HomeMy WebLinkAboutFile Documents.950 Cemetery Ln.0072.2018 (3).ARBK0072-2018-ARBK_BuildingComments_2 Page: 1 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: Provide a summary of everything that has been changed since the original submittal. 181005 950 Cemetery Lane Building Resubmittal Set.pdf (8) Page: 9 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: Indicate which walls are dwelling separation walls (which walls are shared with the other unit of the duplex). Reference a 1 hour fire/STC 45 rated assembly. Print the full, original listed assembly instructions on the plans. For example, reference detail 2/A5.0 where it occurs in the plans and sections. Detail 2/A5.0 reference GA File No. WP 3242; therefore you should print WP 3242 on the plans. (2015 IRC R302.3 and appendix K) Page: 16 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: R308.4 Safety Glazing windows Author: nickt Color: On the plans or window schedule, label each individual window that must be safety glazed (R308.4). Page: 18 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: Detail air sealing at new living room straightened wall. Page: 19 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: Detail 2/A5.0 refers to an interior partition wall. Revise to reference an exterior wall. TERY LANE- UNIT 1 N COLORADO SHEET INDEXT TEAM Provide a summary of everything that has been changed since the original submittal. D W14W13W11 W18D16 D17D21 D20 D18W17 W28D03DG1 D19 W15W16W123 6 7 F 2 4 W SOUTHZ-201 WESTZ-202 23'-6"22'-4 3/4"5 1/2"1'-7 3/4"2'-6 1/2"1'-7 3/4"3 1/2"4'-11 1/2"3'-3 1/2"1'-9"1'-7"5 1/2"18'-7 1/2"4 1/2"4'-6 1/2"3 1/2"35'-4"4 1/2"5 1/2"1'-4 3/4"1'-6 1/4"3 1/2"5'-8 1/2"5 1/2"11'-11"5'-3"2'-4"2'-1"3 1/2"CA 4.1 1A 4.0 #DrgID#LayID BA 3.4SLOT DRAIN,NO CURB TOP OF ROOF BELOW NEW SINGLE DOOR RECONFIGURE ENTRY STORAGE MASTER BEDROOM POWDER MASTERBATH W/C STEAMSHOWER DRESSER MASTERCLOSET CUBBIESBOOTDRYERCLOSETW/BENCHBELOW BENCH LINEN ENTRYELEV. 7,860.22' =ARCH 95'-1 1/2" BA 3.4 5 E D Indicate which walls are dwellingseparation walls (which walls areshared with the other unit of theduplex). Reference a 1 hourfire/STC 45 rated assembly. Printthe full, original listed assemblyinstructions on the plans. Forexample, reference detail 2/A5.0where it occurs in the plans andsections. Detail 2/A5.0 referenceGA File No. WP 3242; thereforeyou should print WP 3242 on theplans. (2015 IRC R302.3 andappendix K) D CDC On the plans or window schedule, label each individual window that must be safety glazed (R308.4). A B MAIN LEVEL =7,865'- 1 1/8" = ARCH 100'-0 T.O.WALL7,877.1' = ARCH 112'-0" T.O.ROOF7,877.6' = ARCH 112'-6" Detail air sealing at new living room straightened wall. MAIN LEVEL T.O. PLY 7,865'- 1 1/8" = ARCH 100'-0 5'-6"NEW WALL, SEE 2/A 5.0 Detail 2/A5.0 refers to an interior partition wall. Revise to reference an exterior wall. Please see attached narrative Please see GA assembly onA1.3 & A1.4, and reference on 2/A5.0 Please refer to "Comments"column in Window Schedule,sheet A6.0 Please refer to 12/A5.0for typical Window/Door detailwith sealing requirements Please refer to Buidling Section 1/A4.0& 1/A4.1 for proper notation. 12/10/18 Page: 19 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: For the slab edge insulation to count, it must extend up to the top of the slab along the edge. Revise drawing to do that or Revise Rescheck to show 0 slab edge insulation. Page: 19 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: Detail air sealing at the new mech room thermal envelope. Page: 21 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: The hearth extension may not be touched unless it is brought up to code. To bring it up to code, you will need to make it entirely supported by non-combustible materials to grade (it may not bear on any wood framing materials in its load path). (2015 IRC R1001.9) Page: 1 File Name: REScheck - 09-24-18_signed.pdf Subject: PlanCheck Author: nickt Color: The plans call for R49 spray foam in the roof assemblies. Continuous insulation is not specified beyond tapered insulation. Revise REScheck to match. REScheck - 09-24-18_signed.pdf (3) Page: 1 File Name: REScheck - 09-24-18_signed.pdf Subject: PlanCheck Author: nickt Color: The drawings show the slab edge insulation starting below the top of the slab rather than at the top. Revise the REScheck to show '0' slab edge insulation. CH ROOM T.O. SLAB 0.22' = ARCH 93'-6" 5'- 1 1/8" = ARCH 100'-0 5'-6"3'-0"3'-0"W WALL, SEE 2/A 5.0 4'-9" = ARCH 89'-8"POSED NEW LOWER SLAB N For the slab edge insulation to count, it must extend up to the top of the slab along the edge. Revise drawing to do that or Revise Rescheck to show 0 slab edge insulation. ROOM T.O. SLAB 2' = ARCH 93'-6" N LEVEL T.O. PLY 1 1/8" = ARCH 100'-0 5'-6"3'-0"THICKENED 2" RIGID INS AT 45 DEGR WALL, SEE 2/A 5.0 NEW MECH R Detail air sealing at the new mech room thermal envelope. Scale: AS NOTED ISSUESCHEMATIC DESIGNPERMIT SETVE SETZONING COMMENTS 1BUILDING COMMENTS PERMIT RESUBMITTALCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 816111" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. A 5.1 10/5/2018 FIREPLACEDETAILS DATE1/24/184/2/187/30/188/14/189/27/18 10/05/18 6"4"1'-11"MIN 2', V.I.F.T.O. LOWER LEVEL F.F. LIVING ROOM FIREPLACE SECTION EL. + RE: FLOOR PLAN EXISTING CMU TO REMAIN EXISTING WOOD BURNING FIREPLACETO REMAIN ADD STEEL FRAME GLASS DOORSON FIREPLACE REPLACE STONE HEARTH ATSAME ELEVATION REMOVE EXISTING STONE VENEERABOVE TO EXPOSE EXISTING FLUEPIPE; WRAP WITH DECORATIVE STEEL.MAINTAIN REQUIRED CLEARANCES NEW METAL CAP AND FLASHING REPLACE FIREPLACE VENEER STEEL ANGLE HEADER EXISTING HEARTH,REMOVE ANDREPLACE NEW STONE CAP T.O. LOWER LEVEL F.F. EL. + RE: FLOOR PLAN REMOVE EXISTING STONE VENEER ABOVE TOEXPOSE EXISTING FLUE PIPE; WRAP WITHDECORATIVE STEEL NEW GWB WALL NEW STEEL FRAME GLASS DOORS NEW STONE SURROUND AND HEARTH EXISTING WOOD BURNING FIREPLACEBEYOND TO REMAIN NEW RAILING, STAIR BEYOND NEW SHELVING FOR WOOD STORAGE NEW STONE CAP 0 6''1'2'SCALE: 1" = 1'-0"3 FIREPLACE 0 6''1'2' 0 6''1'2' The hearth extensionmay not be touchedunless it is brought upto code. To bring it upto code, you will needto make it entirelysupported bynon-combustiblematerials to grade (itmay not bear on anywood framingmaterials in its loadpath). (2015 IRCR1001.9) The plans call for R49 spray foam in the roof assemblies. Continuous insulation is not specified beyond tapered insulation. Revise REScheck to match. The drawings show the slab edge insulation starting below the top of the slab rather than at the top. Revise the REScheck to show '0' slab edge insulation. Please see Building Section 1/A4.1 and detail 7/A5.0 Please see clarifying noteson 3/A5.1 stating the only the veneer is to be replaced. Existing structure is to remain. Please see revised Detail 9/A5.0,calling out insulation assembly to meet RESCheck specifications Please see revised Detail 4/A5.0that shows minimum R-15 sprayfoam insulation applied to existingassembly. Please refer to notes in Details 5/A5.0 & 7/A5.0 12/10/18 Page: 3 File Name: REScheck - 09-24-18_signed.pdf Subject: PlanCheck Author: nickt Color: Revise Rescheck to match the fenestration specs from Windsor. For example, there are doors with U-factors of 0.35, 0.34, and 0.29. Revise Rescheck to match the fenestration specs from Windsor. For example, there are doors with U-factors of 0.35, 0.34, and 0.29. Please see note on A6.0 referencing U-value requirementsof all windows and exterior doors stated in the RESCheck reportsubmitted with the Permit Apllication. The exact window and doorhas not been selected yet, but we have specified the requiredU-value. 12/10/18 Page: 1 File Name: 181005 950 Cemetery Lane Building Resubmittal Set.pdf Subject: PlanCheck Author: nickt Color: Provide a summary of everything that has been changed since the original submittal. TERY LANE- UNIT 1 N COLORADO SHEET INDEXT TEAM Provide a summary of everything that has been changed since the original submittal. Please see attached narrative