emma Rd. Suite ABasalt, CO 81621970 927 4862 info@teaguearch.comwww.harryteaguearchitects.com
700 Gillespie AvenueAspen, CO 81611JOB NO.: 1803
10/12/2018 Permit Set
A101
main level plan
HARRY TEAGUE ARCHITECTS
issuedate
wet stamp
consultant information
3
3
4
4
5
5
6
6
7
7
8
8
2
2
1
1
A A
B B
C C
D D
E E
1A301
1A301
2A301 2A301
5'-11"5'-9"8'8'8'5'-9"5'-11"47'-4"7'-11 3/4"7'-9 1/2"7'-9 1/2"7'-11 3/4"31'-6 1/2"12" typ.12" typ.12" typ.12" typ.Crown at Center T.O. CONC SLAB
100'-0" T.O. EDGE OF CONC SLAB
3A401
1A402
1A401
3A301
6A301
5A301
4A301
New Gravel Fill @entry, to slab New Gravel Fill @entry, to slab
New 4"concrete slabwith 3/8"aggregate
New 4"concrete slabwith 3/8"aggregate
New slabextends tostone treads
Control jointsat grid linesControl jointsat grid lines
existing stonetreads
slope 1/8":1'slope 1/8":1'slope 1/8":1'slope 1/8":1'GENERAL NOTES -1. REFER TO STRUCTURAL FOR OVERALL GRID DIMENSIONS2. REFER TO STRUCTURAL FOR FOUNDATION DIMENSIONS3. (2) NEW INTERIOR CHALKBOARDS, 14' X 4' x 1/2", OWNERSUPPLIED, FRAMED IN 4" X 4" X1/4" STEEL FRAME
SCALE: 1/4" = 1'-0"1 1st FLOOR PLAN
If audiblecommunication isprovided assivtivelistening systems arerequired per 1108.2.7
Page: A103 re ected ceiling plans
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
The plastic roof covering
material is regulated by IBC
section 2609. Please provide a
letter to state your desire for the
use of this proposed structure to
be considered a low-hazard
occupancy and request it to be
exempt from these
requirements.
Page: S2 Lighting
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
Provide a lighting Comcheck
IECC C405
Page: S4 After Renderings of the Structure
File Name: ARCHITECTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
Detail a compliant stair and ramp
at either of these locations
Page: 12
File Name: ROOF CUT SHEETS Polygal Technical Specs.pdf
Subject: PlanCheck
Author: denism
Color:
This is a test for flame spread
index of interior materials.
ROOF CUT SHEETS Polygal Technical Specs.pdf (1)
Page: 1
File Name: STRUCTURAL PLANS.pdf
Subject: PlanCheck
Author: denism
Color:
Provide a completed Special
Inspection Agreement
STRUCTURAL PLANS.pdf (1)
2018 Harry Teague Architects.Aspen Center for Physics129 Emma Rd. Suite ABasalt, CO 81621970 927 4862 info@teaguearch.comwww.harryteaguearchitects.com
PRINT DAT
E
:
10/16/1
8
11:23 AM
700 Gill
e
s
p
i
e
A
v
e
n
u
e
Aspen, CO 81611JOB NO.: 1803
10/12/2018 Permit Set
A103
reflected ceiling plansACP_Pat
i
o
_
1
0
1
2
2
0
1
8
_
p
e
r
m
i
t
.
p
l
n
, /Users/jeff
r
e
y
/
D
o
c
u
m
e
n
t
s
/
A
C
P
/
A
C
P
_
P
a
t
i
o
_
1
0
1
2
2
0
1
8
_
p
e
r
m
i
t
.
p
l
n
HARRY TEAGUE ARCHITECTS
issuedate
wet stamp
consultant information
3 4 5 6 7 821
GFCI-W GFCI-W
GFCI-WEQEQEQEQEQEQEQEQEQEQEQ EQ EQ EQ EQEQ
surface mounted fixture - mounted to the trusses
fixture key WP-GFI receptaclesdirectional surface mounted fixture mounted to the trusses Note:Lighting in accordance with Land Use Code Section 26.575.150 Outdoor Lighting. Lamp used is a3000k, SORAA 95 CRI, 60 Degree Wide LED light, 1040 Lumen. Luminaire is fully shielded.Luminaire to be mounted to the trusses at 9' AFFPre-wire truss for luminaire.Lighting to be connected to (3) new circuits on existing board in Stranahan Hall.dimmable light switches
m
3 4 5 6 7 821
3'-2 3/4"3'-4 1/4"2'-8 1/2"3'-1/2"4'4'4'4'4'4'3'-1/2"2'-8 1/2"3'-4 1/4"3'-2 3/4"
6"4'-4"4'-3 1/2"3'-10 3/4"3'-10 3/4"3'-10 3/4"3'-10 3/4"4'-3 1/2"4'-4"5'-10"
V
I
F
5'-3"
5'-3"
5'-10"~ 22'-0"
V
I
F ~ 18'-3" VIF3'-10"
7'-8"
11'-1"
14'-6"
~ polycarbonate panel width (does not account for purlin width), VIF ~ polycarbonatepanel width, VIF
polycarbonate ribsparallel to rain flowpolycarbonate ribsparallel to rain flowpolycarbonate ribsparallel to rain flow
polycarbonate ribsparallel to rain flowm
12/7.75 12/7.75
12/5.75
12/5.75
3 4 5 6 7 821
1A404
~ 22'-0"
V
I
F ~ 18'-3" VIF3'-10"
7'-8"
11'-1"
14'-6"
2A404 2A404
cedar wood lattice wood frame and cross bracing
m
SCALE: 1/4" = 1'-0"1roof plan with lighting
SCALE: 1/4" = 1'-0"2 roof plan- reflected ceiling planSCALE: 1/4" = 1'-0"3roof plan with cedar mesh
The plastic roofcovering material isregulated by IBCsection 2609. Pleaseprovide a letter tostate your desire forthe use of thisproposed structure tobe considered alow-hazard occupancyand request it to be exempt from theserequirements.
2018 Harry Teague Architects.Aspen Center for Physics129 Emma Rd. Suite ABasalt, CO 81621970 927 4862 info@teaguearch.comwww.harryteaguearchitects.com
700 Gillespie AvenueAspen, CO 81611JOB NO.: 1803
10/12/2018 Permit Set
S2
Lighting
HARRY TEAGUE ARCHITECTS
issuedate
wet stamp
consultant information
3
3
4
4
5
5
6
6
7
7
8
8
2
2
1
1
A A
B B
C C
D D
E E
GFCI-W GFCI-W
GFCI-WEQEQEQEQEQEQEQEQEQEQ EQ EQ EQ EQ EQ EQ
surface mounted fixture - mounted to the trusses
fixture key
WP-GFI receptaclesdirectional surface mounted fixture mounted to the trusses
Note:Lighting in accordance with Land Use Code Section 26.575.150 Outdoor Lighting. Lamp used is a3000k, SORAA 95 CRI, 60 Degree Wide LED light, 1040 Lumen. Luminaire is fully shielded.Luminaire to be mounted to the trusses at 9' AFFPre-wire truss for luminaire.Lighting to be connected to (3) new circuits on existing board in Stranahan Hall.dimmable light switches
m
PAR38 18.5W
Form Factor Operating Temperature Electrical Dimming and FlickerWidth: 122mm (4.80”)Minimum: -40°C (ambient)Wattage: 18.5W Dimmable to <10%Height: 125mm (4.92”)Typical: 70°C - 80°C (base)Power factor: 0.95 Flicker Index: <0.1Weight: 305g Maximum: 90°C (base)Voltage: 120V +/- 12V Percent Flicker: 28%*Frequency: 50/60Hz
930 - 1040 lumen1190 - 1280 lumen9°, 25°, 36°, 60°
2700K, 3000K, 4000KHalogen replacement for indoor & outdoor applications
GENERAL SPECIFICATIONS
POINT SOURCE OPTICS Exceptional beam control enables unique 9° narrow spot and smooth uniform beamsSingle light source, single crisp shadow VP3 VIVID COLOR AND VP3 NATURAL WHITE VIVID series provides accurate color rendering across the visible spectrum from 400nm to 700nm, with CRI/95, R9/95, Rf/90, Rg/100Whiteness rendering matches or exceeds that of halogen and incandescent sources at 2700K and 3000KENERGY EFFICIENCY AND LONG LIFE 85% more energy efficient than standard halogen lampsTypical payback of one year or less Rated lifetime to L70: 35,000hrsWarranty: 3yrs or 25,000hrs whichever comes firstDetailed warranty information available at soraa.com/resources/legal
CERTIFICATIONS JA8-2016-E, RoHS, CE, UL/CUL, FCC Title 47 Part 15B
HIGHLY COMPATIBLENarrow spot compatible with Soraa SNAP System accessoriesThermally and geometrically compatible with standard fixtures and suitable for damp locationsSuitable for fully enclosed fixtures. Can be used with front glass coverWorks with trailing edge and leading edge phase cut dimmers (see www.soraa.com/resources)INTENDED USE AND APPLICATIONS Intended for use in PAR38 compatible recessed downlights, track lighting and other indoor and outdoor applicationsSoraa lamps are designed to safely turn down in any thermal environment not conducive to minimum airflow or proper ventilation
OUTPUT RANGE: VIVID SERIESOUTPUT RANGE: BRILLIANT SERIESBEAM ANGLE RANGE
COLOR TEMPERATURE RANGEAPPLICATION
DIME26
* These Soraa lamps are certified to California’s demanding JA8 standard, which requires <30% flicker
SPECIFICATIONS BY MODEL NUMBER* SORAA LED PAR38 18.5W
CCT: Correlated Color Temperature McA: White Point Accuracy in McA step SNAP: SORAA SNAP System Compatible *Specifications are at stable warm operating conditions (25°C ambient)
Model #Product CodeCCT (K)Beam AngleField AngleCBCP (Cd)Halogen EquivalentTotal Flux(Lm)Efficacy (Lm/W)McAJA8-2018 SNAP
VIVID SERIESSP38-18-09D-927-03 00977 2700 9 16 17200 100 930 50 3 YES YESSP38-18-25D-927-03 00979 2700 25 40 5020 100 930 50 3 YES -SP38-18-36D-927-03 00981 2700 36 60 2320 100 930 50 3 YES -SP38-18-60D-927-03 00983 2700 60 90 1020 100 930 50 3 YES -SP38-18-09D-930-03 00993 3000 9 16 18500 100 1000 54 3 YES YESSP38-18-25D-930-03 00995 3000 25 40 5400 100 1000 54 3 YES -SP38-18-36D-930-03 00997 3000 36 60 2500 100 1000 54 3 YES -SP38-18-60D-930-03 00999 3000 60 90 1100 100 1000 54 3 YES -SP38-18-09D-940-03 01009 4000 9 16 19240 100 1040 56 4 NA YESSP38-18-25D-940-03 01011 4000 25 40 5600 100 1040 56 4 NA -SP38-18-36D-940-03 01013 4000 36 60 2600 100 1040 56 4 NA -SP38-18-60D-940-03 01015 4000 60 90 1140 100 1040 56 4 NA -BRILLIANT SERIESSP38-18-09D-827-03 00985 2700 9 16 22000 120 1190 64 3 NA YESSP38-18-25D-827-03 00987 2700 25 40 6420 120 1190 64 3 NA -SP38-18-36D-827-03 00989 2700 36 60 2960 120 1190 64 3 NA -SP38-18-60D-827-03 00991 2700 60 90 1300 120 1190 64 3 NA -SP38-18-09D-830-03 01001 3000 9 16 23680 120 1280 69 3 NA YESSP38-18-25D-830-03 01003 3000 25 40 6900 120 1280 69 3 NA -SP38-18-36D-830-03 01005 3000 36 60 3200 120 1280 69 3 NA -SP38-18-60D-830-03 01007 3000 60 90 1400 120 1280 69 3 NA -
Provide a lightingComcheck IECC C405
2018 Harry Teague Architects.Aspen Center for Physics129 Emma Rd. Suite ABasalt, CO 81621970 927 4862 info@teaguearch.comwww.harryteaguearchitects.com
PRINT D
A
T
E
:
10/16/1
8
11:23 AM 700 Gillespie AvenueAspen, CO 81611JOB NO.: 1803
10/12/2018 Permit Set
S4
After Renderings ofthe Structure
ACP_P
a
t
i
o
_
1
0
1
2
2
0
1
8
_
p
e
r
m
i
t
.
p
l
n
, /Users/jef
f
r
e
y
/
D
o
c
u
m
e
n
t
s
/
A
C
P
/
A
C
P
_
P
a
t
i
o
_
1
0
1
2
2
0
1
8
_
p
e
r
m
i
t
.
p
l
n
HARRY TEAGUE ARCHITECTS
issuedate
wet stamp
consultant information
Rendering- After, Exterior
Rendering- After, Interior
Detail a compliant stairand ramp at either ofthese locations
- 12 - 4. Technical information 4.1 Acoustic Accordance with DIN 52210-75, the maximum obtainable sound transmission class for a particular thickness is listed below. Sheet Thickness (mm) Sound reduction Values (dB) 4 15 6 - 8 18 10 19 16 21 20 22 25 - 32 23 4.2 Chemical resistance Polygal sheets have been successfully used in combination with building materials and glazing components. The chemical stability depends on many factors such as concentration of the chemical agents and on exposure temperatures. Considering the complexity of chemical compatibility, all chemicals which come into contact with polycarbonate should always be tested. Polygal offers lab service for testing chemical stability and gaskets and sealants which have been approved. In general, polycarbonate is not compatible with PVC (polyvinyl chloride). 4.3 Fire performance Polygal has received high ratings in several major American & European 3rd Party Laboratories. More detailed information and official test reports are available from your local Service Center or authorized dealer. Much of this information can also be found on our website (www.polygal-northamerica.com). Flammability Method Classification* BS 476/7 Class 1 DIN 4102 B-1 (10&16 mm) NSP 92501 M-1, M-2 ASTM D-635 CC-1 ASTM-E-84 Class A EN 13501 B, s1, d0 *Classifications depend on sheet type and thickness. 4.4 UV protection Solar radiation has a harmful component by UV rays which initiate degradation of many polymeric materials including polycarbonate. This depends on geographic locations, seasons, etc. Polygal's polycarbonate sheets feature a specially coextruded UV absorption and protection layer, which provides long-lasting high stability against damaging UV radiation, protects against outdoor weathering and retains its original color and light transmission as shown in the accelerated weathering tests illustrated in the graph below.
This is a test for flamespread index ofinterior materials.
Provide a completed SpecialInspection Agreement