HomeMy WebLinkAboutFile Documents.729 W Francis St.0090.2019.ARBK0090-2019-ARBK_BuildingComments_1
Page: 1
File Name: 18041336_729 W Francis St Aspen_Asbestos
Data-1.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a sampling description
narrative from the asbestos
inspector and a copy of the
inspector's license.
18041336_729 W Francis St Aspen_Asbestos Data-1.pdf (1)
Page: 4
File Name: 729Francis_2019.04.22_For PERMIT.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide verification that walls to
be demoed are non-bearing.
Stamped by an engineer or
architect.
729Francis_2019.04.22_For PERMIT.pdf (3)
Page: 5
File Name: 729Francis_2019.04.22_For PERMIT.pdf
Subject: PlanCheck
Author: nickt
Color:
This is a duplex and your scope
will disturb the dwelling
separation at the ceiling. Provide
the original instructions of a
listed 1 hour fire, STC 45 rated
assembly for the ceiling. 2015
IRC R302.3 and appendix K.
Page: 5
File Name: 729Francis_2019.04.22_For PERMIT.pdf
Subject: PlanCheck
Author: nickt
Color:
CO detector required outside
bedrooms per Ordinance 40,
2016.
Provide a sampling
description narrative from
the asbestos inspector
and a copy of the
inspector's license.
BEDROOM 2
LL-10
BEDROOM 1
LL-09
BATH 2
LL-11
BEDROOM 3
LL-07
LIVING RM
LL-01
KITCHEN
LL-03
HALLWAY
LL-06
LAUNDRY
LL-04
DINING
LL-0211"2' - 5"
D1
D1
D8 - CARPET
8"1' - 1"3' - 1 1/2"D1 D1D3D7
7 1/2"7"D1
D3
D1 5' - 7"D1
D7
D10
D7
D7D7
D7
D7
N.I.C. [PART OF UPPER LEVEL - UNIT 2]
D10
D3
D3
D1 D1
D9
D8 - CARPET
D8 - CARPET
D8 - TILE
D8 - TILE
D8 - TILE
D8 - TILE
D8 - TILE
D8 - TILE
BATH 1
LL-08
MUD RM
LL-05
EXISTING ELECTRICAL PANEL TO REMAIN
D1
2' - 6"
NOELLE@MATTERINTERIORS.C
NICOLE STEWARTNICOLE@MATTERINTERIORS.CO
NOTES:
1. REFERENCE COVER SHEET F
2. INFORMATION ON THIS SHEE FIELD SURVEY OBSERVATIONS DRAWINGS. THE DRAWINGS RE INFORMATION AS ACCURATE AS CONTRACTOR SHALL BE RESPO ALL EXISTING CONDITIONS PRIO DESIGNER IMMEDIATELY IF ACT DIFFER FROM INFORMATION IND DRAWINGS.
3. ALL DIMENSIONS ARE FINISH-
4. ALL DIMENSIONS TO BE FIELD CONSTRUCTION AND/OR FABRI
PROJECT
PLANNING APPROVALS
ISSUANCES
729 W FRANCIS S
ASPEN, CO, 8161
Provide verification
that walls to bedemoed arenon-bearing. Stamped
by an engineer orarchitect.
10' - 6 3/4"
1/4" = 1'-0"ID-1.01
2
LOWER LEVEL PROP
REFLECTED CEILING
This is a duplex and your scope will disturb the
dwelling separation at the ceiling. Provide the original
instructions of a listed 1 hour fire, STC 45 rated
assembly for the ceiling. 2015 IRC R302.3 and
appendix K.
EDROOM 2
LL-10
BEDROOM 1
LL-09
BATH 2
LL-11
HALLWAY
LL-06
DROOM 3
LL-07
ID-2.00
2
CLOSET
LL-12
BATH 1
LL-08
MUD RM
EXISTING LIGHT FIXTURE,RELOCATED.
T FIXTURE [ER]
LIGHT FIXTURES [ER]
NEW SD
LIGHT FIXTURES [ER]
LIGHT FIXTURE [ER]
NEW SD
T FIXTURE [ER]
T FIXTURES [ER]
NEW SD
NEW SD
REMOVE EXISTING LIGHT FIXTURES.
PATCH CEILING TO MATCH EXISTING.
LIGHT FIXTURES [ER]
D
N
N
N N
N
1
2 F D IN C
A
D D D
3
4 C
P
NEW CO DETECTORS PER CITY ORDINANCE 31, 2011VERIFY EXISTING SMOKE DETECTOR SYSTEM IS IN OPERATION AND MEETS IRC R314
A MINIMUM OF 75% OF ALL LAMPS INSTALLED IN
PERMANENT LIGHT FIXTURES MUST BE HIGH
EFFICIENCY IN DWELLING UNITS.(2015 IECC R404.1 & C405.1)
NOTES:
CO detector requiredoutside bedrooms per
Ordinance 40, 2016.