HomeMy WebLinkAboutFile Documents.700 S Monarch St.0069.2019 (2).ARBK
Property Address
700 S. Monarch St. #104
Aspen, CO 81611
Element Environmental Project#:
Hendrickson 031219 Monarch
Client Job Name
Monarch
TABLE OF CONTENTS
1.0 - Scope of Work
2.0 - Sampling Requirements
3.0 - Sampling Methodology
4.0 - Laboratory
5.0 - Suspect Materials Sampled
6.0 - Table of Results
7.0 - Description of Sampling Area
8.0 - Conclusion
9.0 - Lab Report
10.0 - Certificates
Asbestos Samples Analyzed: 21
Positive Asbestos Samples: 11
___________________________________________________ ASBESTOS LEAD HAZMAT RESTORATION www.elementconsults.com Asbestos Sampling Report
Date: 03/15/2019
Date of Inspection: 03/12/2019
Client:
Hendrickson Construction
130 Primrose Path
Aspen, CO 81611
Attn:
Chris Hendrickson
Building Inspector:
Ellen Johnson
CDPHE #23799
Joshua Johnson
CDPHE #18401
189 County Rd. 135
Glenwood Springs, CO 81601
josh@elementconsults.com
(970) 274-3139
03/29/2019
Project #-Hendrickson 031219 Monarch
2
1.0- This was an inspection for suspect ACM (Asbestos Containing Material) for a remodel.
Element Environmental conducted a visible inspection for visible materials that would
be impacted during the remodel. This inspection was limited to the areas found in the
Description of the Sampling Area 7.0. Although sampling is destructive in nature, this
was a non-invasive inspection. It was of materials that were accessible. If other suspect
materials become visible/apparent during demolition or construction activities, work in
that area should be halted and more sampling/testing must take place, per Colorado
regulations. Any suspect materials that were not tested are to be assumed to contain
asbestos.
2.0- A limited bulk sampling of from all suspect materials was conducted in accordance with
Colorado State Requirements. The minimum number of samples per homogenous areas
are as follows:
2.1- Surfacing Materials- <1,000 sq.ft.- Minimum of 3 samples
1,000 sq.ft.- 5,000sq.ft.- Minimum of 5 samples
>5,000 sq.ft. Minimum of 7 samples
2.2- Miscellaneous materials- Minimum of 2 samples
2.3- Thermal Systems Insulation (TSI)- Minimum of 3 samples
3.0- The purpose of the inspection is to identify materials that are homogenous. A
homogeneous area is defined as one which shares suspect material, texture, color,
location, and/or apparent time of construction. The materials are segregated into
separate homogenous areas. The size is determined and then samples are taken. The
materials are touched to determine friability. Friable ACM is material that can be
crushed or reduced to powder by hand pressure. The samples are taken in a random
numerical sequence.
4.0- Ellen Johnson, a Colorado Department of Public Health & Environment certified building
inspector, certification number: 23799, performed the inspection. The findings were
reviewed by Josh Johnson, a Colorado Department of Public Health & Environment
certified building inspector, certification number: 18401. Samples taken were sent to
CEI Labs in Cary, North Carolina. The samples were analyzed by PLM (Polarized Light
Microscopy) analysis. Per the CDPHE Regulation any sample that is found by a lab to be
trace, or <1% asbestos, is considered to be ACM material. This material would still be a
regulated material by CDPHE. The sample must have an additional “point count”
performed to be considered less than 1% and not be regulated by the CDPHE. The lab’s
documents with analyses and findings are found below.
03/29/2019
Project #-Hendrickson 031219 Monarch
3
5.0- SUSPECT MATERIALS SAMPLES
• Drywall
• Joint Compound
• Tape
• Texture
• Wallpaper
• Carpet and Pad
• Tile Grout
6.0- TABLE OF RESULTS
HOMOGENOUS
AREA
DESCRIPTION OF AREA ACM CATEGORY NUMBER
OF
SAMPLES
APPROXIMATE
SQ.FT.*
ACM ASSESSMENT CATEGORIES
% AND TYPE OF
ASBESTOS FOUND
(A) Light Roll Texture on All Ceilings
and in Both Bedrooms Surfacing
5 ~1500 sq.ft. No. 7 – Friable ACM with low
potential for damage
2% Chrysotile in 3 of 5
Samples
(B) Cream Colored Wallpaper in
Living Room, Entry and Hall Surfacing
3 ~700 sq.ft. No. 7 – Friable ACM with low
potential for damage
2% Chrysotile in 2 of 3
Samples
(C) Grey Colored Wallpaper in Both
Bathrooms Surfacing 3 ~250 sq.ft. No. 7 – Friable ACM with low
potential for damage
2% Chrysotile in 3 of 3
Samples
(D) Carpet throughout Condo Miscellaneous 2 ~800 sq.ft. Non-Friable Non-ACM No Asbestos Detected
(E) Floor Tile Grout in Kitchen and
Entry Miscellaneous 2 ~200 sq.ft. Non-Friable Non-ACM No Asbestos Detected
(F) Floor Tile Grout in Bathrooms Miscellaneous 1 ~700 sq.ft. Non-Friable Non-ACM No Asbestos Detected
(G) Wall Tile Grout in Kitchen and
Bathrooms Miscellaneous 2 ~100 sq.ft. Non-Friable Non-ACM No Asbestos Detected
(H) Orange Peel Texture in Bedroom
Closets and Entry Closet Surfacing 3 ~300 sq.ft. No. 7 – Friable ACM with low
potential for damage
2% Chrysotile in 3 of 3
Samples
Key:
ACM Assessment Categories:
1- Damaged or significantly damaged Thermal Systems Insulation
(TSI) ACM
2- Damaged friable surfacing ACM
3- Significantly damaged friable Surfacing ACM
4- Damaged or significantly damaged friable Miscellaneous ACM
5- ACM with potential for damage
6- ACM with potential for significant damage
7- Friable ACM with low potential for damage
Other- ACM not classified in the above Assessment Categories
N/A- Not Applicable
* Square footage is estimated and not for bidding purposes
03/29/2019
Project #-Hendrickson 031219 Monarch
4
7.0- DESCRIPTION OF SAMPLING AREA
• The Light Roll Texture on all the Ceilings and in Both Bedrooms
• The Cream-Colored Wallpapered Walls in the Entry, Living Room and Hallway
• The Grey-Colored Wallpapered Walls in Both Bathrooms
• The Carpet and Padding throughout
• The Tile Grout throughout
8.0- CONCLUSION
The areas on the Table that are in Black did not contain asbestos.
The areas on the table in Red contained asbestos:
• The Light Roll Texture on all ceilings and on walls in both Bedrooms
• All Wallpapered Walls
• The Orange Peel Texture in the Bedroom Closets and the Entryway Closet
*In summary, ALL of the Drywall throughout the condo contains asbestos.
These materials become friable when they are removed. If these materials are to be disturbed or removed, the
materials MUST be remediated in accordance with the CDPHE Regulation No. 8 by a licensed abatement
contractor. For residential projects over 32 square feet of surfacing material, 50 linear feet of pipe insulation, or 55
gallon drum of waste; and for commercial projects with 160 square feet of surfacing material, 260 linear feet of
pipe insulation, or a 55 gallon drum of waste, a permit is required. The permit is through the CDPHE. Along with
the permit, a final air clearance is required by a certified Air Monitoring Specialist. For projects over 3,000 square
feet, a Project Design and Project Manager is required. Element Environmental is certified and can perform Final
Clearances, Project Design, and Project Management if required. All work performed MUST follow all EPA, State
Regulation 8, and OSHA regulations to protect the general public, the client, and the workers.
Sincerely,
Ellen Johnson
03/29/2019
Project #-Hendrickson 031219 Monarch
5
9.0- LAB REPORT
03/29/2019
Project #-Hendrickson 031219 Monarch
6
03/29/2019
Project #-Hendrickson 031219 Monarch
7
03/29/2019
Project #-Hendrickson 031219 Monarch
8
03/29/2019
Project #-Hendrickson 031219 Monarch
9
03/29/2019
Project #-Hendrickson 031219 Monarch
10
03/29/2019
Project #-Hendrickson 031219 Monarch
11
03/29/2019
Project #-Hendrickson 031219 Monarch
12
03/29/2019
Project #-Hendrickson 031219 Monarch
13
03/29/2019
Project #-Hendrickson 031219 Monarch
14
03/29/2019
Project #-Hendrickson 031219 Monarch
15
03/29/2019
Project #-Hendrickson 031219 Monarch
16
10.0- CERTIFICATES
03/29/2019