HomeMy WebLinkAboutFile Documents.625 E Hyman Ave.0011.2019.ACBK0010&0011-2019-ACBK_BuildingComment1 Subject: PlanCheck Page Label: [4] 4 21718.20_Muse Bldg_Permit Layouts - A2-1 Author: justinh File Name: 21718.20_Drawings_2019-02-21.pdf Color: Please show compliant maneuvering clearances at all doors per ANSI 404.2.3, and dimension the clear width at all doors measured from the face of the door open at 90 degrees to the stop (32" minimum) to show compliance with ANSI 404.2.2. Doors to private offices need only have maneuvering clearances on the outside of the door, there is no requirement for accessibility within the individual office suites, the only requirement is to be able to enter the office. Show your 36" wide accessible route and parallel approach at the refrigerator. 21718.20_Drawings_2019-02-21.pdf (2) Subject: PlanCheck Page Label: [6] 6 21718.20_Muse Bldg_Permit Layouts_RCP - A3-1 Author: justinh File Name: 21718.20_Drawings_2019-02-21.pdf Color: This switch should also be shown as being an occupant sensor per C405.2.1 unless a time switch control for the space is existing/proposed. BOOTH 32 SF PHONE R E SCALE: UNIT 103KITCHENETTE 1/2" = 1'-0" 1 A2.1 Please show compliant maneuvering clearances at all doors per ANSI 404.2.3, and dimension the clear width at all doors measured from the face of the door open at 90 degrees to the stop (32" minimum) to show compliance with ANSI 404.2.2. Doors to private offices need only have maneuvering clearances on the outside of the door, there is no requirement for accessibility within the individual office suites, the only requirement is to be able to enter the office. Show your 36" wide accessible route and parallel approach at the refrigerator. EQ.FC-12 880 CFM RA GRILLE 24/8 EXISTING S.A.90 CFM 16" Ø O.S.A. EXISTING 10"Ø BYPASS DAMPER Z D This switch should also be shown as being an occupant sensor per C405.2.1 unless a time switch control for the space is existing/proposed.