HomeMy WebLinkAboutFile Documents.401 E Cooper Ave.0063.2018 (8).ACBKPage 1 6/19/2018Commercial Heat Loss and Heat Gain Calculation Report Prepared By: S.E. Engineering For:SBX Aspen [Copy 1] Aspen, CO Design Conditions:Denver; Latitude: 39; Time 4:00 PM Indoor:Outdoor: Summer temperature:75 Summer temperature:82 Winter temperature:72 Winter temperature:-15 Relative humidity:50 Summer grains of moisture:25 Daily temperature range:28 Building Component Sensible Latent Total Total Gain Gain Heat Gain Heat Loss (BTUH)(BTUH)(BTUH)(BTUH) Miscellaneous 8,225 2,000 10,225 0 People 1,000 800 1,800 0 Ceilings 490 0 490 835 Lights 369 0 369 0 Ventilation 308 0 308 3,828 Partitions 231 0 231 231 Infiltration 77 0 77 1,876 Duct 0 0 0 0 Skylights 0 0 0 0 Door Leakage 0 0 0 0 Doors 0 0 0 0 Windows 0 0 0 0 Walls 0 0 0 1,879 Floors 0 0 0 0 Whole Building - All Components 10,700 2,800 13,500 8,649 ( 1 tons ) HVAC-Calc Commercial 4.0 by HVAC Computer Systems Ltd.888 736-1101 Load calculations are estimates only, actual loads may vary due to weather and construction differences. 06/20/2018