Loading...
HomeMy WebLinkAboutFile Documents.630 E Cooper Ave.0005.2019 (9).ARBK1Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Models: Installation Manual Installation and Appliance Setup INSTALLER: Leave this manual with party responsible for use and operation. OWNER: Retain this manual for future reference. NOTICE: DO NOT discard this manual! In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional Commonwealth of Massachusetts requirements. This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 in the United States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. DANGER HOT GLASS WILL CAUSE BURNS. DO NOT TOUCH GLASS UNTIL COOLED. NEVER ALLOW CHILDREN TO TOUCH GLASS. A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals. • DO NOT store or use gasoline or other flam- mable vapors and liquids in the vicinity of this or any other appliance. • What to do if you smell gas - DO NOT try to light any appliance. - DO NOT touch any electrical switch. DO NOT use any phone in your building. - Leave the building immediately. - Immediately call your gas supplier from a neighbor’s phone. Follow the gas sup- plier’s instructions. - If you cannot reach your gas supplier, call the fire department. • Installation and service must be performed by a qualified installer, service agency, or the gas supplier. WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. SL-5F SL-7F 01/08/2019 2 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Safety Alert Key: • DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury. • WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury. • CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. • NOTICE: Used to address practices not related to personal injury. Table of Contents Installation Standard Work Checklist ....................3 1 Product Specific and Important Safety Information A. Appliance Certification ............................4 B. Glass Specifications ..............................4 C. BTU Specifications ...............................4 D. High Altitude Installations ..........................4 E. Non-Combustible Materials Specification. . . . . . . . . . . . . . 4 F. Combustible Materials Specification .................4 G. Electrical Codes .................................4 H. California ......................................4 I. Requirements for the Commonwealth of Massachusetts . .5 2 Getting Started A. Design and Installation Considerations ...............6 B. Good Faith Wall Surface ..........................6 C. Tools and Supplies Needed ........................7 D. Inspect Appliance and Components ..................7 3 Framing and Clearances A. Appliance/Decorative Front Dimension Diagram ........8 B. Clearances to Combustibles ......................10 C. Constructing the Appliance Chase ..................11 D. Floor Protection ................................11 4 Termination Location and Vent Information A. Vent Termination Minimum Clearances ..............12 B. Chimney Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 C. Approved Pipe .................................14 D. Use of Elbows .................................15 E. Measuring Standards ............................16 F. Use of Flex Vent ................................17 G. Vent Diagrams .................................17 5 Vent Clearances and Framing A. Pipe Clearances to Combustibles ..................31 B. Wall Penetration Framing/Firestops .................31 C. Ceiling Firestop/Floor Penetration Framing ...........32 D. Install Attic Insulation Shield .......................32 6 Appliance Preparation A. Vent Collar Preparation - Top or Rear ...............33 B. Securing and Leveling the Appliance ................35 7 Venting and Chimneys A. Assemble Vent Sections (DVP Pipe) ................36 B. Assemble Vent Sections (SLP Pipe) ................37 C. Assemble Slip Sections ..........................37 D. Secure the Vent Sections .........................38 E. Disassemble Vent Sections .......................38 F. Vertical Termination Requirements ..................39 G. Horizontal Termination Requirements ...............40 8 Electrical Information A. General Information .............................42 B. Wiring Requirements ............................42 9 Gas Information A. Fuel Conversion ................................45 B. Gas Pressure ..................................45 C. Gas Connection ................................45 D. High Altitude Installations .........................45 E. Air Shutter Setting ..............................46 10 Finishing A. Facing and Finishing ............................47 B. Mantel and Wall Projections .......................48 C. Install Decorative Front/Hood ......................49 11 Appliance Setup A. Remove Fixed Glass Assembly ....................50 B. Remove the Shipping Materials ....................50 C. Clean the Appliance .............................50 D. Install the Log Assembly and Lava Rock .............51 E. Install Fixed Glass Assembly ......................58 F. Install Optional Trim Kits. . . . . . . . . . . . . . . . . . . . . . . . . . 58 12 Reference Materials A. Vent Components Diagrams ......................59 B. Accessories ...................................70  = Contains updated information.01/08/2019 3Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Installation Standard Work Checklist Appliance Install YES IF NO, WHY? Veri ed that the chase is insulated and sealed. (Pg. 11) ___________________________ Veri ed clearances to combustibles. (Section 3) ___________________________ Fireplace is leveled and secured. (Pg. 35) ___________________________ Venting/Chimney Section 7 (Pg 36-41) Venting con guration complies to vent diagrams. ___________________________ Venting installed, locked and secured in place with proper clearance. ___________________________ Firestops installed. ___________________________ Attic insulation shield installed. ___________________________ Exterior wall/Roof  ashing installed and sealed. ___________________________ Terminations installed and sealed. ___________________________ Electrical Section 8 (Pg 42-44) 120VAC unswitched power provided to the appliance. ___________________________ Switch wires properly installed. ___________________________ Gas Section 9 (Pg 45-46) Proper appliance for fuel type. ___________________________ Was a conversion performed? ___________________________ Leak check performed and inlet pressure veri ed. ___________________________ Veri ed proper air shutter setting for installation type. ___________________________ Finishing Section 10 (Pg 47-49) Combustible materials not installed in non-combustible areas. ___________________________ Veri ed all clearances meet installation manual requirements. ___________________________ Mantels and wall projections comply with installation manual requirements. ___________________________ Appliance Setup Section 11 (Pg 50-58) All packaging and protective materials removed (inside & outside of appliance). ___________________________ Refractories, logs, media and embers installed correctly. ___________________________ Glass assembly installed and secured. ___________________________ Accessories installed properly. ___________________________ Mesh, doors, or decorative front properly installed. ___________________________ Manual bag and all of its contents are removed from inside/under the appliance and given to party responsible for use and operation. ___________________________ Started appliance and veri ed no gas leaks exist. ___________________________ Customer: Lot/Address: Model (circle one): SL-5F SL-7F Date Installed: Location of Fireplace: Installer: Dealer/Distributor Phone # Serial #: Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective action needed _____________________________________________________________________________________ _________________________________________________________________________________________________ _________________________________________________________________________________________________ Comments Communicated to party responsible ____________________ by ______________________on ___________ (Builder / Gen. Contractor/) (Installer) (Date) 2499-982 10/16 = Contains updated information. Hearth & Home Technologies recommends the following: • Photographing the installation and copying this checklist for your  le. • That this checklist remain visible at all times on the appliance until the installation is complete. This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this installation manual. WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions could lead to a  re or explosion. ATTENTION INSTALLER: Follow this Standard Work Checklist 01/08/2019 4 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 B. Glass Specifications Hearth & Home Technologies appliances manufactured with tempered glass may be installed in hazardous lo- cations such as bathtub enclosures as defined by the Consumer Product Safety Commission (CPSC). The tempered glass has been tested and certified to the re- quirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certification Council SGCC# 1595 and 1597. Architectural Testing, Inc. Reports 02-31919.01 and 02-31917.01). This statement is in compliance with CPSC 16 CFR Sec- tion 1201.5 “Certification and labeling requirements” which refers to 15 U.S. Code (USC) 2063 stating “…Such certificate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered.” Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order. C. BTU Specifications A. Appliance Certification E. Non-Combustible Materials Specification Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof. Materials that are reported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered non-combustible materials. F. Combustible Materials Specification Materials made of or surfaced with wood, compressed pa- per, plant fibers, plastics, or other material that can ignite and burn, whether flame proofed or not, or plastered or unplastered shall be considered combustible materials. G. Electrical Codes NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1. • A 110-120 VAC circuit for this product must be pro- tected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks. NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE. This appliance is tested and approved as either supplemen- tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations. D. High Altitude Installations NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction. When installing above 2000 feet elevation: • In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet. • In CANADA: Input ratings are certified without a reduction of input rate for elevations up to 4500 feet (1370 m)above sea level. Please consult provincial and/ or local authorities having jurisdiction for installations at elevations above 4500 feet (1370 m). Check with your local gas utility to determine proper orifice size. NOTICE: This installation must conform with local codes. In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada. 1 Product Specific and Important Safety Information This product is listed to ANSI standards for “Vented Gas Fireplace Heaters” and applicable sections of “Gas Burn- ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”. Models (U.S. or Canada) Maximum Input BTU/h Minimum Input BTU/h Orifice Size (DMS) SL-5F (NG)(0-2000 FT)17,500 12,000 45 SL-5F (Propane)(0-2000 FT)17,000 13,500 1.25 mm SL-7F (NG)(0-2000 FT)24,000 16,500 42 SL-7F (Propane)(0-2000 FT)20,500 16,500 54 MODELS: SL-5F, SL-7F LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Direct Vent Heater STANDARD: ANSI Z21.88-2017 • CSA 2.33-2017 H. California WARNING: This product and the fuels used to operate this product (liquid propane or natural gas), and the products of combustion of such fuels, can expose you to chemicals including benzene, which is known to the State of California to cause cancer and reproductive harm. For more information go to: www. P65Warnings.ca.gov.01/08/2019 5Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 I. Requirements for the Commonwealth of Massachusetts For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfied: Installation of Carbon Monoxide Detectors At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addi- tion, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detec- tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors. In the event that the side wall horizontally vented gas fu- eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur- ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accor- dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. Signage A metal or plastic identification plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu- eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- STRUCTIONS”. Inspection The state or local gas inspector of the side wall horizon- tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. Exemptions The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: • The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and • Product Approved side wall horizontally vented gas fu- eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: • Detailed instructions for the installation of the venting system design or the venting system components; and • A complete parts list for the venting system design or venting system. Gas Equipment Venting System NOT Provided When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro- vide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer: • The referenced “special venting system” instructions shall be included with the appliance or equipment in- stallation instructions; and • The “special venting systems” shall be Product Ap- proved by the Board, and the instructions for that sys- tem shall include a parts list and detailed installation instructions. A copy of all installation instructions for all Product Ap- proved side wall horizontally vented gas fueled equip- ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. See Gas Connection section for additional Common- wealth of Massachusetts requirements. Note: The following requirements reference various Massachusetts and national codes not contained in this document. 01/08/2019 6 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 2 Getting Started A. Design and Installation Considerations Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required. Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fire officials or authorities having jurisdiction over restrictions, installation inspection and permits. Before installing, determine the following: • Where the appliance is to be installed. • The vent system configuration to be used. • Gas supply piping requirements. • Electrical wiring requirements. • Framing and finishing details. • Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualified service technician, service agency or your dealer. Figure 2.1 Good Faith Wall Surface Temperatures Above Appliance (SL-5F/SL-7F) B. Good Faith Wall Surface NOTICE: Temperatures listed above are taken with a temperature measuring probe as prescribed by the test standard used for appliance certification. Temperatures on walls or mantels taken with an infrared thermometer may yield increased temperatures of up to 30 degrees or more depending on the thermometer settings and material characteristics being measured. MEASUREMENTS FROM TOP EDGE OF THE OPENING 6 in. 18 in. 24 in. 30 in. 36 in. 48 in. TO CEILING 42 in. 12 in.142°F APPLIANCE FRONT FIREPLACE OPENING 132°F 128°F 125°F 122°F 120°F 117°F 116°F Installation and service of this appliance should be performed by qualified personnel. Hearth & Home Technologies recommends HHT Factory Trained or NFI certified professionals. 01/08/2019 7Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 D. Inspect Appliance and Components • Carefully remove the appliance and components from the packaging. • The vent system components and decorative doors and fronts may be shipped in separate packages. • If packaged separately, the log set and appliance grate must be installed. • Report to your dealer any parts damaged in shipment, particularly the condition of the glass. • Read all of the instructions before starting the instal- lation. Follow these instructions carefully during the installation to ensure maximum safety and benefit. WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, in- complete or substitute components. Keep appliance dry. C. Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available. Tape measure Framing material Pliers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter Electric drill and bits (1/4 in.) Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non-corrosive leak check solution 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws Caulking material (300 ºF minimum continuous exposure rating) One 1/4 in. female connection (for optional fan).Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions: • Installation and use of any damaged appliance or vent system component. • Modification of the appliance or vent system. • Installation other than as instructed by Hearth & Home Technologies. • Improper positioning of the gas logs or the glass door. • Installation and/or use of any component part not approved by Hearth & Home Technologies. Any such action may cause a fire hazard. WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance if any part has been under water. Call a qualified service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water. 01/08/2019 8 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 3 Framing and Clearances A. Appliance/Decorative Front Dimension Diagram Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5. Figure 3.1 Appliance Dimensions SL-5F SL-7F Location Inches Millimeters Inches Millimeters A 36 914 41 1041 B 31-1/8 791 36-1/8 918 C 27-3/16 691 32-1/16 814 D 18-1/16 459 21-1/2 546 E 34-1/16 865 37-5/8 956 F 3-9/16 90 3-9/16 90 G 6-7/8 175 6-7/8 175 H 23-3/8 594 26-7/8 683 I 34-3/8 873 37-7/8 962 J 36-7/16 926 39-15/16 1014 K 8 203 8 203 L 8-13/16 224 8-13/16 224 M 16-5/16 414 16-5/16 414 N 1/2 13 1/2 13 O 25-3/4 654 30-3/4 781 P 12-7/8 327 15-3/8 391 Q 15-7/8 403 15-7/8 403 R 6-5/8 168 6-5/8 168 S 2-3/16 56 2-3/16 56 T 6 152 6 152 U 1 25 1 25 V 30-1/16 764 33-9/16 853 L M NO P RØ Q GAS LINE ACCESS T S F ELECTRICALACCESSG H JI KØC V A B U E D 01/08/2019 9Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A C B D E F G Figure 3.2 Appliance Dimensions - Firescreen and Clean Face Decorative Fronts CLEAN FACE DECORATIVE FRONTS C B D E F GA A B C D E F G SL-5F in.30-5/16 27-1/4 29-1/2 25-7/8 28-3/4 2-3/16 1-1/2 mm 770 692 749 657 730 56 38 SL-7F in.35-13/16 31-1/8 34-3/8 29-5/8 32-1/2 2-1/8 1-5/16 mm 910 791 873 752 826 54 33 FIRESCREEN DECORATIVE FRONTS (Factory-Supplied) A B C D E F G SL-5F in.30-13/16 23-5/16 26-9/16 18-11/16 25-7/16 3-1/2 4-9/16 mm 783 592 675 475 646 89 116 SL-7F in.35-13/16 26-13/16 31-1/2 22-3/16 28-15/16 3-1/2 4-9/16 mm 910 681 800 564 735 89 116 01/08/2019 10 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 B. Clearances to Combustibles When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 3.3). WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access. Due to high temperatures, the appliance should be lo- cated out of traffic and away from furniture and draperies. NOTICE: Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference. Figure 3.3 Appliance Locations K C A L F I B G E D J J G A F C A HM N Refer to Section 10.B for mantel and wall projection information. Consider the mantel or cabinet system to be installed and comply with the necessary requirements for elevated hearth. Refer to instructions included with cabinet system. Models A B C D E Min. F Min.G H I J K L M N SL-5F in.42 37 59-1/2 See Section 10.B for Alcove Instal- lation 1 1/2 44 62-1/4 16-1/4 48-1/2 68-3/4 15-1/16 7-1/2 7-1/8 mm 1067 940 1511 25 13 1118 1581 413 1232 1746 383 191 181 SL-7F in.45-1/2 42 64-3/8 1 1/2 45-1/2 64-3/8 16-1/4 48-1/2 68-3/4 16-5/8 7-1/2 9 mm 1156 1067 1635 25 13 1156 1635 413 1232 1746 422 191 229 01/08/2019 11Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 C. Constructing the Appliance Chase A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase. NOTICE: Treatment of ceiling firestops and wall shield firestops and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps. NOTICE: When installing a sprinkler head in a fireplace chase, it is recommended to use a sprinkler head with a sprinkler activation temperature classified as Extra High. Keep sprinkler head away from vent and chimney. Chases should be constructed in the manner of all out- side walls of the home to prevent cold air drafting prob- lems. The chase should not break the outside building envelope in any manner. Walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infiltration may be an issue, the inside surfaces may be sheetrocked and taped (or an equivalent method may be WARNING! Risk of Fire! Maintain specified air space clearances to appliance and vent pipe: • Insulation and other materials must be secured to prevent accidental contact. • The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney. • Failure to maintain airspace may cause overheating and a fire. used) to achieve maximum air tightness. To further prevent drafts, the wall shield and ceiling fire- stops should be caulked with caulk with a minimum of 300 ºF continuous exposure rating to seal gaps. Gas line holes and other openings should be caulked with caulk with a minimum of 300 ºF continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement surface, a layer of plywood may be placed underneath to prevent conducting cold up into the room. D. Floor Protection NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood. Figure 3.4 Clearances to Combustibles C B D A MINIMUM FRAMING DIMENSIONS* Models A B C D E F G H I J DVP Pipe SLP Pipe Rough Opening (Height) **DVP Pipe SLP Pipe Rough Opening (Width) Clearance to Ceiling Combustible Floor Combustible Flooring Behind Appliance Sides of Appliance Front of ApplianceRough Opening (Width) Rough Opening (Width) Rough Opening (Depth) Rough Opening (Depth) SL-5F in.10 8-5/8 34-3/4 16-1/4 16-1/4 37 32 0 0 1/2 1/2 36 mm 254 219 883 413 413 940 813 0 0 13 13 914 SL-7F in.10 8-5/8 38-1/4 16-1/4 16-1/4 42 32 0 0 1/2 1/2 36 mm 254 219 972 413 413 1067 813 0 0 13 13 914 * Adjust framing dimensions for interior sheathing (such as sheetrock) C** Add 12 inches for rear venting with one 90º elbow. E FROM TOP OF HOOD TO CEILING I F GJ H 01/08/2019 12 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Vent Termination Minimum Clearances Roof Pitch H (Min.) Ft. Flat to 6/12...........................................................1.0* Over 6/12 to 7/12 .................................................1.25* Over 7/12 to 8/12 .................................................1.5* Over 8/12 to 9/12 .................................................2.0* Over 9/12 to 10/12 ...............................................2.5* Over 10/12 to 11/12 .............................................3.25 Over 11/12 to 12/12 .............................................4.0 Over 12/12 to 14/12 .............................................5.0 Over 14/12 to 16/12 .............................................6.0 Over 16/12 to 18/12 .............................................7.0 Over 18/12 to 20/12 .............................................7.5 Over 20/12 to 21/12 .............................................8.0 Figure 4.1 Minimum Height From Roof To Lowest Discharge Opening HORIZONTALOVERHANG VERTICALWALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCHIS X/ 12 LOWEST DISCHARGE OPENING 2 FT.MIN.20 INCHES MIN. H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 4 Termination Location and Vent Information Fire Risk. Maintain vent clearance to combustibles as specified. • DO NOT pack air space with insulation or other materials. Failure to keep insulation or other materials away from vent pipe could cause overheating and fire. WARNING Figure 4.2 Staggered Termination Caps Gas, Wood or Fuel Oil Termination Cap B Gas Termination Cap ** A * *If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instructions supplied with the decorative cap cover. ** A B 6 in. (minimum) up to 20 in. 152 mm/508 mm 18 in. minimum 457 mm 20 in. and over 0 in. minimum In a staggered installation with both gas and wood or fuel oil terminations, the wood or fuel oil termination cap must be higher than the gas termination cap. * H minimum may vary depending on regional snowfall. Refer to local codes. 01/08/2019 13Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 4.3 Minimum Clearances for Termination O N P R Q X = AIR SUPPLY INLET A = 12 inches.................clearances above grade, veranda, porch, deck or balcony B = 9 inches...................clearance to window or door that may be opened, or to permanently closed window C = 18 inches.................clearance below unventilated soffit 18 inches.................clearance below ventilated soffit 30 inches .................clearance below vinyl soffits and electrical service D = 6 inches...................clearance to outside corner E = 6 inches...................clearance to inside corner F = 3 ft. (Canada) ..........not to be installed above a gas me- ter/regulator assembly within 3 feet horizontally from the center-line of the regulator G = 3 ft ...........................clearance to gas service regulator vent outlet H = 12 inches.................clearance to non-mechanical (unpow- ered) air supply inlet, combustion air inlet or direct-vent termination i = 3 ft. (U.S.A.) 6 ft. (Canada) ...........clearance to a mechanical (powered) air supply inlet All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below termination.J = 7 ft. ......................... On public property: clearance above paved sidewalk or a paved driveway. A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. V = VENT TERMINAL = AREA WHERE TERMINAL IS NOT PERMITTED C J B D B F B A EV V VV V V M H or i V G X V H A V V H Electrical Service V KV K V L C V N = 6 inches ...........non-vinyl sidewalls 12 inches .........vinyl sidewalls O = 18 inches .........non-vinyl soffit and overhang 42 inches .........vinyl soffit and overhang P = 8 ft. QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2/3 x Q ACTUAL 4 caps 12 feet 1/2 x Q ACTUAL QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL Covered Alcove Applications (Spaces open only on one side and with an overhang) Measure horizontal clearances from this surface. Measure vertical clearances from this surface. CLEARANCE = 6 IN. CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffic areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer. • Local codes or regulations may require different clearances. • Vent system termination is NOT permitted in screened porches. • Vent system termination is permitted in porch areas with two or more sides open. • Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements. • Vinyl protection kits are suggested for use with vinyl siding. M = 18 inches ....................clearance under veranda, porch, deck, balcony or overhang 42 inches ................vinyl or composite overhangPermitted when veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor. K = 6 inches................. clearance from sides of electrical service L = 12 inches................ clearance above electrical service Location of the vent termination must not interfere with access to the electrical service. B. Chimney Diagram 01/08/2019 14 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 C. Approved Pipe This appliance is approved for use with Hearth & Home Technologies DVP or SLP venting systems. Refer to Sec- tion 12.A for vent component information and dimensions. DO NOT mix pipe, fittings or joining methods from differ- ent manufacturers. The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall. WARNING! Risk of Fire or Asphyxiation. This appli- ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance. 01/08/2019 15Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 D. Use of Elbows Diagonal runs have both vertical and horizontal vent as- pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. See Figure 4.4. Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows. See Figure 4.4. Figure 4.5 shows the vertical and horizontal offsets for DVP or SLP elbows. Figure 4.4 HORIZONTAL VERTICAL RUN RISEEFFECTIVELENGTHY X X X DVPPipe Effective Length Rise/Run Inches Millimeters Inches Millimeters DVP4 4 102 2-3/4 70 DVP6 6 152 4-1/4 108 DVP12 12 305 8-1/2 216 DVP24 24 610 17 432 DVP36 36 914 25-1/2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108 DVP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216 Vent Type X Inches Millimeters DVP 16-1/4 413 SLP 11-1/4 286 Figure 4.5 Vertical and Horizontal Offset for DVP and SLP Elbows Vent Type X Y Inches Millimeters Inches Millimeters DVP 4-1/2 114 17 432 SLP 5 127 11-3/4 298 SLP Pipe Effective Length Rise/Run Inches Millimeters Inches Millimeters SLP4 4 102 2-3/4 70 SLP6 6 152 4-1/4 108 SLP12 12 305 8-1/2 216 SLP24 24 610 17 432 SLP36 36 914 25-1/2 648 SLP48 48 1219 34 864 SLP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108 SLP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216 01/08/2019 16 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 E. Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards: • Pipe measurements are shown using the effective length of pipe. See Section 12.A (Figure 12.1 for DVP, Figure 12.6 for SLP) for information on effective length of pipe components. • Horizontal terminations are measured to the outside mounting surface (flange of termination cap) (see Figure 4.8). • Vertical terminations are measured to top of last section of pipe. See Figure 4.7. • Horizontal pipe installed level with no rise. MEASURE TO SHADED SURFACE (OUTSIDE MOUNTING SURFACE) Figure 4.6 Measure to Outside Mounting Surface Figure 4.7. Measure to Top of Last Section of Pipe 01/08/2019 17Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 To replace the first 90º starter elbow with two 45º elbows, refer to Figure 4.7. All other 90º elbows can be replaced with two 45º elbows. General Rules: • SUBTRACT 3 ft. from the total H measurement for each 90º elbow installed horizontally. • SUBTRACT 1-1/2 ft. from the total H measurement for each 45º elbow installed horizontally. • Elbows may be placed back to back anywhere in the system as long as the first 90º elbow is a starter elbow except as shown in Figure 4.9. • When penetrating a combustible wall, a wall shield firestop must be installed. • When penetrating a combustible ceiling, a ceiling firestop must be installed. • Horizontal runs of vent do not require vertical rise; horizontal runs may be level. • Horizontal termination cap should have a 1/4 inch downward slant to allow any moisture in cap to be released. See Figure 4.9. G. Vent Diagrams Top Vent—Horizontal Termination—Two 45º Elbows Installation requirements to replace the first 90º elbow with two 45º elbows: 4 ft min. (1.22 m) 25 ft max. (7.62 m) 1/4 in. max. (6 mm) Figure 4.9 F. Use of Flex Vent The flex vent must be supported with the spacing between support intervals not exceeding 4 feet, with no more than ½ inch sag between supports. A support is required at each change in venting direction, and in any location where it is necessary to maintain the necessary clearance to combustibles. A simple “up and out” installation (Figure 4.8) requires only enough sup- port to maintain the necessary clearance to combustibles. However, the vent attachment point and the firestop loca- tion are considered to be supports. Figure 4.8 3 in. CLEARANCE TERMINATION CAP FLEX-VENT 1 in. CLEARANCE 01/08/2019 18 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 V1 Minimum**H1 Maximum 90 Elbow Only**2 ft.610 mm 1/2 ft.**152 mm 2 ft.610 mm 1-1/2 ft.**457 mm 3 ft.914 mm 2-1/2 ft.**762 mm 5 ft.1.5 m 3-1/2 ft.1.1 m 7 ft.2.1 m 4-1/2 ft.1.4 m 15 ft.4.6 m H1 MAX. =15 ft. (4.6 m) V1 + H1 MAX. = 40 ft. (12.2 m) ** See Warning. Figure 4.10 Top Vent - Horizontal Termination One Elbow Fire Risk. • When using SLP-HRC-SS termination cap on top vented fireplaces, a one foot minimum vertical vent section is required before installing first elbow. WARNING** Note: Use SLP Series components only. H1 V1 ELBOW HEAT SHIELD (Required when V1 = less than 1-1/2 ft.) Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation. See Figure 4.8. 01/08/2019 19Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Top Vent - Horizontal Termination - (continued) Figure 4.11 Two Elbows V1 Minimum**H1 + H2 Maximum 90 Elbow Only**1/2 ft.152 mm 1/2 ft.**152 mm 1 ft.305 mm 1-1/2 ft.**457 mm 2 ft.610 mm 2-1/2 ft.**762 mm 4 ft.1.2 m 3-1/2 ft.1.1 m 6 ft.1.8 m 4-1/2 ft.1.4 m 14 ft.4.3 m H1 + H2 MAX. =14 ft. (4.3 m) V1 + H1 + H2 MAX. = 40 ft. (12.2 m) **See Warning Below. Fire Risk. • When using SLP-HRC-SS termination cap on top vented fireplaces, a one foot minimum vertical vent section is required before installing first elbow. WARNING** Note: Use SLP Series components only. INSTALLED HORIZONTALLY H1 H2 V1 Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation. See Figure 4.8. 01/08/2019 20 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Three Elbows V1 Minimum**H1 Maximum H1 + H2 Maximum V2 V1 + V2 Minimum 90 Elbow Only**1-1/2 ft.457 mm 2 ft.610 mm ** 1/2 ft.**152 mm 1-1/2 ft.457 mm 4 ft.1.2 m ** 1-1/2 ft.457 mm 3 ft.914 mm 6 ft.1.8 m ** 2-1/2 ft.762 mm 5 ft.1.5 m 10 ft.3.0 m ** 3-1/2 ft.1.1 m 7 ft.2.1 m 14 ft.4.3 m ** 4-1/2 ft.1.4 m 14 ft.4.3 m 14 ft.4.3 m ** H1 + H2 MAX. =14 ft. (4.3 m) V1 + V2 + H1 + H2 MAX. = 40 ft. (12.2 m) No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 CANNOT exceed 40 ft. (12.2 m). ** See Warning Below. Fire Risk. • When using SLP-HRC-SS termination cap on top vented fireplaces, a one foot minimum vertical vent section is required before installing first elbow. WARNING** Top Vent - Horizontal Termination - (continued) Figure 4.12 Note: Use SLP Series components only. H2 H1 V2 V1 Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation. See Figure 4.8. 01/08/2019 21Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 4.13 V1 = 60 ft. Max. (18.3 m) Top Vent - Vertical Termination No Elbows Figure 4.14 EXHAUST BAFFLE Top Vent Application Rear Vent Application Exhaust restrictors are recommended for these verti- cally terminated products which have excessive draft. Exhaust restrictors will compensate for high draft, and restore visual flame height. If the vent configuration has a total vertical of 15-60 feet, an exhaust restrictor may be needed. The exhaust restrictor can be located in the appliance manual bag. Note: Be sure to rein- stall the exhaust baffle after exhaust restrictor installation. Exhaust restrictor Exhaust restrictor Exhaust restrictor Instructions 1. Install the exhaust restrictor over the center of the ex- haust outlet in the firebox. See Figure 4.14. 2. Center the exhaust restrictor in the open end of the exhaust outlet and secure through the slots on the ex- haust restrictor with the 2-1/4 in. self tapping screws provided in the appliance manual bag. To access the exhaust openings, remove the exhaust baffle. To re- move exhaust baffle, re- move the two wing nuts. Note: If installing a vertical vent/termination off the top of the appliance, the optional vertical termination baffle may be needed. Note: Use SLP Series components only. V1 01/08/2019 22 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Top Vent - Vertical Termination - (continued) Figure 4.15 Two Elbows Note: Use SLP Series components only. V1 Minimum H1 Maximum V2 V1 + V2 Minimum 90 Elbow Only 1-1/2 ft.457 mm ** 1/2 ft.152 mm 2 ft.610 mm ** 1-1/2 ft.457 mm 3 ft.914 mm ** 2-1/2 ft.762 mm 5 ft.1.5 m ** 3-1/2 ft.1.1 m 7 ft.2.1 m ** 4-1/2 ft.1.4 m 15 ft.4.6 m ** H1 MAX. =15 ft. (4.6 m) V1 + V2 + H1 MAX. = 40 ft. (12.2 m) *No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 CANNOT exceed 40 ft. (12.2 m). H1 V1 V2 Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation. See Figure 4.8. 01/08/2019 23Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 4.16 Three Elbows V1 Minimum H1 + H2 Maximum V2 V1 + V2 Minimum 90 Elbow Only 1/2 ft.152 mm ** 1/2 ft.152 mm 1 ft.305 mm ** 1-1/2 ft.457 mm 2 ft.610 mm ** 2-1/2 ft.762 mm 4 ft.1.2 m ** 3-1/2 ft.1.1 m 6 ft.1.8 m ** 4-1/2 ft.1.4 m 14 ft.4.3 m ** H1 + H2 MAX. =14 ft. (4.3 m) V1 + V2 + H1 + H2 MAX. = 40 ft. (12.2 m) *No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 CANNOT exceed 40 ft. (12.2 m). Note: Use SLP Series components only. INSTALLED HORIZONTALLY H1 H2 V1 V2 Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation. See Figure 4.8. Top Vent - Vertical Termination - (continued) 01/08/2019 24 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Top Vent - Vertical Termination - (continued) Four 90º Elbows Figure 4.17 V1 MIN.H1 MAX.V2 MIN.H2 MAX.V3 MIN. 1-1/2 ft.457 mm 4 ft.1.2 m 4 ft.1.2 m 4 ft.1.2 m 3-1/2 ft.1.1 m V1 + V2 + V3 + H1 + H2 Maximum= 40 ft. (12.2 m)Note: Use SLP Series components only. V1 H1 V2 V3 H2 Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation. See Figure 4.8. 01/08/2019 25Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Rear Vent - Horizontal Termination Figure 4.19 Figure 4.18 No Elbows H1 = 9 in. (229 mm) MaximumRear Vent - Horizontal Termination One 45º Elbow Note: Use DVP Series components only. Note: Use DVP Series components only. H1 H1 = 24 in. Max. (610 mm) H1 01/08/2019 26 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 H1 MAX.V1 MIN.H2 MAX.H1 + H2 MAX. 1-1/2 ft.457 mm Back to back elbows 1 ft.305 mm 2-1/2 ft.762 mm 3 ft.914 mm 1 ft.305 mm 3 ft.914 mm 6 ft.1.8 m 5 ft.1.5 m 3 ft.914 mm 5 ft.1.5 m 10 ft.3.0 m 7 ft.2.1 m 5 ft.1.5 m 7 ft.2.1 m 14 ft.4.3 m H1 MAX. = 7 ft. (2.1 m) H1 + H2 MAX. = 14 ft. (4.3 m) V1 + H1 + H2 MAX. = 40 ft. (12.2 m) Figure 4.20 H1 MAX.V1 MIN.H2 + H3 MAX.H1 + H2+ H3 MAX. 1-1/2 ft.457 mm Back to back elbows 1 ft.305 mm 2-1/2 ft.762 mm 3-1/2 ft.1.1 m 1 ft.305 mm 2 ft.610 mm 5-1/2 ft.1.7 m 5-1/2 ft.1.7 m 2 ft.610 mm 4 ft.1.2 m 9-1/2 ft.2.9 m 7-1/2 ft.2.3 m 3 ft.914 mm 6 ft.1.8 m 13-1/2 ft.4.1 m H1 MAX. = 7-1/2 ft. (2.3 m) H1 + H2+ H3 MAX. = 13-1/2 ft. (4.1 m) V1 + H1 + H2+ H3 MAX. = 40 ft. (12.2 m) Figure 4.21 Note: Use DVP Series components only. Note: Use DVP Series components only. Two Elbows Rear Vent - Horizontal Termination - (continued) Three Elbows H1 H2 V1 INSTALLED HORIZONTALLY H3 H1 H2 V1 01/08/2019 27Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Rear Vent - Vertical Termination Figure 4.22 Figure 4.23 V1 MIN.H1 MAX. 1 ft.305 mm 3-1/2 ft.1.1 m 2 ft.610 mm 5-1/2 ft.1.7 m 3 ft.914 mm 7-1/2 ft.2.3 m H MAX. = 7-1/2 ft. (2.3 m) V1 + H1 MAX. = 40 ft. (12.2 m) H1 + H2 MAX V1 MIN. Back to back elbows 1/2 ft.152 mm 2-1/2 ft.762 mm 1 ft.305 mm 4-1/2 ft.1.4 m 2 ft.610 mm 6-1/2 ft.2.0 m 3 ft.914 mm H MAX. = 6-1/2 ft. (2 m) V + H+ H1 MAX. = 40 ft. (12.2 m) Note: Use DVP Series components only. Note: Use DVP Series components only. Two Elbows One Elbow H1 V1 INSTALLED HORIZONTALLY H1 H2 V1 01/08/2019 28 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 V1 MIN.H1 MAX.H2 MAX.H1 + H2 MAX.V2 V1 + V2 Minimum Back to back elbows 1-1/2 ft.457 mm 1 ft.305 mm 2-1/2 ft.762 mm ** 1 ft.305 mm 3-1/2 ft.1.1 m 3 ft.914 mm 6-1/2 ft.2.0 m ** 2 ft.610 mm 5-1/2 ft.1.7 m 5 ft.1.5 m 10-1/2 ft.3.2 m ** 3 ft.914 mm 7-1/2 ft.2.3 m 7 ft.2.1 m 14-1/2 ft.4.4 m ** H1 MAX. = 7-1/2 ft. (2.3 m) H1 + H2 MAX. = 14-1/2 ft. (4.4 m) V1 + V2 + H1 + H2 MAX. = 40 ft. (12.2 m) *No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 CANNOT exceed 40 ft. (12.2 m). Figure 4.24 Three Elbows Note: Use DVP Series components only. Rear Vent - Vertical Termination - (continued) V2 V1 H2 H1 01/08/2019 29Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 EXHAUST VENT PIPEINLET AIR VENT PIPE Figure 4.25. Coaxial/Colinear Appliance Connector OUTSIDE FACE OF FIREPLACE TOP OF FIREPLACE OPENING SHADED AREA DEFINED AS “INSIDE EXISTING MASONRY FIREPLACE” 3 IN. MIN. 5 IN. MIN. EXHAUST VENT PIPE Figure 4.26. Existing Fireplace DV-46DVA-GCL Clearance Requirements Clearances to Combustibles: Refer to Section 3 for clearances to the appliance, man- tel, mantel legs and wall projection. Refer to Section 5 for pipe clearances to combustibles. Termination Cap For installation of termination cap see minimum vent heights for various pitched roofs. See Section 4.A. Flue Damper Fully lock the solid fuel fireplace’s flue damper in the open position, OR completely remove it. Venting Components The LINK-DV30B is approved for use with the coaxial/co- linear venting application. The LINK-DV30B kit includes: • Two 30 foot sections of flexible vent pipe (3 inches Ø). One section is used to draw combustion air and the other section is used to expel exhaust gases. • One vertical termination cap. WARNING! Risk of Fire! Coaxial to colinear venting con- figuration may only be used in existing non-combustible chimney. Installation in any other venting application could cause fire. Prior to installing the gas appliance: • Have the chimney and adjacent structure inspected and cleaned by qualified professionals. Hearth & Home Technologies recommends that NFI or CSIA certified professionals, or technicians under the direction of certi- fied professionals, conduct a minimum of a NFPA 211 Level 2 inspection of the chimney. • Replace component parts of the chimney and fireplace as specified by the professionals. • Ensure all joints are properly engaged and the chimney is properly secured. Coaxial to Colinear Venting The coaxial to colinear adapter (DV-46DVA-GCL) is ap- proved for installations into solid fuel masonry or factory built fireplaces that have been installed in accordance with the National, Provincial, State and local building codes. The DV-46DVA-GCL must be recessed into exist- ing masonry fireplace. See Table 1 and Figure 4.26. Table 1 CLEARANCE TO COMBUSTIBLES REQUIREMENTS DV-46DVA-GCL 3 IN. Exhaust Vent Pipe 5 IN.CAUTION! DO NOT use any flue restrictor when vent- ing with the DV-46DVA-GCL adapter and LINK-DV30B kit. This could result in poor flame appearance, sooting, pilot malfunction, or overheating. 01/08/2019 30 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 4.27 EXISTING CHIMNEY HEARTHFLOOR EXISTING CHIMNEY EXHAUST AIR VENT PIPE INLET AIR VENT PIPE To minimize cold air drafts, seal with non-combustible insulation. TERMINATION CAP DIRECT VENT FIREPLACE V COAXIAL/COLINEAR APPLIANCE CONNECTOR The first 3 feet of exhaust flue must be stainless flex pipe. TERMINATION CAP EXISTING CHIMNEY EXISTING CHIMNEY EXHAUST AIR VENT PIPE V FLOOR HEARTH H To minimize cold air drafts, seal with non-combustible insulation.DIRECT VENT FIREPLACE DVP-2SL COAXIAL/COLINEAR APPLIANCE CONNECTOR INLET AIR VENT PIPE The first 3 feet of exhaust flue must be stainless flex pipe. TOP VENTREAR VENT V Minimum 10 ft.3.05 m Maximum 40 ft.12.2 m V H Minimum 10 ft.3.05 m 0 ft.0 mm Maximum 40 ft.12.2 m 2 ft.610 mm NOTICE: To achieve optimum perfor- mance of appliance, minimize or avoid bends in exhaust vent pipe. CAUTION! DO NOT use any flue restric- tor when venting with the DV-46DVA-GCL adapter and LINK-DV30B kit. This could result in poor flame appearance, sooting, pilot malfunction, or overheating. Connecting the DV-46DVA-GCL Adapter to Appliance Top Vent • Remove top seal cap and insulation if equipped. See Section 6, “Appliance Preparation.” Attach the DV-46DVA-GCL adapter to the appliance starting collar with 3-1/2 in. self-tapping screws. See Figure 4.27. Rear Vent • Remove the rear seal cap and insulation if equipped. Connect the DVP-2SL adapter to the vertically positioned elbow. Follow installation instructions included with DVP- 2SL kit. Secure DV-46DVA-GCL adapter to DVP-2SL with 3-1/2 in. self-tapping screws. See Figure 4.27. Connecting the LINK-DV30B to the DV-46DVA-GCL adapter • Insert the two sections of flexible vent pipe down the existing chimney. • Attach one section of stainless steel flex pipe to the exhaust collar on top of the DV-46DVA-GCL adapter with three screws. WARNING! Risk of Fire, Explosion or Asphyxiation! Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance. • May impair safe operation of this appliance or other appliances connected to the flue. • Vent this appliance directly outside. • Use separate vent system for this appliance. • Attach one section of flexible vent pipe to the stainless steel flex pipe with three self-tapping screws. • Attach one section of flexible vent pipe to the inlet collar on top of the DV-46DVA-GCL adapter with three self- tapping screws. • To minimize cold air drafts, seal around the flex vents at the damper inside the chimney with non-combustible unfaced fiberglass or rock wool insulation. The DV-46DVA-GCL adapter must be recessed into existing masonry fireplace. This measurement is taken from the top of the fireplace opening. See Table 1 and Figure 4.26. 01/08/2019 31Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Pipe Clearances to Combustibles WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles: • Between ceiling firestops • Between wall shield firestops • Around vent system Failure to keep insulation or other material away from vent pipe could cause overheating and fire. 5 Vent Clearances and Framing Figure 5.2 Wall Penetration Figure 5.1 Horizontal Venting Clearances To Combustible Materials * When using SLP pipe, minimum clearances from the vent pipe to combustible materi- als at inside wall firestops are: Top: 2-1/2 in. (64 mm) Bottom: 1/2 in. (13 mm) Sides: 1 in. (25 mm) Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). • DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. • If wall thickness is less than 4 in. the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required. • SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to 194 mm thick). • If wall thickness is less than 4-3/8 the existing heat shields must be field trimmed. If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required. (DVP-SLP Pipe Shown) 3 in. (76 mm) top clearance * 1 in. (25 mm) clearance bottom & sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in. (76 mm) top clearance * 1 in. (25 mm) clearance bottom & sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in. (76 mm) top clearance 1 in. (25 mm) clearance around vertical sections B. Wall Penetration Framing/Firestops Combustible Wall Penetration Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop(s). The wall shield firestop maintains minimum clearances and prevents cold air infiltration. * Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe. A*B*C D SL-5F in.37-7/16 24-3/8 36-7/16 23-3/8 mm 951 619 926 594 SL-7F in.41 27-7/8 40 26-7/8 mm 1041 708 1016 683 C D B*A* 10 in.12 in. 10 in.10 in. ELBOW HEAT SHIELD WARNING! Risk of Fire! Elbow heat shield required when V1 = less than 1-1/2 ft. Clearances to combustibles must be maintained. See Section 5.A. • The opening must be framed on all four sides using the same size framing materials as those used in the wall construction. • SLP pipe - A wall shield firestop must be placed on each side of an interior wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be maintained. • DVP pipe - A wall shield firestop is required on one side only on interior walls. If your local inspector requires a wall shield firestop on both sides, then both wall shield firestops must have a heat shield (refer to Section 12.A.) attached to them. • See Section 7.G. for information for regarding the in- stallation of a horizontal termination cap. Non-Combustible Wall Penetration If the hole being penetrated is surrounded by non-com- bustible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable. Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary. 01/08/2019 32 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 C. Ceiling Firestop/Floor Penetra- tion Framing A ceiling firestop MUST be used between floors and attics. • DVP pipe only - Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/floor (see Figure 5.3). • SLP pipe only - Frame opening 9 in. x 9 in. (229 mm x 229 mm) whenever the vent penetrates a ceiling/floor (see Figure 5.3). • Frame the area with the same sized lumber as used in ceiling/floor joist. • The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield. It must be under joists between floors that are not insulated. Refer to Figure 5.4. • Secure with three fasteners on each side. WARNING! Risk of Fire! DO NOT pack insu- lation around the vent. Insulation must be kept back from the pipe to prevent overheating. Figure 5.3 Installing Ceiling Firestop Figure 5.4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING ATTIC ABOVE A PIPE DVP SLP A 10 in. (254 mm) 9 in. (229 mm) A D. Install Attic Insulation Shield WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies requires the use of an attic shield. The International Fuel Gas Code requires an attic shield constructed of 26 gauge minimum steel that extends at least 2 in. (51 mm) above insulation. • Attic insulation shields must meet specified clearances to combustible materials and be secured in place. • An attic insulation shield kit is available from Hearth & Home Technologies. Contact your dealer to order. Install attic insulation shield according to instructions included with kit. 01/08/2019 33Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp. NOTICE: Once appliance is set up for top or rear venting, it CANNOT be changed at a later time. A. Vent Collar Preparation - Top or Rear 6 Appliance Preparation Top Vent Figure 6.3 Rotate the top heat shield to the vertical position as shown above. The heat shield must remain in the vertical position. Figure 6.5 Remove the seal cap. Figure 6.6 Remove the insulation basket and white insula- tion from the center vent pipe. Figure 6.2 Remove the two screws holding the top heat shield in place. For rear vent, see next page. Note: Actual appliance may look different than the appliance shown in this section. 2 SCREWS 2 SCREWS Figure 6.4 Replace the two screws as shown. WARNING! Risk of Fire! Do not remove heat shield. El- evated header temperatures may cause a fire. Figure 6.1 For top vent, remove the screw holding the elbow heat shield in place. 01/08/2019 34 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Rear Vent NOTICE: Once appliance is set up for top or rear venting, it CANNOT be changed at a later time. NOTICE: Once the seal cap has been removed it CANNOT be reattached. Figure 6.8 Fold the tabs toward the center of the fire plug (90º) and remove the insulation gasket. Figure 6.10 Fold the center parts of the retaining band toward the center as shown. Remove the seal cap. Figure 6.11 Discard the seal cap, remove and discard the insulation basket. Note: Once the seal cap has been removed it CANNOT be reattached. Figure 6.12 Attach the first vent section (it will snap into place). Slide the insulation gasket onto the vent section, up against the appliance and over the tabs. Use four self- tapping screws to secure gasket to outer wrap. Figure 6.9 Cut the metal retaining band and fold the sides out. Figure 6.7 Remove the insulation from the outer vent pipe. 01/08/2019 35Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 B. Securing and Leveling the Appliance WARNING! Risk of Fire! Prevent contact with: • Sagging or loose insulation • Insulation backing or plastic • Framing and other combustible materials Block openings into the chase to prevent entry of blown- in insulation. Make sure insulation and other materials are secured. DO NOT notch the framing around the appliance standoffs. Failure to maintain air space clearance could cause overheating and fire. The diagram shows how to properly position and secure the appliance. See Figure 6.13. Nailing tabs are provided to secure the appliance to the framing members. • Bend out nailing tabs on each side. • Place the appliance into position. • Keep nailing tabs flush with the framing. • Level the appliance from side to side and front to back. • Shim the appliance as necessary. It is acceptable to use wood shims underneath the appliance. • Secure the appliance to the framing by using nails or screws through the nailing tabs. • Optional: Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance. Figure 6.13 Proper Positioning and Securing of an Appliance NAILING TABS (BOTH SIDES) 01/08/2019 36 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 7 Venting and Chimneys A. Assemble Vent Sections (DVP Pipe) Attach Vent to the Firebox Assembly Note: The end of the pipe sections with the lanced tabs will face toward the appliance. Attach the first pipe section to the starting collar: • Lanced pipe end of the starting collar. • Inner pipe over inner collar. • Push the pipe section until all lanced tabs snap in place. • Lightly tug on pipe to confirm it has locked. Figure 7.1 High Temperature Silicone Sealant Figure 7.2 A B Figure 7.3 Assemble Pipe Sections Per Figure 7.2: • Start the inner pipe on the lanced end of section A into the flared end of section B. • Start the outer pipe of section A over the outer pipe of section B. • Once both vents sections are started, push firmly until all lanced tabs lock into place. • Lightly tug on the pipe to confirm the tabs have locked. It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer pipe sections together. If predrilling holes, DO NOT penetrate inner pipe. For 90º and 45º elbows that are changing the vent direction from horizontal to vertical, one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2 in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe. WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip sections. Use care when remov- ing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent could leak. Figure 7.4 Seams Note: Make sure that the seams are not aligned to prevent unintentional disconnection. INCORRECT CORRECT Lances Required Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications All outer pipe joints must be sealed with 100% silicone (300 ºF minimum continuous exposure rating), including the slip section that connects directly to the horizontal ter- mination cap. • Apply a bead of silicone sealant (300 ºF minimum con- tinuous exposure rating) inside the female outer pipe joint prior to joining sections. See Figure 7.1. OR Apply a bead of silicone sealant (300 ºF minimum con- tinuous exposure rating) to the outside of connecting joint after joining sections OR Apply aluminum foil tape (300 ºF minimum continuous exposure rating) to the outside of connecting joint after joining sections. On horizontal pipe runs, it is recom- mended that the tape seam is positioned on the bottom side of the vent pipe. • Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed in this manner, unless otherwise stated. 01/08/2019 37Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 B. Assemble Vent Sections (SLP Pipe) To attach the first vent component to the starting collars of the appliance: • Lock the vent components into place by sliding the pipe section onto the collar. • Align the seam of the pipe and seam of collar to allow engagement. Rotate the vent component to lock into place. Use this procedure for all vent components. See Figure 7.5. • Slide the gasket over the first vent section and place it flush to the appliance. This will prevent cold air infiltration. Caulk with a minimum of 300 ºF continuous exposure rating may be used to hold the part in place. • Continue adding vent components, locking each succeeding component into place. • Ensure that each succeeding vent component is securely fitted and locked into the preceding component. Required Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications All outer pipe joints must be sealed with high temperature silicone (300 ºF minimum continuous exposure rating), in- cluding the slip section that connects directly to the hori- zontal termination cap. • Apply a bead of silicone sealant (300 ºF minimum con- tinuous exposure rating) inside the female outer pipe joint prior to joining sections. See Figure 7.1. OR Apply a bead of silicone sealant (300 ºF minimum con- tinuous exposure rating) to the outside of connecting joint after joining sections OR Apply aluminum foil tape (300 ºF minimum continuous exposure rating) to the outside of connecting joint after joining sections. On horizontal pipe runs, it is recom- mended that the tape seam is positioned on the bottom side of the vent pipe. • Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed in this manner, unless otherwise stated. Figure 7.5 Adding Venting Components WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip sections. Use care when remov- ing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent could leak. Note: Align seams to engage pipe, then rotate counterclockwise to lock C. Assemble Slip Sections • Slide the inner flue of the slip section into the inner flue of the pipe section and the outer flue of the slip section over the outer flue of the pipe section. See Figure 7.6. • Slide together to the desired length. Figure 7.6 Slip Section Pilot Holes Figure 7.7 Screws into Slip Section Pilot hole NOTICE: When installing a vent system with an HRC termination cap, all pipe system joints shall be sealed using a high temperature silicone sealant (300 ºF minimum continuous exposure rating). • Apply a bead of silicone sealant (300 ºF minimum continuous exposure rating) inside the female outer pipe joint prior to joining sections. • Only outer pipes are sealed, sealing the inner flue is not required. • All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed. • Continue adding pipe as necessary following instructions in “Assembling Pipe Sections.” NOTICE: If slip section is too long, the inner and outer flues of the slip section can be cut to the desired length. • Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe section. • Secure the pipe and slip section with two screws no longer than 1/2 in. (13 mm), using the pilot holes in the slip section. See Figure 7.7. 01/08/2019 38 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 120º Figure 7.8 Securing Vertical Pipe Sections 120º Figure 7.9 Securing Horizontal Pipe Sections E. Disassemble Vent Sections • Rotate either section (see Figure 7.10) so the seams on both pipe sections are aligned as shown in Figure 7.11. • Pull carefully to separate the pieces of pipe. Figure 7.11 Align and Disassemble Vent Sections Figure 7.10 Rotate Seams for Disassembly D. Secure the Vent Sections • Vertical runs originating off the top of the appliance, with no offsets, must be supported every 8 ft. (2.44 m) after the maximum allowed 25 ft. (7.62 m) of unsupported rise. • Vertical runs originating off the rear of the appliance, or after any elbow, must be supported every 8 ft. (2.44 m). • Horizontal runs must be supported every 5 feet (1.52 m). • Vent supports or plumbers strap (spaced 120º apart) may be used to support vent sections. See Figures 7.8 and 7.9. • Wall shield firestops may be used to provide horizontal support to vent sections. • SLP ceiling firestops have tabs that may be used to provide vertical support. WARNING! Risk of Fire, Explosion or Asphyxiation! Improper support could allow vent to sag and separate. Use vent run supports and connect vent sections per in- stallation instructions. DO NOT allow vent to sag below connection point to appliance. 01/08/2019 39Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 F. Vertical Termination Requirements Install Metal Roof Flashing • See minimum vent heights for various pitched roofs (Figure 7.12) to determine the length of pipe to extend through the roof. • Slide the roof flashing over the pipe sections extending through the roof as shown in Figure 7.13. Roof Pitch H (Min.) Ft. Flat to 6/12........................................1.0* Over 6/12 to 7/12 ............................1.25* Over 7/12 to 8/12 ..............................1.5* Over 8/12 to 9/12 ..............................2.0* Over 9/12 to 10/12 ............................2.5* Over 10/12 to 11/12 .........................3.25 Over 11/12 to 12/12 ...........................4.0 Over 12/12 to 14/12 ...........................5.0 Over 14/12 to 16/12 ...........................6.0 Over 16/12 to 18/12 ...........................7.0 Over 18/12 to 20/12 ...........................7.5 Over 20/12 to 21/12 ...........................8.0 Figure 7.12 Minimum Height From Roof To Lowest Discharge Opening HORIZONTALOVERHANG VERTICALWALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCHIS X/ 12 LOWEST DISCHARGE OPENING 2 FT.MIN.20 INCHES MIN. H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING NOTICE: Failure to properly caulk the roof flashing and pipe seams could permit entry of water. • Caulk the gap between the roof flashing and the outside diameter of the pipe. • Caulk the perimeter of the flashing where it contacts the roof surface. See Figure 7.13. • Caulk the overlap seam of any exposed pipe sections that are located above the roof line. CAULK Figure 7.13 Figure 7.14 Insert Bolt into Brackets Assemble and Install Storm Collar CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp. • Slide the storm collar onto the exposed pipe section and align brackets. • Insert a bolt (provided) through the brackets and install nut. Do not completely tighten. • Slide the assembled storm collar down the pipe section until it rests on the roof flashing (see Figure 7.14). • Tighten nut and make sure the collar is tight against the pipe section. • Caulk around the top of the storm collar. See Figure 7.15. * H minimum may vary depending on regional snowfall. Refer to local codes. 01/08/2019 40 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 SCREWS CAULK STORM COLLAR (1 of 3) Figure 7.15 TERMINATION CAP Install Vertical Termination Cap • Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section. • Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe (see Figure 7.15). Important Notice: Heat shields may not be field constructed. G. Horizontal Termination Requirements Heat Shield Requirements for Horizontal Termination WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thick- ness. • DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap (shown in Figure 7.16). • Heat shields must overlap 1-1/2 in. (38 mm) mini- mum. There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 7.16. If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used. • If the wall thickness is less than 4 in./102 mm (DVP) or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained. • Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm). • The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields. • Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual. • Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section. 01/08/2019 41Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 7.16 Venting Through the Wall Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield firestop is required on the exterior side of a combustible wall. Install Horizontal Termination Cap (DVP and SLP Pipe) WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent. • 1-1/2 (38 mm) minimum overlap of flue telescoping section is required. Failure to maintain overlap could cause overheating and fire. • Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base. • Flash and seal as appropriate for siding material at outside edges of cap. • When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149 installation codes and refer to Section 4 of this manual. CAUTION! Risk of Burns! Local codes may require in- stallation of a cap shield to prevent anything or anyone from touching the hot cap. NOTICE: For certain exposures which require superior resistance to wind-driven rain penetration, a flashing kit and HRC caps are available. When penetrating a brick wall, a brick extension kit is available for framing the brick. Termination Cap Specification Chart (depth without using additional pipe sections) SL Series DVP-TRAPK1 Top Vent Depth DVP-TRAP1 Rear Vent Depth DVP-TRAPK2 Top Vent Depth DVP-TRAP2 Rear Vent Depth N/A 3-1/8 in. to 5 in.N/A 5-1/2 in. to 9-1/2 in. DVP-HPC1 Top Vent Depth DVP-HPC1 Rear Vent Depth DVP-HPC2 Top Vent Depth DVP-HPC2 Rear Vent Depth N/A 3-1/8 in. to 5-1/4 in.N/A 5-1/4 in. to 9-3/8 in. DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8) DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8) DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8) DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2) INTERIOR HEAT SHIELD OR EXTENDED HEAT SHIELDWALL SHIELD FIRESTOP HEAT SHIELD1-1/2 IN. (38 MM) MIN. OVERLAP SHEATHING VENT DEPTH FROM BACK OF APPLIANCE TO OUTSIDE SURFACE OF EXTERIOR WALL (SEE CHART BELOW) SLIP SECTION CAN BE EXTENDED INNER VENT OUTER VENT EXTERIOR 01/08/2019 42 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. General Information WARNING! Risk of Shock or Explosion! DO NOT wire 110-120 VAC to the valve or to the appliance wall switch. Incorrect wiring will damage controls. NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1. • Wire the appliance junction box to unswitched 110- 120 VAC. This is required for proper operation of the appliance. • A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks. • Low voltage and 110-120 VAC voltage cannot be shared within the same wall box. 8 Electrical Information WHTWHTBLK BLKGRN wire inside box Copper ground attached to GRN screw with GRN wire 14/2WG Cover Plate outside firebox Romex Connector Figure 8.1 Junction Box Detail NOTICE: DO NOT wire 110-120 VAC to wall switch. Junction Box Installation If the box is being wired from the INSIDE of the appliance: • Remove the screw attaching the junction box/receptacle to the outer shell, rotate the junction box inward to dis- engage it from the outer shell. See Figure 8.1. • Pull the electrical wires from outside the appliance through the opening into the valve compartment and secure wires with a Romex connector. See Figure 8.1. • Make all necessary wire connections to the junction box/ receptacle and reattach the junction box/receptacle to the outer shell. Electrical Service and Repair WARNING! Risk of Shock! Label all wires prior to dis- connection when servicing controls. Wiring errors could cause improper and dangerous operation. Verify proper operation after servicing. WARNING! Risk of Shock! Replace damaged wire with type 105º C rated wire. Wire must have high temperature insulation. B. Wiring Requirements Intellifire Ignition System Wiring • Wire the appliance junction box to 110-120 VAC for proper operation of the appliance. WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance junction box to a switched circuit. Incorrect wiring will override IPI safety lockout. • Refer to Figure 8.2, Intellifire Pilot Ignition (IPI) Wiring Diagram. • This appliance is equipped with an Intellifire control valve which operates on a 3 volt system. • Plug the 3-volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries (not included) into the battery pack before use. NOTICE: Batteries should only be used as a power source in the event of an emergency power outage. Batteries should not be used as a primary long-term power source. Battery polarity must be correct when installing batteries. When using batteries as a power source, the 3-volt transformer must be unplugged from the receptacle. Do not store batteries in the battery pack when the appliance is powered by the 3-volt transformer connected to permanent electrical service Accessories Requirements • This appliance may be used with a wall switch, wall mounted thermostat and/or a remote control. Wiring for optional Hearth & Home Technologies approved accessories should be done now to avoid reconstruction. Follow instructions that come with those accessories. 01/08/2019 43Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 8.2 Intellifire Pilot Ignition (IPI) Wiring Diagram TRANSFORMER WALL SWITCH 3 VAC PLUG IN BLACK RED BATTERY PACK ORANGETO BROWNTO BROWNGREENGROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR HOTNEUTRALI SJUNCTION BOX (110-120 VAC) 01/08/2019 44 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Wall Switch Installation for Fan (Optional) If the box is being wired to a wall mounted switch for use with a fan. See Figure 8.3. • The power supply for the appliance must be brought into a switch box. • The power can then be supplied from the switch box to the appliance using a minimum of 14-3 with ground wire. • At the switch box connect the black (hot) wire and red (switch leg) wire to the wall switch as shown. • At the appliance connect the black (hot), white (neutral) and green (ground) wires to the junction box as shown. • Add a 1/4 in. insulated female connector to the red (switch leg) wire, route it through the knockout in the face of the junction box, and connect to the top fan switch connector (1/4 in. male) as shown. Red Switch Switch Box Red BlackBlack Green GreenWhite Power Supply Wires White RedBlackGreenWhiteMinimum 14-3 AWG with Ground Junction Box Knockout Figure 8.3 Junction Box Wired to Wall Switch or BC10 RHEOSTAT SWITCH TEMPERATURE SENSOR Figure 8.4 Fan Wiring with Rheostat BLUE RHEOSTAT SWITCH TEMPERATURE SENSOR SWITCH JUNCTION BOX Figure 8.5 Detail of Fan Wiring with Rheostat Temperature Sensor Wiring for Fan (Optional) If the fan will not be installed for operation with a wall switch, the temperature sensor will need to be installed. See Figure 8.4 for location of the temperature sensor and fan control. • The power supply for the appliance must be brought into the junction box. • Install rheostat in location as seen in Figure 8.4. • Connect temperature sensor switch wire and rheostat switch wires to junction box as shown in Figure 8.5. 01/08/2019 45Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Fuel Conversion • Make sure the appliance is compatible with available gas types. • Conversions must be made by a qualified service technician using Hearth & Home Technologies specified and approved parts. B. Gas Pressure • Optimum appliance performance requires proper input pressures. • Gas line sizing requirements will be determined in ANSI Z223.1 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada. • Pressure requirements are: C. Gas Connection • Refer to Reference Section 3 for location of gas line access in appliance. • Gas line may be run through knockout(s) provided. • The gap between supply piping and gas access hole may be caulked with caulk with a minimum of 300 ºF continuous exposure rating or stuffed with non- combustible, unfaced insulation to prevent cold air infiltration. • Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes. • Pipe incoming gas line into valve compartment. • Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve. WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line. • A small amount of air will be in the gas supply lines. WARNING! Risk of Fire or Explosion! Gas build-up dur- ing line purge could ignite. • Purge should be performed by qualified service technician. • Ensure adequate ventilation. • Ensure there are no ignition sources such as sparks or open flames. Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally. WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loos- ened during shipping and handling. WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory. WARNING! Risk of Fire or Explosion! High pressure will damage valve. Low pressure could cause explosion. • Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating. • Install regulator upstream of valve if line pressure is greater than 1/2 psig. 9 Gas Information Gas Pressure Natural Gas Propane Minimum inlet pressure 5.0 in. w.c.11.0 in. w.c. Maximum inlet pressure 10.0 in. w.c.13.0 in. w.c. Manifold pressure 3.5 in. w.c.10.0 in. w.c. Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter). Note: A listed (and Commonwealth of Massachusetts ap- proved) 1/2 in. (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 in. (13 mm) control valve inlet. • If substituting for these components, please consult local codes for compliance. Fire Risk. Explosion Hazard. High pressure will damage valve. • Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig. • Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig. WARNING D. High Altitude Installations NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction. When installing above 2000 feet elevation: • In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet. • In CANADA: Input ratings are certified without a reduction of input rate for elevations up to 4500 feet (1370 m)above sea level. Please consult provincial and/ or local authorities having jurisdiction for installations at elevations above 4500 feet (1370 m). Check with your local gas utility to determine proper orifice size.01/08/2019 46 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 E. Air Shutter Setting Air shutter settings should be adjusted by a qualified service technician at the time of installation. The air shutter is set at the factory for minimum vertical vent run. Adjust air shutter for longer vertical runs. By sliding the air shutter to the right, you will be opening the air shutter. To adjust loosen the wing nut. Care should be taken when adjusting the air shutter so as not to cause the appliance to soot. If sooting occurs the air shutter will need to be opened by sliding the air shutter to the right. When finished, tighten the wing nut. See Figure 9.1. NOTICE: If sooting occurs, provide more air by opening the air shutter. Air Shutter Settings Models NG Propane SL-5F 1/4 in.1/2 in. SL-7F 1/4 in.1/2 in. SHUTTER ADJUSTMENT Measure from left edge of slot to center of first stud. Figure 9.1 Air Shutter Adjustment 01/08/2019 47Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 10 Finishing A. Facing and Finishing • Metal front faces may be covered with non-combustible materials only. • Facing and/or finishing materials must not interfere with air flow through louvers, operation of louvers or doors, or access for service. • Facing and/or finishing materials must never overhang into the glass opening. • Observe all clearances when applying combustible materials. • Seal joints between the finished wall and appliance top and sides using a 300 ºF minimum sealant. Refer to Figure 10.1. WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation of doors and louvers. 0 IN.0 IN. 0 IN. SHEETROCK/FINISH WALL MATERIAL UP TO 1/2 IN. THICK MAY BE COMBUSTIBLE - TOP AND SIDES HIGH TEMPERATURE SEALANT (300° F/149° C MIN.) TOP AND SIDE SEAL JOINT Figure 10.1 Noncombustible Facing Diagram Stop finishing material flush with fireplace surround opening. Figure 10.2 Clean Face Decorative Front Finishing Details Non-combustible facing up to 4 inches thick may be used. Stop finishing material flush with fireplace surround open- ing. See Figure 10.2. WARNING! Risk of Overheating and Fire! Non-combus- tible material must not exceed 6 inches in thickness. NOTICE: Surface temperatures around the appliance will become warm while the appliance is in operation. Ensure finishing materials used for all surfaces (floor, walls, mantels, etc.) will withstand temperatures up to 190°F. FINISH WALL MATERIAL MAY BE COMBUSTIBLE - TOP AND SIDES NON-COMBUSTIBLE FACING (SHADED AREA) DECORATIVE FRONT NON-COMBUSTIBLE FINISHING MATERIAL 6 IN. MAXIMUM THICKNESS NON-COMBUSTIBLE FINISHING MATERIAL 6 IN. MAXIMUM THICKNESS 01/08/2019 48 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 B. Mantel and Wall Projections WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing closer than the minimums listed must be constructed entirely of non-combustible materials (i.e., steel studs, concrete board, etc.). Figure 10.3 Clearances To Combustible Mantels Or Other Combustibles Above Appliance Note: All measurements in inches. 5 6 7 8 9 1034 5 12 11109 876 TOP OF HOOD OR FIREPLACE OPENING 4 12 13 11 32 CEILING Figure 10.6 Non-Combustible Zone 1/2 in. SHEETROCK OR COMBUSTIBLE MATERIAL 3-1/2 in. 1/2 in. NON-COMBUSTIBLE ZONE Figure 10.5 Non-Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening) Note: Clearance from opening to perpendicular wall. UNLIMITED TOP VIEW FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram (Figure 3.1). 3 IN. MIN. 6 IN. MAX. Non-Combustible Mantel Leg or Wall Projection Figure 10.4 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening) 5-3/8 IN. MINIMUM 3 IN. MINIMUM Note: Clearance from opening to perpendicular wall. UNLIMITED FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram (Figure 3.1). Combustible Mantel Leg or Wall Projection 01/08/2019 49Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 WARNING! Risk of Fire! Install ONLY doors or fronts approved by Hearth & Home Technologies. Unapproved doors or fronts could cause fireplace to overheat. This fireplace has been supplied with an integral barrier to prevent direct contact with the fixed glass panel. DO NOT operate the fireplace with the barrier removed. Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one. 1. Remove decorative front by lifting up and away from appliance. 2. Install four shoulder bolts as shown in figure 10.7. 3. Hang decorative front onto shoulder bolts. 4. Install hood on appliance by inserting into the two hood clips. See Figure 10.7. C. Install Decorative Front/Hood Figure 10.7 Install Decorative Front and Hood 01/08/2019 50 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Remove Fixed Glass Assembly WARNING! Risk of Asphyxiation! Handle fixed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches. • DO NOT strike, slam or scratch glass. • DO NOT operate fireplace with glass removed, cracked, broken or scratched. • Replace as a complete assembly. Removing Fixed Glass Assembly • Pull the four glass assembly latches out of the groove on the glass frame. Remove glass door from the appli- ance. See Figure 11.1. 11 Appliance Setup Figure 11.1 Fixed Glass Assembly B. Remove the Shipping Materials Remove shipping materials from inside or underneath the firebox. • The splatter guard is a piece of corrugated material used to protect the appliance during the installation process before finishing work on the whole hearth is complete. Splatter guards may be factory installed or accompany the decorative front, depending on the fireplace model. Splatter guards must be re- moved before appliance is fired. WARNING! Risk of Fire! Close the ball valve before in- stalling the splatter guard to prevent accidental lighting. Remove the splatter guard before lighting the appliance. C. Clean the Appliance Clean/vacuum any sawdust that may have accumulated inside the firebox or underneath in the control cavity. LATCHES (BOTH BOTTOM AND TOP) GLASS ASSEMBLY 01/08/2019 51Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 D. Install the Log Assembly and Lava Rock Log Set Assembly: LOGS-550F Models: SL-550F, SL-550F-LP, SL-5F LOG PLACEMENT INSTRUCTIONS CAUTION: Logs are fragile, handle with care. Log #1 (2297-700): Place Log #1 into position by holding it upright and placing it onto the pins on the back of the basepan. See Figure 3. Log #1 will sit upright as shown in Figure 4. Figure 3. Log #1 - Bottom View Log #2 (2033-709): Log #2 has holes on the bottom side that will be used for positioning them in the firebox. See Figure 5. Place Log #2 on the pins in the front of the firebox as shown in Figure 6. Figure 1.Figure 2. Location of Log Placement Pins and Corresponding Log #’s Figure 4. Log #1 in Position Figure 5. Log #2 - Bottom View 1 54 3 2 HOLES FOR LOG LOCATION PINS Figure 6. Log #2 in Position 2 1 1 11 LOG PLACEMENT PINS (CIRCLED) 5 HOLES FOR LOG LOCATION PINS Note: If using a glass media or stone kit, skip this section. Refer to the instructions included with the kit. 01/08/2019 52 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 7. Log #3 Bottom View 3 2 1 Figure 8. Log #3 in Position Log #3 (2033-708): Log #3 also has holes on the bottom side that will be used for positioning it in the firebox. See Figure 7. Place the two holes on the bottom of Log #3 onto the pins on the left side of the basepan as shown in Figure 8. Figure 9. Log #4 in Position 1/4 IN. FLAT AREAS HOLES FOR LOG LOCATION PINS LOCATING PIN 1 3 2 4 LOCATING GROOVES Log #4 (2033-721): Place Log #4 on the left side of the firebox as shown in Figure 9. Position one end on the flat spot on the top of Log #1 and place the other end against the locating pin on the basepan. There should be a gap of approximately 1/4 inch between the bottom left edge of the log and the firebox. LAVA ROCK (4021-297): Place lava rock on the base pan and around the logs as shown in Figure 10. Use the supplied rock jig to prevent the rock from going in between the base pan and burner. DO NOT allow any lava rock to fall in the slot and onto the burner. Figure 10. Lava Rock and Rock Jig LAVA ROCK ROCK JIG WARNING RISK OF EXPLOSION! • Place lava rock according to instructions. • Do NOT place lava rock on burner top. • Do NOT place lava rock in a position that they may fall into area in front of pilot. • Use ONLY Hearth & Home Technologies-approved optional media with this appliance. • Do NOT use more than 3 pounds of lava rock per fireplace. Improperly placed lava rock interferes with proper burner op- eration. Delayed ignition may occur. Remove the rock jig by removing the shipping screw on the back. Keep the rock jig and screw in the lower cavity of the appliance. It will be needed for future cleaning of the logs and lava rock or servicing of the appliance. Once the rock jig is removed, visually inspect the burner area to ensure that no lava rock is there. See Figure 11. Note: When applying Lava Rock or Media in areas of the base pan that is covered by mesh, apply only one layer of Lava Rock or Media. 01/08/2019 53Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 2297-983E Log #5 (2033-720): Log #5 is used twice in this log set. The left log is located by placing the “Y-Shaped” end on the locating grooves of Log #3 and setting the other end on the flat area of Log #1. See Figure 9 to reference locations of flat areas and grooves. Figure 12 shows the left side Log #5 in position. The right side Log #5 is located by placing the “Y-Shaped” end on the locating grooves of Log #1 and setting the other end on the right side log #2. See Figure 12 and Figure 13. The log should be approximately 1-1/2 inch from the end of Log #2. See Figure 14. Figure 12. Log #5 (1st of 2) 5 Figure 13. Log #5 (2nd of 2)Figure 14. Log #5 Placement Figure 15. Logs-550F Installed 14 3 2 LOCATING GROOVESNO LAVA ROCK IN BURNER SLOT (INSIDE DASHED LINE) Figure 11. Rock Jig Removed 01/08/2019 54 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Log Set Assembly: LOGS-750F Models: SL-750F, SL-750F-LP, SL-7F LOG PLACEMENT INSTRUCTIONS CAUTION: Logs are fragile, handle with care. Log #1 (2298-700): Place Log #1 into position by holding it upright and placing it onto the pins on the back of the basepan. See Figure 3. Log #1 will sit upright as shown in Figure 4. Figure 3. Log #1 - Bottom View Log #2 (2033-709): Log #2 is used twice in this log set. Log #2 also has holes on the bottom side that will be used for positioning them in the firebox. See Figure 5. Locate the two Log #2’s and place them on the pins in the front of the firebox as shown in Figure 6 and Figure 7. Figure 1.Figure 2. Location of Log Placement Pins and Corresponding Log #’s Figure 4. Log #1 in Position Figure 5. Log #2 - Bottom View 1 4 43 3 2 2 HOLES FOR LOG LOCATION PINS Figure 6. Log #2 - First of Two in Position 2 1 1 1 1 3 2 2 22 3 LOG PLACEMENT PINS (CIRCLED) 01/08/2019 55Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 7. Log #2 (2nd of 2) 1 2 2 3 2 1 Figure 8. Log #3 (1st of 2) Log #3 (2033-721): Log #3 is used twice in this log set. Place one of the #3 logs on the left side of the firebox as shown in Figure 8. Position one end on the flat spot on the top of Log #1 and place the other against the locating pin on the basepan. There should be approx. a 1/4 inch gap between the end of the log and the firebox. The other Log #3 will be placed on the right in a position to mirror the first Log #3. Place it in position by placing one end on the flat of Log #1 and the other against the locating pin on the basepan. There should be approx. a 1/4 inch gap between the end of the log and the firebox. See Figure 9. Figure 9. Log #3 (2nd of 2) LOCATING PIN 1/4 IN. LOCATING PIN 1/4 IN. Figure 10. Flat Area of Log #1 Used for Log #4 Placement FLAT AREA 31 01/08/2019 56 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 Figure 11. Lava Rock and Burner Tube Slot Cover Figure 12. Burner Tube Slot Cover Removed LAVA ROCK (4021-297): Place lava rock on the base pan and around the logs as shown in Figure 11. Use the supplied burner tube slot cover to prevent the rock from going in between the base pan and burner. DO NOT allow any lava rock to fall in the slot and onto the burner. WARNING RISK OF EXPLOSION! • Place lava rock according to instructions. • Do NOT place lava rock on burner top. • Do NOT place lava rock in a position that they may fall into area in front of pilot. • Use ONLY Hearth & Home Technologies-approved optional media with this appliance. • Do NOT use more than 3 pounds of lava rock per fireplace. Improperly placed lava rock interferes with proper burner op- eration. Delayed ignition may occur. Remove the burner tube slot cover by removing the shipping screw on the back. Keep the burner tube slot cover and screw in the lower cavity of the appliance. It will be needed for future cleaning of the logs and lava rock or servicing of the appliance. Once the burner tube slot cover is removed, visually inspect the burner area to ensure that no lava rock is present. See Figure 12. Log #4 (2033-720): Log #4 is used twice in this log set. The right log is located by placing the “Y-Shaped” end on the flat area of Log #1 and setting the other end on the right side Log #2. See Figure 10 and Figure 13. The log should be approximately one inch from the end of the right side Log #2. See Figure 14. Figure 13. Log #4 (1st of 2)Figure 14. Log #4 (1st of 2) 1 IN. 3 1 4 2 NO LAVA ROCK IN BURNER SLOT (INSIDE DASHED LINE) LAVA ROCK BURNER TUBE SLOT COVER Note: When applying Lava Rock or Media in areas of the base pan that is covered by mesh, apply only one layer of Lava Rock or Media. 01/08/2019 57Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 2298-983D Place the other Log #4 on the left side of the firebox by placing the thin end on the flat area of Log 1. See Figure 15. The “Y-Shaped” section will rest on the left side Log #2. See Figure 16. The left branch of the “Y” should rest where the “burned” area of the left Log #2 begins. See Figure 17. Figure 15. Log #4 (2nd of 2) 1 3 FLAT AREA Figure 16. Log #4 (2nd of 2) Figure 17. Log #4 (2nd of 2) Resting on Burned Area of Log #2. BURNED AREA OF LOG #22 4 4 Figure 18. Logs-750F Installed 01/08/2019 58 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 E. Install Fixed Glass Assembly WARNING! Risk of Asphyxiation! Handle fixed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches. • DO NOT strike, slam or scratch glass. • DO NOT operate fireplace with glass removed, cracked, broken or scratched. • Replace as a complete assembly. • Replace the glass door on the appliance. Pull out and latch the four glass assembly latches into the groove on the glass frame. See Figure 11.1. F. Install Optional Trim Kits • Install optional trim kits and/or surrounds using the instructions included with the accessory. • Use non-combustible materials to cover the gap between the sheet rock and the appliance (when applicable to model). 01/08/2019 59Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 12 Reference Materials A. Vent Components Diagrams Figure 12.1 DVP Vent Components 10-1/2 in. (267 mm) 10-7/8 in. (276 mm) 45 ° 7-3/8 in. (187 mm) 11-3/8 in. (289 mm) 1-1/4 in. (32 mm) 9-1/4 in. (235 mm) 13-1/4 in. (337 mm) 1/2 in. TYP DVP90ST (90° Elbow) 10 in. (254 mm) 10 in. (254 mm) 1 in. (25 mm) 12 in. (305 mm) 14 in. (356 mm) 1 in. (25 mm) 8 in. (203 mm) 6 in. (152 mm) 10 in. (254 mm) 1- 1/2 in. (38 mm) 5 in. (127 mm)12 in. (305 mm) UP DVP-HVS (Vent Support) DVP-WS (Wall Shield Firestop) DVP-FS (Ceiling Firestop) DVP45 (45º Elbow) DVP Pipe (see chart) EffectiveHeight/Length 4-7/8 in. (124 mm) (13 mm) Finished Height: 19-3/4 in./502 mm UNIV-AS2 (Attic Insulation Shield) Tab=1 in. (25.4 mm) 20-3/4 in. (527 mm) 14 IN. (356 MM) 14 IN. (356 MM) 20 IN. (508 MM) 12 IN. (305 MM)DVP-RDS ROOF DECK INSULATION SHIELD Pipe Effective Length Inches Millimeters DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219 DVP6A 3 to 6 76 to 152 DVP12A 3 to 12 76 to 305 01/08/2019 60 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 DVP-HPC1 DVP-HPC2 DVP-TRAP1 DVP-TRAP2 DVP-HPCK1-B DVP-HPCK2-B DVP-TRAPK2DVP-TRAPK1 DVP-TRAP Horizontal Termination Cap 15-1/8 in. (384 mm) 12 in. (305 mm) 8 in. (203 mm) Max Effective Length Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required. Heat Shield A. Vent Components Diagrams (continued) Figure 12.2 DVP Vent Components Term Cap Minimum Effective Length Maximum Effective Length Trap1 3-1/8 in. 4-5/8 in. 79 mm 117 mm Trap2 5-3/8 in. 9-3/8 in. 137 mm 238 mm 01/08/2019 61Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 13-1/4 in. (337 mm) 24-5/8 in. (625 mm) 27-1/2 in. (699 mm) RF6Roof Flashing Multi-pak 31 in.(787 mm) 24-5/8 in.(625 mm) 13-1/4 in.(337 mm) RF12 Roof Flashing Multi-pak Cap Shield DRC-RADIUS 13-7/8 in. (352 mm) 9-1/2 in. (241 mm) 14 in. (356 mm) COOL-ADDM Cap Shield 11-5/8 in. (295 mm) 5-3/4 in. (146 mm) 7-1/8 in. (181 mm) 12-1/8 in. (308 mm) DVP-BEK2 DVP-HPC Cap Brick Extension 13-7/8 in. (352 mm) 5 in. (127 mm) 11-7/8 in. (302 mm) DVP-TRAPFL Flashing 26 in. 660 mm DVP-HSM-B Extended Heat Shield A. Vent Components Diagrams (continued) Figure 12.3 DVP Vent Components 01/08/2019 62 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 DVP-TB1 BasementVent Cap 12 in. (305 mm) 1-1/2 in. (38 mm) 7-3/8 in. (187 mm) 14 in. (356 mm) 17-3/4 in. (451 mm) 7-1/4 in. 12 in. 305 mm (184 mm) 5-1/4 in.(133 mm) 12-1/2 in.(318 mm) DVP-TVHW VerticalTermination Cap (Highwind) 14 in.(356 mm) 12 in. (305 mm) 12-1/8 in. (314 mm) 7-1/8 in. (181 mm) 8-3/4 in. (222 mm) 1-5/8 in. (41 mm) 16-7/8 in. (429 mm) DVP-HPCHigh Performance Cap 1 in. (25 mm) 14 in. (356 mm) 3/8 in. (10 mm) 1 in. (25 mm) 7-1/4 in. (184 mm) 7-3/4 to 10-3/8 in. (197 to 264 mm) DVP-FBHT FireBrickTermination Cap A. Vent Components Diagrams (continued) Figure 12.4 DVP Vent Components 01/08/2019 63Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Vent Components Diagrams (continued) Fire Risk. • When using SLP-HRC-SS termination cap on top vented fireplaces, a one foot minimum vertical vent section is required before installing first elbow. WARNING 13 in. (330 mm) 15 in. (381 mm) 8-1/8 in. (206 mm) SLP-HRC-SS HORIZONTAL TERMINATION CAP • When using DVP-TB1 termination cap on top vented fireplaces, a three foot minimum vertical vent section is required before installing first elbow. DVP-TB1 HORIZONTAL TERMINATION CAP SLP90 SL-2DVP DVP-TB1DVP-TB1 ASSEMBLY Figure 12.5 Vent Components 13 in. (330 mm) 15 in. (381 mm) 8-1/8 in. (206 mm) DVP-HRC-SS 10-7/8 in. 276 mm 10-1/2 in. 267 mm 3°87° Effective Length 5-3/4 to 8-3/8 in. 146 to 213 mm 5-1/2 in. 140 mm 8-3/8 in. 213 mm DVP-HRC-ZC-SS 01/08/2019 64 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 12-1/2 IN. 318 mm 20-3/4 IN. 527 mm 13-5/8 IN. 346 mmEFFECTIVE LENGTH 32 IN. (813 mm) MIN. 35 IN. (889 mm) MAX. A. Vent Components Diagrams (continued) Figure 12.6 PVI-SLP-B Vent Components Optional Wire Harness DESCRIPTION PART NUMBER 10 FT PV Wire Harness PVI-WH10 20 FT PV Wire Harness PVI-WH20 40 FT PV Wire Harness PVI-WH40 60 FT PV Wire Harness PVI-WH60 80 FT PV Wire Harness PVI-WH80 100 FT PV Wire Harness PVI-WH100 PVI-SLP-B Power Vent Inline SLP-LPC SLP Low Profile Cap (Approved for use with PVI-SLP-B only) Note: Wire harnesses required to power the PVI-SLP-B connect to the appliance and are ordered separately from PVI-SLP-B. Contact your dealer to order. 16 IN. 406 mm 15 IN. (381 mm) 16-11/16 IN. (424 mm) 9-3/16 IN. (233 mm) 4-1/2 IN. 114 mm 16-11/16 IN. 424 mm 13-5/8 IN. (346 mm) 12-1/2 IN. (318 mm) Note: The PVI-SLP-B requires a PV-IPI-CK be installed on this appliance. The PV-IPI-CK is ordered separately from the PVI-SLP-B. Contact your dealer to order. 01/08/2019 65Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Vent Components Diagrams (continued) Figure 12.7 PVLP-SLP Vent Components PVLP-HS Heat Shield 14 IN. 356 mm 15-1/2 IN. 394 mm 11-1/2 IN. 292 mm 8 IN. 203 mm 4-3/8 IN. 112 mm 10 IN. 254 mm 5-1/4 IN. 135 mm 2-1/4 IN. 57 mm 9-1/2 IN. 241 mm 4-3/4 IN. 121 mm 2-1/4 IN. 57 mm 1-1/2 IN. 38 mm 6-1/4 IN. 159 mm Front View Top View Side View PVLP-BEK Brick Kit Required Wire Harness DESCRIPTION PART NUMBER 10 FT PV Wire Harness PVI-WH10 20 FT PV Wire Harness PVI-WH20 40 FT PV Wire Harness PVI-WH40 60 FT PV Wire Harness PVI-WH60 80 FT PV Wire Harness PVI-WH80 100 FT PV Wire Harness PVI-WH100 Note: Wire harnesses required to power the PVLP-SLP connect to the appliance and are ordered separately from PVLP-SLP. Contact your dealer to order. Note: The PVLP-SLP requires a PV-IPI-CK be installed on this appliance. The PV-IPI-CK is ordered separately from the PVLP-SLP. Contact your dealer to order. Note: A PVLP-HS heat shield is available and sold separately. Use if the PVLP-SLP is installed in a high traffic area. PVLP-SLP Power Vent Low Profile 01/08/2019 66 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Vent Components Diagrams (continued) Figure 12.8 SLP Series Vent Components 8-3/4 in. 222 mm 6-1/2 in. 165 mm 6-5/8 in. 168 mm 6 in. 152 mm 6-1/2 in. 165 mm 6-5/8 in. 168 mm 9-7/8 in. 251 mm 6-1/2 in. 165 mm9-1/4 in. 235 mm SLP45 45° Elbow SLP90 90° Elbow Effective Height/ Length SLP PIPE SLP-HVS Horizontal Pipe Support SLP-FS Ceiling Firestop SLP-WS Wall Shield Firestop 10-7/8 in. 276 mm 8-7/8 in. 225 mm 1-1/2 in. 38 mm 8-11/16 in. 220 mm 8-11/16 in. 220 mm 1-1/2 in. 38 mm 12 in. 305 mm 12 in. 305 mm 5-1/2 in. 146 mm Effective Height/Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 - 6 51 - 152 SLP12A 2 - 12 51 - 305 SLP-FLEX-2 24 610 SLP-FLEX-3 36 914 SLP-FLEX-5 60 1524 SLP-FLEX-10 120 3048 01/08/2019 67Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 A. Vent Components Diagrams (continued) Figure 12.9 SLP Series Vent Components SLP-WT-BK Wall Thimble-Black SL-2DVP Adapter 26 in. 660 mm DVP-HSM-B Extended Heat Shield SLP-TRAP Horizontal Termination Cap 15-1/8 in. (384 mm) Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required. Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3-1/8 in. 4-3/4 in. 79 mm 121 mm Trap2 5-1/4 in. 9-1/4 in. 133 mm 235 mm 8 in. (203 mm) 12 in. (305 mm) Max Effective Length 14-7/16 in. 367 mm 14-7/16 in. 367 mm 2-5/16 in. 59 mm 3-15/16 in. (101 mm) 6-11/16 in. (169 mm) 8 in. (203 mm) 3-15/16 in. (101 mm) 3-13/16 in. (97 mm) 5-1/16 in. (128 mm) 6-3/8 in. 163 mm 4-3/16 in. 106 mm 4-5/8 in. 117 mm 5-1/16 in. 128 mm8-1/8 in. 206 mm DVP-2SL Adapter 4 in. 102 mm 12-5/8 IN. (321 mm) 12-5/8 IN. (321 mm) 20 IN. (508 mm) 10-5/8 IN. (270 mm) SLP-RDS ROOF DECK INSULATION SHIELD 01/08/2019 68 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 1 in. (25 mm) 14 in. (356 mm) 3/8 in. (10 mm) 1 in. (25 mm) 7-1/4 in. (184 mm) 7-3/4 to 10-3/8 in. (197 to 264 mm) 13 in. 330 mm 13 in. 330 mm 1-5/16 in. 34 mm10-9/16 in. 269 mm 14 in. 356 mm 12-1/2 in. 318 mm 12 in. 305 mm SLP-FLEX-TRAP Horizontal Termination Kit 14 in. 356 mm 14-1/16 in. 357 mm 7-1/2 in. 192 mm 10-3/4 in. 273 mm SLP-CCS-BK Cathedral Ceiling Support Box-Black SLP-DCF-BK Ceiling Firestop BlackSLP-TVHW Vertical Termination Cap DVP-FBHT Horizontal Termination Cap 17-7/8 IN. 454 mm 7-3/8 IN. 187 mm 14 IN. 356 mm 12 IN. 305 mm SLP-TB1 Basement Vent Cap 6 IN.152 mm SLK-SNKD Snorkel Termination Cap 13-1/2 in. 343 mm 28-1/2 in. 724 mm 10-11/16 in. 271mm 4-3/4 in. 121 mm 4-1/8 in. 105 mm A. Vent Components Diagrams (continued) Figure 12.10 SLP Series Vent Components 01/08/2019 69Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 LINK-DV30B Flex Liner Kit DV-46DVA-GCL Coaxial/Colinear Appliance Connector 768-380A Stainless Steel Flex Pipe DVP-2SL Adapter COAXIAL to COLINEAR VENTING Figure 12.11 Coaxial to Colinear Vent Components 01/08/2019 70 Heat & Glo • SL-5F, SL-7F Installation Manual • 2499-980 Rev. i • 9/18 B. Accessories Wall Switches Follow the instructions supplied with the control installed to operate your fireplace: For safety: • Install a switch lock or a wall control with child protection lockout feature. • Keep controls out of reach of children. See your dealer if you have questions. Optional Fan The optional fan may be installed by a qualified service technician. Refer to installation information in Section 8. Follow the instructions supplied with the fan kit to operate your fan. See your dealer if you have questions. Printed in U.S.A. - Copyright 2018 Heat & Glo, a brand of Hearth & Home Technologies 7571 215th Street West, Lakeville, MN 55044 www.heatnglo.com Please contact your Heat & Glo dealer with any questions or concerns. For the location of your nearest Heat & Glo dealer, please visit www.heatnglo.com. Install approved accessories per instructions included with accessories. Contact your dealer for a list of ap- proved accessories. WARNING! Risk of Fire and Electric Shock! Use ONLY Hearth & Home Technologies-approved optional acces- sories with this appliance. Using non-listed accessories could result in a safety hazard and will void the warranty. 01/08/2019