HomeMy WebLinkAboutFile Documents.700 Ute Ave.0069.2018 (12).ARBKCalculations approved by ACCA to meet all requirements of Manual J 7th Ed.
2018-Mar-22 15:02:00
Right-Suite® U niv er sal 2017 17.0.21 RSU03203 Page 1
Z:\Retrofit\Bid's\Aspen Alps #215\Project1.rup Calc = MJ7 Front Door faces: S
Job:Load Short Form Mar 21, 2018Date:Entire House By:
Mountain Air Mechanical, Inc.
6001 West 2nd Street Bldg B, Rifle, CO 81650 Phone: 970-625-4352 Fax: 970-625-4356 Email: mjf@mountainair.biz Web: www.mountainair.biz
Project Information
Aspen Alps Unit 215For:
700 Ute Avenue, Aspen, CO
Design Information
InfiltrationClgHtg
SimplifiedMethod821Outside db (°F)
AverageConstruction quality7070Inside db (°F)
1 (Average)Fireplaces1270Design TD (°F)
H-Daily range
5050Inside humidity (%)
050Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 80 AFUE Efficiency 0 SEER
Heating input Btuh0 Sensible cooling Btuh0
Heating output Btuh0 Latent cooling Btuh0
Temperature rise °F0 Total cooling Btuh0
Actual air flow cfm709 Actual air flow cfm709
Air flow factor cfm/Btuh0.023 Air flow factor cfm/Btuh0.053
Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 1.00
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
block load 1161 30741 13251 709 709
Entire House d 1161 30741 13251 709 709
Other equip loads 0 0
Equip. @ 0.87 RSM 11475
Latent cooling 0
TOTALS 1161 30741 11475 709 709
3/30/2018
Calculations approved by ACCA to meet all requirements of Manual J 7th Ed.
2018-Mar-22 15:02:00
Right-Suite® U niv er sal 2017 17.0.21 RSU03203 Page 1
Z:\Retrofit\Bid's\Aspen Alps #215\Project1.rup Calc = MJ7 Front Door faces: S
Job:Project Summary Mar 21, 2018Date:Entire House By:
Mountain Air Mechanical, Inc.
6001 West 2nd Street Bldg B, Rifle, CO 81650 Phone: 970-625-4352 Fax: 970-625-4356 Email: mjf@mountainair.biz Web: www.mountainair.biz
Project Information
Aspen Alps Unit 215For:700 Ute Avenue, Aspen, CO
Notes:
Design Information
Aspen Pitkin Co SARD, CO, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F1 Outside db °F82Inside db °F70 Inside db °F70Design TD °F70 Design TD °F12Daily range H
Relative humidity %50Moisture difference gr/lb0
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh30741 Structure Btuh13251DuctsBtuh0DuctsBtuh0Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
(none)(none)Humidification Btuh0 Blower Btuh0PipingBtuh0Equipment load Btuh30741 Use manufacturer's data n
Rate/swing multiplier 0.87InfiltrationEquipment sensible load Btuh11475
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average1 (Average)Fireplaces Structure Btuh0DuctsBtuh0Central vent (0 cfm)Btuh0
CoolingHeating (none)11611161Area (ft²)Equipment latent load Btuh0
1335213352Volume (ft³)Air changes/hour 0.501.20 Equipment total load Btuh11475
Equiv. AVF (cfm)111267 Req. total capacity at 0.70 SHR ton1.4
Heating Equipment Summary Cooling Equipment Summary
Make MakeTradeTrade
Model CondAHRI ref Coil
AHRI refEfficiency80 AFUE Efficiency 0 SEER
Heating input Btuh0 Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0
Temperature rise °F0 Total cooling Btuh0Actual air flow cfm709 Actual air flow cfm709
Air flow factor cfm/Btuh0.023 Air flow factor cfm/Btuh0.053Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 1.00
3/30/2018