HomeMy WebLinkAboutFile Documents.287 McSkimming Rd.0044.2018 (7).ARBKREScheck Software Version 4.6.4
Compliance Certificate
Project McSkimming Residence
Energy Code:2015 IECC
Location:Aspen, Colorado
Construction Type:Single-family
Project Type:New Construction
Conditioned Floor Area:5,788 ft2
Glazing Area 27%
Climate Zone:7 (9922 HDD)
Permit Date:
Construction Site:
287 McSkimming Road
Aspen, CO 81611
Owner/Agent:
Good Property Co.
1065B Cemetery Lane
Aspen, CO 81611
212-993-6442
josh@goodpropertycompany.com
Designer/Contractor:
Vivian Hsu
Henry Built Corporation
4632 Ohio S. Drive
Seattle, WA 98132
646-798-3866
vivian@henrybuilt.com
Permit Number:
Compliance: Passes using UA trade-off
8.7% Better Than Code Maximum UA:1167 Your UA:1066
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Compliance:
Envelope Assemblies
Assembly
Gross Area
or
Perimeter
Cavity
R-Value
Cont.
R-Value U-Factor UA
Upper Level Roof: Flat Ceiling or Scissor Truss 492 50.2 0.0 0.026 12
Skylight: Wood Frame:Double Pane with Low-E 29 0.400 12
Main Level Roof: Flat Ceiling or Scissor Truss 2,461 50.2 0.0 0.026 64
Living Room Roof: Flat Ceiling or Scissor Truss 998 48.8 0.0 0.026 26
Basement Roof: Flat Ceiling or Scissor Truss 108 26.0 0.0 0.039 2
Skylight: Wood Frame:Double Pane with Low-E 47 0.490 23
North Walls (Above Grade): Wood Frame, 16" o.c.1,664 26.0 5.0 0.039 30
North Windows: Wood Frame:Double Pane with Low-E 478 0.310 148
North Glass Doors: Glass 412 0.330 136
East Walls (Above Grade): Wood Frame, 16" o.c.1,278 26.0 5.0 0.039 42
East Windows: Wood Frame:Double Pane with Low-E 145 0.350 51
East Glass Doors: Glass 65 0.320 21
South Walls (Above Grade): Wood Frame, 16" o.c.1,690 26.0 5.0 0.039 62
South Windows: Wood Frame:Double Pane with Low-E 35 0.280 10
South Solid Doors: Solid 64 0.280 18
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 1 of10
02/08/18Report date:
2/8/18
02/26/201802/26/2018
Assembly
Gross Area
or
Perimeter
Cavity
R-Value
Cont.
R-Value U-Factor UA
West Walls (Above Grade): Wood Frame, 16" o.c.1,220 26.0 5.0 0.039 28
West Windows: Wood Frame:Double Pane with Low-E 209 0.280 59
West Glass Doors: Glass 149 0.330 49
West Solid Doors: Solid 144 0.300 43
Basement Walls (Above Grade): Solid Concrete or Masonry:Exterior Insulation 125 13.0 10.0 0.045 0
Basement Windows: Wood Frame:Double Pane with Low-E 120 0.320 38
Basement Walls (Below Grade): Solid Concrete or Masonry
Wall height: 12.0'
Depth below grade: 12.0'
Insulation depth: 10.5'
3,401 13.0 10.0 0.034 116
Basement Walls (Adjacent To Crawler): Solid Concrete or Masonry
Wall height: 12.0'
Depth below grade: 8.0'
Insulation depth: 12.0'
574 13.0 10.0 0.038 22
Garage Slab: Slab-On-Grade:Heated
Insulation depth: 6.0'
57 10.0 0.684 39
Master Floor (Above Crawler): All-Wood Joist/Truss:Over Unconditioned Space 467 38.0 0.0 0.026 12
Entry Floor (Above Crawler): All-Wood Joist/Truss:Over Unconditioned Space 113 38.0 0.0 0.026 3
Name - Title Signature Date
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.4 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Project Notes:
Calcs By: Joey Brenner - Rader Engineering (970)-845-7910
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 2 of10
02/08/18Report date:
Joey Brenner - Engineer 2/8/18
02/26/201802/26/2018
Inspection Checklist
Requirements: 0.0% were addressed directly in the REScheck software
REScheck Software Version 4.6.4
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Pre-Inspection/Plan Review Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
103.1,
103.2
[PR1]1
Construction drawings and
documentation demonstrate
energy code compliance for the
building envelope. Thermal
envelope represented on
construction documents.
Complies
Does Not
Not Observable
Not Applicable
103.1,
103.2,
403.7
[PR3]1
Construction drawings and
documentation demonstrate
energy code compliance for
lighting and mechanical systems.
Systems serving multiple
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
Complies
Does Not
Not Observable
Not Applicable
302.1,
403.7
[PR2]2
Heating and cooling equipment is
sized per ACCA Manual S based
on loads calculated per ACCA
Manual J or other methods
approved by the code official.
Heating:
Btu/hr_____
Cooling:
Btu/hr_____
Heating:
Btu/hr_____
Cooling:
Btu/hr_____
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 3 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Foundation Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.1.2
[FO1]1
Slab edge insulation R-value.R-_____
Unheated
Heated
R-_____
Unheated
Heated
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.2
[FO3]1
Slab edge insulation
depth/length.
_____ ft _____ ft Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.1
[FO4]1
Conditioned basement wall
insulation R-value. Where interior
insulation is used, verification
may need to occur during
Insulation Inspection. Not
required in warm-humid locations
in Climate Zone 3.
R-_____
R-_____
R-_____
R-_____
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2
[FO5]1
Conditioned basement wall
insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
402.2.9
[FO6]1
Conditioned basement wall
insulation depth of burial or
distance from top of wall.
_____ ft _____ ft Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2.1
[FO11]2
A protective covering is installed
to protect exposed exterior
insulation and extends a
minimum of 6 in. below grade.
Complies
Does Not
Not Observable
Not Applicable
403.9
[FO12]2
Snow- and ice-melting system
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 4 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Framing / Rough-In Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.1.1,
402.3.4
[FR1]1
Door U-factor.U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.1,
402.3.1,
402.3.3,
402.3.6,
402.5
[FR2]1
Glazing U-factor (area-weighted
average).
U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.1.3
[FR4]1
U-factors of fenestration products
are determined in accordance
with the NFRC test procedure or
taken from the default table.
Complies
Does Not
Not Observable
Not Applicable
402.1.1,
402.3.3,
402.3.6,
402.5
[FR5]1
Skylight U-factor.U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.1
[FR10]1
Mass wall exterior insulation R-
value. If more than ½ of the
insulation is on the wall interior,
the interior insulation
requirement applies and
verification may need to occur
during Insulation Inspection.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2
[FR11]1
Mass wall exterior insulation
installed per manufacturer’s
instructions.
Complies
Does Not
Not Observable
Not Applicable
402.4.1.1
[FR23]1
Air barrier and thermal barrier
installed per manufacturer’s
instructions.
Complies
Does Not
Not Observable
Not Applicable
402.4.3
[FR20]1
Fenestration that is not site built
is listed and labeled as meeting
AAMA /WDMA/CSA 101/I.S.2/A440
or has infiltration rates per NFRC
400 that do not exceed code
limits.
Complies
Does Not
Not Observable
Not Applicable
402.4.5
[FR16]2
IC-rated recessed lighting fixtures
sealed at housing/interior finish
and labeled to indicate ≤2.0 cfm
leakage at 75 Pa.
Complies
Does Not
Not Observable
Not Applicable
403.2.1
[FR12]1
Supply and return ducts in attics
insulated >= R-8 where duct is
>= 3 inches in diameter and >=
R-6 where < 3 inches. Supply and
return ducts in other portions of
the building insulated >= R-6 for
diameter >= 3 inches and R-4.2
for < 3 inches in diameter.
Complies
Does Not
Not Observable
Not Applicable
403.3.3.5
[FR15]3
Building cavities are not used as
ducts or plenums.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 5 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Framing / Rough-In Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
403.4
[FR17]2
HVAC piping conveying fluids
above 105 ºF or chilled fluids
below 55 ºF are insulated to ≥R-
3.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
403.4.1
[FR24]1
Protection of insulation on HVAC
piping.
Complies
Does Not
Not Observable
Not Applicable
403.5.3
[FR18]2
Hot water pipes are insulated to
≥R-3.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
403.6
[FR19]2
Automatic or gravity dampers are
installed on all outdoor air
intakes and exhausts.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 6 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Insulation Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
303.1
[IN13]2
All installed insulation is labeled
or the installed R-values
provided.
Complies
Does Not
Not Observable
Not Applicable
402.1.1,
402.2.6
[IN1]1
Floor insulation R-value.R-_____
Wood
Steel
R-_____
Wood
Steel
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2,
402.2.7
[IN2]1
Floor insulation installed per
manufacturer’s instructions and
in substantial contact with the
underside of the subfloor, or floor
framing cavity insulation is in
contact with the top side of
sheathing, or continuous
insulation is installed on the
underside of floor framing and
extends from the bottom to the
top of all perimeter floor framing
members.
Complies
Does Not
Not Observable
Not Applicable
402.1.1,
402.2.5,
402.2.6
[IN3]1
Wall insulation R-value. If this is a
mass wall with at least ½ of the
wall insulation on the wall
exterior, the exterior insulation
requirement applies (FR10).
R-_____
Wood
Mass
Steel
R-_____
Wood
Mass
Steel
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2
[IN4]1
Wall insulation is installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 7 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Final Inspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.1.1,
402.2.1,
402.2.2,
402.2.6
[FI1]1
Ceiling insulation R-value.R-_____
Wood
Steel
R-_____
Wood
Steel
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.1.1.1,
303.2
[FI2]1
Ceiling insulation installed per
manufacturer’s instructions.
Blown insulation marked every
300 ft².
Complies
Does Not
Not Observable
Not Applicable
402.2.3
[FI22]2
Vented attics with air permeable
insulation include baffle adjacent
to soffit and eave vents that
extends over insulation.
Complies
Does Not
Not Observable
Not Applicable
402.2.4
[FI3]1
Attic access hatch and door
insulation ≥R-value of the
adjacent assembly.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
402.4.1.2
[FI17]1
Blower door test @ 50 Pa. <=5
ach in Climate Zones 1-2, and
<=3 ach in Climate Zones 3-8.
ACH 50 =_____ACH 50 =_____Complies
Does Not
Not Observable
Not Applicable
403.2.3
[FI4]1
Duct tightness test result of <=4
cfm/100 ft2 across the system or
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough-in
tests, verification may need to
occur during Framing Inspection.
_____ cfm/100
ft2
_____ cfm/100
ft2
Complies
Does Not
Not Observable
Not Applicable
403.3.2
[FI27]1
Ducts are pressure tested to
determine air leakage with
either: Rough-in test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the system including
the manufacturer’s air handler
enclosure if installed at time of
test. Postconstruction test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer’s air
handler enclosure.
_____ cfm/100
ft2
_____ cfm/100
ft2
Complies
Does Not
Not Observable
Not Applicable
403.3.2.1
[FI24]1
Air handler leakage designated
by manufacturer at <=2% of
design air flow.
Complies
Does Not
Not Observable
Not Applicable
403.1.1
[FI9]2
Programmable thermostats
installed for control of primary
heating and cooling systems and
initially set by manufacturer to
code specifications.
Complies
Does Not
Not Observable
Not Applicable
403.1.2
[FI10]2
Heat pump thermostat installed
on heat pumps.
Complies
Does Not
Not Observable
Not Applicable
403.5.1
[FI11]2
Circulating service hot water
systems have automatic or
accessible manual controls.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 8 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Final Inspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
403.6.1
[FI25]2
All mechanical ventilation system
fans not part of tested and listed
HVAC equipment meet efficacy
and air flow limits.
Complies
Does Not
Not Observable
Not Applicable
403.2
[FI26]2
Hot water boilers supplying heat
through one- or two-pipe heating
systems have outdoor setback
control to lower boiler water
temperature based on outdoor
temperature.
Complies
Does Not
Not Observable
Not Applicable
403.5.1.1
[FI28]2
Heated water circulation systems
have a circulation pump. The
system return pipe is a dedicated
return pipe or a cold water supply
pipe. Gravity and thermos-
syphon circulation systems are
not present. Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
Complies
Does Not
Not Observable
Not Applicable
403.5.1.2
[FI29]2
Electric heat trace systems
comply with IEEE 515.1 or UL
515. Controls automatically
adjust the energy input to the
heat tracing to maintain the
desired water temperature in the
piping.
Complies
Does Not
Not Observable
Not Applicable
403.5.2
[FI30]2
Water distribution systems that
have recirculation pumps that
pump water from a heated water
supply pipe back to the heated
water source through a cold
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 104ºF.
Complies
Does Not
Not Observable
Not Applicable
403.5.4
[FI31]2
Drain water heat recovery units
tested in accordance with CSA
B55.1. Potable water-side
pressure loss of drain water heat
recovery units < 3 psi for
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units < 2 psi for
individual units connected to
three or more showers.
Complies
Does Not
Not Observable
Not Applicable
404.1
[FI6]1
75% of lamps in permanent
fixtures or 75% of permanent
fixtures have high efficacy lamps.
Does not apply to low-voltage
lighting.
Complies
Does Not
Not Observable
Not Applicable
404.1.1
[FI23]3
Fuel gas lighting systems have
no continuous pilot light.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 9 of10
02/08/18Report date:
02/26/201802/26/2018
Section
#
& Req.ID
Final Inspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
401.3
[FI7]2
Compliance certificate posted.Complies
Does Not
Not Observable
Not Applicable
303.3
[FI18]3
Manufacturer manuals for
mechanical and water heating
systems have been provided.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: McSkimming Residence
Data filename: J:\Jobs\2017 - Jobs\17009.00 - 287 McSkimming
Res\Mechanical\Calculations\Rescheck\17009-Rescheck-020818.rck
Page 10 of 10
02/08/18Report date:
02/26/201802/26/2018
2015 IECC Energy
Efficiency Certificate
Insulation Rating R-Value
31.00Above-Grade Wall
23.00Below-Grade Wall
38.00Floor
50.25Ceiling / Roof
_______Ductwork (unconditioned spaces):
Glass & Door Rating SHGCU-Factor
0.31Window
0.33Door
0.49Skylight
Heating & Cooling Equipment Efficiency
_______Heating System:_________________________
_______Cooling System:_________________________
_______Water Heater:___________________________
Name:Date:
Comments
02/26/201802/26/2018