HomeMy WebLinkAboutFile Documents.720 E Durant Ave.0064.2018 (20).ACBKYou cannot simply write in a squarefootage on your ComCheck, the changein floor area will change your allowedwatts. This report needs to be re-run
using the correct square footage.
Please type in the owner/agent and
designer/contractor information into the
project information section when
making these changes. When you print
the report be sure to select yes under
the completion status window that pops
up so that it generates a final report
with a place for your signature on the
report.
The spec for the
current limiter you've
provided does not
come in an 8 amp size
which is what would
be required to limit
your track lighting to
960 watts. Please
provide a spec on for
a 8 amp current limiter
or explain how you
intend to limit all track
lighting to 960 watts.
Your ComCheck still is
not showing the 4' LED
lighting fixtures shown
on the RCP and a
spec on it was not
submitted, this
comment still stands
from the previous
round of review.
COMcheck Software Version 4.3.5.1
V Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions' column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Plan Review I Complies? I Comments/Assumptions
Plans, specifications, and/or
UComplies
calculations provide all information
Oboes
Not
with which compliance can be
determined for the interior lighting
Not observable
and electrical systems and equipment
ONot Applicable
and document where exceptions to
the standard are claimed. Information
uiations, wattage of
transformers and
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 1 J2 I Medium Impact (Tier 2) 13 1 Low Impact (Ter 3)
Project Title: Green Joint Report date: 05/14/18
Dam filename: Page 2 of 5
Section
n
Rough -In Electrical Inspection
Complies?
Comments/Assumptions
& Re .IO
C405.2.1
Lighting controls installed to uniformly
OComplies
[EL15]1
reduce the lighting load by at least
ODOe$ Not
SOW
E]Not Observable
[]Not Applicable
C405.2.1
Occupancy sensors installed in
OComplies
[ELi6]'
required spaces.
[]Does Not
[]Not Observable
[]Not Applicable
C405.2.1,
Independent lighting controls installed
DComplies
C405.2.2.
per approved lighting plans and all
DDoes Not
3
manual controls readily accessible and
ONot Observable
[EL2311
visible to occupants.
ONot Applicable
C405.2.2.
Automatic controls to shut off all
OComplies
1
building lighting installed in all
DDoes Not
[EL22]2
buildings.
ONot Observable
[]Not Applicable
C405.2.3
Daylight zones provided with
OComplies
1EL16]'
individual controls that control the
DDoes Not
lights independent of general area
ONot Observable
lighting.
ONot Applicable
C405.2.3,
Primary sidelighted areas are
OComplies
C405.2.1
equipped with required lighting
DDoes Not
1,
C405.2.3.
controls.
ONot Observable
2
[]Not Applicable
[EL20]1
C405.2.3,
Enclosed spaces with daylight area
OComplies
C405.2.3.
under skylights and rooftop monitors
[]Does Not
1,
are equipped with required lighting
ONOt Observable
0405.2.3.
3
controls.
ONm Applicable
[EL21]1
C405.2.4
Separate lighting control devices for
OComplies
[EL4]1
specific uses Installed per approved
DDoes Not
lighting plans.
[]Not Observable
ONot Applicable
C405.2.4
Additional Interior lighting power
OComplies
[ELS11
allowed for special functions per the
DDoes Not
approved lighting plans and Is
ONot Observable
automatically controlled and
Applicable
separated from general lighting.
.[]Not
0405.3
Exit signs do net exceed 5 watts per
OComplies
[EL6]1
face.
'DDoes Not
DNot Observable
ONot Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Green Joint Report date: 05/14/18
Data filename: Page 3 of 5
Section
#
Final Inspection
Complies?
Comments/Assumptions
& Ra .ID
C303.3.
Furnished O&M Instructions for
OComplies
C408.2.5.
systems and equipment to the
ODoes Not
2
building owner or designated
[F1171s
representative.
ONat Observable
ONot Applicable
C405.4.1
Interior installed lamp and fixture
OComplies See the in or Lighting fixture schedule far values.
[1`I18)c
lighting power Is consistent with what
ODoes Not
is shown on the approved lighting
ONot Observable
plans. demonstrating proposed watts
are less than or equal to allowed
ONot Applicable
watts.
C408.2.5.
Furnished as -built drawings for
OComplies
1
electric power systems within 90 days
ODoes Not
(FI16P
of system acceptance.
ONot Observable
ONot Applicable
C408.3
Lighting systems have been tested to
OComplies
[FI3311
ensure proper calibration, adjustment,
[]Does Not
programming, and operation.
ONot Observable
ONot Applicable
Additional Comments/Assumptions:
1 1 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 3'1 Low Impact (Tier 3)
ProjectTitle: Green Joint Report date: 05/14/18
Data filename: Page 4 of 5
Project'ftle: Green Joint Report date: 05114/18
Data filename: Page 5 of 5