HomeMy WebLinkAboutFile Documents.971 Ute Ave.0247.2017.ARBK0084-2017-ARBK_BuildingComments_1
Page: A-103
File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
If new range hood exhausts
greater than 400cfm, interlocked
makeup air will be required.
2015 IMC 505.2.
2017.04.06_971 Ute Ave._Permit Set.pdf (5)
Page: A-105
File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide an exhaust fan in the
master bath area containing the
bathtub and shower.
Page: D-101
File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
The walls and ceiling separating
the ADU bath and kitchen from
the rest of the house must be 1
hour fire rated with an STC
rating of at least 50. You will
likely be disturbing the existing
drywall. Provide listed
assemblies to be used to replace
the drywall if more than 32sqft is
disturbed.
Page: G0.00
File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide an asbestos inspection
report including the narrative, lab
data, and inspector's
certifications.
Page: G0.00
File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
This project was submitted after
April 10, 2017, putting it on the
2015 codes. Revise to make all
codes be 2015 except for the
2014 NEC.
DWDW
KITCHEN
308
WOOD
LIVING
303
WOOD
DN
CLOSET
305
WOOD
NEW POCKET DOOR
SKYLIGHT ABOVE
BUILT IN
EXISTING STAIR TO REMAIN
WASHER
E KITCHEN
APPLIANCES
"4'-0 9/32"10'-8"7'-1"4'-3 1/2""If new range hood
exhausts greater than
400cfm, interlocked
makeup air will be
required. 2015 IMC
505.2.
F
MSTR BATH
201
MASTER BED
202
Provide an exhaust fan
in the master bath area
containing the bathtub
and shower.
C E FD
41'-0"
16'-3"14'-0"2'-10"4'-2"
BED
101
CARPET
ADU BED
103
CARPET
ADU BATH
102
STONE
ADU KITCHEN
104
STONE
CLOSET113CARPET
ADU CLOSET
105
CARPET
BATH
111
MEDIA ROOM
107
CARPETOOM
ET
ADU STAIR106CONCRETE
UP
REF
BUILT IN
D CABINETS
REPLACE EXISTING FIXTURES AND CABINETS
AREAS OF WORK
The walls and ceilingseparating the ADUbath and kitchen fromthe rest of the house
must be 1 hour firerated with an STC
rating of at least 50.You will likely be
disturbing the existingdrywall. Provide listed
assemblies to be usedto replace the drywall ifmore than 32sqft isdisturbed.
Provide an asbestos inspection report
including the narrative, lab data, and
inspector's certifications.
CIVIL ENGINEER:
-CONTACT:--
A.F.F.
PROJECT ADDRESS:
PARCEL ID:
FIRE SPRINKLER SYSTEM INSTALLED:
APPLICABLE CODES:·2009 IRC (International Residential Code) Chapters 1-10·2009 IRC appendixes:·Manufactured homes, F: Radon, J: Existing Buildings & Structures, H:Patio Covers, K: Sound Transmission.
·2009 IPC (International Plumbing Code)
·2009 IMC (International Mechanical Code)·2009 IFGC (International Fuel Gas Code)·2009 IECC (International Energy Conservation Code) - Prescriptive Path
·2009 IFC (International Fire Code)
·2014 NEC (National Electrical Code)
971 Ute Aveune, Aspen CO 81611
273718295029
NO
R-15
3,682.79 sq ft EXISTING, 3,682.79 sq ft PROPOSED (NO CHANGE)
Residential
Front - 25', Side and Rear - 10'
ZONING:
F.A.R.
PERMITTED USE:
SETBACKS:
PROJECT DIR
CONTACT: Ryan Doremus
STRUCTURAL ENGINEER:
LANDSCAPE DESIGN:
OWNER/CLIENT:
ARCHITECT:
Aspen, CO 81611
Thunderbowl Architects
300 Spring St. Suite 201
Ajax Holdings
PROJECT STATISTICS
TYPE:
OCCUPANCY:
OVERALL PROJECT HEIGHT AND AREA:
PROJECT SUMMARY:
Type V - Non-rated
Type R-3
Maximum Height N/A - Area N/A
INTERIOR REMODEL OF EXISTING BATHROOMS AND
UPDATING KITCHEN CABINETRY AND PLUMBING FIXTURES.
--CONTACT:-
CONTRACTOR
ENOTES DIMENSION
ENOTES DIMENSION
R DENOTES FINISH
-CONTACT:--
Kaegebein Fine HomebuildingCONTACT: Nate Kaegebein-
--
MECHANICAL DESIGN:
--
CONTACT:
-
CONTACT: Ryan Doremus (Thunderbowl Architects)
Aspen, CO 81611300 Spring St. Suite 201
This project was
submitted after April
10, 2017, putting it on
the 2015 codes.
Revise to make all
codes be 2015 except
for the 2014 NEC.
A-103 NOW HAS A
NEW NOTE
REFLECTING
EXISTING HOOD AND
RANGE TO REMAIN
A-105 NOW HAS A NEW
FAN LOCATED IN THE
MAIN BATHROOM AREA
G0.00 NOW HAS A
UPDATED APPLICABLE
CODES TO REFLECT THE
2015 CODE ADOPTION
INCLUDED IS THE
ASBESTOS
CERTIFICATE
SEE NOTE ON
D-101, AND
ATTACHED
LISTED WALL
ASSEMBLY
City of Aspen
Received
6/26/17
Building Department