HomeMy WebLinkAboutFile Documents.320 W Bleeker St.0188.2017 (10).ARBK747 Sheridan Blvd, Unit 8B Lakewood, Colorado 80214 Phone: (303) 232-5145 Fax: (303) 232-1238 e-mail: henry@air-rightinc.com T.A.B. Report Project: 320 W. Bleeker Aspen, CO Prepared for: Rutgers Construction Report issue date: December 12, 2019 Air-Right, Inc. Project Number 19375 The data presented in this report is an exact record of system performance and was obtained in compliance with NEBB procedural standards. Any variance from the design requirements shall be documented in this report. The results shown and information presented in this report is certified to be accurate and complete to the extent possible by the equipment and procedures used to balance the project. The final air distribution system measurements are in compliance with NEBB Procedural Standards for testing, adjusting, and balancing of environmental systems, and the project specifications. Certified by: _________________________________ Date: December 12, 2019 The final Hydronic distributions system measurements are in compliance with NEBB procedural standards for testing, adjusting, and balancing of environmental systems, and the project specifications. Certified by: _________________________________ Date: December 12, 2019 Air-Right, Inc. warrants the air and hydronic system presented in this report is operating at the specified levels as shown in this report at and only at this time. Air-Right, Inc. makes no other warranties, stated or implied, concerning the continued performance, operation, or safety in the use of this equipment past this this time. NEBB Air and Hydronic Systems Certified Professional: Timothy A. Topping NEBB Number 2589 Certification Expiration/renewal date: 03/31/20 Test, Adjust, and Balance Report Air-Right, Inc. 747 Sheridan Blvd. Unit 8B, Lakewood, CO 80214, Phone: (303) 232 5145 Fax: (303) 232-1238 Table of Contents Cover page 1 NEBB TAB Certification 2 Table of Contents 3 Abbreviations 4 Furnace Report 5-8 Fan Coil Report 9-10 Supply Fan Report 11-12 ERV Report 13 Fan Unit Report 14-25 Pump Test Report 26-33 Drawings 34-36 PageDocument ABBREVIATIONS ACU Air Conditioning Unit AHU Air Handling Unit AMP(S)Amps ATMOS Atmosphere BAS Building Automation System CD Ceiling Diffuser CFM Cubic Feet per Minute CRAC Computer Room Air Conditioner CWP Chilled Water Pump DD Direct Drive DDB Dual Duct Box dP (DP)Differential Pressure EF Exhaust Fan EFF Efficiency EI Exhaust Inlet ERV Energy Recovery Vessel FCU Fan Coil Unit FFU Fan Filter Unit FL Amps Full Load Amperage FLR Floor Register FPM Feet per Minute FPVAV Fan Powered Variable Air Volume FR Frame FT. HD.Feet of Head FUR Furnace GPM Gallons per Minute HP Horse Power HRV Heat Recovery Vessel HWP Heating (Hot) Water Pump Hx (HX)Heat Exchanger Hz (HZ)Hertz MAU (MUA)Make-Up Air Unit Max Maximum Min Minimum NA Not Applicable NAC No Access NG None (Not) Given No Number OSA Outside Air PD Pressure Drop PDU Pool Dehumidification Unit PF Power Factor PH Phase PSI Pounds per Square Inch RF Return Fan RI Return Inlet RPM Revolutions per Minute RTU Roof Top Unit SF Service Factor SD Supply Diffuser SF Supply Fan SWR Side Wall Register TSTAT Thermostat VAV Variable Air Volume Volt Voltage VP Velocity Pressure Furnace/Fan Coil F-1 UNIT DATA Manufacturer Trane Design CFM 1375 CFM Model S9V2B060U4PSBBA Design OSA 124 CFM Serial Number 18471P8F3G Design ESP 0.7 in. H2O MOTOR DATA Manufacturer No Access S.F.1.0 Motor HP Not Given Frame Not Given RPM Variable Volts 120 Phase 1 Amps 15.0 DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Belt Size NA STARTER DATA Manufacturer Thermally Protected Range NA Model NA Set at (Amps)NA Amps Size NA Set at (Hz)NA Hz TEST DATA CFM 1334 CFM RPM Direct Drive RPM OSA 127 CFM Volts 121 Volts Return CFM 1207 CFM Amps 1.2 Amps TEST PRESSURE Filter In -0.11 in. H2O Fan In No Access in. H2O Filter Out No Access in. H2O Fan Out No Access in. H2O LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze F-1 2019-12-12 Cooling Coil In No Access in. H2O Heating Coil In No Access in. H2O Cooling Coil Out 0.18 in. H2O Heating Coil Out No Access in. H2O TEST PRESSURE NOTES: Motor Data Amps All data taken from unit tag. F-1 / Summary SUMMARY Name Type Size Design CFM Prelim CFM Final CFM % of Design Outlet-001 SG-1 6 x 6 50 42 48 96 Outlet-002 SG-1 6 x 6 50 57 51 102 Outlet-003 SG-1 12 4 150 143 152 101 Outlet-004 SG-1 6 x 6 20 36 22 110 Outlet-005 SG-1 6 x 6 40 35 43 108 Outlet-006 SG-1 12 x 4 150 141 148 99 Outlet-007 SG-1 12 x 4 75 92 73 97 Outlet-008 SG-1 18 x 4 300 255 278 93 Outlet-009 SG-1 12 x 4 100 82 97 97 Outlet-010 SG-1 6 x 6 50 41 47 94 Outlet-011 SG-1 6 x 6 20 17 22 110 Outlet-012 SG-1 24 x 4 250 193 233 93 Outlet-013 SG-1 6 x 6 30 46 33 110 Outlet-014 SG-1 12 x 4 90 71 87 97 Totals 1375 1251 1334 LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze F-1 2019-12-12 F-3 UNIT DATA Manufacturer Trane Design CFM 1375 CFM Model S9V2B060U4PSBBA Design OSA 0 CFM Serial Number 18471RJ53G Design ESP 0.7 in. H2O MOTOR DATA Manufacturer No Access S.F.1.0 Motor HP Not Given Frame Not Given RPM Variable Volts 120 Phase 1 Amps 15.0 DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Belt Size NA STARTER DATA Manufacturer Thermally Protected Range NA Model NA Set at (Amps)NA Amps Size NA Set at (Hz)NA Hz TEST DATA CFM 1417 CFM RPM Direct Drive RPM OSA 0 CFM Volts 122 Volts Return CFM 1417 CFM Amps 1.3 Amps TEST PRESSURE Filter In -0.21 in. H2O Fan In No Access in. H2O Filter Out No Access in. H2O Fan Out No Access in. H2O Cooling Coil In No Access in. H2O Heating Coil In No Access in. H2O Cooling Coil Out 0.33 in. H2O Heating Coil Out No Access in. H2O LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze F-3 2019-12-12 NOTES: Test Data CFM No manual volume dampers installed on system, unable to proportion, unit set for total. F-3 / Summary SUMMARY Name Type Size Design CFM Prelim CFM Final CFM % of Design Outlet-001 SG-2 12 x 4 50 76 76 152 Outlet-002 SG-2 12 x 4 100 148 148 148 Outlet-003 SG-2 30 x 4 375 308 308 82 Outlet-004 SG-2 24 x 3 150 132 132 88 Outlet-005 SG-2 24 x 3 150 139 139 93 Outlet-006 SG-4 36 x 8 550 614 614 112 Totals 1375 1417 1417 LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze F-3 2019-12-12 FC-2 UNIT DATA Manufacturer Enviro-Tec Design CFM 2500 CFM Model V-190409-02 Design OSA 1600 CFM Serial Number 6EGM 000586 Design ESP Not Given in. H2O MOTOR DATA Manufacturer Marathon S.F.1.15 Motor HP 1 Frame 56 RPM 1725 Volts 115/208-230 Phase 1 Amps 14.7/7.2-7.4 DRIVE DATA Motor Drive 1VL44 Motor Bore 5/8” Fan Drive AK74 H Fan Bore H-1 No. Belts 1 Belt Size A-50 STARTER DATA Manufacturer Thermally Protected Range NA Model NA Set at (Amps)NA Amps Size NA Set at (Hz)NA Hz TEST DATA CFM 2559 CFM RPM 855 RPM OSA 1687 CFM Volts 237 Volts Return CFM 872 CFM Amps 7.0 Amps TEST PRESSURE Filter In -0.31 in. H2O Fan In -0.87 in. H2O Filter Out No Access in. H2O Fan Out 0.20 in. H2O Cooling Coil In Not Applicable in. H2O Heating Coil In No Access in. H2O Cooling Coil Out Not Applicable in. H2O Heating Coil Out -0.87 in. H2O LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze FC-2 2019-12-12 FC-2 / Summary SUMMARY Name Type Size Design CFM Prelim CFM Final CFM % of Design Outlet-001 SG-3 12 x 4 100 115 109 109 Outlet-002 SG-2 12 x 4 50 78 62 124 Outlet-003 SG-2 36 x 4 400 363 407 102 Outlet-004 SG-3 30 x 4 300 375 318 106 Outlet-005 SG-3 30 x 4 300 333 293 98 Outlet-006 SG-3 12 x 4 150 208 145 97 Outlet-007 SG-3 12 x 4 150 134 157 105 Outlet-008 SG-2 12 x 4 150 146 153 102 Outlet-009 SG-2 12 x 4 150 139 147 98 Outlet-010 SG-2 12 x 4 150 127 163 109 Outlet-011 SG-3 12 x 4 150 176 142 95 Outlet-012 SG-3 36 x 4 450 422 463 103 Totals 2500 2616 2559 NOTES: Summary Outlet-002 / Final CFM No manual volume damper installed. Outlet-008 / Final CFM No manual volume damper installed. LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze FC-2 2019-12-12 Supply Fan SF-1 UNIT DATA Manufacturer Fantech Design CFM 198 Model FR 150 Design Static 0.4 Serial Number 1004300545 MOTOR DATA Manufacturer Not Given Frame Not Given Motor HP 68.3 W Volts 120 RPM Not Given Amps 0.59 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 304 Amps T1 0.55 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.04 Volts T1-T3 NA Fan Out 0.12 LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze SF-1 2019-12-12 NOTES: UNIT DATA Design CFM Fan labeled 280 CFM @ 0.2” WC. TEST DATA CFM Single speed Direct Drive fan. LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze SF-1 2019-12-12 Design Actual %Design Actual % ERV ERV-1 UNIT DATA Manufacturer RenewAire Design Supply Static 0.40 in. H2O Model Number EV130 Design Exhaust Static 0.40 in. H2O Serial Number B197586R FAN MOTOR Manufacturer Fasco Phase 1 Frame Not Given Service Factor 1.00 Horsepower 0.1 Rated Volts 115 RPM Not Given FL Amps 1.19 DRIVE DATA Motor Drive Direct Drive Fan Bore NA Motor Bore NA Number of Belts NA Fan Drive NA Belt Size NA STARTER Manufacturer Thermally Protected Rated Amps NA Size NA Test at NA Hz TEST DATA Supply Air 124 127 102 Exhaust Air 129 129 100 Actual RPM Direct Drive Amps T1 0.9 Volts T1-T2 121 Amps T2 NA Volts T2-T3 NA Amps T3 NA Volts T1-T3 NA LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze ERV-1 2019-12-12 Exhaust Fans EF-1A UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0510VSS1 Design Static 0.25 Serial Number 806 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.39 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 78 Amps T1 0.27 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1A 2019-12-12 NOTES:TEST DATA CFM Fan set at lowest available speed. EF-1B UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 73 Amps T1 0.12 RPM Direct Drive Amps T2 NA VoltsT1-T2 120 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1B 2019-12-12 NOTES: TEST DATA CFM Fan set at lowest available speed. EF-1C UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 67 Amps T1 0.11 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1C 2019-12-12 EF-1D UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 74 Amps T1 0.11 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1D 2019-12-12 NOTES: TEST DATA CFM Fan set at lowest available speed. EF-1E UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 66 Amps T1 0.12 RPM Direct Drive Amps T2 NA VoltsT1-T2 119 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1E 2019-12-12 EF-1F UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 74 Amps T1 0.11 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1F 2019-12-12 NOTES: TEST DATA CFM Fan set at lowest available speed. EF-1G UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 84 Amps T1 0.13 RPM Direct Drive Amps T2 NA VoltsT1-T2 119 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1G 2019-12-12 NOTES: TEST DATA CFM Fan set at lowest available speed. EF-1H UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 67 Amps T1 0.1 RPM Direct Drive Amps T2 NA VoltsT1-T2 119 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1H 2019-12-12 EF-1I UNIT DATA Manufacturer Panasonic Design CFM 62 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 76 Amps T1 0.12 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-1I 2019-12-12 NOTES: TEST DATA CFM Fan set at lowest available speed. EF-2 UNIT DATA Manufacturer Panasonic Design CFM 72 Model FV-0511VQ1 Design Static 0.25 Serial Number 80424 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.17 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 79 Amps T1 0.13 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.01 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-2 2019-12-12 NOTES: TEST DATA CFM Fan set at lowest available speed. EF-3 UNIT DATA Manufacturer Panasonic Design CFM 257 Model FV-30VQ3 Design Static 0.25 Serial Number 806 MOTOR DATA Manufacturer Panasonic Frame Not Given Motor HP Not Given Volts 120 RPM Not Given Amps 0.61 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 309 Amps T1 0.5 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.02 Volts T1-T3 NA Fan Out No Access LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze EF-3 2019-12-12 DBF-1 UNIT DATA Manufacturer Fantech Design CFM 86 Model DEDPV-705 Design Static 1.0 Serial Number 1004251325 MOTOR DATA Manufacturer Not Given Frame Not Given Motor HP 69 W Volts 120 RPM Not Given Amps 0.6 Phase 1 Power Factor Not Given S.F.1.0 Nom. Efficiency Not Given DRIVE DATA Motor Drive Direct Drive Motor Bore NA Fan Drive NA Fan Bore NA No. Belts NA Size NA STARTER DATA Manufacturer Thermally Protected Set at (Amps)NA Range NA VFD set at NA Hz TEST DATA CFM 92 Amps T1 0.6 RPM Direct Drive Amps T2 NA VoltsT1-T2 121 Amps T3 NA Volts T2-T3 NA Fan In -0.02 Volts T1-T3 NA Fan Out 0.01 LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze DBF-1 2019-12-12 NOTES: TEST DATA CFM Single speed Direct Drive fan. Pump Test Report P-1 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 27 Model Number UPS26-150F Rating FT. HD.15 Serial Number 95906630 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 335 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 3.1 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 120 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 3.0 Amps dP PSI No Ports PSI Final DP Setpoint Medium PSI LOCATION:PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-1 2019-12-12 P-2 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 14 Model Number UPS26-99FC Rating FT. HD.14 Serial Number 52722512P1 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 179 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 1.5 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 121 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 1.5 Amps dP PSI No Ports PSI Final DP Setpoint Medium PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-2 2019-12-12 P-3 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 14 Model Number UPS26-99FC Rating FT. HD.14 Serial Number 52722512P1 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 179 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 1.5 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 120 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 1.5 Amps dP PSI No Ports PSI Final DP Setpoint Medium PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-3 2019-12-12 P-4 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 9 Model Number UPS15-58FC Rating FT. HD.9 Serial Number 59896341P1 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 87 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 0.75 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 120 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 0.72 Amps dP PSI No Ports PSI Final DP Setpoint High PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-4 2019-12-12 P-5 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 2 Model Number UPS15-58FC Rating FT. HD.15 Serial Number 59896341P1 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 80 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 0.66 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 119 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 0.63 Amps dP PSI No Ports PSI Final DP Setpoint Medium PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-5 2019-12-12 P-6 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 6 Model Number UPS15-58FC Rating FT. HD.13 Serial Number 59896341P1 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 87 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 0.75 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 120 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 0.73 Amps dP PSI No Ports PSI Final DP Setpoint High PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-6 2019-12-12 P-7 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 7 Model Number UPS26-99FC Rating FT. HD.25 Serial Number 52722512P1 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 197 W Type Not Given RPM 3 Speed Volts 115 Phase 1 Amps 1.8 Frame Not Given STARTER Manufacturer Thermally Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 119 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 1.7 Amps dP PSI No Ports PSI Final DP Setpoint High PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze P-7 2019-12-12 RP-1 PUMP IDENTIFICATION Manufacturer Grundfos Rating GPM 2 Model Number 10-16APM BU/LC Rating FT. HD.1.5 Serial Number 98420224 MOTOR Manufacturer Grundfos S.F.1.0 Motor HP 6 W Type Not Given RPM Single Speed Volts 115/230 Phase 1 Amps 0.07 Frame Not Given STARTER Manufacturer Electronically Protected Size NA Model NA Setting NA MEASURED Pump Off Pressure No Ports PSI Valve Open DP No Ports PSI Valve Shut DP No Ports PSI Valve Open SP No Ports PSI Valve Shut SP No Ports PSI Valve Open Diff Valve Shut Diff FINAL Discharged Pressure No Ports PSI dP Ft. Hd No Ports ft Discharged Pressure Ft. Hd.No Ports PSI GPM NAC GPM Suction Pressure No Ports PSI Volts 119 Volts suction Pressuer Ft. Hd.No Ports PSI Amps 0.07 Amps dP PSI No Ports PSI Final DP Setpoint Not Applicable PSI LOCATION: PROJECT NUMBER: 19375 CONTACT: Jason Gerze RP-1 2019-12-12 GODED NOTES - (D INSTALL (2)12/4 T -I XFER GRILLES, ONE HIGH AND ONE LOW. CONNECT WITH 12/4 (UNLINED) DUCTwow- O INSTALL DBF-I ON 4'4 DRYER EA DUCT. 3O 12/5 (UNLINED) WALL STACK ® ROUTE 16/5 (INLNED, EA) DUCT ON TOP OF 12/12 FG -211 SA DUCT AND UP TO MAIN LEVEL FIREPLACE CHASE. J O5 4" CPUC OR PP RUE AND 4" PVC CA PIPE FOR @_I, TER'11NATE ABOVE ROOF WITH CONCENTRIC VENT KIT. © 28/6 Rs -2 RA CONNECT TO (2) 12/5 (UNLINED) WALL STACKS AND ROUTE TO 18/143 RA DUCT. O 18/4 SG -1 300. 10"4 RUN -OUT. ® 36/5 11 RA 0 INSTALL SECONDARY LINT TRAP. PROVIDE ACCESS. 10 30/4 TG -1 XFER (TYP OF 2) FOR LAUNDRY MAKE-UP AIR II ROUTE DUCT UP IN STRUCTURE. @ 16/16 (FC -2a i3 S"4 OED FOR MECH ROOM SUPPLY. COVER WITH WIRE MESH. I4 84 OED FOR MECO ROOM RELIEF. COVER WITH WIRE MESH. 1 15 3" CPUC OR PP FLUE AND 3" PVC CA PIPE FOR E_L TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. 16 3" CPVC OR PP FLUE AND 3" PVC CA PIPE FOR E_3. TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. IT 1 4 ERV -1 EA DUCT. C IS 16/5 (UNLINED, EA). TERMINATE WITH ISM LV -I ABOVE ROOF ON SIDEWALL OF CHIMNEY. 19 INSTALL ON GARAGE WALL ABOVE FLAT DINING ROOM ROOF. ® 12"4 BYPASS DUCT AND DAMPER 21 6/6 SG -1 30 Q INSTALL HUMIDIFIER N VERTICAL SECTION OF DUCT PER MANUFACTURERS, INSTRUCTIONS. Q RE: M203/A FOR CONTINUATION. I ® ACCESS PANEL ON SLOPED CEILING. ©5 20/20 (FC -2 RA) ® 12/4 SG -1 15 I' Q (2) 12/4 TG -1 >T -ER GRILLES. CONNECT TO 24/4 TG -I XFER GRILLE WITH 12/4 (UNLINED) DUCTWORK ® ARCWITECT TO COORDINATE INSTALLATION OF CONDENSINCs UNITS TO ENSURE NOISE LEVEL AT PROPERTY LINE MEETS CITY - - - Or ASPEN'S REQUIREMENTS. ACOUSTICAL MATERIAL MAY NEED - TO BE INSTALLED TO REDUCE CONDENSING UNIT NOISE LEVELS. _ - 10/8 (E-ig SA) �- I a--------- I - - - - I LOWER HALL 016 L11 LAUNDRY RM OU I �3��E.CONNECT-) 1w-2 I 2OK RA). CONNECT T OF F_ rI&A6 (F_I o a -I F_I IBSA4COK Or E GT TO o� F:LOOfR O SGA 50 00 JM BERM 3 0220 —12/4 SSC. -150 4 /6 W&--140 IBDRM 2 1 di 4"0 EA UP (T? 1 I ©I 6/6 W' --L 20 2 (51,N -OUT) It 41 -I- 1 L 5 14 - F y la S v_ 3 (5� - 14 22 IA.de © Q 15 20/20 (FC -2 J 6F-1 1e1� y i 13 H- I I I I I I I I I I I \ 1 18"4 OA NUG) 1 / I I I C12/4 SG -I 100_ 6'4 RUN -OUT) y 4"m {BATH EA) ( OF 3) 1 BDRM 11 009 II SG -I 50 (5"4 =-OUT) I I 0 10 S6 L 12/8 (F -Ib) 10/8 (UNLINED) UP (FO -2b SA) REC RM oot S I II Il UP T_____________________ A I u i 0 S R to A 1 A I 1 A ml 1 EUEST BDIRM 002 I I N - II N I vs cai � 12/12 (FC -2a)`- I I a � I � I 61_14T Bl T I I I I I I 1 1 I I I I I I I I I I I I - T•4 (TYP OF 4) 44 (BATH EA) (TYP OF 2) City of A•pw Stamp N ow =INA in 0 r �I (V 1 LUin Y LALQ � H 0 O � u l7 Q Q 'Q �W LL Uj Z �Z 01Xr W to Q � ll.l C �o^ tM tM tM � PE Stamp Rp00 t)(; P, Gje�S/1 /1asss� ;w 5 2 rvs S �F SS1UNAL O 1�1 W � W W • h+H O M o M laeued For No. Date Comment 1 4/16/11 SO SET 2 523A I ELEC, COORD. 3 6/30/17 COORDINATION 4 IAIAT PERMIT 5 2/5AS PEFT'tiT COMMENTS 6 5/10/18 CONSTRUCTION LOWER LEVEL MECHANICAL PLAN NORTH Protect No. Scale: 11024.00 1/4" IN P-0" Drawn By: Checked By: JCB JDR M201 FIREP T 18/12 LYJ. EA BACK TERRACE 118 4"0 (TYP OF �Bo `IUD RM tt0 12/4 SG -3 100-1 20/10 (FC -2 RA) I I I PROPOSED SOFFIT I I I I I I lR I I RZ-11 RADIANT ZONE I I I I I I I I BACKYARD 114 n II II u QIH QGI QFI Q Q I � I I I I I I I I I I I I I I I I I I I I I x-12/4 5G-2 5111 L - 1 J, II II I - - I I I )WD I t0s I T 4/4- 1150(2) n I I DINING TERRACE / vs / I I I I I !UNLINED) 1w z FAMILY RM 07 30/4 SG -3 300— � O 30/4 SG -3 300f I II I I I I I I I I I I I I I I I 1 I I I I FRONTITERRACE I 117 I I I I I I I I I I I I I I I I I I I I I _0 I _ I I I I I City of Aspen Stamp MHZkn N � N t LA 11-1 w 2 ZZ [ (� A0so. V � z� q Ic YU V \ ul ul Z Z (9 x Lu Q Ili 3 ems V4 Z ul r PE Stamp 'Poo POa %l �y`iF' m U /7`5/10/18 n: o ;w 50002 IL SSrOMhI. EN w U O �m O Qz a/ v E � 3 W Q� W LL �j w a Lu m w • W N � w Q Nr a w= PQ J o kyLu M N w M l,-tu :1 0 >� Q jL I Q Q Issued For W No. Date Comment r U 1 4/26/1, SD SET Q 2 5123/1, JELEC, COORD. 3 6/30/11 COORDINATION za U 4 ln,n, PER11r 5 2/5/18 PEIRMIT COMMENTS 3 6 5/10/18 CONSTRUCTION Q 6 J 3 MAIN LEVEL MEG 4ANICAL PLAN W u =wz r mLU - Z Zu! Z�q Q 0 - NORTH NORTH w m w .111 Project No. Scale; G Z Q 11024.00 1/4" 1'-0" o m Drawn By: Checked By: 8 N JCE5 JDR w z = Qw� M202 W Q �o CODED NOTES: Q INSTALL (2) 12/4 TG- I XFER GRILLES, ONE HIGH AND ONE LOW. CONNECT WITH 12/4 (UNLINED) DUCTWORK O INSTALL DBF-I ON 4"0 DRYER EA DUCT. O3 12/5 (UNLINED) WALL STACK ® ROUTE 16/5 (UNLINED, EA) DUCT ON TOP OF 12/12 FC -21:1 SA DUCT AND UP TO MAIN LEVEL FIREPLACE CHASE. O5 4" CPUC OR PP FLUE AND 4" PVC CA PIPE FOR 5--1 TERMINATE J ABOVE ROOF WITH CONCENTRIC VENT KIT. © 28/6 Fia-2 RA. CONNECT TO (2) 12/5 (UNLINED) WALL STACKS AND ROUTE TO 18/14 FF=3 RA DUCT. O 18/4 53-1 300. 104 RUN -OUT. ® 36/5 RG -2 RA. O9 10 INSTALL SECONDARY LINT TRAP. PROVIDE ACCESS. 30/4 TG -I XFER (TYP OF 2) FOR LAUNDRY MAKE-UP AIR II ROUTE DUCT UP IN STRUCTURE. @ 16/I6 (FC -2a). 13 8110 OED FOR MECH ROOM SUPPLY. COVER WITH WIRE MESH. 14 8"0 OED FOR MECW ROOM RELIEF. COVER WITH WIRE MESH. 15 3" CPVC OR PP FLUE AND 3" PVC CA PIPE FOR F -L TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. 16 3" CPUC OR PP FLUE AND 3" PVC CA PIPE FOR F-3. TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. 1, -T"* ERV -1 EA DUCT. IS 16/5 (UNLINED, EA). TERMINATE WITH ISA2 LV=1 ABOVE ROOF ON 5IDEWALL OF CHIMNEY. 19 INSTALL ON GARAGE WALL ABOVE FLAT DINW. ROOM ROOF. ® 124, BYPASS DUCT AND DAMPER 21 6/6 6G-1 30 22 INSTALL HUMIDIFIER IN VERTICAL SECTION OF DUCT PER MANUFACTURER'5 INSTRUCTIONS. �3 RE: M203/A FOR CONTINUATIOK ® ACCESS PANEL ON SLOPED CEILING. ©5 20/10 (FC -2 RA) © 12/4 $G -I 15 / 2l (2) 12/4 TTG -1 XGRILLES. RILLES. CONNECT TO 24/4 TG -I XFER GRILLE WITH 12/4 (UNLINED) DUCTWORK ® ARCHITECT TO COORDINATE INSTALLATION OF CONDENSING UNITS TO ENSURE NOISE LEVEL AT PROPERTY LINE MEETS CITY OF ASPEN'S REQUIREMENTS. ACOUSTICAL MATERIAL MAY NEED TO BE INSTALLED TO REDUCE CONDENSING UNIT NOISE LEVELS. FIREP T 18/12 LYJ. EA BACK TERRACE 118 4"0 (TYP OF �Bo `IUD RM tt0 12/4 SG -3 100-1 20/10 (FC -2 RA) I I I PROPOSED SOFFIT I I I I I I lR I I RZ-11 RADIANT ZONE I I I I I I I I BACKYARD 114 n II II u QIH QGI QFI Q Q I � I I I I I I I I I I I I I I I I I I I I I x-12/4 5G-2 5111 L - 1 J, II II I - - I I I )WD I t0s I T 4/4- 1150(2) n I I DINING TERRACE / vs / I I I I I !UNLINED) 1w z FAMILY RM 07 30/4 SG -3 300— � O 30/4 SG -3 300f I II I I I I I I I I I I I I I I I 1 I I I I FRONTITERRACE I 117 I I I I I I I I I I I I I I I I I I I I I _0 I _ I I I I I City of Aspen Stamp MHZkn N � N t LA 11-1 w 2 ZZ [ (� A0so. V � z� q Ic YU V \ ul ul Z Z (9 x Lu Q Ili 3 ems V4 Z ul r PE Stamp 'Poo POa %l �y`iF' m U /7`5/10/18 n: o ;w 50002 IL SSrOMhI. EN w U O �m O Qz a/ v E � 3 W Q� W LL �j w a Lu m w • W N � w Q Nr a w= PQ J o kyLu M N w M l,-tu :1 0 >� Q jL I Q Q Issued For W No. Date Comment r U 1 4/26/1, SD SET Q 2 5123/1, JELEC, COORD. 3 6/30/11 COORDINATION za U 4 ln,n, PER11r 5 2/5/18 PEIRMIT COMMENTS 3 6 5/10/18 CONSTRUCTION Q 6 J 3 MAIN LEVEL MEG 4ANICAL PLAN W u =wz r mLU - Z Zu! Z�q Q 0 - NORTH NORTH w m w .111 Project No. Scale; G Z Q 11024.00 1/4" 1'-0" o m Drawn By: Checked By: 8 N JCE5 JDR w z = Qw� M202 W Q �o CODED NOTES_ OI INSTALL (2) 12/4 TG -I XFER GRILLES, ONE HIGH AND ONE LOW. CONNECT WITH 12/4 (UNLINED) DUCTWORK O2 INSTALL p -5F -i ON 4"0 DRYER EA DUCT. O3 12/5 (UNLINED) WALL STACK ® ROUTE 16/5 (UNLINED, EA) DUCT ON TOP OF 12/12 FC -210 SA DUCT AND UP TO MAIN LEVEL FIREPLACE CHASE. \ O 4" CPUC OR PP FLUE AND 4" PVC CA PIPE FOR 51 TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. © 28/6 RG -2 RA CONNECT TO (2) 12/5 (UNLINED) WALL STACKS AND ROUTE TO 18/14 FF=3 RA DUCT. O 18/4 SG -I 300. 10"0 RUN -OUT. ® 36/5 R3-2 RA 9O INSTALL SECONDARY LINT TRAP. PROVIDE ACCESS. 10 30/4 TG -1 >T -ER (TYP OF 2) FOR LAUNDRY MAKE-UP AIR I II ROUTE DUCT UP IN STRUCTURE. 12 16/16 (FC=2a). 13 8"0 OED FOR MECH ROOM SUPPLY. COVER WITH WIRE MESH. 14 8"0 OED FOR MECH ROOM RELIEF. COVER WITH WIRE MESH, 15 3" CPVC OR PP FLUE AND 3" PVC CA PIPE FOR E-1. TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. I6 3" CPVC OR PP FLUE AND 3" PVC CA PIPE FOR E� TERMINATE ABOVE ROOF WITH CONCENTRIC VENT KIT. Il 141 ERV -1 EA DUCT. 18 16/5 (UNLINED, EA). TERMINATE WITH 18/12 LV -1 ABOVE ROOF ON SIDEWALL OF CHIMNEY. 19 INSTALL ON GARAGE WALL ABOVE FLAT DINING ROOM ROOF. ® 12" o BYPASS DUCT AND DAMPER 21 6/6 '-6Lj 30 22 INSTALL HUMIDIFIER IN VERTICAL SECTION OF DUCT PER MANUFACTURER'S INSTRUCTIONS. Q3 IRE: M203/A FOR CONTINUATION. ® ACCESS PANEL ON SLOPED CEILING. ©5 20/10 (FC -2 RA) © 12/4 5G-1 15 21 (2) 12/4 TG -I >C -ER GRILLES. CONNECT TO 24/4 TG -1 XFER GRILLE — WITH 12/4 (UNLINED) DUCTWORK © ARCHITECT TO COORDINATE INSTALLATION OF CONDENSING UNITS TO ENSURE NOISE LEVEL AT PROPERTY LINE MEETS CITY OF ASPEN'S REQUIREMENTS. ACOUSTICAL MATERIAL MAY NEED TO BE INSTALLED TO REDUCE CONDENSING UNIT NOISE LEVELS. ROOF � � v I 1 l7Qttt Q Q IL W — — 0 — '�► 61 PE Stamp ticpy��o Go�VPP00 Q5/10/18sat iy 5 02 ri I I I O w a FSM W W � W a • w M F�+1 O YO FURNACE FLUE AND CA PIPE. N M leeued For TERMINATE ABOVE ROOF WITH 1 4126/11 SD SET 2 5123/11 ELEC. COORD. 3 6/30/11 COORDINATION CONCENTRIC KIT. 5 2/5/18 PERMIT COMMENTS 6 5/10AS CONSTRUCTION 12/12 SUPPLY (CONNE TED TO �� NORTH BACK SIDE OF 16/16) Scale: 11024ZO 1/4" = 1'-0" 14/12 SUPPLY OVER MASTER BATH 18/14 RA 10"0 BYPASS JCB JDR INSTALL H—° HUMIDIFIER IN VERTICAL SECTION( OF DUCT. _ f_ CC -3 F-3 LA G FILTER BO MECH4ANIC/4L ATTIC SECTION 0 I I I I A 0 I I I I 6 OHO 1 M DECK 205 I 12/4 I PLAT ROOF SOA2 LV -1 EA / ROOF IPVEL—UPPE_. R J� 125'_C T. PLUPPER)J. T.O. PLYLUPP_ ERl 1, 1 1 P-2 3/4' O 1 F°a a M BATH 202 J 14/12 (I M v_ I E i 3 i I m m v BALCONY 208 IL I I d I I I I L 16/16 FEP SA) � I I I I I I M BDRM +36/8 6G-4 550 I 1 I I I i I I I I I i I 7--10"0 ISYPA55 DAMPER RE: M203/A FOR CONTINUATION. — E' I I — 1 I I \—UPEN TO LIVING ROOM B I 0— — A R a I I � �Lu W (-4 1 Ln T b I 1 l7Qttt Q Q IL W — — 0 — '�► 61 PE Stamp ticpy��o Go�VPP00 Q5/10/18sat iy 5 02 ri I I I I C �wi �Lu W (-4 1 Ln T b N co l7Qttt Q Q IL W tD r �Z 6)X W � 0 Ln CQt TM '�► 61 PE Stamp ticpy��o Go�VPP00 Q5/10/18sat iy 5 02 ri A`S`S/GHAL ti�G` O w a FSM W W � W a • w M F�+1 O M N M leeued For No. Date CommeeK 1 4126/11 SD SET 2 5123/11 ELEC. COORD. 3 6/30/11 COORDINATION 4 1/11/11 PERMIT 5 2/5/18 PERMIT COMMENTS 6 5/10AS CONSTRUCTION UPPER LEVEL MECHANICAL PLAN NORTH Project No. Scale: 11024ZO 1/4" = 1'-0" Drawn By: Checked By: JCB JDR M203 III LU z z W LU Cf LL W W z O 3 LU tu J N N fCj Cj O F J � m Cl O W r tt1 � O Q Z J Q u 3 } Q O LL oz lu J a N ww x r L O ad) wx J w z yl lu LL �(V LU m0 0 azq oQ x aIV w � O 3 Q j J 0 z0 r 3 i U a w L�3: Of z _ d) YAW tu z N Z Q x W LILU W ]UQp K Z rao 1 w iul gd�ryry_ j W � 3L� LU ;�o