HomeMy WebLinkAboutFile Documents.555 E Durant Ave.0017.2019 (8).ACBKInterior Lighting Compliance Certificate Project Title: 2015 IECC Project Type:Alteration Construction Site:Owner/Agent:Designer/Contractor: Project Information Energy Code: Gorsuch Aspen - Ski and Cafe Expansion Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts (B X C) 1-Retail:Sales Area 780 1.59 1240 2-Common Space Types:Storage >=50 - <=1000 sq.ft. 351 0.63 221 1461Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures Retail:Sales Area (780 sq.ft.) LED 1: AM4: Element Multiples 1x4 Open: Other: 4 1 72 72 LED 3: A4: Element Recessed Downlight - 4": Other: 1 11 32 352 LED 4: A2: Element Recessed Downlight - 2": Other: 1 3 12 37 LED 11: L2-f: Linear Window Lt 4.5 W/ft 6.0': Other: 1 2 27 54 Common Space Types:Storage >=50 - <=1000 sq.ft. (351 sq.ft.) LED 3: A4: Element Recessed Downlight - 4": Other: 1 22 32 704 1219Total Proposed Watts = Interior Lighting Compliance Statement Interior Lighting PASSES 02-19-19 05/08/2019 justinh COMcheck Software Version 4.1.1.0 ez8", Inspection Checklist Energy Code: 2015 IECC Requirements: 100.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review fi Req.ID Complies? Comments/Assumptions C103.2 :Plans, specifications, and/or OComplies Requirement will be met. [PR4]1 :calculations provide all information ❑Does Not :with which compliance can be ❑Not Observable :determined for the interior lighting land electrical systems and equi pment ONot Applicable ,and document where exceptions to :the standard are claimed. Information 1 provided should include interior 1, lighting power calculations, wattage of bulbs and ballasts, transformers and 'control devices. Additional Comments/Assumptions: 1 I High Impact (Tier 1) M Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Gorsuch Aspen - Ski and Cafe Expansion Report date: 02/19/19 Data filename: C:\Users\tfrye\Dmpbox (Resort Design)\Resort Design Team Folden24442 Gorsuch - Aspen Page 2 of 5 IhDocs\Gorsuch Aspen - Ski and Cafe Expansion.cck Section # Rough -In Electrical Inspection Complies? Comments/Assumptions & RB .ID C405.2.1 ',Lighting controls installed to uniformly OComplies Requirement will be met. [EL15]r reduce the lighting load by at least ❑Does Not 1,50%. ONot Observable ONot Applicable C405.2.1 (Occupancy sensors installed in OComplies Requirement will be met. [EL181r !required spaces. ❑Does Not ONot Observable ! ONot Applicable C405.2.1, Independent lighting controls installed OComplies Requirement will be met. C405.2.2. per approved lighting plans and all ❑Does Not 3 !, manual controls readily accessible and ONot Observable a [EL23] ',visible to occupants. ONot Applicable C405.2.2. !Automatic controls to shut off all OComplies Requirement will be met. 1 building lighting installed in all ❑Does Not [EL22]2 1, buildings. ONot Observable ONot Applicable C405.2.3 Daylight zones provided with OComplies Exception: Requirement does not apply. [EL16]' individual controls that control the ❑Does Not !, lights independent of general area lighting. ONot Observable ONot Applicable C405.2.3, I Primary sidelighted areas are OComplies Exception: Requirement does not apply. C405.2.3. equipped with required lighting ❑Does Not 1, controls. C405.2.3. ❑Not Observable 2 ONot Applicable [EL201c C405.2.3, Enclosed spaces with daylight area OComplies Exception: Requirement does not apply. C405.2.3. Funder skylights and rooftop monitors ❑Does Not 1, are equipped with required lighting C405.2.3. (controls. phot Observable 3 I ONot Applicable [EL21]c C405.2.4 (Separate lighting control devices for OComplies Requirement will be met. [EL4p specific uses installed per approved ❑Does Not (lighting plans. [-]Not Observable 1 ❑Not Applicable C405.2.4 ,Additional interior lighting power OComplies Requirement will be met. [ELSp allowed for special functions per the ❑Does Not approved lighting plans and is automatically controlled and ONot Observable separated from general lighting. ONot Applicable C405.3 Exit signs do not exceed 5 watts per OComplies Requirement will be met. [EL67r face. ❑Does Not ONot Observable ❑Not Applicable Additional Comments/Assumptions: 1 I High Impact (Tier 1) M Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Gorsuch Aspen - Ski and Cafe Expansion Report date: 02/19/19 Data filename: C:\Users\tfrye\Dropbox (Resort Designs\Resort Design Team Folder\24442 Gorsuch - Aspen Page 3 of 5 hDocs\Gorsuch Aspen - Ski and Cafe Expansion.cck Section # Final Inspection Complies? Comments/Assumptions & RB .ID C303.3, Furnished O&M instructions for ❑Complies Requirement will be met. C408.2.5.:systems and equipment to the ❑Does Not 2 building owner or designated [FI17]s ',representative. phot Observable ONot Applicable C405.4.1 Interior installed lamp and fixture OComplies See the Interior Lighting fixture schedule for values. [FI18]' lighting power is consistent with what ❑Does Not is shown on the approved lighting ❑Not Observable plans, demonstrating proposed watts ONot Applicable :are less than or equal to allowed watts. C408.2.5. (Furnished as -built drawings for OComplies Requirement will be met. 1 :,electric power systems within 90 days ODoes Not [FI16]s !,of system acceptance. ONot Observable '', ONot Applicable C408.3 Lighting systems have been tested to OComplies Requirement will be met. [FI331' :ensure proper calibration, adjustment, ❑Does Not programming, and operation. ONot Observable ONot Applicable Additional Comments/Assumptions: 1 I High Impact (Tier 1) M Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) Project Title: Gorsuch Aspen - Ski and Cafe Expansion Report date: 02/19/19 Data filename: C:\Users\tfrye\Dropbox (Resort Design)\Resort Design Team Folder\24442 Gorsuch - Aspen Page 4 of 5 II\Docs\Gorsuch Aspen - Ski and Cafe Expansion.cck Project Title: Gorsuch Aspen - Ski and Cafe Expansion Report date: 02/19/19 Data filename: C:\Users\tfrye\Dmpbox (Resort Design)\Resort Design Team Folder\24442 Gorsuch - Aspen Page 5 of 5 II\Docs\Gorsuch Aspen - Ski and Cafe Expansion.cck