HomeMy WebLinkAboutFile Documents.601 E Hyman Ave.0096.2018.ACBK0096-2018-ACBK_BuildingComment1
Subject: PlanCheck
Page Label: 2
Author: justinh
File Name: 01_Arch_Stamped.pdf
IBC 303.1.2 categorizes an
assembly space with an
occupant load of less than 50 as
a B occupancy. Please revise
this table accordingly. 2 water
closets are required (this would
have been the case for A3
occupancy as well, one unisex
restroom does not meet the
requirement for 2 fixtures and
you do not meet the exceptions
from IPC 403.2 for separate
facilities). You may use a
common restroom located within
500' on an accessible route on
the story above as the second
required water closet, but you
would then need to demonstrate
that the total number of fixtures
for all spaces utilizing these
common restrooms is still being
met.
01_Arch_Stamped.pdf (4)
Subject: PlanCheck
Page Label: 2
Author: justinh
File Name: 01_Arch_Stamped.pdf
Please remove this note as you
are providing a water
fountain/bottle filler. IBC 2902.5
doesn't exempt you from the
requirement of a drinking
fountain, it just allows it to be
placed in a public location
elsewhere on site.
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: 01_Arch_Stamped.pdf
What is housed in this pit? If
mechanical equipment or sumps
are contained or accessed via
this pit compliant access will be
required to be maintained rather
than being optional.
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: 01_Arch_Stamped.pdf
Specifically identify this wall as
non structural (which we can
accept as structural verification
since you've stamped and
signed the plan) or provide
separate structural verification.
2
EXIT
DISTANCE BETWEEN EXITS26'-6"TRAVEL DISTANCE = 87'-10"
CODE NOTESOCCUPANCY CLASSIFICATION: A-3MAXIMUM 'A' OCCUPANCY WITH ONE EXIT: 49PROPOSED OCCUPANCY (BASEMENT TOTAL, EXCLUDING RESTROOM): 31
PLUMBING FIXTURE CALCULATIONS
27 OCCUPANTS / 214/125 OCCUPANTS PER MALE FIXTURE = 0.1114/65 OCCUPANTS PER FEMALE FIXTURE = 0.2227/200 OCCUPANTS PER LAVATORY = 0.1427/5000 OCCUPANTS PER DRINKING FOUNTAIN = 0.05OTHER
14 OCCUPANTS PER SEX1 FIXTURE - MALE1 FIXTURE - FEMALE1 LAVATORY - UNISEX1 DRINKING FOUNTAIN1 SERVICE SINK
NOTESPROJECT PROPOSES 1 UNISEX
NOT REQUIRED PER IBC 2902.5
330 SF
EXEMPT(CEILING HEIGHT = 2'-7" < 5'-6")
SCALE:A0.1-TI 1/8" = 1'-0"
4 BASEMENT LEVEL CODE PLAN
IBC 303.1.2 categorizes an assemblyspace with an occupant load of less than 50
as a B occupancy. Please revise this tableaccordingly. 2 water closets are required
(this would have been the case for A3occupancy as well, one unisex restroom
does not meet the requirement for 2 fixturesand you do not meet the exceptions fromIPC 403.2 for separate facilities). You mayuse a common restroom located within 500'on an accessible route on the story above
as the second required water closet, butyou would then need to demonstrate that
the total number of fixtures for all spacesutilizing these common restrooms is stillbeing met.
EXIT
OCCUPANCY CALCULATION -MECHANICALAREA ÷ OCCUPANT PER SF = OCCUPANT LOAD
523 SF / 300 = 2 OCCUPANTS
UNIT NET AREA BOUNDARY
1 HOUR RATED WALL
2 HOUR RATED WALL
EXIT PATHWAY
*BUILDING IS FULLY SPRINKLERED PER NFPA 13
ANTS PER SEX- MALE- FEMALE
Y - UNISEXG FOUNTAINSINK
NOTESPROJECT PROPOSES 1 UNISEX RESTROOM (EXISTING)
NOT REQUIRED PER IBC 2902.5
N
Please remove this note as you are providing
a water fountain/bottle filler. IBC 2902.5
doesn't exempt you from the requirement of a
drinking fountain, it just allows it to be placed in
a public location elsewhere on site.
002
MECHANICAL
T.O. CONC.88'-0"7'-6"
T.O. CONC.95'-6"
W-1A7.1
W1-TI
A7.1-TI
7'-6"
T.O. PIT BELOW83'-0"3'-0"(
W-6
A7.1
731 SF
001C
PILATES STUDIO T.O. CONC.88'-0"27'-11"REMOVE EXISTING RAILING AND FRAME NEW FLUSH FLOOR OVER PITOPTION: ADD ACCESS PANEL FOR STORAGE
T.O. FIN. FL.88'-0 3/4"
NEW LVT PLANK FLOORING
RECESSED WATER BOTTLE FILLER, 4" M PROJECTION INTO
0
3'-0"(W)
001E
3'-0"(W) x 7'-0"(H)
W2-TIA7.1-TI
What is housed in this
pit? If mechanical
equipment or sumps
are contained or
accessed via this pit
compliant access will
be required to be
maintained rather than
being optional.
OPERTY LINE
GREY DASHED LINES INDICATE
FOOTER OUTLINES BELOW
68'-9"10"
DASHED LINE INDICATES EXISITNG
WALL TO BE DEMOLISHED
Specifically identify
this wall as non
structural (which we
can accept as
structural verification
since you've stamped
and signed the plan)
or provide separate
structural verification.
RB: Level 2 bathroom to be the second
bathroom and is on an accessible pathway
within 500'.
RB: Updated note to reflect there is a code
required fountain on level 1, but this project
proposes a fountain in the basement for
convenience.
RB: There is no equipment in the pit.
RB: Wall has been noted as non-structural.
Subject: PlanCheck
Page Label: [2] 960304-M01-24x36
Author: justinh
File Name: 02_Mech_Stamped.pdf
What category are you using to
calculate Pz? I would think that
a pilates studio would be
categorized as health
club/aerobics room in IMC table
403.1.1 which has an occupant
density of 40 per 1000 sf. This
would make Pz for studio 001C
= 29.24 and Pz for 001B =
22.08. This would significantly
increase the overall CFM
requirement. Please clarify the
methodology behind your Pz
calculation or revise as needed.
Please provide more information
regarding the exhaust rate to
show that your ventilation
system will be approximately
balanced as required by IMC
403.1
02_Mech_Stamped.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 03a_Elec Comcheck.pdf
It appears you've done this
ComCheck using the building
area method, this must be done
using the space by space
method as the entire building is
not a gymnasium. The SF you
are using also seems higher
than what I am measuring.
Provide cutsheets on all fixtures
highlighting NRTL listing and
maximum fixture wattage. Be
sure that you are using max
fixtures wattage on your
ComCheck rather than lamp
wattage unless current limiting
devices are being used (if so,
they need to be shown on the
electrical/lighting plan).
03a_Elec Comcheck.pdf (2)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 03a_Elec Comcheck.pdf
Please fill out the owner/agent
portion on both the lighting and
mechanical ComCheck.
1 SUMMARY
SON]
Ra
[CFM/SQ.FT.]
Pz
[PEOPLE]
Vbz
[CFM]Ez Vot
[CFM]
0.06 13 304 0.8 380
2 SUMMARY
SON]
Ra
[CFM/SQ.FT.]
Pz
[PEOPLE]
Vbz
[CFM]Ez Vot
[CFM]
0.06 6 154
0.8 200
0.06 0 3
DE.
Rp * Pz + Ra * Az (EQUATION 4-1)Vbz / Ez (EQUATION 4-2)Voz (EQUATION 4-3 - SINGLE ZONE SYSTEMS)
G FIXTURE SCHEDULE
CTURER*
DEL #
FAUCET TRIM MFR.* &
MODEL #ACCESSORIES REMARKS
VICTORIAN SQUARE
BASEMENT TENANT
IMPROVEMENT
What category are you using to
calculate Pz? I would think that a
pilates studio would be categorized as
health club/aerobics room in IMC
table 403.1.1 which has an occupant
density of 40 per 1000 sf. This would
make Pz for studio 001C = 29.24 and
Pz for 001B = 22.08. This would
significantly increase the overall CFM
requirement. Please clarify the
methodology behind your Pz
calculation or revise as needed.
Please provide more information
regarding the exhaust rate to show
that your ventilation system will be
approximately balanced as required
by IMC 403.1
COMcheck Software Version 4.0.8.2
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:601 E3. HYMAN AVENUEASPEN, CO 81611
Owner/Agent:Designer/Contractor:ANNA-LISA CONNERSBG BUILDINGWORKS2222 CHAPEL PLACEAC-201AVON, CO 81620ARCONNERS@BGBUILDINGWORKS.COM
Project Information
Energy Code:
VICTORIAN SQUARE
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Pilates studio (Gymnasium)1473 0.94 1385
1385Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Pilates studio ( Gymnasium 1473 sq.ft.)
LED 1: C1: LINEAR COVE LIGHT: Other:1 40 5 204
LED 2: C2: 4' LINEAR COVE LIGHT: Other:1 12 38 451
LED 3: S1: SURFACE ADJUSTABLE ACCENT LIGHT: Other:1 19 25 475
Linear Fluorescent 1: (RL): RELOCATED FLUORESCENT: 48" T8 32W: Electronic:2 1 63 63
Linear Fluorescent 1 copy 1: (E): EXISTING FLUORESCENT: 48" T8 32W: Electronic:2 1 63 63
1256Total Proposed Watts =
It appears you've done this ComCheck
using the building area method, this must
be done using the space by space
method as the entire building is not a
gymnasium. The SF you are using alsoseems higher than what I am measuring.
Provide cutsheets on all fixtures
highlighting NRTL listing and maximum
fixture wattage. Be sure that you are
using max fixtures wattage on your
ComCheck rather than lamp wattage
unless current limiting devices are being
used (if so, they need to be shown on the
electrical/lighting plan).
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
601 E3. HYMAN AVENUE
ASPEN, CO 81611
Owner/Agent:
Project Information
Energy Code:
VICTORIAN SQUARE
Allowed Interior Lighting Power
A
Area Category Flo
1-Pilates studio (Gymnasium)
Proposed Interior Lighting Power
Please fill out the
owner/agent portion
on both the lighting
and mechanical
ComCheck.