HomeMy WebLinkAboutFile Documents.675 E Durant Ave.0043.2019 (13).ACBK0043-2019-ACBK_BuildingComment1
Subject: PlanCheck
Page Label: A0.5 BUILDING CODE ANALYSIS - EGRESS &
OCCUPANCY
Author: justinh
File Name: 03_21808_TLNLobbyChair9ChangeOrder1_2019-
05-10.pdf
Color:
Revise the egress path to be
clear of the revised column
locations. Currently columns are
shown in the path.
03_21808_TLNLobbyChair9ChangeOrder1_2019-05-10.pdf (3)
Subject: PlanCheck
Page Label: A2.1 PROPOSED FLOOR PLAN
Author: justinh
File Name: 03_21808_TLNLobbyChair9ChangeOrder1_2019-
05-10.pdf
Color:
Your revised approach on the
pull side of door 120B does not
meet the dimensional
requirements of ANSI 404.2.3.2,
this fire rated door will have a
closer and therefore needs a
clearance of 54" measured out
from the wall. Please revise.
Subject: PlanCheck
Page Label: A7.1COPYRIGHT 2019
ROWLAND+BROUGHTON ARCHITECTURE AND URBAN
DESIGNTUC IMCDDMATIOM AMH HCCiriM IMTCWT
mWTAlWCn AM TUIC HOri IMCMT IC A£>^£IVIBU££>
AINUDETAILSQrAI P- AQ MflTFn
Author: justinh
File Name: 03_21808_TLNLobbyChair9ChangeOrder1_2019-
05-10.pdf
Color:
Where are these infills being
proposed? I do not see where
they are referenced on any floor
plan and am not 100% sure that
I understand what you are
actually proposing. Please
clarify.
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 06_KGM-TLN-LOBBY_C9_COMCHECK
REPORT_190510.pdf
Color:
Provide a cutsheet for the
various sconce (DF) fixtures
proposed. This fixture shows up
multiple times in the report at
various wattages but no
cutsheets were included for it in
the change order package.
06_KGM-TLN-LOBBY_C9_COMCHECK REPORT_190510.pdf (2)
Subject: PlanCheck
Page Label: 2
Author: justinh
File Name: 06_KGM-TLN-LOBBY_C9_COMCHECK
REPORT_190510.pdf
Color:
These fixtures were shown on
the previously approved
ComCheck as custom lighting
powered by five 96W drivers for
a total of 480W. Revise this to
match the previously approved
ComCheck or provide new
information regarding the fixture
that matches what you show
here.3'-2"3'-2"
3'-2"3'-2"3'-2"6'-0"
3'-2"
ACCESSIBLE PATH
EGRESS P
EGRESS PATH
EGRESS PATHEGR
E
S
S
PA
T
H
LOUNGE AREA
BAR AREA
BARADA
VESTIBULEACCESSIBLE PATHLIFT33-1/2" HIGH BAR
COUNTER, REFERENCEA0.4 FOR ACCESSIBILITYREQUIREMENTS
ACCESSIBLE PATH34" HIGH TABLE
28 3'-2"3'-2"
111
'
-1
0
"
ADA
ADA
ADA
ADA
28" HIGH TABLES
ADA
ADA5'-0"ADA
W
WAYFINDING SIGNAGEFOR LIFT AT ELEMENT 47
49 sf
791 sf
1
CO1
1CO1
Revise the egress
path to be clear of therevised column
locations. Currently
columns are shown inthe path.
BAR
BUS
CHAIR 9120
ENTRY
117
CORRIDOR
118
CORRIDOR
119
120A
120B 125A
125B
DN
NOT INSCOPE
NOT IN
SCOPE
DN
EXIST.LIFT
8
7
620'-0"20'-0"VITREOUS CHINABATHROOM SINKCAXTONK-20000
4'-5"12'-1 15/16"7'-8"2'-5"5"6'-10"5"11 1/8"4"5"5"5"1'-6 7/8"1'-7 7/8"
1
1ID2.09
119B
119ASEE RICCA'S
DRAWINGS FOR BAR
EQUIPMENT LAYOUT
AND EXISTING FLOOR
SINK LAYOUT
117A
A7.16
4'-0"
A7.18
1
CO1
1
CO1
Your revised approach on the pull
side of door 120B does not meet
the dimensional requirements ofANSI 404.2.3.2, this fire rated door
will have a closer and therefore
needs a clearance of 54" measured
out from the wall. Please revise.
Where are these infillsbeing proposed? I donot see where theyare referenced on anyfloor plan and am not100% sure that Iunderstand what youare actually proposing. Please clarify.
Project Type:Alteration
Construction Site:675 E Durant AveAspen, CO 81611
Owner/Agent:Aspen Skiing Company Designer/Contractor:KGM Archiectural Lighting270 Coral CircleEl Segundo, CA 90245310-552-2191
Allowed Interior Lighting Power
AArea Category BFloor Area
(ft2)
CAllowed
Watts / ft2
DAllowed Watts
(B X C)
1-Reception + Concierge (Hotel:Hotel Lobby)1478 1.06 1567
2-Living Room (Hotel:Hotel Lobby)1283 1.06 13603-Chair 9 (Common Space Types:Dining Area - Bar Lounge/Leisure)1576 1.07 1686
4-Corridor (Common Space Types:Corridor/Transition >=8 ft wide)734 0.66 484
5-Stairs (Common Space Types:Stairwell)122 0.69 84
6-Office (Common Space Types:Office - Enclosed)500 1.11 555
7-Restrooms (Common Space Types:Restrooms)348 0.98 341
6078Total Allowed Watts =
Proposed Interior Lighting Power
E(C X D)DFixtureWatt.
AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture
C# ofFixtures
Reception + Concierge ( Hotel:Hotel Lobby 1478 sq.ft.)LED 1: F4: RECESSED DOWNLIGHT: Other:1 10 13 130
LED 2: F3: RECESSED COMBO DOWNLIGHT: Other:2 6 26 156
LED 3: F6: SURFACE MOUNTED DOWNLIGHT: Other:1 6 12 75
LED 4: F5: RECESSED SMALL DOWNLIGHT: Other:1 4 7 28LED 5: F14: SURFACE MOUNTED SELF COVE LINEA: Other:1 35 7 234LED 6: F9: INDIRECT LED TAPE LIGHT: Other:1 30 2 45LED 7: F8: SURFACE MOUNTED LINEAR UPLIGHT: Other:1 68 3 204LED 31: F16: SURFACE MOUNTED LINEAR LED STRI: Other:1 4 3 12
LED 34: F19: RECESSED DOWNLIGHT: Other:1 1 18 18
LED 35: F20: SURFACE MOUNTED AMBIENT FIXTURE: Other:1 1 20 20
LED 35: DF: SCONCE AT RECEPTION: Other:1 2 2 4
LED 36: F21: RECESSED DOWNLIGHT: Other:1 3 12 38Incandescent 1: DF: SCONCE AT ENTRANCE: Incandescent 40W:2 2 40 80
Living Room ( Hotel:Hotel Lobby 1283 sq.ft.)LED 8: F1: SURFACE MOUNTED COMBO DOWNLIGHT: Other:2 10 26 260LED 9: F2: SURFACE MOUNTED SINGLE DOWNLIGH: Other:1 10 13 130
Project Title:
Data filename:
The Little Nell - Lobby + Chair 9
X:\TLN - Lobby + C9 refresh - 18361 (JM-AF)\Calculations\Power density\KGM-TLN-LOBBY+C9_CLACULATION.cck
05/10/19Report date:
61 ofPage
Provide a cutsheet for
the various sconce
(DF) fixtures
proposed. This fixture
shows up multiple
times in the report at
various wattages butno cutsheets wereincluded for it in thechange orderpackage.
E(C X D)DFixtureWatt.
AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast BLamps/Fixture
C# ofFixtures
LED 10: F3: RECESSED COMBO DOWNLIGHT: Other:2 4 26 104LED 11: F4: RECESSED DOWNLIGHT: Other:1 8 13 104
LED 13: F8: SURFACE MOUNTED LINEAR UPLIGHT: Other:1 83 3 249
LED 14: F10: RECESSED IN-GRADE UPLIGHT: Other:1 27 1 27LED 15: DF: SCONCE BY WINDOW: Other:1 2 10 20LED 32: F10A: RECESSED IN-GRADE UPLIGHT: Other:1 10 1 10LED 35: DF: SCONCE AT FIREPLACE: Other:1 4 25 100
Chair 9 ( Common Space Types:Dining Area - Bar Lounge/Leisure 1576 sq.ft.)LED 18: F12: RECESSED PINHOLE DOWNLIGHT: Other:1 50 13 650LED 20: F15: SURFACE MOUNTED LINEAR GRAZER: Other:1 31 5 161LED 21: F16: SURFACE MOUNTED LINEAR LIGHT: Other:1 5 3 15LED 22: F21: RECESSED DOWNLIGHT: Other:1 2 12 25
LED 23: DF: SCONCE BY WINODW: Other:2 8 100 800
LED 31: F17: RECESSED STEP LIGHT: Other:1 4 3 10LED 33: F5A: RECESSED SMALL DOWNLIGHT: Other:1 5 7 35LED 34: F18: SURFACE MOUNTED LINEAR LED STRI: Other:1 20 3 60LED 34: DF: CEILING MOUNTED CUSTOM FIXTURE: Other:1 1 40 40
Corridor ( Common Space Types:Corridor/Transition >=8 ft wide 734 sq.ft.)LED 25: F19: RECESSED DOWNLIGHT: Other:1 13 18 234LED 27: F7: RECESSED COVE LIGHT: Other:1 81 2 202LED 35: F17A: RECESSED STEP LIGHT: Other:1 4 3 10
Stairs ( Common Space Types:Stairwell 122 sq.ft.)
LED 30: F19: RECESSED DOWNLIGHT: Other:1 6 12 75
Office ( Common Space Types:Office - Enclosed 500 sq.ft.)LED 32: F21: RECESSED DOWNLIGHT: Other:1 9 12 112
Restrooms ( Common Space Types:Restrooms 348 sq.ft.)LED 36: E: EXISTING DOWNLIGHT: Other:1 12 14 162LED 37: F22: RETROFIT DOWNLIGHT: Other:1 6 14 81LED 38: F18: LINEAR UNDER COUNTER: Other:1 13 3 39LED 39: DF: SCONCE AT MIRROR: Other:1 2 3 6
4767Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lightingsystems have been designed to meet the 90.1 (2013) Standard requirements in COMcheck Version 4.1.0.0 and to comply withany applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature DateAnne Friedman | Associate 2019-05-10
These fixtures were shown on thepreviously approved ComCheck as
custom lighting powered by five 96Wdrivers for a total of 480W. Revise
this to match the previouslyapproved ComCheck or provide newinformation regarding the fixture thatmatches what you show here.
Fixed on sheet A0.5 - The
columns weren't exactly where
they were initially drawn. This
is accurate and egress still
works fine.
RB RESPONSES IN BLUE 5/21/2019
Revised on A2.1 and A0.5 as
well as the field
See A2.1 we have added bubbles around the two windows on the pool side
that are getting filled in. One at back of Ch 9 bar one above Ch 9 fireplace.
Added 1.5" rigid to comply with IECC C402.1.3
See "KGM-TLN Lobby & Ch9 Decorative Fixture Submittal Combined" -
UPDATED 05/23/2019
See "KGM-TLN Lobby & Ch9 Decorative Fixture
Submittal Combined", New ComCheck, and Lighting
Plan with Decorative Fixtures Named.
RB RESPONSES IN GREEN 5/23/2019
RESPONSE FOR CH 9 FIXTURE FROM KGM-This fixture is being custom made over seaS. Previously we only know the design and quantity of the fixture. We know it will have low voltage LED strips in them but haveno idea the output or quantity of the LED strips. We took a very very conservative approach and intentionally over estimated how much power it could draw and put theestimated number into comcheck. Now we have actual electrical information from the manufacturer, and we change the number to the actual one as he can verify from the
submittals. KGM "For the ceiling fixture in Chair9, KGM also increased the output and added the wattage of the driver into account to over compensate at first.
KGM also increased the wattage of the existing down light fixture in the bathroom, now that we have information of exact fixture they are using on site.
05/23/2019