HomeMy WebLinkAboutFile Documents.980 E Hyman Ave.0014.2019.ARBK0014-2019-ARBK_BuildingComment1
Subject: PlanCheck
Page Label: ID.01 EXISTING AND PROPOSED LOWER
LEVEL FLOOR PLANS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
Replacement exterior doors are
also required to have a U value
of .28 or less. Note this
requirement on your door
schedule or provide cutsheets
on the proposed replacement
doors.
2019.01.23_980 E HYMAN AVE. UNIT1.pdf (7)
Subject: PlanCheck
Page Label: ID.01 EXISTING AND PROPOSED LOWER
LEVEL FLOOR PLANS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
Closets housing clothes dryers
are required to provide a
minimum of 100 square inches
of opening for make up air per
IMC 504.6 (usually
accomplished with a small
transfer grill). Note this
requirement on your plan.
Subject: PlanCheck
Page Label: ID.02 EXISTING AND PROPOSED UPPER
LEVEL FLOOR PLANS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
Identify demising walls on your
floor plans, the section shows
that you have another unit above
you but I cannot tell if there are
other units adjacent to you.
Please revise.
Subject: PlanCheck
Page Label: ID.04 WALL ASSEMBLIES & DETAILS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
Show that the new hearth
extension meets the
requirements of IBC 2111.10
and 2111.11. The hearth
extension cannot be supported
by any combustible framing
unless you can find
documentation in the original
fireplace installation instructions
that says otherwise (this
generally requires specific
hearth extension equipment from
the manufacturer in order to be
installed on combustible
framing).
HEATER 10" HIGH
ATH 4
TILE
G 7' - 6 13/16"
BATH 3
TILE
CLG 7'-6 1116"
CLOSET 5
HALL 2
CONCRETECLG 8'-1 5/8"
STAIR
CARPET
13'-6"8 12"
R14 @ 7.5" +/-UPAV &
HOUSEKEEPING
6"
2'-6"13'-6"812"4'-0"
WIRE CABLE RAILING
512"'-814"
3'-6"
ADD HANDRAIL 3'-0"10'-218"
2'-6"CLEARPERCODECABINET MANUF.
VERIFY W/ LIGHTING
SPEC DEPTH OF SHELF
IN CABINET W/ HANGING.
A
ID.04
C
ID.04Q
M
I
KP
J
DOG
WASH
3012"
100'-0"
B
ID.01 SCALE:
PROPOSED LOWER LEVEL PLAN
1/4" = 1'-0"
GORMAN
37 34" x 72 34"
Replacement exterior
doors are also required
to have a U value of
.28 or less. Note this
requirement on your
door schedule or
provide cutsheets on
the proposed
replacement doors.HEATER 10" HIGHHEATER 10" HIGH
BEDROOM 4CARPETCLG 8'- 5/8"BEDROOM 3CARPETCLG 8'- 5/8"
HEATER 10"
BATH 4TILECLG 7' - 6 13/16"
BATH 3
TILECLG 7'-6 1116"
FOUNDATION LEDGE 52 12"FOUNDATION LEDGE 52 12"
CLOSET 4CARPETCLG 7' - 6 13/16"
CLOSET 3CARPET
HALL 2
CONCRETECLG 8'-1 5/8"
RS
K-2882VERTICYLLAVATORYVITREOUS CHINA
K-2882VERTICYLLAVATORYVITREOUS CHINA
512"3'-814"2'-10"4'-218"2'-6"914"2'-6"5'-138"812"1'-1012"3'-6"512"5'-0"3'-158"
2'-6"
RADON PIPE
NEW LOCATION
EXISTING LEDGE
CABINET MANUF.VERIFY W/ LIGHTINGSPEC DEPTH OF SHELF
IN CABINET W/ HANGING.
CABINET MAN VERIFY W/ LIGHT SPEC DEPTH OF SH IN CABINET W/ HANG 8'-378"BID.04 BID.04
AID.04
A
ID.04
B
ID.04
A
ID.04 Q
M
P
9
10
O
3012"
B
ID.01 SCALE:
PROPOSE
GORMAN
NEW CASEMENT
32 34" x 72 34"
NEW DBL HUNG
32 34" x 72 34"
Closets housing clothes
dryers are required to provide
a minimum of 100 squareinches of opening for makeup air per IMC 504.6 (usuallyaccomplished with a smalltransfer grill). Note thisrequirement on your plan.
BUILT IN DRESSER
AND HANGING
Identify demising walls on your floor
plans, the section shows that you have
another unit above you but I cannot tell
if there are other units adjacent to you.
Please revise.
EXISTING
FIREBOX 2512"EXISTINGMETAL 2X4 FRAMING
58" CEMENT BOARD
THIN SET
SPLIT FACE STONE
FURR OUT. W/ METAL STUDS
CONFIRM W/ DESIGNER
METAL
CEMENT BOARD UNDERMETAL EXTENDS 3"
PAST TILE UNDER
CARPET
CARPET ANDMETAL FLUSH
METAL FIREPLACE SURROUND W/
12" LIP.1212"20"
METAL MANTEL
STEEL METAL DOORS W/MESH
CEMENT BOARD UNDER
METAL EXTENDS 3"
PAST TILE UNDER
CARPET
METAL FLUSH
1212"20"
WALL ASSEMBLIES &
DETAILS
H
ID.04SCALE:
FIREPLACE
1" = 1'-0"
GORMAN
I
ID.04SCALE:
FIREPLACE
1" = 1'-0"
GORMAN
SHEET:
ISSUE DATE:
SHEET TITLE:
DRAWN BY: ANNE GRICE INTERIORSGORMANASPEN EAST UNIT #1980 E HYMAN AVEASPEN, CO 81611PARCEL #273718206027BUILDING PERMIT SET
01 23 2019
10.05.18 PRICING SET09.19.18 SCHEMATIC DESIGN
12.10.18 PROGRESS PRICING SET
01.07.19 CLIENT MEETING
Show that the new hearth extensionmeets the requirements of IBC 2111.10and 2111.11. The hearth extension
cannot be supported by any combustibleframing unless you can finddocumentation in the original fireplaceinstallation instructions that saysotherwise (this generally requiresspecific hearth extension equipmentfrom the manufacturer in order to beinstalled on combustible framing).
Subject: PlanCheck
Page Label: ID.05 WALL ASSEMBLIES & DETAILS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
These assemblies do not match,
the quiet rock assembly you
have is a wall assembly rather
than the floor ceiling assemblies
you've detailed. Specifying quiet
rock as the top layer of your
upper level floor/ceiling
assembly between you and the
unit above doesn't work, you
would need to pull up their
flooring to install this. Please
submit a different listed/tested
assembly for your ceiling
assembly, I know quiet rock has
ceiling assemblies available.
Subject: PlanCheck
Page Label: ID.08 MUDROOM ELEVATIONS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
Dimension the spacing of the
cable rails, code requires they
restrict the passage of a 4"
sphere so they must be spaced
less than that. Cable rails can
deflect various amounts
depending on the tension
applied to these at installation,
you will need to space them
accordingly so that when pushed
in opposite directions any two
cables will still restrict the
passage of a 4" sphere. This
requirement will be verified at
inspection, but the spacing
needs to be called out on your
plan.
Subject: PlanCheck
Page Label: ID.08 MUDROOM ELEVATIONS
Author: justinh
File Name: 2019.01.23_980 E HYMAN AVE. UNIT1.pdf
Color:
Are these open risers? If so,
they appear to exceed the 4"
opening limitation. Please verify
what is proposed and revise if
needed.
1 HOUR, TYPE X
58" QUIET ROCKGYPSUM CEILING PANEL1 HR FIRE RATINGEXISTING STRUCTURE
VENEER PLASTER
58" SHEETROCK, FIRECODE COREGYPSUM PANELS CEILING1 HR FIRE RATING
EXISTING STRUCTURE
VENEER PLASTER
4" RECESSED CANFIRE RATED LIGHT COVER
KID.05SCALE:
QUIETROCK ASSEMBLY @ PARTY WALLS
NTS
GORMAN
LID.05SCALE:
TYP. CEILING ASSEMBLY
1 1/2" = 1'-0"
GORMAN MID.05SCALE:
TYP. RECESSED LIGHTING ASSEMBLY
1 1/2" = 1'-0"
GORMAN
These assemblies do not match, the quiet rockassembly you have is a wall assembly rather than thefloor ceiling assemblies you've detailed. Specifyingquiet rock as the top layer of your upper levelfloor/ceiling assembly between you and the unitabove doesn't work, you would need to pull up theirflooring to install this. Please submit a differentlisted/tested assembly for your ceiling assembly, Iknow quiet rock has ceiling assemblies available. 4'-3"DOGCRATE
36" DEEPKE STORAGEWOOD BACK
2'-6"4'-0"
A/VEQUIPMENT
4'-878"
21" DEEP
HOUSEKEEPINGCLOSET
21" DEEPHANGING/COATSTORAGE 8'-158"LL
BLACK METALSTRINGER
CABLE RAIL SYSTEM
SPACED 3 12"WOOD STAIR TREAD
BOOT
DRYER
WALL W/ WOOD PANEL
HOOKS FOR HELMETS 4'-0"3'-0"3 12"B
ID.08 SCALE:
STAIR/ MUDROOM ELEVATION
1/2" = 1'-0"
GORMAN
Dimension the spacing of the cable rails, code requires they restrictthe passage of a 4" sphere so they must be spaced less than that. Cable rails can deflect various amounts depending on the tensionapplied to these at installation, you will need to space themaccordingly so that when pushed in opposite directions any twocables will still restrict the passage of a 4" sphere. This requirementwill be verified at inspection, but the spacing needs to be called out
on your plan.
RAIL ON DRYWALL
BOOT
DRYER
Are these open risers? If so, they
appear to exceed the 4" opening
limitation. Please verify what is
proposed and revise if needed.