HomeMy WebLinkAboutFile Documents.535 E Hyman Ave.0007.2019.ACBK0007-2019-ACBK_BuildingComment1
Subject: PlanCheck
Page Label: 00 ELECTRICAL ETAILS AND SCHEDULES
Author: justinh
File Name: Plan Set.535 E Hyman Unit 104.2019.02.01.pdf
Color:
Per the cutsheets provided
fixture A2/A2E is a 20 W fixture,
and the chandelier is only 240W
fixture (4x60W), please revise.
Please also include the vertical
illuminated orb shown on A-102
as that appears to be another
decorative light fixture (see
additional power allowances for
decorative fixtures if additional
watts are need to pass).
Plan Set.535 E Hyman Unit 104.2019.02.01.pdf (3)
Subject: PlanCheck
Page Label: 101 ELECTRICAL ECTED CEILING PLAN
Author: justinh
File Name: Plan Set.535 E Hyman Unit 104.2019.02.01.pdf
Color:
Show the daylight zones on your
lighting plan (IECC C405.2.3.2)
Subject: PlanCheck
Page Label: A-102 REFLECTED CEILING PLAN
Author: justinh
File Name: Plan Set.535 E Hyman Unit 104.2019.02.01.pdf
Color:
This light fixture should be
shown on your architectural and
electrical lighting plans unless I
am misunderstanding what it is.
Please also account for it on the
ComCheck and provide a
cutsheet on it.
Per the cutsheets provided fixtureA2/A2E is a 20 W fixture, and thechandelier is only 240W fixture (4x60W),please revise. Please also include the
vertical illuminated orb shown on A-102as that appears to be another decorativelight fixture (see additional powerallowances for decorative fixtures if
additional watts are need to pass).
ELECTRICAL
SCALE: 1/4" = 1'-0"
1
E101
FIXTURES ARE SWITCHED, ROUTE ADDITIONAL POWER FROM THE
SAME CIRCUIT AHEAD OF ALL SWITCHING FOR POWER LOSSSENSING.
4.PROVIDE OCCUPANCY SENSOR FOR AUTOMATIC SHUT OFF OF
ROOM LIGHTING. SEE DETAIL E002.
5.THE REMAINING FIXTURES ON THIS RUN ARE BACKED UP BY AN
INVERTER (FIXTURE RP#). CONNECT FIXTURES AS SHOWN IN DETAIL
SUCH THAT THE SWITCH IS OVER-RIDDEN DURING A POWER
FAILURE, AND EMERGENCY FIXTURES ARE SWITCHED WITH THESALES FLOOR LIGHTS. SEE DETAIL E004.
6.NEW EMERGENCY BATTERY UNIT RP#. WIRE TO CIRCUIT SHOWN.
COORDINATE INSTALLATION LOCATION WITH NEXTORE PROJECTMANAGER.
7.PROVIDE CONNECTION TO EDGE-LIT "OLIVER PEOPLES" LETTERS.
COORDINATE FINAL J-BOX QUANTITIES AND LOCATIONS WITHSIGNAGE VENDOR SHOP DRAWINGS. ROUTE CIRCUIT TO PANEL '104'VIA TIME CLOCK.
8.PROVIDE CONNECTION TO EDGE-LIT BLADE SIGN. COORDINATEFINAL J-BOX LOCATION WITH SIGNAGE VENDOR SHOP DRAWINGS.ROUTE CIRCUIT TO PANEL '104' VIA TIME CLOCK.
9.3-WAY SWITCHES FOR ON/OFF CONTROL OF OFFICE LIGHTS.DIMMING LEVELS TO BE SET AT DRIVER BOARD SWITCH ONLY.
10.PROVIDE DAYLIGHT SENSORS FOR AUTOMATIC DIMMING OF LED
LIGHTS IN DAYLIGHT ZONES. INITIAL SETPOINT SHALL BE 35 FC;ADJUST PER OPERATIONS MANAGER.
A1 A1EA1EA1A2
A2 A2
A2
LIGHT FIXTURE SCHEDULE - OLIVER PE TAG DESCRIPTION MANUFACTU
A1 2 LAMP, WITH TRIM BLACK INTERIOR, 40W ENGINE,LED DOWNLIGHT INTENSE
A1E
2 LAMP, WITH TRIM, BLACK INTERIOR, 40WENGINE, LED DOWNLIGHT, 7W EMERGENCYOPTION INTENSE
A2 1 LAMP, WITH TRIM, BLACK INTERIOR, 20WENGINE, LED DOWNLIGHT INTENSE
A2E
1 LAMP, WITH TRIM BLACK INTERIOR, 20W ENGINE,LED DOWNLIGHT, 7W EMERGENCY OPTION INTENSE
F1 BACK OF HOUSE; 2X2 LED TROFFER 3,200 LUMENS3500K DIMMABLE 0-10V CREE
CONTROLSCOSCEILING OCCUPANCY SENSOR SENSORSWI
b
d
7
7
J
J104-22
104-22
xx-xx
S2
SW4
1.ROUTE CIRCUIT THROUGH CONTACTOR CONTROLLED BY TIMECLOCK. SEE DETAILL001.
2.ROUTE DEDICATED 120V, 20A CIRCUIT FROM EXISTING PANEL TO FRONT OF STOREFOR NEW ILLUMINATED STORE FRONT SIGN. CONTROL SIGN WITH HONEYWELL (OREQUAL) RPLS530A 7 DAY, 14 EVENT DIGITAL TIME SWITCH INSTALLED AT PANEL, ANEXTERIOR PHOTOSWITCH, WIRED IN SERIES, SUCH THAT PHOTOSWITCH ONLYALLOWS OPERATION DURING DAYLIGHT HOURS AND TIMESWITCH TURNS SIGN OFF
ON A TIME SCHEDULE. INSTALL LOCAL DISCONNECT AT 12FT AFF.
PROVIDE 15FT WHIP TOSIGN LOCATION.VERIFY EXACTREQUIREMENTS WITH
SIGN VENDOR.
EXTERIOR SIGNAGE
C, 2 CHANNEL
HANNEL 2
Show the daylight
zones on your lighting
plan (IECC C405.2.3.2)
L TYPE DESCRIPTION
A3 RECESSED (3) SPOT
SEE ELEC. SHEETS FOR MFG, SPECS ETC.(TYP. ALL LIGHTS IN SCHEDULE)
X4
C1
X1
SPK1
RECESSED (1) SPOT
EXIT SIGN
EMERGENCY LIGHT
AUDIO SPEAKER
CAMERA
EMERGENCY LIGHT
COMBINATION EXIT SIGN/ EMERGENCY LIGHT
EXHAUST FAN
MILLWORK "PUCK" LED LIGHT
D2 LED STRIP LIGHTING
D1
2 X 2 LED LIGHT FIXTURE
RECESSED (2) SPOT
D3 LED STRIP LIGHTING
TRAFFIC COUNTER
LIGHTING SCHEDULE
A2
F1
CAMERA
X6
X3
UNIT 108
1
A-210
2
A-210
114e
104G 104T
SA
TC
SPK1
CAMA1
A2
A1 A1
A1
A1
A2
A2 A2 A2
1'-5"7'-10"3'-3"5'-0"0"2'-0"2'-0"4'-0"2'-4 1'-3 1/2"11 1/4"1'-0"4
4
2
7
15
F1
20
2'-0"2'-0"11"2'-0"
13
21
22
VERTICAL ILLUMINATED ORB
SCALE: N.T.S.6
POWER FROM ABOVE. (LEAVE 10' COIL WIRE ATCEILING)
NOTE: REFERENCE SHOP DRAWINGSFOR ADDITIONAL INFORMATION
This light fixture shouldbe shown on your
architectural andelectrical lighting plansunless I ammisunderstanding whatit is. Please alsoaccount for it on theComCheck and provide
a cutsheet on it.