Loading...
HomeMy WebLinkAboutFile Documents.950 Cemetery Ln.0072.2018 (7).ARBK0072-2018-ARBK_BuildingComments_1 Page: A 0.3 FIRE AREA File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Revise the fire area plans to not include the eave overhangs. Only include outdoor covered areas if they are usable areas such as a covered porch. plans.pdf (10) Page: A 1.3 LEVEL PLAN-PROPOSED File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Provide a wall section at the new thermal envelope at the utility room addition. Indicate the following: -Insulation matching REScheck. -Flashing/waterproofing. -Show the air sealing strategy. Note locations that require caulking, sealing, taping, etc. Note which components are included in the air barrier such as spray foam, gypsum, housewrap, and/or exterior insulation. Page: A 1.4 PLAN-PROPOSED File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Provide a wall section at the new thermal envelope at the straightened living room wall. Indicate the following: -Insulation matching REScheck. -Flashing/waterproofing. -Show the air sealing strategy. Note locations that require caulking, sealing, taping, etc. Note which components are included in the air barrier such as spray foam, gypsum, housewrap, and/or exterior insulation. Page: A 1.4 PLAN-PROPOSED File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Detail and dimension the guard at the hot tub. Guard must extend a minimum of 18" above the top of the hot tub edge unless the edge is 18" or greater, in which case the guard must be 36" measured from the top of the hot tub. Per City Policy. Scale: AS NOTED ISSUESCHEMATIC DESIGNPERMIT SETCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 816111" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. A 0.3 4/1/2018 FIRE AREA DATE1/24/18 KIM RAYMOND ARCHITECTS, INC.| 300 E. HYMAN AVENUE, SUITE 100 || www.kimraymondarchitects.com || 970-925-2252 |4/2/18454 sq ft 123UP12RISE(6")11RUN(11") A FIRE SPRINKLER SYSTEM ISREQUIRED IF THE FIRE AREA ISGREATER THAN 5,000 SF. 819 sq ft DOWN 1,387 sq ft421 sq ft 36 sq ft 143 sq ft 19 sq ft 141 sq ft 445 sq ft 563 sq ft 488 sq ft 1,240 sq ft UNIT 2 MAIN LEVEL UNIT 2 UPPER LEVEL UNIT 2 LOWER LEVEL FIRE AREA UNIT1 LOWER LEVEL 1,273 UNIT 1 MAIN LEVEL 2,006 UNIT 1 TOTAL 3,279 UNIT 2 LOWER LEVEL 488 UNIT 2 MAIN LEVEL 1,685 UNIT 2 UPPER LEVEL 704 UNIT 2 TOTAL 2,877 DUPLEX TOTAL 6,156* A FIRE SPRINKLER SYSTEM ISREQUIRED IF THE FIRE AREA ISGREATER THAN 5,000 SF. 04'8' 16'SCALE: 1/8" = 1'-0"1LOWER LEVEL FIRE AREA 04'8' 16'SCALE: 1/8" = 1'-0"2MAIN LEVEL FIRE AREA Revise the fire areaplans to not include theeave overhangs. Onlyinclude outdoorcovered areas if theyare usable areas suchas a covered porch. Scale: AS NOTED ISSUESCHEMATIC DESIGN PERMIT SETCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 816111" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. A 1.3 4/1/2018 LOWERLEVEL PLAN-PROPOSED DATE1/24/18 KIM 4/2/18123UP12RISE(6")11RUN(11")D09W06 W05 D13 D07D15D14D11 D08 D10 D05C 3 3 6 6 5 5 7 7 B E D F 2 2 4 4 A 4'-11 3/4" 7 1/4"10'-11 3/4"11'-8 1/2" 7 1/4 " 6' 4 1/2 " 10'-2 1 / 2 " 4 1/2 " 8'-11 1 / 2 " 10 1/4 " 10'-2" 3"12'-6 1/2"4 1/2"7'-8 1/2"4 1/2"5'-3 1/2" 74'-4 3/4"22'-4 1/4"7'-9 1/2" 15'-5"12'-11" 9'-4 1/2" 6'-6 1/2" 2'-11 1/4"14'-11"8'-8 1/4"6'-5"3 1/2"5'-3 1/2" 3" 9' EAST2#LayID SOUTHZ-201 NORTHZ-201 WESTZ-202 EAST2#LayID FAMILY ROOM CLOSET 1 OWNER'SCLOSET BATH 1 DOUBLEQUEEN BUNK XL TWINBUNK Drawersunder beddouble high W/D DOUBLEHANG HOOKS / SHELVES HWH NEW UTILITY ROOM TV CA 4.1 1A 4.0 1A 4.0 2A 4.0 2A 4.0 AA 4.1 Provide a wall section at the new thermal envelopeat the utility room addition. Indicate the following:-Insulation matching REScheck.-Flashing/waterproofing.-Show the air sealing strategy. Note locations thatrequire caulking, sealing, taping, etc. Note whichcomponents are included in the air barrier such asspray foam, gypsum, housewrap, and/or exteriorinsulation. Scale: AS NOTED ISSUESCHEMATIC DESIGNPERMIT SETCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 816111" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. A 1.4 4/1/2018 MAIN LEVELPLAN-PROPOSED DATE1/24/18 KIM RAYMOND ARCHITECTS, INC.| 300 E. HYMAN AVENUE, SUITE 100 || www.kimraymondarchitects.com || 970-925-2252 |4/2/18 D DOWNW20W19W23W22D16 D17D21 D20 D18D22 D01 D02 D19D04W29W30 W27W28 W24W25W26 D06W12C C 3 3 6 6 5 5 7 7 B B E E D D F F 1 1 2 2 4 4 A A N W EAST2#LayID EASTZ-202 SOUTHZ-201 NORTHZ-201 WESTZ-202 EAST2#LayID 11'-11 3 / 4 " 23'-6"22'-4 3/4"41'-6 1/2"1'-10"5'-1" 27'-4" 17'-7 1/ 2 " 74'-4 3/4"22'-4 1/4"7'-9 1/2"15'-5"12'-11"15'-11" 43'-3"41'-3"11'-11 3 / 4 " 5'-10 1/2 " 8'-1 1/ 2 " 12'-8 1/ 4 " 2'-7" 4 1/2"8'-2 1/2"4'-6 1/2"3 1/2"3'-4 1/2"5'-4"4 1/2"5'-7 1/2"3'-1/2"2'-10 1/2"3 1/2" 5'-10" 2'-2" 4'-1 1/2" 8'11'-11"8'-2 1/2"5'-3"CA 4.1 CA 4.1 1A 4.0 1A 4.0 2A 4.0 2A 4.0 AA 4.1 AA 4.1 #DrgID#LayID INSTALL NEW RADIANTHEAT, TYP. SLOT DRAIN TOP OF ROOF BELOW CALDERASPAS MARTINIQUE HOT TUBWITH SAFETY COVER; CEC COMPLIANT;47 SF EXEMPT FROM RREMP NEW PARTIAL WALLS TO HIDEHOT TUB CUT BACK WALL;INSTALL RAIL WOOD PANELEDWALL, PROVIDETECTUS HINGESWOOD PANELEDWALL, PROVIDETECTUS HINGES NEW STRUCTURALBEAM ABOVE VERIFY NEWSTRUCTURALCOLUMNS, TYP WOOD BURNINGFIREPLACE TO REMAIN NEW SINGLE DOOR RECONFIGURE ENTRY STORAGE ENCLOSE CARPORTTO CREATEGARAGE LAUNDRY KITCHEN MASTER BEDROOM POWDER MASTERBATH W/C STEAMSHOWER BBQ DRESSER DESKPANTRY MASTERCLOSET CUBBIES BENCH OVENS BOOTDRYER CLOSETW/BENCHBELOW SKIS BENCH LINEN F SCALE: 1/4" = 1'-0"MAIN LEVEL PLAN Provide a wall section at the new thermal envelopeat the straightened living room wall. Indicate thefollowing:-Insulation matching REScheck.-Flashing/waterproofing.-Show the air sealing strategy. Note locations thatrequire caulking, sealing, taping, etc. Note whichcomponents are included in the air barrier such asspray foam, gypsum, housewrap, and/or exteriorinsulation. DW23 W22D21D22D01 D02D04W29W30 C 3 5 B D 1 2 4 A N W EAST2#LayID NORTHZ-201 EAST2#LayID 27'-4" 74'-4 3/4" 22'-4 1/4"7'-9 1/2"15'-5"12'-11" 43'-3"41'-3""8'-1 1/2"12'-8 1/4"2'-7"4 1/2"8'-2 1/2"4'-6 1/2"3 1/2"3'-4 1/2"4 1/2"2'-10 1/2"2'-2"4'-1 1/2"8'8'-2 1/2" 1A 4.0 2A 4.0 AA 4.1 #DrgID#LayID CALDERASPAS MARTINIQUE HOT TUBWITH SAFETY COVER; CEC COMPLIANT;47 SF EXEMPT FROM RREMP NEW PARTIAL WALLS TO HIDEHOT TUB CUT BACK WALL;INSTALL RAIL WOOD PANELEDWALL, PROVIDETECTUS HINGESWOOD PANELEDWALL, PROVIDETECTUS HINGES NEW STRUCTURALBEAM ABOVE VERIFY NEWSTRUCTURALCOLUMNS, TYP WOOD BURNINGFIREPLACE TO REMAIN ENCLOSE CARPORTTO CREATEGARAGE LAUNDRY POWDER DRESSER PA CUBBIESBOOTDRYERCLOSETW/BENCHBELOW SKIS LINEN Detail and dimensionthe guard at the hottub. Guard mustextend a minimum of18" above the top ofthe hot tub edgeunless the edge is 18"or greater, in whichcase the guard mustbe 36" measured fromthe top of the hot tub.Per City Policy. CC/ KRA RESPONSES TO COMMENTS ARE IN GREEN, BELOW SEE REVISED A 0.3 FIRE AREA WITH EAVES, ETC. EXCLUDED SEE DETAIL 7/A 5.0 FOR UTILITY ROOM WALL ASSEMBLY SEE DETAIL 6/A 5.0 FOR WALL ASSEMBLY AT NEW STRAIGHTENED WALL(S) SEE DETAIL 4/A 5.0 FOR HOT TUB RAILING 10/19/2018 Page: A 1.4 PLAN-PROPOSED File Name: plans.pdf Subject: PlanCheck Author: nickt Color: If any walls that are shared with the other unit are to be disturbed, provide a listed 1 hour fire and STC 45 rated assembly per 2015 IRC R302.3 and appendix K. Page: A 1.4 PLAN-PROPOSED File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Mechanicals show the garage being heated. Provide a door to complete the thermal envelope. Also update the elevation view. Page: A 5.0 DETAILS File Name: plans.pdf Subject: PlanCheck Author: nickt Color: REScheck calls for R-56 insulation in the new roof. Revise to match. Page: A 5.1 DETAILS File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Detail the existing hearth extension condition. If it is altered beyond refacing the veneer, it and the fireplace must be made to be supported by non-combustible construction. (2015 IRC R1001.9) Page: M-2 BASEMENT LEVEL HVAC PLANS File Name: plans.pdf Subject: Mech for existing but total gut Author: nickt Color: Show all new intake, exhaust, flue, and vent outlets with dimensions to openings and property lines. Scale: AS NOTED ISSUESCHEMATIC DESIGNPERMIT SETCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 816111" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK. A 1.4 4/1/2018 MAIN LEVELPLAN-PROPOSED DATE1/24/18 KIM RAYMOND ARCHI | 300 E. HYMAN AVENUE, | www.kimraymondarchit | 970-925-2252 4/2/18 D DOW N W20 W19W23W22D16 D17D21 D20 D18D22D01 D02D19D04W29W30 W27W28 W24W25W26 D06W12 C C 3 3 6 6 5 5 7 7 B B E E D D F F 1 1 2 2 4 4 A A N W EAST2#LayID EASTZ-202 SOUTHZ-201 NORTHZ-201 WESTZ-202 EAST2#LayID 11'-11 3 / 4 " 23'-6"22'-4 3/4" 41'-6 1/ 2 " 1'-10" 5'-1" 27'-4"17'-7 1/2"74'-4 3/4"22'-4 1/4"7'-9 1/2"15'-5"12'-11"15'-11" 43'-3" 41'-3"11'-11 3/4"5'-10 1/2"8'-1 1/2"12'-8 1/4"2'-7"4 1/2"8'-2 1/2"4'-6 1/2"3 1/2"3'-4 1/2"5'-4"4 1/2" 5'-7 1/2 " 3'-1/2" 2'-10 1/2"3 1/2" 5'-10"2'-2"4'-1 1/2"8'11'-11"8'-2 1/2" 5'-3" CA 4.1 CA 4.1 1A 4.0 1A 4.0 2A 4.0 2A 4.0 AA 4.1 AA 4.1 #DrgID#LayID INSTALL NEW RADIANTHEAT, TYP. SLOT DRAIN TOP OF ROOF BELOW CALDERASPAS MARTINIQUE HOT TUBWITH SAFETY COVER; CEC COMPLIANT;47 SF EXEMPT FROM RREMP NEW PARTIAL WALLS TO HIDEHOT TUB CUT BACK WALL;INSTALL RAIL WOOD PANELEDWALL, PROVIDETECTUS HINGESWOOD PANELEDWALL, PROVIDETECTUS HINGES NEW STRUCTURALBEAM ABOVE VERIFY NEWSTRUCTURALCOLUMNS, TYP WOOD BURNINGFIREPLACE TO REMAIN NEW SINGLE DOOR RECONFIGURE ENTRY STORAGE ENCLOSE CARPORTTO CREATEGARAGE LAUNDRY KITCHEN MASTER BEDROOM POWDER MASTERBATH W/C STEAMSHOWER BBQ DRESSER DESKPANTRY MASTERCLOSET CUBBIES BENCH OVENS BOOTDRYER CLOSETW/BENCHBELOW SKIS BENCH LINEN F SCALE: 1/4" = 1'-0"MAIN LEVEL PLAN If any walls that areshared with the otherunit are to bedisturbed, provide alisted 1 hour fire andSTC 45 ratedassembly per 2015IRC R302.3 andappendix K. D16D01D02D04W30 W12C 3 B E D F 1 2 4 EAST2#LayID EASTZ-202 SOUTHZ-20111'-11 3/4"23'-6" 27'-4"41'-3"11'-11 3/4"5'-10 1/2"8'-1 1/2"12'-8 1/4"2'-7"4'-6 1/2"3 1/2"3'-4 1/2"5'-4"4 1/2"11'-11"5'-3"CA 4.1 1A 4.0 AA 4.1 CUT BACK WALL;INSTALL RAIL WOOD PANELEDWALL, PROVIDETECTUS HINGES WOOD PANELEDWALL, PROVIDETECTUS HINGES NEW STRUCTURALBEAM ABOVE VERIFY NEWSTRUCTURALCOLUMNS, TYP WOOD BURNINGFIREPLACE TO REMAIN NEW SINGLE DOOR RECONFIGURE ENTRY STORAGE ENCLOSE CARPORTTO CREATEGARAGE CUBBIES BENCH BOOTDRYER CLOSETW/BENCHBELOW SKIS SCALE: 1/4" = 1'-0" MAIN LEVEL PLAN Mechanicals show thegarage being heated.Provide a door tocomplete the thermalenvelope. Also updatethe elevation view.REMODELLANE, UNIT 1O 81611ALL DESIGNS, IDEAS ARRANGEMENTSAND PLANS INDICATED BY THESEDRAWINGS AND SPECIFICATIONS ARETHE PROPERTY AND COPYRIGHT OF KIMRAYMOND ARCHITECTS, INC. ANDSHALL NEITHER BE USED ON ANY OTHERWORK NOR BE USED BY ANY OTHERPERSON FOR ANY USE WHATSOEVERWITHOUT WRITTEN PERMISSION.WRITTEN DIMENSIONS SHALL TAKEPRECEDENCE OVER SCALEDDIMENSIONS AND SHALL BE VERIFIED ATTHE SITE. ANY DIMENSIONALDISCREPANCY SHALL BE BROUGHT TOTHE ATTENTION OF THE ARCHITECTPRIOR TO COMMENCEMENT OF WORK.KIM RAYMOND ARCHITECTS, INC.| 300 E. HYMAN AVENUE, SUITE 100 || www.kimraymondarchitects.com || 970-925-2252 | FINISH, N D NG RE: FLOOR PLAN1/8"2x FRAMING WITHSOUND BATT INSULATION NOTE:EXISTING 2x FRAMING TO REMAINIF NO DEMOLITION REQUIRED,RE: FLOOR PLANS GWB "J" METAL CORNER STRUCTURE - SEE SHEET S2.2 3/4" CDX PLY RIGID INSULATION,TAPERED TPO OR SIMILAR 1/2" DENSDECK NEW SPRAY FOAM INSULATION (7"=R-49) NEW GWB INTERIOR FINISH INTERIOR EXTERIORSLOPERE: ROOF PLAN 03''6''9''SCALE: 3" = 1'-0"10 NEW CLASS A ROOF REScheck calls forR-56 insulation in the new roof.Revise to match. Scale: AS NOTED ISSUE SCHEMATIC DESIGN PERMIT SETCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 816111" ACTUALIF THE ABOVE DIMENSION DOESNOT MEASURE ONE INCH (1")EXACTLY, THIS DRAWING WILLHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES. A 5.1 4/2/2018 FIREPLACEDETAILS DATE 1/24/18 4/2/18 4"1'-11"T.O. LOWER LEVEL F.F. LIVING ROOM FIREPLACE SECTION EL. + RE: FLOOR PLAN EXISTING CMU TO REMAIN EXISTING WOOD BURNING FIREPLACETO REMAIN ADD STEEL FRAME GLASS DOORSON FIREPLACE STONE HEARTH REMOVE EXISTING STONE VENEER ABOVE TOEXPOSE EXISTING FLUE PIPE; WRAP WITHDECORATIVE STEEL NEW METAL CAP AND FLASHING T.O. LOWER LEVEL F.F. EL. + RE: FLOOR PLAN REMOVE EXISTING STONE VENEER ABOVEXPOSE EXISTING FLUE PIPE; WRAP WITDECORATIVE STEEL NEW GWB WALL NEW STEEL FRAME GLASS DOORS NEW STONE SURROUND AND HEARTH EXISTING WOOD BURNING FIREPLACEBEYOND TO REMAIN NEW RAILING, STAIR BEYOND NEW SHELVING FOR WOOD STORAGE 0 6'' 1'2'SCALE: 1" = 1'-0"3 FIREPLACE0 6'' 1'2' 0 6'' 1'2' Detail the existinghearth extensioncondition. If it isaltered beyondrefacing the veneer, itand the fireplace mustbe made to besupported bynon-combustibleconstruction. (2015IRC R1001.9) Show all new intake, exhaust, flue, and vent outlets with dimensions to openings andproperty lines. SEE DETAIL 3/A 5.0 FOR ASSEMBLY OF STC AND ONE HOUR FIRE RATED PARTITION WALL SEE MAIN LEVEL PLAN A 1.4, ELEVATION A 3.1 AND DOOR SCHEDULE A 6.0 FOR THE NEW GARAGE PERSON DOOR SEE REVISED DETAIL 10/A 5.0 SEE ADDITIONAL INFORMATION ADDED TO A 5.1 SEE MECHANICAL ROUTING, TERMINATIONS AND DISTANCES TO PROPERTY LINE ON A 2.0 AND A 2.1, (REFLECTED CEILING PLANS) AND A 3.1 AND A3.2 (ELEVATIONS) 10/19/2018 Page: S3.1 STRUCTURAL DETAILS File Name: plans.pdf Subject: PlanCheck Author: nickt Color: Provide a special inspection agreement form signed by the special inspector, fabricator, owner, and contractor. Page: 1 File Name: REScheck.950 Cemetery Lane.2018.04.pdf Subject: PlanCheck Author: nickt Color: For this R-15 slab insulation to count, it must be on the side of the slab, starting at the top of the slab, then extend down for a depth of 4' or to the inside or outside of the slab for 4'. Provide details showing the proposed condition and have the REScheck match it. REScheck.950 Cemetery Lane.2018.04.pdf (2) Page: 2 File Name: REScheck.950 Cemetery Lane.2018.04.pdf Subject: PlanCheck Author: nickt Color: Revise Rescheck to match the fenestration specs from Windsor. For example, there are doors with U-factors of 0.35, 0.34, and 0.29. Provide a specialinspection agreementform signed by thespecial inspector,fabricator, owner, andcontractor. For this R-15 slab insulation tocount, it must be on the side ofthe slab, starting at the top of theslab, then extend down for adepth of 4' or to the inside oroutside of the slab for 4'. Providedetails showing the proposedcondition and have the REScheckmatch it. Revise Rescheck to match the fenestration specs from Windsor. For example, there are doors with U-factors of 0.35, 0.34, and 0.29. SEE SIGNED SPECIAL INSPECTION FORM 10/19/2018