Daylight controls required per
C405.2.3. Show the daylight
zones on the plan, all lighting
within those zones must be on
compliant daylight controls.
Plan Set.415 E Hyman.2017.09.pdf (5)
Subject: PlanCheck
Page Label: A-05
Author: denism
File Name: Plan Set.415 E Hyman.2017.09.pdf
Provide an accessible route to
the front door from the Mall.
IEBC section 9006 and 705.2
Subject: PlanCheck
Page Label: A-301
Author: justinh
File Name: Plan Set.415 E Hyman.2017.09.pdf
Provide a ceiling assembly.
Subject: PlanCheck
Page Label: A-05
Author: justinh
File Name: Plan Set.415 E Hyman.2017.09.pdf
Provide more information or a
cutsheet on this door/hardware
to show it complies with ICC
A117.1-2009 sec 309. The
required 32" clear width must
take into account any projection
of the door when in the fully
opened position, please verify
this.
Subject: PlanCheck
Page Label: EL1-1
Author: denism
File Name: Plan Set.415 E Hyman.2017.09.pdf
Show compliant light reduction
controls per IECC C405.2.2.2
typical throughout. Private
offices require occupant sensor
controls per C405.2.1.
OPEN OFFICE103
PRIVATE OFFICE
107
PRIVATE OFFICE
106
PRIVATE OFFICE
105
PRIVATE OFFICE109
PRIVATE OFFICE
108
CONFERENCE ROOM104
STAFF DESKS102
SHOWROOM101
STORAGE HYMAN MALLUP
DN
DN
PRIVATE OFFICE110RIVATE OFFICE111
TV DISPLAYS
Bighorn Consulting Engineers, Inc.Mechanical & Electrical Engineers569 S. Westgate Dr., Suite 1Grand Junction, CO 81505phone: 970-241-8709, fax: 970-241-9514SOTHEBY'S ASPEN415 E. HYMANASPEN COLORADO 81611Daylight controlsrequired per C405.2.3. Show the daylightzones on the plan, alllighting within thosezones must be oncompliant daylightcontrols.
DRAWING ISSU
ID
BUILD
COPYRIGHT
PROJECT NO:
DRAWN BY:
DATE OF PUBL
PARCEL ID#
ZONE DISTRICT
C
B
DN
DN
Provide an accessible
route to the front door
from the Mall. IEBC
section 9006 and
705.2
F-1
PEN OFFICE
113
Provide a ceiling
assembly.
1'-10"2'-8"
2'-8"2'-0"
Provide more information or a cutsheet on this
door/hardware to show it complies with ICC
A117.1-2009 sec 309. The required 32" clear
width must take into account any projection of
the door when in the fully opened position,
please verify this.
OPEN OFFICE
PRIVATE OFFICE
107
PRIVATE OFFICE
106
PRIVATE OFFICE
105
PRIVATE OFFICE
108
MECH
Show compliant light
reduction controls per
IECC C405.2.2.2
typical throughout.
Private offices require
occupant sensor
controls per C405.2.1.
FP Response: An accessible lift will be
installed from the Hyman Mall to the
building common space. Contractor to
confirm specifications.
BCE Response: A note has been added
to EL1-1 indicating daylight controls to be
required.
FP Response: A-301 has been updated to
reference C-1 ceiling assembly on A-501.
FP Response: Cutsheets have been
provided showing door hardware.
BCE Response: A note has been added
to EL1-1 indicating occupancy sensor
controls to be required.