HomeMy WebLinkAboutFile Documents.395 Thunderbowl Ln.0255.2018.ARBK02552018arbk_BuildingComments_1
Page: 1
File Name: 17032-Rescheck-signed.pdf
Author: bonniem
Subject: PlanCheck
Color:
Provide revised wall and roof
assemblies to match REScheck
where insulation values differ
from what was approved on the
master permit.
17032-Rescheck-signed.pdf (1)
Page: L800 hardscape details
File Name: LANDSCAPE PLANS.pdf
Author: bonniem
Subject: Spa Cover
Color:
Note that pool and spa cover
must comply with APSP-14 and
be ASTM F1346 listed and/or
provide a spec for the cover
showing that it meets this criteria
(2015 IECC 403.11, 2015 ISPSC
305.1).
LANDSCAPE PLANS.pdf (1)
Page: S1.42 SITE RETAINING WALL PLAN NORTH
File Name: STRUCTURAL PLANS.pdf
Author: bonniem
Subject: PlanCheck
Color:
Evolve Structural Design does
not provide a design for the pool.
The pool design must be
stamped by an engineer
because the depth exceeds 4 ft.
Provide a stamped structural
design for the pool.
STRUCTURAL PLANS.pdf (1)
Provide revised wall and roof
assemblies to match REScheck where
insulation values differ from what was
approved on the master permit.
21'-6"
POOL
TER
G
9'-6"
POOL/SPA COVER
SCALE: 1" = 1'-0"
Note that pool and spa
cover must comply
with APSP-14 and be
ASTM F1346 listed
and/or provide a spec
for the cover showing
that it meets this
criteria (2015 IECC
403.11, 2015 ISPSC
305.1).
RE: S1.01 FOR BUILDINGFOUNDATIONS TYP
PATIO SLAB ON GRADE4" CONCRETE SLAB ON INSUL PER ARCH ONAPPROVED NATIVE OR PREPARED SUBGRADE PERGEOTECH REPORT. REINFORCE SLAB WITH6x6-W2.1xW2.1 WWF OR #3 @ 12"o.c EA WAY -CENTERED. PROVIDE 114" DEEP SAW-CUT CONTROLJOINTS @ 12'-0" o.c. MAX EACH WAY - TYP
12" W MIN THICKENEDEDGE TURNED DOWN TOFROST DEPTH - TYP w/ #4@ 18"o.c. EA WAY U.N.O.
RE: LANDSCAPEDRAWINGS FORPATIO DIMENSIONS& CONFIG TYP
POOL BY OTHERS
T.O. SLAB STLOPES AND STEPSPER LANDSCAPE ARCH TYP
#4 @ 18"o.c. EA WAY E.F. - COORD.THICKENED EDGE DEPTH w/ POOLCONSTRUCTION REQUIREMENTS - TYP
RE: S1.01 FORBUILDING FDNS - TYP
DOWEL ALL PATIO SLAB EDGESTO FOUNDATION WALLS w/ #4DOWELS @ 18"o.c. HOOKEDINTO WALL OR EMBED 6" INEPOXY - TYP U.N.O.
RE: S1.41 FORRETAINING WALLINFO
FOUNDATION NOTES:
1.REFER TO SHEET S0.01 FOR GENERAL NOTES.2.SEE FRAMING PLANS ABOVE FOR COLUMN & POST LOCATIONS & SIZES.3.CONCRETE FOOTINGS & THICKENED SLABS SHALL BE PER PLAN & SCHEDULE.4.ALL CONCRETE WALLS SHALL BE CENTERED ON FOOTINGS - U.N.O.5.SEE 3/S5.01 FOR ALL CONCRETE REINFORCING STANDARD HOOKS AND BENDS.6.PROPER SURFACE & BELOW GRADE PERIMETER DRAINAGE SHALL BE INSTALLED PER CIVIL &GEOTECHNICAL ENGINEERS TO RELIEVE FOUNDATION WALLS FROM HYDROSTATIC PRESSURES.7.REFER TO SHEET S5.01 FOR TYPICAL CONCRETE DETAILS.8.DO NOT PLACE BACKFILL AGAINST BASEMENT WALLS UNTIL ALL SUPPORTING ELEMENTS,INCLUDING MAIN LEVEL FLOOR SHEATHING, ARE IN PLACE AND SECURELY ANCHORED, ORUNTIL ADEQUATE TEMPORARY SHORING IS INSTALLED.9.ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS & FIELD VERIFIEDBY CONTRACTOR.10.SOILS CONDITIONS TO BE VERIFIED IN FIELD AT OPEN HOLE BY SOILS ENGINEER PERFOUNDATIONS NOTES ON S0.01.11.ANCHOR ALL SILL PLATES TO TOP OF CONCRETE WITH 58" DIAMETER ANCHOR BOLTS WITHMINIMUM 7" EMBEDMENT AT 6'-0" MAXIMUM, 2 ANCHORS MINIMUM PER PLATE, 4" FROM EACHEND, U.N.O.. REFER TO BWP SCHEDULE FOR ATYPICAL A.B.'S AND SPACINGS, REFER TO PLANSABOVE FOR LOCATIONS12.REFER TO PLANS AND SCHEDULE FOR ALL HOLDOWN ANCHORS BETWEEN FRAMING AND INTOCONCRETE. REFER TO PLANS ABOVE FOR SPECIFICATIONS.13.ISOLATE ALL SLABS-ON-GRADE FROM STRUCTURAL ELEMENTS WITH EXPANSION JOINTMATERIAL - U.N.O.
REVIS 12/22
STRU
04/19
04/26
05/18 07/20
Evolve StructuralDesign does notprovide a design forthe pool. The pooldesign must bestamped by anengineer because thedepth exceeds 4 ft.Provide a stampedstructural design forthe pool.
Response:
REScheck has been revised to match wall and roof
assemblies shown in plans. See attached REScheck
Response:
-Bonnie mentioned that the APSP-14 standard is not required
with Aspen's current codes, and that it doesn't apply to the
cover and pool
-See attached sheet from CoverPools with the ASTM rating
Response:
See stamped set of Pool Structural Plans
attached.
06/18/2019