Loading...
HomeMy WebLinkAboutFile Documents.675 E Durant Ave.0043.2019 (13).ACBK0043-2019-ACBK_BuildingComment1 Subject: PlanCheck Page Label: A0.5 BUILDING CODE ANALYSIS - EGRESS & OCCUPANCY Author: justinh File Name: 03_21808_TLNLobbyChair9ChangeOrder1_2019- 05-10.pdf Color: Revise the egress path to be clear of the revised column locations. Currently columns are shown in the path. 03_21808_TLNLobbyChair9ChangeOrder1_2019-05-10.pdf (3) Subject: PlanCheck Page Label: A2.1 PROPOSED FLOOR PLAN Author: justinh File Name: 03_21808_TLNLobbyChair9ChangeOrder1_2019- 05-10.pdf Color: Your revised approach on the pull side of door 120B does not meet the dimensional requirements of ANSI 404.2.3.2, this fire rated door will have a closer and therefore needs a clearance of 54" measured out from the wall. Please revise. Subject: PlanCheck Page Label: A7.1COPYRIGHT 2019 ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGNTUC IMCDDMATIOM AMH HCCiriM IMTCWT mWTAlWCn AM TUIC HOri IMCMT IC A£>^£IVIBU££> AINUDETAILSQrAI P- AQ MflTFn Author: justinh File Name: 03_21808_TLNLobbyChair9ChangeOrder1_2019- 05-10.pdf Color: Where are these infills being proposed? I do not see where they are referenced on any floor plan and am not 100% sure that I understand what you are actually proposing. Please clarify. Subject: PlanCheck Page Label: 1 Author: justinh File Name: 06_KGM-TLN-LOBBY_C9_COMCHECK REPORT_190510.pdf Color: Provide a cutsheet for the various sconce (DF) fixtures proposed. This fixture shows up multiple times in the report at various wattages but no cutsheets were included for it in the change order package. 06_KGM-TLN-LOBBY_C9_COMCHECK REPORT_190510.pdf (2) Subject: PlanCheck Page Label: 2 Author: justinh File Name: 06_KGM-TLN-LOBBY_C9_COMCHECK REPORT_190510.pdf Color: These fixtures were shown on the previously approved ComCheck as custom lighting powered by five 96W drivers for a total of 480W. Revise this to match the previously approved ComCheck or provide new information regarding the fixture that matches what you show here.3'-2"3'-2" 3'-2"3'-2"3'-2"6'-0" 3'-2" ACCESSIBLE PATH EGRESS P EGRESS PATH EGRESS PATHEGR E S S PA T H LOUNGE AREA BAR AREA BARADA VESTIBULEACCESSIBLE PATHLIFT33-1/2" HIGH BAR COUNTER, REFERENCEA0.4 FOR ACCESSIBILITYREQUIREMENTS ACCESSIBLE PATH34" HIGH TABLE 28 3'-2"3'-2" 111 ' -1 0 " ADA ADA ADA ADA 28" HIGH TABLES ADA ADA5'-0"ADA W WAYFINDING SIGNAGEFOR LIFT AT ELEMENT 47 49 sf 791 sf 1 CO1 1CO1 Revise the egress path to be clear of therevised column locations. Currently columns are shown inthe path. BAR BUS CHAIR 9120 ENTRY 117 CORRIDOR 118 CORRIDOR 119 120A 120B 125A 125B DN NOT INSCOPE NOT IN SCOPE DN EXIST.LIFT 8 7 620'-0"20'-0"VITREOUS CHINABATHROOM SINKCAXTONK-20000 4'-5"12'-1 15/16"7'-8"2'-5"5"6'-10"5"11 1/8"4"5"5"5"1'-6 7/8"1'-7 7/8" 1 1ID2.09 119B 119ASEE RICCA'S DRAWINGS FOR BAR EQUIPMENT LAYOUT AND EXISTING FLOOR SINK LAYOUT 117A A7.16 4'-0" A7.18 1 CO1 1 CO1 Your revised approach on the pull side of door 120B does not meet the dimensional requirements ofANSI 404.2.3.2, this fire rated door will have a closer and therefore needs a clearance of 54" measured out from the wall. Please revise. Where are these infillsbeing proposed? I donot see where theyare referenced on anyfloor plan and am not100% sure that Iunderstand what youare actually proposing. Please clarify. Project Type:Alteration Construction Site:675 E Durant AveAspen, CO 81611 Owner/Agent:Aspen Skiing Company Designer/Contractor:KGM Archiectural Lighting270 Coral CircleEl Segundo, CA 90245310-552-2191 Allowed Interior Lighting Power AArea Category BFloor Area (ft2) CAllowed Watts / ft2 DAllowed Watts (B X C) 1-Reception + Concierge (Hotel:Hotel Lobby)1478 1.06 1567 2-Living Room (Hotel:Hotel Lobby)1283 1.06 13603-Chair 9 (Common Space Types:Dining Area - Bar Lounge/Leisure)1576 1.07 1686 4-Corridor (Common Space Types:Corridor/Transition >=8 ft wide)734 0.66 484 5-Stairs (Common Space Types:Stairwell)122 0.69 84 6-Office (Common Space Types:Office - Enclosed)500 1.11 555 7-Restrooms (Common Space Types:Restrooms)348 0.98 341 6078Total Allowed Watts = Proposed Interior Lighting Power E(C X D)DFixtureWatt. AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture C# ofFixtures Reception + Concierge ( Hotel:Hotel Lobby 1478 sq.ft.)LED 1: F4: RECESSED DOWNLIGHT: Other:1 10 13 130 LED 2: F3: RECESSED COMBO DOWNLIGHT: Other:2 6 26 156 LED 3: F6: SURFACE MOUNTED DOWNLIGHT: Other:1 6 12 75 LED 4: F5: RECESSED SMALL DOWNLIGHT: Other:1 4 7 28LED 5: F14: SURFACE MOUNTED SELF COVE LINEA: Other:1 35 7 234LED 6: F9: INDIRECT LED TAPE LIGHT: Other:1 30 2 45LED 7: F8: SURFACE MOUNTED LINEAR UPLIGHT: Other:1 68 3 204LED 31: F16: SURFACE MOUNTED LINEAR LED STRI: Other:1 4 3 12 LED 34: F19: RECESSED DOWNLIGHT: Other:1 1 18 18 LED 35: F20: SURFACE MOUNTED AMBIENT FIXTURE: Other:1 1 20 20 LED 35: DF: SCONCE AT RECEPTION: Other:1 2 2 4 LED 36: F21: RECESSED DOWNLIGHT: Other:1 3 12 38Incandescent 1: DF: SCONCE AT ENTRANCE: Incandescent 40W:2 2 40 80 Living Room ( Hotel:Hotel Lobby 1283 sq.ft.)LED 8: F1: SURFACE MOUNTED COMBO DOWNLIGHT: Other:2 10 26 260LED 9: F2: SURFACE MOUNTED SINGLE DOWNLIGH: Other:1 10 13 130 Project Title: Data filename: The Little Nell - Lobby + Chair 9 X:\TLN - Lobby + C9 refresh - 18361 (JM-AF)\Calculations\Power density\KGM-TLN-LOBBY+C9_CLACULATION.cck 05/10/19Report date: 61 ofPage Provide a cutsheet for the various sconce (DF) fixtures proposed. This fixture shows up multiple times in the report at various wattages butno cutsheets wereincluded for it in thechange orderpackage. E(C X D)DFixtureWatt. AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture C# ofFixtures LED 10: F3: RECESSED COMBO DOWNLIGHT: Other:2 4 26 104LED 11: F4: RECESSED DOWNLIGHT: Other:1 8 13 104 LED 13: F8: SURFACE MOUNTED LINEAR UPLIGHT: Other:1 83 3 249 LED 14: F10: RECESSED IN-GRADE UPLIGHT: Other:1 27 1 27LED 15: DF: SCONCE BY WINDOW: Other:1 2 10 20LED 32: F10A: RECESSED IN-GRADE UPLIGHT: Other:1 10 1 10LED 35: DF: SCONCE AT FIREPLACE: Other:1 4 25 100 Chair 9 ( Common Space Types:Dining Area - Bar Lounge/Leisure 1576 sq.ft.)LED 18: F12: RECESSED PINHOLE DOWNLIGHT: Other:1 50 13 650LED 20: F15: SURFACE MOUNTED LINEAR GRAZER: Other:1 31 5 161LED 21: F16: SURFACE MOUNTED LINEAR LIGHT: Other:1 5 3 15LED 22: F21: RECESSED DOWNLIGHT: Other:1 2 12 25 LED 23: DF: SCONCE BY WINODW: Other:2 8 100 800 LED 31: F17: RECESSED STEP LIGHT: Other:1 4 3 10LED 33: F5A: RECESSED SMALL DOWNLIGHT: Other:1 5 7 35LED 34: F18: SURFACE MOUNTED LINEAR LED STRI: Other:1 20 3 60LED 34: DF: CEILING MOUNTED CUSTOM FIXTURE: Other:1 1 40 40 Corridor ( Common Space Types:Corridor/Transition >=8 ft wide 734 sq.ft.)LED 25: F19: RECESSED DOWNLIGHT: Other:1 13 18 234LED 27: F7: RECESSED COVE LIGHT: Other:1 81 2 202LED 35: F17A: RECESSED STEP LIGHT: Other:1 4 3 10 Stairs ( Common Space Types:Stairwell 122 sq.ft.) LED 30: F19: RECESSED DOWNLIGHT: Other:1 6 12 75 Office ( Common Space Types:Office - Enclosed 500 sq.ft.)LED 32: F21: RECESSED DOWNLIGHT: Other:1 9 12 112 Restrooms ( Common Space Types:Restrooms 348 sq.ft.)LED 36: E: EXISTING DOWNLIGHT: Other:1 12 14 162LED 37: F22: RETROFIT DOWNLIGHT: Other:1 6 14 81LED 38: F18: LINEAR UNDER COUNTER: Other:1 13 3 39LED 39: DF: SCONCE AT MIRROR: Other:1 2 3 6 4767Total Proposed Watts = Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting PASSES Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature DateAnne Friedman | Associate 2019-05-10 These fixtures were shown on thepreviously approved ComCheck as custom lighting powered by five 96Wdrivers for a total of 480W. Revise this to match the previouslyapproved ComCheck or provide newinformation regarding the fixture thatmatches what you show here. Fixed on sheet A0.5 - The columns weren't exactly where they were initially drawn. This is accurate and egress still works fine. RB RESPONSES IN BLUE 5/21/2019 Revised on A2.1 and A0.5 as well as the field See A2.1 we have added bubbles around the two windows on the pool side that are getting filled in. One at back of Ch 9 bar one above Ch 9 fireplace. Added 1.5" rigid to comply with IECC C402.1.3 See "KGM-TLN Lobby & Ch9 Decorative Fixture Submittal Combined" - UPDATED 05/23/2019 See "KGM-TLN Lobby & Ch9 Decorative Fixture Submittal Combined", New ComCheck, and Lighting Plan with Decorative Fixtures Named. RB RESPONSES IN GREEN 5/23/2019 RESPONSE FOR CH 9 FIXTURE FROM KGM-This fixture is being custom made over seaS. Previously we only know the design and quantity of the fixture. We know it will have low voltage LED strips in them but haveno idea the output or quantity of the LED strips. We took a very very conservative approach and intentionally over estimated how much power it could draw and put theestimated number into comcheck. Now we have actual electrical information from the manufacturer, and we change the number to the actual one as he can verify from the submittals. KGM "For the ceiling fixture in Chair9, KGM also increased the output and added the wattage of the driver into account to over compensate at first. KGM also increased the wattage of the existing down light fixture in the bathroom, now that we have information of exact fixture they are using on site. 05/23/2019