Subject: PlanCheck
Page Label: [4] 4 21718.20_Muse Bldg_Permit Layouts - A2-1
Author: justinh
File Name: 21718.20_Drawings_2019-02-21.pdf
Color:
Please show compliant
maneuvering clearances at all
doors per ANSI 404.2.3, and
dimension the clear width at all
doors measured from the face of
the door open at 90 degrees to
the stop (32" minimum) to show
compliance with ANSI 404.2.2.
Doors to private offices need
only have maneuvering
clearances on the outside of the
door, there is no requirement for
accessibility within the individual
office suites, the only
requirement is to be able to
enter the office. Show your 36"
wide accessible route and
parallel approach at the
refrigerator.
21718.20_Drawings_2019-02-21.pdf (2)
Subject: PlanCheck
Page Label: [6] 6 21718.20_Muse Bldg_Permit Layouts_RCP
- A3-1
Author: justinh
File Name: 21718.20_Drawings_2019-02-21.pdf
Color:
This switch should also be
shown as being an occupant
sensor per C405.2.1 unless a
time switch control for the space
is existing/proposed.
BOOTH
32 SF
PHONE
R
E
SCALE:
UNIT 103KITCHENETTE
1/2" = 1'-0"
1
A2.1
Please show compliant maneuvering clearances at all doors per ANSI
404.2.3, and dimension the clear width at all doors measured from the face
of the door open at 90 degrees to the stop (32" minimum) to show
compliance with ANSI 404.2.2. Doors to private offices need only have
maneuvering clearances on the outside of the door, there is no
requirement for accessibility within the individual office suites, the only
requirement is to be able to enter the office. Show your 36" wide
accessible route and parallel approach at the refrigerator. EQ.FC-12
880 CFM
RA GRILLE
24/8
EXISTING S.A.90 CFM
16" Ø O.S.A.
EXISTING
10"Ø BYPASS
DAMPER
Z
D
This switch should also
be shown as being an
occupant sensor per
C405.2.1 unless a time
switch control for the
space is
existing/proposed.