HomeMy WebLinkAboutFile Documents.315 Dean St.0099.2018 (7).ACBK20A
20A
6A
6A
20A
20A
Relay
Relay
VA (wattage) rating of TracKeeper™ breakers determines wattage calculation
Track length determines wattage calculation
Branch Circuit
Breaker Panel
TracKeeper™
Current Limiting Panel
LiteKeeper™
Relay Panel
(Optional–replaces contactor & timeclock)
Branch Circuit
Breaker Panel
With the TracKeeper™
Without the TracKeeper™
2 runs of single
circuit track totaling 100 ft.
100 ft. x 45 watts/ft = 4500W
(per Title 24 requirements)
6A @ 120V=720W
6A @ 120V=720W
1440W Total
• Helps meet Energy Code Regulations
• Simplifies Load Calculations
• Reduce Installation Costs
TracKeeper™ Current Limiting Panel
The TracKeeper™ current limiting panel helps meet
energy code requirements by using the volt-ampere
rating of the breaker as opposed to calculated values
based on watts per linear foot of track.
Wattage Limits on Track Lighting
California Title 24 ........45-watts per linear foot
ASHRAE 90.1* .............30-watts per linear foot
City of Seattle .............70-watts per linear foot
*Basis for many municipal energy codes across the United States
TracKeeper™ Current Limiting Panel
Amperes V/A (120V)V/AC (277V)
0.5 60 138.5
1 120 277
2 240 554
3 360 831
4 480 1,108
5 600 1,385
6 720 1,662
7 840 1,939
8 960 2,216
10 1,200 2,770
Amperes V/A (120V)V/AC (277V)
13 1,560 3,601
15 1,800 4,155
16 1,920 4,432
20 2,400 5,540
25 3,000 6,925
30 3,600 8,310
32 3,840 8,864
40 4,800 11,080
50 6,000 13,850
60 7,200 16,620
Ordering/Specifying
Specify enclosure size, mounting option, voltage and number of
circuit breakers desired. Breakers must be installed in groups
of two.
Example: TK16-120-14-F specifies a 16 circuit flush mount enclosure
with (14) 120V circuit breakers.
Greengate Catalog #Voltage # of Breakers Mounting Option
TK16 120 or 277 2 to 16*
(Increments of 2)
S = Surface
F = Flush
TK32 120 or 277 18 to 32*
(Increments of 2)
S = Surface
F = Flush
Breaker Options
N.A. Headquarters
203 Cooper Circle
Peachtree City, GA 30269
P: 800-553-3879
F: 800-954-7016
Service and Support Center
6 Green Tree Drive
South Burlington, VT 05403
P: 800-553-3879
F: 800-954-7016
International Headquarters
26 Greenhill Crescent
Watford Business Park
Watford, Herts, WD18 8XG. UK
P: +44 (0)1923 495495
F: +44 (0)1923 228796
www.coopercontrol.com
e: ControlsSales@cooperindustries.com
* Prices listed below.