1. The Contract Documents include: (1) general notes; (2) architectural, mechanical, and structural drawings. All additional specifications, details, drawings,
clarifications, or changes shall automatically become part of the Contract Documents. Any discrepancy between any components of any of the drawings shall
be reported to the Architect immediately for clarification.
2. Alius Design Corps, LLC, shall not be liable in any way for problems which arise from failure, by any third party or any party to this Contract, to follow the
design plans. The Contractor shall obtain and/or request guidance of Alius Design Corp., with respect to any errors, omissions, inconsistencies, or conflicts or
unclear information which may be discovered or alleged.
3. The Plans and Specifications are the intellectual and other property of the Architect and shall not beused without the permission of same.
4. All work shall comply with all state and local codes, ordinances, rules, regulations and laws of building officials or authorities having jurisdiction. All work shall
be performed to the highest standards or craftsmanship by all tradesman. Alius Design Corps, LLC., shall not be responsible for overseeing third party work,
nor shall Alius Design Corps, LLC., be liable for any errors or omissions of third parties who perform work on the Project.
5. The Contract Documents represent the finished structure. They do not indicate the method of construction. The Contractor shall provide all measures
necessary to protect the structure during construction. Observation visits to the site by the Structural Engineer or Architect shall not include inspection of the
____________, nor will the architect or structural engineer be responsible for the contractor's means, methods, techniques, sequences for procedure of
construction, or the safety precautions and the techniques, sequences for procedure of construction, or any safety precautions. The Contractor and not the
Architect shall be responsible for all Federal and OSHA regulations.
6. THE DRAWINGS ARE NOT TO BE SCALED. Written dimensions must be used. In the event of a discrepancy in dimensions, the Architect should be timely
notified for clarification. All dimensions on the drawings shall be verified against the existing conditions. All dimensions are to rough framing or face of
concrete unless noted otherwise.
7. The Construction Documents are intended to include all labor, materials, equipment, and services required to complete all work described herein. It is the
responsibility of the Contractor to bring to the attention of the Architect any conditions which will not permit construction according to these Construction
Documents.
8. The Building Inspector shall be notified by the Contractor if there is need of an inspection as required by the I.R.C., or by any local code or ordinance.
9. LOT STAKED: The Contractor shall arrange for the building to be located and staked after demolition or site clearing, to be approved by the Architect. The
Contractor shall review the lot staking and verify, to the best of his ability, its accuracy. The Contractor shall also check the grade where it meets the building
to evaluate the consistency with the drawings during excavation. All work to be done by a certified surveyor.
10. RECORD DRAWINGS: Contractor shall maintain a complete set of blue/black-line prints of contract drawings and shop drawings for record mark-up purposes
throughout the Contract time. Mark-up drawings during course of the work shall show changes and actual installation conditions, sufficient to form a complete
record for Owner's purposes.
11. SOILS AND CONCRETE: The General Contractor shall arrange for a visual site inspection at the completion of excavation by a soils engineer, and the
required concrete testing prior to any foundation work.
12. Property lines, utilities and topography shown is representative of information taken from a survey. Contractor shall notify Architect of any discrepancy or
variation between the Drawings and actual site conditions.
ABREVIATIONS
A.F.F. ABOVE FINISH FLOOR
ADJ. ADJUSTABLE
ALT. ALTERNATE
A.B. ANCHOR BOLTS
& AND
ARCH. ARCHITECTURAL
@ AT
BM. BEAM
BM. PKT. BEAM POCKET
BRG. BEARING
BLK’G. BLOCKING
BOT. BOTTOM
BLDG. BUILDING
B.O. BY OWNER
CLG. CEILING
CL. CENTER LINE
CLR. CLEAR
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONT. CONTINUOUS
DTL. DETAILS
DWL. DOWEL
E.W. EACH WAY
ELEV. ELEVATION
EXISTG EXISTING
EXT. EXTERIOR
FLR. FLOOR
FTG. FOOTING
FND. FOUNDATION
GA. GAUGE
G.L. GLU-LAM
G.W.B. GYPSUM WALL BOARD
HORIZ. HORIZONTAL
INFO. INFORMATION
INSUL. INSULATION
JST. JOIST
N.I.C. NOT IN CONTRACT
O.C. ON CENTER
OPP. OPPOSITE
PERF. PERFORATED
PL. PLATE
PLY. PLYWOOD
PROP. LINE PROPERTY LINE
REINF. REINFORCEMENT
REQ. REQUIRED
REV. REVISED
SIM. SIMILAR
S.F. SQUARE FEET
STD. STANDARD
THK. THICK
T.P. TOP OF PLATE
T.L. TOP OF LEDGE
T.W. TOP OF WALL
TOT. TOTAL
TYP. TYPICAL
U.N.O. UNLESS NOTED UTHERWISE
V.I.F. VERIFY IN FIELD
033
LBB
CLIENT
RossMore Enterprises
605 E. Main Street Suite 7
Aspen, CO 81611
ARCHITECT
Alius Design Corps, LLC
1331 East Sopris Creek Rd.
Basalt, CO 81611
719.331.9211
michael@aliusdc.com
GENERAL CONTRACTOR
Gary M. Johnson
GENERAL RENOVATION NOTES
1.0 All existing conditions must be verified by the contractor in the field. Unknown and varied conditions may be found. Notify the structural engineer and/or architect of any
structural or architectural conditions found to vary from that indicated from the drawings. Design revisions may be required, and are to be expected as a process of remodel
work.
2.0 All new work, details, surfaces, or finishes shall match adjacent existing surfaces unless noted or directed otherwise by the owner or interior designer. Contractor to verify with
architect any conflict between existing and new conditions.
3.0 All electrical modifications and/or additions to be as directed by owner/lighting designer during construction. Contractor/lighting designer to verify electrical capacity and review
new designs or alterations with architect, prior to implementation.
4.0 All interior electrical fixtures, plumbing fixtures and trim, cabinet design, and other finishes to be at the directive of the owner or interior designer unless noted otherwise in the
drawings. Contractor to provide all necessary prep work for installation of any materials as required.
5.0 Structural engineering – if any modifications to the existing structural system are deemed necessary beyond these shown in the drawings, all existing conditions are to be verified
in the field by a registered structural engineer before proceeding. The architect will not be responsible for any structural modifications not verified or approved by a structural
engineer.
6.0 Contractor will verify and coordinate all openings through floors, ceilings, and walls with all architectural, structural, mechanical, plumbing, and electrical design and
construction.
ARCHITECTURAL
1.1 TITLE SHEET
1.2 PROJECT INFORMATION
1.3 UNIT BUILDING RELATIONSHIP
1.4 FLOOR AREA CALCS
1.5 FLOOR AREA CALCS / COM CHECK & LIGHTING SPECS
3.1 1/4” FLOOR PLANS
3.2 1/4” FLOOR PLANS
3.3 1/4” FLOOR PLANS
7.1 1 ½” FLOOR ASSEMBLIES AND DETAILS
8.1 INTERIOR ELEVATIONS
PROJECT INFORMATION
OCCUPANCY CLASSIFICATION ........................................................................................................................................... BUSINESS (B)
MAX OCCUPANCY DESIGN LOAD ..................................................................................................................................... SEE SHEET 1.3
ZONE DISTRICT ................................................................................................................................................ COMMERCIAL CORE (CC)
LOT SIZE .................................................................................................................................................................................................. N/A
PARCEL I.D. ............................................................................................................................................................................. 73718222006
BUILDING SIZE ....................................................................................................................................................................................... N/A
5.1A
REFERENCE GRID LINE
SPOT ELEVATION
WINDOW MARK
DOOR MARK
ROOM NUMBER
DRAWING REVISION
ASSEMBLY DETAIL CUT
SECTION CUT
EXTERIOR ELEVATION
DETAIL CALLOUT
INTERIOR ELEVATION
ROOM
100
F11
1
T. O. RIDGE
BEAM
123'-6 1/2"
4.4
1
1
7.1
8.1
1
2
3
4
SYMBOL & MATERIAL LEGEND
PROJECT INFORMATION
DRAWING INDEX
PROJECT DIRECTORY
CONSTRUCTION NOTES
ABBREVIATIONS
CHANGE ORDER I 06/06/2017GENERAL NOTES
415 E. HYMAN AVE.
I
I
I
I
8
Received
6/13/17
06/14/
2
0
1
7
nickt
SEE NOTES #1 PLANS
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
ASPEN, CO415 E. HYMAN AVE.MTE
1616
ISSUE
PROJECT No:
DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGN
CORPS LLC. ALL RIGHTS RESERVED
COM CHECK &
LIGHTING SPECS
1.5
01/10/2017SCHEMATIC DESIGN
02/15/2017PERMIT SET
6/6/2017CHANGE ORDER I
LY4RCS / 30K
Applications Recessed Ceiling Mount
DESCRIPTION Energy Used 9 W
Recessed 4" Round LED With Integral Driver In Connection Box.Colour Temperature 3000° K
Fits Where No Other Recessed Fixture Can.Light Output 560 lm
Halogen Equivalent 50 W
FEATURES & BENEFITS Beam Angle 105°
1/2" Thin - Install Directly Under Joists, Maximum Layout Flexibility CRI 84
Type IC Rated - No Housing Required Driver Input 120V AC or 277V-347V AC 50/60 Hz
Fast & Easy To Install - Save On Labour Power Factor 0.98
Driver Inside Connecton Box - No Junction Box Needed Dimming TRIAC Dimmers 10% - 100% (120V only)
Approved Location Insulated Ceiling & Damp Locations
MOUNTING Air Tight Yes
Cut Hole In Ceiling And Snap Fixture In Opening With Attached Spring Clips.Ambient Temperature -40°F (-40°C) to +104°F (+40°C)
2" Above Ceiling Clearance Required For Driver.Projected Life 70% Light Output at 50,000 Hours
Certification cULus, cETLus, Energy Star
Warranty 5 Year on Fixture & Driver
277V - 347V Driver Option Available
Not Dimmable
COMPLIANCE
Project:
Location:
Trim Finish: Qty:
4" Round Super Thin Recessed LED 9W
Notes:
SPECIFICATION
tel: 1-844-24-LOTUS (56887) fax. 1-877-561-6306 www.lotusLEDlights.com
Warehouses
Vancouver, BC Toronto, ON Las Vegas, NV Naples, FL
Type IC & Airtight
CHARACTERISTICS
Body: Durable, Die Cast Aluminum Alloy for Optimal Heat Dissipation.
Paint: Oil Based Spray Painted - Scratch Resistant And Smooth Finish.
LEDs: 77 Pieces Of Custom Packaged LM80 Epistar 3014. Guaranteed 98% Lumen Maintenance After 6,000 Hours.
Strict Binning To Ensure Consistent Light Colour.
Driver: 4th Generation Lotus Designed. Field Proven Since 2011.
Connection Box: Patented Invention By Lotus LED Lights. Saves Contractors Labour In Installation On Every Job.
Testing: Every Single Driver Is Powered For Minimum 24 Hours Together With The Fixture That It Is Shipped With.
Every LED Is Visually Checked Before And After The PCB Is Mounted On The Fixture. No Random Tests – We Hand Test Every Fixture & Driver.
ORDERING GUIDE Example: LY4RCS / 30K / WH ACCESSORIES Sold Separately
Trim Finish Low Volage Extension Cables
6ft - cat # EXC6, 20ft - cat # EXC20
WH : White Max 40 ft Extension Allowed
BK : Black
BN : Brushed Nickel Rough-In Plates - cat # RIP4
Order 277V - 347V Optional Driver Separately As cat # LLL-LD1535H Goof Ring White OD 5 3/4" - cat # GR4
tel: 1-844-24-LOTUS (56887) fax. 1-877-561-6306 www.lotusLEDlights.com
PHOTOMETRIC DATA
Warehouses
Vancouver, BC Toronto, ON Las Vegas, NV Naples, FL
LY4RCS / 30K /
Project Title: 415 East Hyman Report date: 06/03/17
Data filename: C:\Users\Michael\Documents\ARCH\Alius Design Corps\Projects\2016\1616_415 E Hyman\Documents\Permit\415 E
Hyman_2.cck Page 1 of 2
COMcheck Software Version 4.0.3.1
Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code: 2009 IECC
Project Title: 415 East Hyman
Project Type: Alteration
Construction Site:Owner/Agent:Designer/Contractor:
415 East Hyman
Aspen, CO 81621
RossMore Enterprises
415 East Hyman St.
Aspen, CO 81621
eric@rossmoreproperty.com
Michael Edinger
A.D.C.
1331 East Sopris Creek Road
Basalt, CO 81621
719.331.9211
michael@aliusdc.com
Section 2: Interior Lighting and Power Calculation
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B x C)
Office 1333 1 1333
Total Allowed Watts =1333
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
Office (1333 sq.ft.)
LED 1: LED A Lamp 9W:1 23 9 207
Track lighting 1: Wattage based on 15 feet of track 0 0 0 450
Track lighting 2: Wattage based on 15 feet of track 0 0 0 450
Total Proposed Watts =1107
Section 4: Requirements Checklist
Interior Lighting PASSES
Lighting Wattage:
q 1.Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies 1333 1107 Passes
Controls, Switching, and Wiring:
q 2.Daylight zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to
vertical fenestration.
q 3.Daylight zones have individual lighting controls independent from that of the general area lighting.
Exceptions:
q Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device.
q Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a
separate switch for general area lighting.
q 4.Independent controls for each space (switch/occupancy sensor).
Project Title: 415 East Hyman Report date: 06/03/17
Data filename: C:\Users\Michael\Documents\ARCH\Alius Design Corps\Projects\2016\1616_415 E Hyman\Documents\Permit\415 E
Hyman_2.cck Page 2 of 2
Exceptions:
q Areas designated as security or emergency areas that must be continuously illuminated.
q Lighting in stairways or corridors that are elements of the means of egress.
q 5.Master switch at entry to hotel/motel guest room.
q 6.Individual dwelling units separately metered.
q 7.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
q 8.Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either
controlling all luminaires, dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps, switching the middle
lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
q Only one luminaire in space.
q An occupant-sensing device controls the area.
q The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
q Areas that use less than 0.6 Watts/sq.ft.
q 9.Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
q Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
q 10.Photocell/astronomical time switch on exterior lights.
Exceptions:
q Lighting intended for 24 hour use.
q 11.Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
q Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting alteration project represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application. The proposed lighting alteration project has been designed to meet
the 2009 IECC, Chapter 8, requirements in COMcheck Version 4.0.3.1 and to comply with the mandatory requirements in the Requirements
Checklist.
Name - Title Signature Date
Michael T Edinger 06/03/2017Michael Edinger President
6/3/2017 14W LEDme Exterminator II Track Light by WAC Lighting at Lumens.com
https://www.lumens.com/14wledmeexterminatoriitracklightbywaclightingWACP150353.html#cgid=%0A%09%0A%09%0911060%0A%09%0A&&tileInde…1/2
CALL U
877.445.4486
Mon-Fri 6am-6pm PT
at 7am-5pm PT
Details
The WAC Lighting 14W LDme xterminator II Track Light o쮩�ers a slick, modern directional lighting head
to suppl ample projection lighting in our indoor space. Made from die-cast aluminum, the 14W LDme xterminator II Track Light
allows for 355° horizontal rotation and 180° vertical aiming. Rated for 100,000 hours of life and is dimmale with an LV dimmer
(sold separatel.) The 14W LDme xterminator II Track Light dims from 100% - 5%.
WAC Lighting, founded in 1984, has developed a strong reputation for high qualit decorative and task lighting. ased in Garden
Cit, New York, WAC Lighting is a leading manufacturer of low voltage, line voltage and LD lighting, including track sstems,
transformers, lamps, cainet lighting and recessed downlights.
The 14W LDme xterminator II Track Light is availale with the following:
Details:
Designed in 2015
Material: Die-cast Aluminum
uperior illumination with compact design
355° horizontal rotation
180° vertical aiming
Accomodates one lens accessor and one glare control accessor
Rated Life: 100,000 hours
Dimming: 100% - 5%
Dimmale when used with lectronic low voltage (LV) Dimmer dimmers(not included)
Title 24 compliant
TL Listed
Warrant: 5 Years Functional, 2 Years Finish
Made In China
Options:
Finish: lack, rushed Nickel, White
Track Tpe: H-Track, J-Track, L-Track
Light Temperature: 2700K, 2700K (90 CRI), 3000K, 3000K (90 CRI), 3500K, 4000K
eam pread: 20 Degree, 40 Degree
Lighting:
$143.50 - $161.50
FR HIPPING on orders over $75.
FR GIFT ONLY AT LUMN: Use code ALANC to get a FR alance
LD Task Lamp (retail value of $159.50) with qualifing $350+ dweLD or
WAC Lighting purchase during the ummer ale. Limited time onl.
FR VINTAG TRING LIGHT KIT: Use code TRING at checkout to get a
FR Vintage tring Light Kit ulrite (a $100 value) with qualifing $350
purchase during the ummer ale. Limited time onl. One per customer,
while supplies last.
14W LDme xterminator II Track Light
WAC Lighting
elect items in stock, choose options to view or check availailit.
Finish:
Track Tpe:
Light Temperature:
eam pread:
lack rushed Nickel White
H-Track J-Track L-Track
2700K 2700K (90 CRI)3000K 3000K (90 CRI)3500K 4000K
20 Degree 40 Degree
hown in rushed Nickel
CUTOMIZAdd custom contact info, project, logo and more.CRATGenerate PDF pec heet to save, print and share.
Product Options
Finish: lack, rushed Nickel, White
Track Tpe: H-Track, J-Track, L-Track
Light Temperature: 2700K, 2700K (90 CRI), 3000K, 3000K (90 CRI), 3500K,
4000K
eam pread: 20 Degree, 40 Degree
Details
Designed in 2015
Material: Die-cast Aluminum
uperior illumination with compact design
355° horizontal rotation
180° vertical aiming
Accomodates one lens accessor and one glare control accessor
Rated Life: 100,000 hours
Dimming: 100% - 5%
Dimmale when used with lectronic low voltage (LV) Dimmer
dimmers(not included)
Title 24 compliant
TL Listed
Warrant: 5 Years Functional, 2 Years Finish
Made In China
Dimensions
Fixture Width 3.75", Depth 2":
Maximum Hanging Length 4.5":
Lighting
2700K Option: 14 Watt (852 Lumens) 12 Volt Integrated LD: CRI: 85
2700K Option: 14 Watt (860 Lumens) 12 Volt Integrated LD: CRI: 85
2700K (90 CRI) Option: 14 Watt (624 Lumens) 12 Volt Integrated LD: CRI:
90
2700K (90 CRI) Option: 14 Watt (627 Lumens) 12 Volt Integrated LD: CRI:
90
3000K Option: 14 Watt (857 Lumens) 12 Volt Integrated LD: CRI: 85
3000K Option: 14 Watt (872 Lumens) 12 Volt Integrated LD: CRI: 85
3000K (90 CRI) Option: 14 Watt (663 Lumens) 12 Volt Integrated LD: CRI:
90
3000K (90 CRI) Option: 14 Watt (677 Lumens) 12 Volt Integrated LD: CRI:
90
3500K Option: 14 Watt (912 Lumens) 12 Volt Integrated LD: CRI: 85
3500K Option: 14 Watt (917 Lumens) 12 Volt Integrated LD: CRI: 85
4000K Option: 14 Watt (965 Lumens) 12 Volt Integrated LD: CRI: 85
4000K Option: 14 Watt (980 Lumens) 12 Volt Integrated LD: CRI: 85
Additional Details
Product URL: /14w-ledme-exterminator-ii-track-light--wac-lighting-
WACP150353.html
Rating: TL Listed
hown in rushed Nickel
Notes:
14W LDme xterminator II Track Light
WAC Lighting
Call Us 877.445.4486
Product ID: WACP150353
Prepared :Prepared for:
Project:
Room:
Placement:
Approval:
Created June 3rd, 2017
C Spec-Sheet-LY4RCS-30K C Spec-Sheet-LY4RCS-30K
1 compliance-report-signed_2_060317 2 compliance-report-signed_2_060317
A 14W LEDme Exterminator II Track Light by WAC Lighting at Lumens
II
I
Received
6/13/17
06/14/
2
0
1
7
nickt
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
ASPEN, CO415 E. HYMAN AVE.MTE
1616
ISSUE
PROJECT No:
DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGN
CORPS LLC. ALL RIGHTS RESERVED
FLOOR PLANS
3.2
01/10/2017SCHEMATIC DESIGN
02/15/2017PERMIT SET
6/6/2017CHANGE ORDER I
108
101
107
103
105
106
4
7.1
14'-11"51/2"9'-51/2"81/2"14'-4"51/2"25'-61/16"51/2"81/2"9'-11"51/2"11/2"51/2"7'-93/8"51/2"9'-8"51/2"10'-1111/16"51/2"3'-61/2"51/2"4'-5"20'-5"
4'-11"7'-6"7'-8"4'-9"
8'-73/4"51/2"2'-0"3'-93/4"9'-11"3'-05/8"6'-0"
115/8"9'-6"10'-7"2'-11/4"
1'-113/4"2'-0"3'-11/4"
14.2
NEW DOOR TO EXIST. DECK;
EXIST. DOOR LOCATION TO BE FILLED;
LOCATION TO BE V.I.F. BY G.C.; SEE
DETAIL 5 ON SHEET 7.1 FOR HEADER
ALIGN W/ DOOR 108
TYPICAL WALL
CONNECTION
6' W x 4'H TRANSLUCENT
WINDOW
EXIST. STAIR DOWN
TO 3RD FLOOR; SEE SITE
PLAN FOR STAIR RELATIONSHIP
TO BUILDING
AREA OUTSIDE OF
WORK SCOPE
EXIST. DECK
W2TYP. U.N.O.
W1
EXIST. FLOOR
TO REMAIN
W3
CONFERENCEROOM
REF.
WAITING
KITCHEN
ADA BATHROOM
OFFICE #1
OFFICE #2
STORAGE
CL
CL
CL
CL
CL
CL
CL
CL EGRESS PATH = 57'1
1
CC
CC
CC
C
C
C
C
C
C
C
C
CC
C
C C
C
C
C
A
A
A
A
A
A
A
A
A
A
AREA OUTSIDE OF
WORK SCOPE
EXIST. DECK
EXIST. ROOF
STRUCTURE ABOVE
CEILING TO REMAIN; SEE
ASSEMBLY R1
C
CONFERENCEROOM
WAITING
KITCHEN
ADA BATHROOM
OFFICE #1
OFFICE #2
STORAGE
105
63/4"3'-0"3'-0"4'-0"3'-0"4'-6"2'-0"3'-1"
R-63 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS AS VAPOR BARRIER)
SEE INTERIOR ELEVATIONS FOR C.T. HEIGHT
CLEAR FLOOR SPACE FOR
SHOWER ACCESS
LINE OF SINK CLEARANCE
DOOR MANEUVER CLEARANCE
SEE INTERIOR ELEVATIONS FOR
GRAB BAR AND CONTROL DIMS AND
ACCESSORY LOCATIONS
30"x48"CLEAR FLOOR
SPACE
0 2'4'8'SCALE: 1/4" = 1'-0"2 MAIN LEVEL PLAN NEW
0 2'4'8'SCALE: 1/4" = 1'-0"2 MAIN LEVEL R.C.P.
0 1'2'4'SCALE: 1/2" = 1'-0"2 ADA COMPLIANCE PLAN
I
Received
6/13/17
06/14/
2
0
1
7
nickt
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
ASPEN, CO415 E. HYMAN AVE.MTE
1616
ISSUE
PROJECT No:
DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGN
CORPS LLC. ALL RIGHTS RESERVED
ASSEMBLIES &
DETAILS
7.1
01/10/2017SCHEMATIC DESIGN
02/15/2017PERMIT SET
6/6/2017CHANGE ORDER I
3 3/8"3 3/8"1"3/8"7/8"
5/8"5 1/2"5/8"
1"7/8"3/8"3 3/8"3 3/8"3/8"
1"7/8"3 3/8"3/8"
1"7/8"1/8" x 3" ROLLED STEELBASEBOARD BEYOND
5/8" GYP. BOARD TYP.ENGINEERED 2 x 6 STUD TYP.
3/8" CLEAR GLASS
SILICON BEAD
1/8" STEEL CHANNEL TYP.
ENGINEERED 2 x 6 STUD TYP.
1/8" STEEL CHANNEL TYP.
SILICON BEAD
3/8" CLEAR GLASS
BATT INSULATION TYP.
ENGINEERED 2 x 4 STUD TYP.
1/8" x 3" ROLLED STEELBASEBOARD BEYOND
5/8" GYP. BOARD TYP.
ENGINEERED 2 x 6 STUD TYP.3/8" CLEAR TEMPERED GLASS
SILICON BEAD
1/8" STEEL CHANNEL TYP.
ENGINEERED 2 x 6 STUD TYP.
ENGINEERED 2 x 4 STUD TYP.
BATT INSULATION TYP.
1/8" x 3" ROLLED STEELBASEBOARD BEYONDMcFeelys washer head combodrive screws
5/8" GYP. BOARD TYP.
ENGINEERED 2 x 6 STUD TYP.3/8" CLEAR TEMPERED GLASS
SILICON BEAD
1/8" STEEL CHANNEL TYP.
ENGINEERED 2 x 6 STUD TYP.
ENGINEERED 2 x 4 STUD TYP.
BATT INSULATION TYP.
1 3" = 1'-0"
3" = 1'-0"2 GLASS FRAME DETAIL
CL
GLASS FRAME DETAIL
CL
CL
3" = 1'-0"3 GLASS FRAME DETAIL
CL
DOOR HEADER IN EXIST. CMW WALL53" = 1'-0"
3" = 1'-0"4 1 HOUR FIRE RATED WALL CONNECTION1 HOUR FIRE RATED WALL CONNECTION
8" NOMINAL WIDTH EXIST.
CMU EXTERIOR BEARING WALL
EXIST. WALL FURRING
NEW BLOCKING FOR FIRE RATING
NEW TYPE X 5/8" SHEET ROCK BACKER FOR
FIRE RATING
WOOD TRIM TO MATCH EXIST.
EXIST. WALL FURRING
8" NOMINAL WIDTH EXIST.
CMU EXTERIOR BEARING WALL
WT 6 x 15 STEEL HEADER; GROUTED W/ 6"
BACKSPAN BEYEOND DOOR
5/8"SEE PLAN 5/8"
5/8"SEE PLAN 5/8"
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR
FINISH - SEE SCHEDULE
WALL FRAMING W/ BLOCKING AS REQUIRED
SOUND ATTENUATING INSULATION - REFER TO
SPECS
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR
FINISH - SEE SCHEDULE
5/8" TYP. X GYPSUM WALL BOARD SEE INTERIOR
SCHEDULE FOR FINISH
WALL FRAMING W/ BLOCKING AS REQUIRED
SOUND ATTENUATING INSULATION - REFER TO
SPECS
5/8" TYP. X GYPSUM WALL BOARD SEE INTERIOR
SCHEDULE FOR FINISH; SEE DETAIL 4 ON SHEET
7.1 FOR PLAN DETAIL
WALL FRAMING W/ BLOCKING AS REQUIRED
SOUND ATTENUATING INSULATION - REFER TO
SPECS
8" NOMINAL WIDTH EXIST.
CMU EXTERIOR BEARING WALL
1 ½" = 1'-0"W3
1 HOUR RATED NEW WALL
@ EXIST. CMU (TYPICAL)
1 ½" = 1'-0"
INTERIOR WALL (TYPICAL)W1
GL
GL
1 ½" = 1'-0"
1 HOUR FIRE RATED INTERIOR WALL (TYPICAL)W2
GL
UL SYSTEM DESIGN NO. U314
UL SYSTEM DESIGN NO. U314
EXIST. RAFTER TO REMAIN
EXIST. ROOF DECK TO REMAIN
NEW RECESSED CAN; SEE SPECS.
SQUARLINE METAL
ACCOUSTIC CEILING PANEL;
24X24
EXIST. ROOF MENBRANE AND RIGID
INSULATION TO REMAIN
FULL COAT, COMPLETE COVERAGE
FORCEFIELD FIREGAURD E-84 INTUMESCENT
PAINT
WIRE TIE FOR DROP PANEL PER MANUF. REC.
1 HOUR RATED CEILING ASSEMBLYR11 ½" = 1'-0"
UL TEST NO. U263, SEE ASSEMBLY FC-8 ON SHEET 7.2
ALL EXIST. EXTERIOR WALL CAVITIES
WILL BE FILL W/ INSULATION IF
EXPOSED.
I