Loading...
HomeMy WebLinkAboutFile Documents.614 North St.0248.2017 (7).ARBK 1 Bighorn Consulting Engineers, Inc. 569 South Westgate Drive, Suite 1, Grand Junction, CO 81505 Phone: 970-241-8709 Fax: 970-241-9514 614 W North, Aspen Mechanical Design Narrative September 14, 2017 This narrative is to provide permit information on the above residence. Full mechanical design will follow to coordinate with architectural layout of the space. General The residence is approximately 4,000 ft2, two-story structure with a basement. Energy Compliance The walls, windows, roof, foundation, partitions, etc will meet the prescriptive requirements of the IECC. Should this deviate from the prescriptive requirements, a ResCheck document will be completed to show compliance. A REMP check sheet will be submitted if necessary with regard to any snowmelt being designed and required renewable energy on the residence. Plumbing Boilers will be installed in the residence for space heating and domestic water heating. The boilers will be similar to the Lochinvar Knight, WHN models. The boilers will take care of the heating in the fan coils, radiant floor heating, kitchen make up air for a hood over 400 CFM and the domestic water load. The loads for those items are as follows: FCā€™s (70,000 BTUH), Kitchen Hood MUA (75,000 BTUH), Radiant Floor (80,000 BTUH), Domestic Hot Water (132,000 BTUH). If we use the boiler for all systems, we can take credit for some of the systems not performing simultaneously. We can credit approximately ½ of the domestic water load. The total boiler load output would be 291,000 BTUH. When you de-rate this for altitude (0.84) and efficiency (0.92) the input for the boiler system needs to be approximately 375,000 BTUH. The project should plan on installing (2) two boilers at WHN-200. These would give slightly more than the load called for in the load calculations and would provide some redundancy in case one boiler was being repaired. Condensate from the boiler system would need to go through a neutralizer as it will be acidic. Domestic hot water will be routed from the mechanical room on the lower level. The water heaters will be sidearm water heaters similar to Lochinvar SIT-60 (2). The heating fluid will come from the boiler system in the residence. M. Blaine Buck 9-15-17 10/11/17 2 Heating, ventilating and air-conditioning The HVAC system in the residence will consist of the following. Fan Coils for cooling and supplemental heating and radiant floor heating for 1st stage of heating. The lower level will have radiant heating installed in the floors. No supplemental heat would be required for this level. A 300 CFM heat recovery ventilator will be required for this level to provide for ventilation. Ducts will be routed from the toilet rooms for exhaust and supply to each room with a small 4ā€ supply duct. Exhaust and outside air will be taken in and/or exhausted through a wall vent. The main level will have radiant heating and a fan coil installed. The fan coil will be approximately 2,000 CFM and have a 4 ton condensing unit on the exterior of the building for cooling. The fan coil will have 4 zones on the main level for separate control. The fan coil shall be variable speed on a VFD so it does not require a bypass damper. The radiant floor will be the 1st stage of heating. The fan coil shall have a heating water coil installed to cover the outside make up air necessary for the kitchen hood as well as enough load to make the air temperature from the fan coil reach 95 degrees in the winter. The condensing unit shall be a minimum 16 SEER similar to the Lennox XC16. The fan coil will be similar to the Lennox CBWMV model sized correctly for the coil and CFM. The upper level will have radiant heating and a fan coil installed. The fan coil will be approximately 1,400 CFM and have a 3 ton condensing unit on the exterior of the building for cooling. The fan coil will have 4 zones on the upper level for separate control. The fan coil shall be variable speed on a VFD so it does not require a bypass damper. The radiant floor will be the 1st stage of heating. The condensing unit shall be a minimum 16 SEER similar to the Lennox XC16. The fan coil will be similar to the Lennox CBWMV model sized correctly for the coil and CFM. The in-floor radiant heating shall be piped at 10ā€ on center piping at ½ā€ in the floor. Each zone and loop shall be routed to manifold boxes at select locations on each level. The boiler system described above shall have pumps for each system for injection pumping, different water temperatures and controls. The domestic water system shall have a priority call when it is in need of boiler water, it will be first priority and will drive the temperature of the heating water system. Exhaust fans will be installed at all toilet room locations to provide code required exhaust in those locations. Grilles, Registers and diffusers will be floor and/or ceiling as required in the spaces. The registers will be installed as near to the outside walls as possible. Linear grilles shall be used in most locations. END OF MECHANICAL NARRATIVE 10/11/17