HomeMy WebLinkAboutFile Documents.320 W Bleeker St.0188.2017 (14).ARBKBuildingComment3
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 12_RREMP.pdf
Please provide a spec on the
proposed boiler to document this
efficiency.
12_RREMP.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 13_Line Grade Verification Form.pdf
Please identify the specific sheet
where this is shown as I did not
see it. Plat B14 P23 gives an
example of how this should be
shown where they've tied the
NW corner of the building to the
property corner with two
separate dimensions to different
points.
13_Line Grade Verification Form.pdf (2)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 13_Line Grade Verification Form.pdf
Submit a line grade verification
form without your signature here,
this is for the surveyor's
signature once part B has been
completed.
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: 17_Signed Special Inspection and Testing
Agreement.pdf
You are missing signatures on
this for the special inspection of
structural welding and high
strength bolting.
17_Signed Special Inspection and Testing Agreement.pdf (1)
Subject: PlanCheck
Page Label: A-002
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Please verify that no
snowmelted areas will be using
a pervious paver system. If any
are then a insulation detail
showing the hole pattern that
provides 30% open space and
an area weighted average R10
insulation value will be required.
2017 0803_320 W Bleeker Permit Combinded Set.pdf (33)
Please provide a spec on the
proposed boiler to document
this efficiency.
Please identify the specific
sheet where this is shown as I
did not see it. Plat B14 P23
gives an example of how this
should be shown where they've
tied the NW corner of the
building to the property corner
with two separate dimensions to
different points.
Submit a line grade verification form without
your signature here, this is for the surveyor's
signature once part B has been completed.
You are missing signatures on this for the special
inspection of structural welding and high strength bolting.
A
5
26.56 SF
OWMELT B
SNOWMELT AREA:
SNOWMELT A: 38 S
SNOWMELT A2: 55 S
SNOWMELT B: 227 S
Please verify that no
snowmelted areas will
be using a pervious
paver system. If any
are then a insulation
detail showing the hole
pattern that provides
30% open space and
an area weighted
average R10 insulation
value will be required.
1.
2.
3.
4.
5.
2/27/2018
Subject: PlanCheck
Page Label: A-002
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Provide documentation that this
spa is certified by the CEC or
AAPSP-14 as well as
documentation that the spa
cover meets the safety
requirements of ASTM F-1346.
Subject: PlanCheck
Page Label: A-004
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Provide a cutsheet on the
proposed outdoor fire pit that
shows gas appliance is intended
for out door use.
Subject: PlanCheck
Page Label: A-004
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Will this water feature be
heated? If so it needs to be
included as pool on your REMP
worksheet.
Subject: PlanCheck
Page Label: A-101
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Note that a separate elevator
permit from NWCCOG is
required for elevator work.
Subject: PlanCheck
Page Label: A-104
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Snow stops required here as this
would shed onto the open trellis
below.
5
7'-4"53.78 SF
SELF-CONTAINED SPA
7'-4"
Provide documentation
that this spa is certified
by the CEC or
AAPSP-14 as well as
documentation that the
spa cover meets the
safety requirements of
ASTM F-1346.
HJ
22'-6"5'-1/4" / 12"WP TERRACE
6" STEP TO GRADE MAX 6" STEP TO GRADE MAX
790
790TERR
NEW ASPEN NEW ASPEN
Provide a cutsheet on the proposed outdoor
fire pit that shows gas appliance is intended
for out door use.
H A-202
1
G EF100'-0"
30" HIGH WATER FEATURE PR
6" STEP TO GRADE MAX 6"E
Will this water feature
be heated? If so it
needs to be included
as pool on your REMP
worksheet.
CONC
ELEV
106
A-801
5
BUILT9'-0 1/2"4"10"10"2"4'-1"ELEVEQUIP
Note that a separate
elevator permit from
NWCCOG is required
for elevator work.
HEATED DOWNSPOUT GUTTER &POUT
GUTTER
.
SCUPPER5'-7"FLAT
ROOF
.
OVERFLOWSCUPPER
R 7 1/4"
.
A-50312
Snow stops required
here as this would
shed onto the open
trellis below.
6.
7.
8.
9.
10.
2/27/2018
Subject: PlanCheck
Page Label: A-104
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Show all venting on the roof
plan, only fireplace venting is
currently shown but there should
also be venting for plumbing and
for the radon mitigation system.
Subject: PlanCheck
Page Label: A-104
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Identify the slope of this portion
of roof. Snow stops are required
where the pitched roof is above
emergency escape window wells
or other potentially occupied
spaces.
Subject: PlanCheck
Page Label: A-107
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Dimension the size of the attic
access panel to show it meets
the requirements of R807.1.
Subject: PlanCheck
Page Label: A-201
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
These three windows are
required to be safety glazed per
R308.4.3, please note this on
the window schedule. The two
operable windows also require
fall protection devices per
R312.2.1, as GG6 is an egress
window it must have a opening
control device that complies with
ASTM F 2090. Note this
requirement on your window
schedule.
Subject: PlanCheck
Page Label: A-201
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
B1 is also required to be safety
glazed per R308.4.3, please
revise on the schedule.
22'-6"5'-6"
1/4" PER 1'-0" (TYP)
DECKBELO
SCUPPER
TRELLIS
Show all venting on the roof plan, only fireplace venting
is currently shown but there should also be venting for
plumbing and for the radon mitigation system.
2
A-302
1
A-302
12" / 12"12" / 12"
HEATED GUTTER& DOWNSPOUT
.
1/4" PER 1'-0"
...OVERFLOWSCUPPER
FLATROOF
OVERFLOWSCUPPER
DECKBELOW
Identify the slope of
this portion of roof.
Snow stops are
required where the
pitched roof is above
emergency escape
window wells or other
potentially occupied
spaces.
D
1
A-302
SWOOPED CEILING
REMOVABLE ACCESS PANEL
Dimension the size of
the attic access panel
to show it meets the
requirements of
R807.1.
T.O.F.F. (UPPER)111'-5 3/4"
T.O. F.F. (MAIN)100'-0"
4
1
A-301 5
HEDGE
FENCE
GG4
EL. 110'-0"T.PL (SITTING)
ASPHALT SHINGLEROOF
STANDING SEAMMETAL ROOF
107AJ8
J5
7'-4"3
8'-10"2'-6"3'-6"PROPERTY LINESIDE SETBACK5'-0"24'-10 11/16"1/3 POINT
22'-8 13/16"TOP OF FLAT ROOF
J9
J7J6
GG6GG5R 5'-2"EGRESS WINDOW
8'-9"X6 X6
G
A
G A L A M B O SARCHITECTS, INC.
314 D AABCASPEN, CO 81611(970) 429-1286
These three windows are required
to be safety glazed per R308.4.3,please note this on the window
schedule. The two operable
windows also require fallprotection devices per R312.2.1,
as GG6 is an egress window it
must have a opening controldevice that complies with ASTMF 2090. Note this requirement on
your window schedule.
2
A-302
HGF
B1102A5'-9"10'-0"8'-0"1J8
B2B3
8'-10"EXISTING GRADEFINISH GRADE CORNER BOARD (TYP)
OPEN
J61'-6"10'-0"A-6021
X5 X6
B1 is also required to
be safety glazed per
R308.4.3, please
revise on the
schedule.
11.
12.
13.
14.
15.
2/27/2018
Subject: PlanCheck
Page Label: A-201
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Note that grates over emergency
escape window wells shall be
releasable/removable from the
inside without use of key, tool, or
special knowledge and that the
opening force required shall not
exceed 15lbs - R310.4 and COA
8.16.020 (z)
Subject: PlanCheck
Page Label: A-202
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Note that grates over emergency
escape window wells shall be
releasable/removable from the
inside without use of key, tool, or
special knowledge and that the
opening force required shall not
exceed 15lbs - R310.4 and COA
8.16.020 (z)
Subject: PlanCheck
Page Label: A-301
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
This foundation is not shown in
the structural foundation plan.
Revise on plan or the other for
consistency.
Subject: PlanCheck
Page Label: A-401
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Your handrail height dimensions
are not aligned correctly with the
handrail, please revise.
Subject: PlanCheck
Page Label: A-401
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
This handrail's perimeter is
greater than 6.25" and therefor
should comply as type II handrail
per R311.7.8.3(2), please revise.
H1H2H3J1J4
7'-5"AREA WELL (TYP)
A4 A3 A2
GRATE OVER WELL
CORNER BOARD
J2J3
8'-0"6"6" MAX
EGRESS WINDOW (TYP)6'-10 1/8"1'-Note that grates over
emergency escape
window wells shall be
releasable/removable
from the inside without
use of key, tool, or
special knowledge and
that the opening force
required shall not
exceed 15lbs - R310.4
and COA 8.16.020 (z)
AREA WELL (TYP)1
GRATE OVER WELL Note that grates over
emergency escape
window wells shall be
releasable/removable
from the inside without
use of key, tool, or
special knowledge and
that the opening force
required shall not
exceed 15lbs - R310.4
and COA 8.16.020 (z)
T.O. F.F. (MAIN)100'-0"
EXISTING ALLEY6'-0OT TUB
This foundation is not
shown in the structural
foundation plan.
Revise on plan or the
other for consistency.
9
"3'-0"3'-0"Your handrail height dimensions
are not aligned correctly with the
handrail, please revise.1 1/2"2"G
A
This handrail's
perimeter is greater
than 6.25" and
therefor should comply
as type II handrail per
R311.7.8.3(2), please
revise.
16.
17.
18.
19.
20.
2/27/2018
Subject: PlanCheck
Page Label: A-401
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
This handrail is not shown as
being continuous for the full flight
of stairs - R311.7.8.2
Subject: PlanCheck
Page Label: A-401
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
What was meant to be noted
here?
Subject: PlanCheck
Page Label: A-401
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Space between a handrail and
an adjacent wall shall not be less
than 1.5" per R311.7.8.2, please
revise.
Subject: PlanCheck
Page Label: A-402
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Per R1001.9 the hearth and
extension must be supported by
non combustible construction,
and the hearth must be a
minimum of 2" thick. Structural
detail 16/S301 shows 1.5"
gypcrete topping as the hearth
extension directly on top of the
floor sheathing. Provide greater
detail here to show compliance
and revise the associated
structural details to match.
Subject: PlanCheck
Page Label: A-501
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Provide more information on the
radon mitigation system to show
full compliance with Appendix F
of the IRC - location of
termination, routing of vent pipe,
location of potential future fan
installation if needed, etc.
A-401
7
64
16T @ 11" = 14'-8"3'-5 1/4"3'-7 1/2"1H4'-5 1/2"U31 3/4"UP17 R @ 7.5"UP
11"
ALE 3/8" = 1'-0"
TAIR - LOWER LEVEL This handrail is not
shown as being
continuous for the full
flight of stairs -
R311.7.8.2
?
?
?
?
2
What was meant to be
noted here?
1 1/2" DIM HANDRA
A-401
7
64
1 1/4" DIM HANDRAIL1"R LEVEL
Space between a
handrail and an
adjacent wall shall not
be less than 1.5" per
R311.7.8.2, please
revise.
DN
2" COFR
2
CO2'-5 1/8"4 7/8"5 1/2"PO4'-0"8"4'-0"4"
4"4"8"1'-0"FURRING
3/4"6"
CONC SLABRE: STRUCT
4" FIREBRICK
4" FIREBRICK
WOODLAND DIRECTFLAMING EMBERANSI VENTEDBURNING W/LOGST.B.D.
STEEL ANGLESUPPORT
STONE MANTEL
8" CMU GROUTSOLID AT CHAMBER
STONE HEARTHFLUSH W/ WOODFLOOR
MIN
CMU GROUT SOLID
(MAIN)100'-0"
R
SCALE 1/2" = 1'-0"2 SECTION THRU LVG FIREPLACE
Per R1001.9 the hearth and extension must besupported by non combustible construction, and the
hearth must be a minimum of 2" thick. Structural detail
16/S301 shows 1.5" gypcrete topping as the hearth
extension directly on top of the floor sheathing.
Provide greater detail here to show compliance andrevise the associated structural details to match.
FOUNDATION DRAIN AROUNDPERIMETER PER SOILS REPORT
RADON MITIGATION
ROUGH-IN, 4" PERFORATEDPIPE AROUND PERIMETERTIE TO PIPE UP THRU ROOF A
FOU
3
SCALE 1 1/2" = 1'-0"1 TYPICAL FOUNDATION @ LOWER LEVEL
Provide more information on the radon
mitigation system to show full compliance
with Appendix F of the IRC - location of
termination, routing of vent pipe, location of
potential future fan installation if needed, etc.
21.
22.
23.
24.
25.
2/27/2018
Subject: PlanCheck
Page Label: A-501
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
It appears that you are
proposing to use drywall and
framing to accomplish the air
sealing requirements of IECC
402.4, please provide additional
details showing how this air
barrier will be continuous in all
typical locations/transitions to
other materials. See the
attached samples of details for
air sealing and include other
relevant details to show how this
continuous air barrier will be
accomplished, it shows various
detailing for multiple types of
compliant air barrier methods.
Drywall does not need to be the
method of air sealing, you can
select/combine methods as
needed. The plans need to
clearly depict how the air barrier
is to be constructed so that the
contractor has clear direction as
to how to accomplish this now
that visual inspection of the air
barrier continuity is required.
Subject: PlanCheck
Page Label: A-503
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Provide documentation that your
asphalt shingle and copper
standing seam roof assemblies
are class A (specs, UL listings,
ESR reports, etc) similar to what
you have provided for the flat
roof assembly.
Subject: PlanCheck
Page Label: A-601
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Include interior doors in the door
schedule as well. Note any
applicable safety glazing and be
sure to show that the door
connecting garage and the
residence meets the
requirements of R302.5.1.
Subject: PlanCheck
Page Label: A-602
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Specify this slope as the max
allowed is 2% per R311.3
5/8" GWB
CAULK/SEAL GWBTO PLATE (TYP)
SILL PLATE INSTALLED
OVER SILL GASKET (TYP)
R-49 FOAMINSULATION
GARAGE
It appears that you are proposing to use
drywall and framing to accomplish the air
sealing requirements of IECC 402.4, please
provide additional details showing how this air
barrier will be continuous in all typical
locations/transitions to other materials. See
the attached samples of details for air sealing
and include other relevant details to show
how this continuous air barrier will be
accomplished, it shows various detailing for
multiple types of compliant air barrier
methods. Drywall does not need to be the
method of air sealing, you can
select/combine methods as needed. The
plans need to clearly depict how the air
barrier is to be constructed so that the
contractor has clear direction as to how to
accomplish this now that visual inspection of
the air barrier continuity is required.
SCALE 1 1/2" = 1'-0"
9 ROOF OVERHANG AT ENTRY
Provide documentation that your asphalt shingle
and copper standing seam roof assemblies are
class A (specs, UL listings, ESR reports, etc)
similar to what you have provided for the flat roof
assembly.
1. REFER TO BUILDING ELEVATIONS FTYPE, HEIGHT AND OPERATION.2. WINDOW WIDTH AND HEIGHT ARE UVERIFY ALL ROUGH OPENINGS IN F3. PROVIDE SCREENS AT ALL OPERAB4. CONTRACTOR TO PROVIDE WOODTO MATCH DETAILS AND EXISTING 5. FIXED WINDOW SASH DIMENSIONSAND AWNING SASH.6. WINDOWS TO BE ARCADIA OR SIM7. COLOR TO BE DETERMINED.PROVIDE SAMPLE FOR APPROVAL 8. PROVIDE NESTING CRANKS (TYP).9. PROVIDE SAFETY GLAZING IN ALL D10. PROVIDE SAFETY GLAZING IN WIND11. GLAZING TO HAVE MAX U-VALUE O12. PROVIDE SHOP DRAWINGS FOR APPRIOR TO ORDERING.13. PATIO DOORS TO BE PROVIDED BCOLOR TO MATCH WDWS.
GENERAL NOTESDOOR SCHEDULE
Mark Door Glass Type Details Hardware Comments Door AreaWidth Height Thickness Head Detail Jamb Detail Sill Detail
102A 3'-0" 8'-0" 2 1/4" SAFETY 6/A-602 5/A-602 4/A-602 LOCKSET 20.44 SF104A 5'-9" 8'-10" 1 3/4" SAFETY 6/A-602 5/A-602 7/A-602 LOCKSET 46.04 SF107A 6'-3" 7'-4" 1 3/4" SAFETY 6/A-602 5/A-602 7/A-602 LOCKSET 41.42 SF110A 3'-0" 8'-0" 2 1/4" SAFETY 6/A-602 5/A-602 7/A-602 LOCKSET 20.44 SF114A 3'-0" 8'-0" 2 1/4"6/A-602 5/A-602 7/A-602 LOCKSET 20.44 SF114B 9'-0" 8'-6" 1 1/2"6/A-602 5/A-602 7/A-602 LOCKSET OVERHEAD DOOR, PROVIDE OPERATOR 70.78 SF209A 2'-8" 8'-0" 1 3/4" SAFETY 6/A-602 5/A-602 7/A-602 LOCKSET 17.89 SF
Include interior doorsin the door scheduleas well. Note anyapplicable safetyglazing and be sure to
show that the doorconnecting garageand the residencemeets therequirements ofR302.5.1.
SLOPE
PORCH
T.O.F.F. (ENTRY)100'-7"
WOOD OR METAL
THRESHOLD
METAL FLASHING
OVER RIGID INSULATION
TILE FLOOR (VERIFY)4 3/4"1"Specify this slope as
the max allowed is 2%
per R311.3
26.
27.
28.
29.
2/27/2018
Subject: PlanCheck
Page Label: A-701
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
This space also requires a bath
fan for the shower as the fan for
the toilet is in a separate
compartment.
Subject: PlanCheck
Page Label: A-703
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
This space also requires a bath
fan for the shower as the fan for
the toilet is in a separate
compartment.
Subject: PlanCheck
Page Label: M000
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Per the ResCheck windows and
glass doors have a U value of
.32, please revise.
Subject: PlanCheck
Page Label: M100
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Provide specs and an installation
manual for this dryer booster
fan.
Subject: PlanCheck
Page Label: M201
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
This layout is different that what
is shown on the floor plans,
revise one or the other for
consistancy.
C1
C7 EQEQTV
BDRM 1
009
GUEST BDRM
002
BATH 1
010
F
TV
A2
A2
A2A2
A2A2
A2
EQ EQ
A2
A2A2
X1X1
LIGHTEDL3
D1
D1
A3 A3
F
F1 D7A3
A2
A2
A2
2'-0"
C/S C/S
Y Y Y
A2
EQ EQ
A2
3'-0"3'-0"3'-0"3'-0"3'-0"3'-0"
D1
This space alsorequires a bath fan for
the shower as the fan
for the toilet is in a
separate
compartment.
2
A-302
C/S
A1
W/PGFI
X10
C22
A1
A4
A4
A3
A3GFIGFI
D23
C23 A2 A2 A1
A1
LIGHTEDMIRROR
A2 A2
3'-0"3'-0"
A1
A1
A1 D23D23D23
ALCOVE
206
CPT
M
M BATH
202
L3
LIGH
L3
C/S
Y
Y
Y
Y
F
A1
This space also
requires a bath fan for
the shower as the fan
for the toilet is in a
separate
compartment.
Per the ResCheck
windows and glass
doors have a U value
of .32, please revise.
7/17/1
Provide specs and aninstallation manual forthis dryer booster fan.
This layout is differentthat what is shown onthe floor plans, reviseone or the other forconsistancy.
30.
31.
32.
33.
34.
2/27/2018
Subject: PlanCheck
Page Label: M202
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Identify the CFM of the range
exhaust, if it is greater than 400
CFM then make-up air will be
required IMC 505.2.
Subject: PlanCheck
Page Label: S301
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
The hearth extension is required
to be a minimum of 2" thick, and
supported by noncombustible
construction with no combustible
material against the underside of
the hearth or extension per
R1001.9. Please revise this
detail to show compliance.
Subject: PlanCheck
Page Label: Z-004
Author: justinh
File Name: 2017 0803_320 W Bleeker Permit Combinded
Set.pdf
Provide an area sheet that
shows gross floor area and fire
area as required by our IRC
building submittal guide. Ensure
that you are measuring gross
area as defined in the 2015 IBC
(area with the inside perimeter of
the exterior walls, without
deduction for stairways, interior
walls, or other features and any
areas under the horizontal
projection of the roof or floor
above).
Subject: PlanCheck
Page Label: 2
Author: justinh
File Name: 6_Asbestos Test-320 W Bleeker St, Aspen,
CO-03-2017.pdf
A clean air report from the
asbestos abatement will be
required prior to approval and
issuance as well as a copy of the
state license to demolish the
structure.
6_Asbestos Test-320 W Bleeker St, Aspen, CO-03-2017.pdf (1)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: 9_17024-Permit Rescheck Report-071717.pdf
Fill out this portion of the
ResCheck fully
9_17024-Permit Rescheck Report-071717.pdf (1)
Identify the CFM of the
range exhaust, if it is
greater than 400 CFM
then make-up air will
be required IMC
505.2.
10
S301
UPPER LEVEL FLAT LO
SCAL
FLOOR SHEATHING
4 1/2" SLAB WITH W.W.F
11
S301
TYPICAL BEAM CONN
SCAL
BEARING WALL ABOVEWHERE EXISTS RE: PLAN
3/8" X WIDTH OF BEAM BENT
END PLATE HANGER WITH 5"WIDE TOP FLANGE BEARINGON LVL BEAM AND (4)-3/4"THRU BOLTS
LVL BEAM RE: PLAN
12
S301
TYPICAL BEAM CONN
SCAL
FRAMING ABOVE WHERE
EXISTS RE: PLAN
AISC SINGLE SHEARCONNECTION WITH 3/4" BOLTSTYPICAL U.N.O. (3- BOLTSEACH LEG FOR W12X BEAMS;
2-BOLTS EACH LEG FOR W10XAND W8X BEAMS)
15
S301
STEEL CONNECTION AT DECK
SCALE: 3/4" = 1'-0"
BOLTS AT 2'-0" STAGGERED
16
S301
SECTION AT FIREPLACE
SCALE: 3/4" = 1'-0"
2X FURRING
FLOOR SHEATHING
STEEL BEAMS RE: PLANWITH SINGLE SHEAR
CONNECTIONS PERSECTION 12/S301
1 1/2" GYPCRETETOPPING
6" SLAB UNDER CMUWITH #5 AT 1'-0" EACHWAY AT MID-HEIGHT
SOLID WEB PACK WITH 1/2"
BOLTS THRU WEB AT 2'-0"STAGGERED FOR JOISTSATTACHMENT WITH IUSHANGERS (NOT SHOWN)
CMU FIREPLACE RE: ARCH
1/2" X 3 1/2'" HEADEDANCHOR STUDS AT SLAB
The hearth extension is required to be aminimum of 2" thick, and supported by
noncombustible construction with no
combustible material against the underside ofthe hearth or extension per R1001.9. Please
revise this detail to show compliance.
EXEMPTIONS
FLOOR AREA SUM
GARAGE EXEMPTIO
DECK EXEMPTION
SUBGRADE LEVEL
MAIN LEVEL
GARAGE
UPPER LEVEL
DECK
TOTAL
FRONT PORCHES
PATIOS
NOTES
EXISTING HOUSE I-100% R-100% W
EXISTING SITE RET
Provide an area sheet that shows gross floor area and fire area
as required by our IRC building submittal guide. Ensure that you
are measuring gross area as defined in the 2015 IBC (area with
the inside perimeter of the exterior walls, without deduction for
stairways, interior walls, or other features and any areas under
the horizontal projection of the roof or floor above).
A clean air report from
the asbestos
abatement will be
required prior toapproval and issuance
as well as a copy of
the state license todemolish the structure.
nc.
chitects.net
Designer/Contractor:
ur UA:938
ed on code trade-off rules.
7/17/17
Fill out this portion of
the ResCheck fully
35.
36.
37.
38.
39.