HomeMy WebLinkAboutFile Documents.720 E Durant Ave.0064.2018 (3).ACBK07/12/2018
justinh
RENEWAIRE.COM 1.800.627.4499 10
SPECIFICATIONS & DIMENSIONS
Specifications may be subject to change without notice.
INDOOR UNIT SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 100-200 CFM
Standard Features:
Painted cabinet
Line-cord power supply
Low-voltage circuit for controls
Unit may be mounted in any orientation
Controls:
Onboard 24 VAC transformer/relay package
with switched dry contacts
Filters:
Total qty. 2, MERV 8, spun-polyester media:
10 1/2" x 21 3/4" x 1"
Unit Dimensions & Weight:
33 1/2" L x 24" W x 20" H
68 lbs.
Max. Shipping Dimensions & Weight (on pallet):
34" L x 44" W x 34" H
110 lbs.
Motor(s):
Qty. 1, Double-shaft standard motor
Accessories:
Backdraft damper 8"
Wall cap 8" - taupe plastic, galvanized,
paintable galvanneal
Louver with 8" round duct connection -
12" (W) x 8" (H)
Percentage timer control (PTL)
Push-button point-of-use controls (PBL), PTL req'd.
Percentage timer control with furnace interlock (FM)
Electric duct heater - EK series (1–60 kW),
for commercial use only
6"Typ. 8 1/8" 9" 5 1/2"Typ.OA EA
RA FA
34" Line Cord24" Overall(with HangingBracket)11 7/8"Typ. 28 3/4" Case
33 1/4" Overall
2 1/4" Typ.
6" Nominal
Typ.
8" Nominal
Typ.18 1/8"Case 2 5/8" 7/8" Typ. 21 3/4" Overall(with Hanging Bracket) 20" Overall 22 1/4" MinimumService Area
(Door can be
Removed fromHinges.)18 1/2"MinimumSercive Area 23 7/8" Case
Door
Swing
24V AC
Control
Terminal
LEFT VIEW FRONT VIEW RIGHT VIEW
TOP VIEW
Model: EV200Drawing Type: Unit DimensionVersion: APR16
ABBREVIATIONSEA: Exhaust Air to outsideOA: Outside Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
INSTALLATION ORIENTATIONUnit may be installed in any orientation.
NOTE1.UNLESS OTHERWISE SPECIFIED,DIMENSIONS ARE ROUNDED TO THENEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
UNIT DIMENSIONS
AIRFLOW CONFIGURATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream
can be switched with OA/FA airstream.
200EV Energy Recovery Ventilator
Standard
Download specification at:
renewaire.com/specifications
UNIT PERFORMANCE CORE PERFORMANCE
Airflow CFM ESP in H20 Temp EFF%Total EFF%
Winter/Summer*
122 0.70 81 77/64
149 0.60 79 75/61
168 0.50 78 73/59
176 0.40 78 72/59
186 0.30 77 72/58
192 0.20 77 71/57
207 0.10 76 70/56
* See HVI certification ratings on page 164 of RenewAire’s Full Line Volume XVIII Catalog.
ELECTRICAL DATA
HP Volts HZ Phase Input Watts FLA
0.1 120 60 Single 157 @ 181 CFM 1.5
Note: Indirect Gas-Fired Duct Furnace is not available on the EV200.
07/12/2018
justinh