HomeMy WebLinkAboutFile Documents.700 Ute Ave.0069.2018 (18).ARBKConcentric Vent Termination Kit Instructions
Part # KGAVT0501CVT, KGAVT0601CVT
272 Duchaine Blvd.New Bedford, MA 02745 508-763-8071
lp-166 Rev. 3.13.17
STOP! Follow these instructions or warranty will be void!
This installation shall be done by a qualified service agency
in accordance with these instructions, all applicable
codes, and requirements of the authority having
jurisdiction. Failure to follow these instructions could result
in substantial property damage, severe personal injury, or
death.
The manufacturer reserves the right to make changes or updates without notice and will not be held liable for errors in literature.
NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.
Safety Considerations
Installing and servicing heating equipment can be
hazardous due to gas and electrical components. Only
trained service personnel should install or service heating
equipment.
The following defined terms are used throughout this manual
to bring attention to the presence of hazards of various risk
levels or to important product information.
DANGER indicates an imminently hazardous situation which,
if not avoided, will result in serious personal injury or death.
WARNING indicates a potentially hazardous situation which,
if not avoided, could result in personal injury or death.
NOTE: Read the entire appliance installation manual
and these instructions BEFORE starting installation. These
instructions cover installation of the 2” and 3” concentric
vent termination kit ONLY.
Prior to installation, examine all components for possible
shipping damage. When working on heating equipment,
observe all precautions in the literature, on tags, and
on labels attached to the unit. Follow all safety codes. Wear safety glasses and gloves. Have a fire extinguisher
available.
This vent kit is to be used only for terminating HTP boilers
and water heaters. Do not use this kit to terminate any other
appliance. Failure to follow this warning could result in fire,
serious personal injury, or death.
Before beginning any installation or modification, be sure
the main electrical disconnect switch is in the “OFF” position.
Electrical shock can cause serious personal injury or death.
Field supplied pipe and fittings are required to complete
the installation. The combustion air and vent pipe fittings
must conform to American National Standards Institute
(ANSI) and American Society for Testing and Materials
(ASTM) standards D1785 (schedule-40 PVC), D2665 (PVC-
DWV), D2441 (SDR-21 and SDR 26 PVC), D2661 (ABS DWV),
or F628 (schedule-40 ABS). Pipe cement and primer must
conform to ASTM standards D2564 (PVC) or D2235 (ABS).
In Canada, construct all combustion air inlet and exhaust
vent pipes for this unit with CSA or ULC certified Schedule-40
PVC, PVC-DWV pipe and pipe cement.
Do not operate the appliance with rain cap removed. Re-
circulation of combustion products may occur. Water may also
collect inside larger combustion air pipe and flow to burner
enclosure. Operating appliance without rain cap could result in
product damage, improper operation, personal injury, or death.
Figure 1 - Kit Components
Kit Components and Dimensions
Figure 2 - Kit Dimensions
08/09/2018
lp-166 Rev. 3.13.17
2
Roof Termination1. Determine the best location for the termination kit.
NOTE: A roof termination is less susceptible to damage. It has
reduced chances for intake contaminants and less visible
vent vapors.
2. Cut a hole in the roof 4” in diameter for 2” concentric vent,
or 5” in diameter for 3” concentric vent kit.
3. Partially assemble concentric vent termination kit.
a. Cement Y concentric fitting to larger diameter kit pipe
(see Fig. 1).
b. Cement rain cap to smaller diameter kit pipe (see Fig. 1).
4. Install Y concentric fitting and pipe assembly through the
hole in the roof and field supplied boot/flashing. NOTE: Do
not allow insulation or other material to accumulate inside
the pipe assembly when installing through the hole.
5. Secure assembly to roof structure as shown in Fig. 4 using
field supplied metal strapping or equivalent support material.NOTE: Ensure termination height is above the roof surface
or anticipated snow level (1’ in USA or 1 ½’ in Canada) as
shown in Fig. 3.
NOTE: If assembly is too short to meet height requirements,
the two pipes supplied in the kit may be replaced by using
same diameter, field supplied SDR-26 PVC (D2241) pipe. Do
not extend dimension D more than 60” (See Fig. 2.) DO NOT
USE COUPLINGS TO EXTEND PIPE.NOTE: When shortening the length of the concentric vent,
the inner pipe is longer than the outer pipe. Make sure you
cut the same amount from each pipe. DO NOT make the
pipes equal in length.
6. Install rain cap and small diameter pipe assembly in
roof penetration assembly. Ensure small diameter pipe is
cemented and bottomed in Y concentric fitting.
7. Cement air inlet and exhaust vent pipes to concentric vent
termination assembly. See Fig. 4 for proper pipe attachment.
8. Operate boiler through a heating cycle to ensure air
inlet and exhaust vent pipes are properly connected to
concentric vent termination connections.NOTE: Multiple vertical venting is not allowed.
Figure 3 - Roof Termination
Figure 4 - Roof InstallationIt is very important to properly glue all joints. Failure to do so
can result in property damage, serious personal injury, or death.
08/09/2018
lp-166 Rev. 3.13.17
3
Sidewall Termination1. Determine the best location for the termination kit.
a. Position termination kit where vent vapors will not
damage plants, shrubs, air conditioning equipment, or
the existing structure.
b. Position termination kit so it will not be affected by
wind (which may cause recirculation of combustion
products), airborne leaves, light snow, or fertilizer.
c. Position termination kit where it will not be subjected to
damage from foreign objects, such as stones, balls, etc.
d. Position termination kit where the vent noise will not be
objectionable to abutters.
2. Cut a hole in the sidewall 4” in diameter for 2” concentric
vent kit, or 5” in diameter for 3” concentric vent kit.
3. Partially assemble concentric vent termination kit.
a. Cement the Y concentric fitting to larger diameter kit
pipe (see Fig. 1).
b. Cement the rain cap to the smaller diameter kit pipe
(see Fig. 1).
4. Install Y concentric fitting and pipe assembly through
the hole.NOTE: Do not allow insulation or other materials to
accumulate inside pipe assembly when installing through
hole.
5. Install rain cap and small diameter pipe assembly in Y
concentric fitting and large pipe assembly. Ensure small
diameter pipe is bottomed and cemented in Y concentric
fitting.
6. Secure assembly to structure using field supplied metal
strapping or equivalent support material (see Fig. 6).
NOTE: Ensure termination location clearance dimensions
are as shown in Fig. 5.
NOTE: If assembly needs to be extended to allow sidewall
thickness requirement, the two pipes supplied in the
kit may be replaced by using the same diameter, field
supplied SDR-26 (D2241) pipe. Do not extend Dimension D
to more than 60” (see Fig. 2). DO NOT USE COUPLINGS TO
EXTEND PIPE.
7. Cement air inlet and exhaust vent pipes to concentric
vent termination assembly. See Fig. 6 for proper pipe
attachment.
8. Operate boiler/heater through a heating cycle to ensure
air inlet and exhaust vent pipes are properly connected to
concentric vent termination connections.
9. Allow 8” center-to-center distance between concentric
vent terminations on multiple boiler installations (see Fig.
7).
Figure 5 - Sidewall Termination
Figure 6 - Sidewall Installation
Figure 7 - Multiple Boiler Installations
It is very important to properly glue all joints. Failure to do
so can result in property damage, serious personal injury, or
death.
08/09/2018