HomeMy WebLinkAboutFile Documents.535 E Hyman Ave.0080.2018.ACBK0080-2018-ACBK_BuildingComment1
Subject: PlanCheck
Page Label: A00.05 ACCESSIBLE PATH REFERENCE PLAN
Author: justinh
File Name: PlanSet.535 E Hyman Unit 108.2018.06.pdf
Show a parallel approach clear
space at the cashwrap station.
PlanSet.535 E Hyman Unit 108.2018.06.pdf (5)
Subject: PlanCheck
Page Label: A00.05 ACCESSIBLE PATH REFERENCE PLAN
Author: justinh
File Name: PlanSet.535 E Hyman Unit 108.2018.06.pdf
The boulder is obstructing your
accessible route in this location,
please revise.
Subject: PlanCheck
Page Label: A80.03 INTERIOR ELEVATIONS
Author: justinh
File Name: PlanSet.535 E Hyman Unit 108.2018.06.pdf
The accessible fitting room
bench should be shown in the
interior elevation to demonstrate
proper seat and back support
height per 2009 ANSI section
903. If any coat racks or hooks
are proposed then at least one
of each type shall be provided
within an accessible reach range
per ANSI 803.5. It should also
be dimensioned in plan view
where shown elsewhere to show
compliance with the sizing
requirements of ANSI 903.
Subject: PlanCheck
Page Label: A90.02 COMPONENTS
Author: justinh
File Name: PlanSet.535 E Hyman Unit 108.2018.06.pdf
Dimension the height of the
cashwrap station on the
elevations to show compliance
with ANSI 904.
B
N.I.S.
3' - 0"
2' - 10"
3/8" = 1'-0"A1 ACCESSIBLE PATH REFERENCE PLAN
Show a parallelapproach clear space
at the cashwrapstation.
1
C
1.2
N.I.S.
The boulder isobstructing youraccessible route in this
location, please
revise.
LEVEL 10' - 0"
C A1
A50.02
LEVEL 10' - 0"
LEVEL 10' - 0"
2A2A51.01
S H E E T N U M B E RP R O J E C T N U M B E R ASPENSTAMPSINTERIOR ELEVATIONS
A80.03HRC010
535 E. HYMAN AVE, UNIT 108ASPEN, CO 81611
FORTY FIVE TEN ASPEN
1/2" = 1'-0"1 FITTING ROOM - EAST ELEVATION
1/2" = 1'-0"2 FITTING ROOM - NORTH ELEVATION
1/2" = 1'-0"3 FITTING ROOM - SOUTH ELEVATION
0'1'2'4'PROJECTNORTH
REV. DATE ISSUE TITLEA 06.19.18 100% DD SETB 06.22.18 PERMIT SET
The accessible fitting room bench should beshown in the interior elevation to demonstrateproper seat and back support height per 2009ANSI section 903. If any coat racks or hooksare proposed then at least one of each typeshall be provided within an accessible reachrange per ANSI 803.5. It should also bedimensioned in plan view where shownelsewhere to show compliance with the sizingrequirements of ANSI 903.
D D
A90.02 A2
A
R 0' - 1"
1/4"
R 0' - 1"7' - 0"3' - 9"0' - 6"LEVEL 10' - 0"
B3
A90.02
LEVEL 10' - 0"
LEVEL 10' - 0"
2' - 6"
LEVEL 10' - 0"
1" = 1'-0"A1 CASHWRAP - PLAN
1" = 1'-0"A2 CASH WRAP - WEST ELEVATION
1" = 1'-0"B2CASHWRAP - NORTH ELEVATION
0'
Dimension the heightof the cashwrapstation on theelevations to show
compliance with ANSI904.
A00.05 - 5G Comments
-THE PARALLEL APPROACH ACCESS HAS BEEN
ADDED TO THE PLANS.
A00.05 - 5G Comments
-THE SIZE OF THE ROCK HAS BEEN MODIFIED
TO ACCOMODATE THE ACCESSIBLE PATH.
-DIMENSIONS HAVE BEEN ADDED TO CLARIFY
THE REQUIRED ACCESSIBLE WIDTH.
A80.03 - 5G Comments
-THE MIRROR AND HANGING ROD WALLS
WERE SWITCHED. THIS DETAIL IS NOW SHOWN
ON 2/A80.03.
-THE DIMENSION CONSTRAINTS AND
REQUIRED CONNECTION FOR BACK SUPPORT
ARE NOTED.
-THE HEIGHT OF THE COAT RACK IS ALSO
NOTED ON 2/A80.03
A90.02 - 5G Comments
-DIMENSIONS HAVE BEEN ADDED TO SHOW
THE TOP OF COUNTER AT 2'-10" AFF.
08/14/2018
Subject: PlanCheck
Page Label: E20.01 Floor Plan - Electrical
Author: justinh
File Name: PlanSet.535 E Hyman Unit 108.2018.06.pdf
The lighting plan must show
compliant lighting controls per
IECC C405.2.1-405.2.5, this will
include either time switch
controls (C405.2.2) or occupant
sensors (C405.2.1) throughout
the space as well as manual
light reduction controls
(C405.2.2.2). Provide cutsheets
for all light fixtures that provide
maximum fixture wattage as well
as NRTL listing.
DDD JDJD
1
C
1.2
B
A-1
A-12
4
1
C
21.2
B
2.3
L1A-5c
A-10
A1
2
EMA-5 EMA-5
EMA-5
EMA-5
X
A-7VIA LTGCONTACTOR
A-9VIA LTGCONTACTOR
L1A-5c
L1A-5c
L1A-5c
L1A-5b
L1A-5b
L1A-5b
L1A-5bL1A-5b
L1A-5b
L1A-5a L1A-5b
L1A-5a L1A-5a L1A-5b
L1A-5b
L1A-5bL1A-5bL1A-5b
L1A-5b
L1A-5bL1A-5b
L1A-5b
L1A-5b
L1A-5a
L1A-5a
L1A-5a
L1A-5b
L1A-5b
L1A-5b
L1A-5b
L1A-5b
L1A-5b
L1A-5bL1A-5bL1A-5b
L1A-5b
L1A-5b
L1A-5b
L1A-5a
L1A-5a
L1A-5bL1A-5aL1A-5a
L1A-5b L1A-5b
L1A-5b
L1A-5b
L1A-5b
L1A-5b
L1A-5bL1A-5b
L2 L2
L3
1/4" = 1'-0"1 Floor Plan - Power 1/4" = 1'-0"2 Reflected Ceiling Plan - Lighting
3 ALL MOUNTING HEIGHTS SHALL BE CONFIRMED WITH ARCHITECT PRIOR TO ROUGH-IN.4 CONTRACTOR SHALL VERIFY DIMMING METHODS FOR DIMMED FIXTURES WITH DIMMERSWITCHES/CONTROLS BEFORE PURCHASE.5 EMERGENCY FIXTURES AND EXIT SIGNS SHALL BE CONNECTED TO THE LOCAL LIGHTINGCIRCUIT AHEAD OF ALL CONTACTORS AND SWITCHING.
The lighting plan must show compliantlighting controls per IECCC405.2.1-405.2.5, this will include eithertime switch controls (C405.2.2) oroccupant sensors (C405.2.1) throughoutthe space as well as manual light reductioncontrols (C405.2.2.2). Provide cutsheetsfor all light fixtures that provide maximumfixture wattage as well as NRTL listing.
A90.02 - 5G Comments
-THE RCP HAS BEEN UPDATED TO REFLECT VE
DESIGN CHANGES.
-THE LIGHTING CONTROLS ARE NOTED UNDER
THE KEYNOTES "1."
-REFER TO "Light.535 E Hyman unit
108.2018.08.pdf" FOR LIGHT FIXTURE
CUTSHEETS.
-A10.02 WAS UPDATED TO REFLECT THE
REVISED LIGHTING AND REVISED CIRCUT.
GENERAL NOTES:
-ADDITIONAL DRAWINGS ARE INCLUDED IN THE COMMENT RESPONSE BECAUSE OF
RELATED CHANGES TO THE COMMENTS ABOVE.
-THE FLOOR ASSEMBLY HAS CHANGED FROM METAL STUD, PLYWOOD, AND TILE TO
CONCRETE OVER STRUCTRUAL FOAM.
PAUL MERRILL
PRINCIPAL
5G STUDIO COLLABORATIVE
214.347.7564
08/14/2018