Subject: PlanCheck
Page Label: A-05
Author: justinh
File Name: Change Order Plan Set.415 E Hyman.2018.02.pdf
Provide a structural detail for
these new window headers.
Change Order Plan Set.415 E Hyman.2018.02.pdf (5)
Subject: PlanCheck
Page Label: A-401
Author: justinh
File Name: Change Order Plan Set.415 E Hyman.2018.02.pdf
Your knee and toe clearance is
drawn backwards with the knee
clearance at the lip of the sink
rather than the back, it is also
missing dimensions showing
compliance with ANSI 306.2 and
306.3. Please revise.
Subject: PlanCheck
Page Label: A-501
Author: justinh
File Name: Change Order Plan Set.415 E Hyman.2018.02.pdf
Provide a cutsheet on this
20-minute rated window
assembly.
Subject: PlanCheck
Page Label: EL1-1
Author: justinh
File Name: Change Order Plan Set.415 E Hyman.2018.02.pdf
Provide compliant lighting
controls per IECC C405.2. All
private offices, the conference
room and copy room require
occupancy sensors per
C405.2.1, other spaces not on
occupancy sensors or daylight
sensors are required to be on
time switch controls. Currently
you are only showing the
daylight zones and manual light
reduction controls (dimmers).
Subject: PlanCheck
Page Label: EL1-1
Author: justinh
File Name: Change Order Plan Set.415 E Hyman.2018.02.pdf
These lights are outside and
should be on a exterior lighting
ComCheck, please submit that
document and remove these
three from the interior lighting
ComCheck.
1'-0"3'-0"1'-0"
5'-0"3'-0"2'-0"PRIVATE OFFICE111 PRIVATE OFFICE109PRIVATE OFFICE110
44
5'-0"5'-0"
5
BA-301
IN-SWINGAUTOMATICDOOR
AUTOMATICPUSH BUTTON
AUTOMATICPUSH BUTTON
EXISTINGELEVATOR
COMMON SPACE
DN
01
Provide a structural
detail for these new
window headers.
60" CIRCTURNING
5'-0"2'-0"3'-0"2'-0"2'-87"2'-1"2'-2"2'-8"1'-6"1'-10"
1'-6"1'-6"1'-3"1'-3"1'-5"1'-3"2'-8"1'-4"2'-10"1'-2"2'-6"SINK WITHACCESSIBLE KNEECLEARANCEPER A-006
UPPER CABINETS/PANTRY
DW
REF
2'-10"9"2'-11"2'-8"1'-4"2'-6"2'-0"3'-0"
1'-3"1'-0"1'-0"1"3'-4"7"
SURFACE WITHACCESSIBLE KNEECLEARANCESEE A-005
EXISTING WINDOWTO REMAIN
SCALE: 01 MAIN
SCALE: 3/4" = 1'-0"02 KITCHEN
SCALE: 3/4" = 1'-0"04 KITCHEN
Your knee and toe clearance isdrawn backwards with the knee
clearance at the lip of the sinkrather than the back, it is also
missing dimensions showingcompliance with ANSI 306.2and 306.3. Please revise.
EXISTING JOIST PER STRUCT
WOOD FLOORING
SHEATHING REF STRUCT
BXU
EXISTING WOOD STUD
FIRE RATEDSEALANT
20-MIN RATEDGLASS
TYPE X GYPBOTH SIDES
COMMON SPACESOTHEBY'SOFFICES
01 SCALE: 1 1/2"= 1'C-1 UNRESTRAI
Provide a cutsheet on
this 20-minute rated
window assembly.
PRIVATE OFFICE
107
PRIVATE OFFICE
106
PRIVATE OFFICE
105
PRIVATE OFFICE
108
Provide compliant lighting controls per IECC C405.2. All private offices, the
conference room and copy room require occupancy sensors per C405.2.1, other
spaces not on occupancy sensors or daylight sensors are required to be on time
switch controls. Currently you are only showing the daylight zones and manual light
reduction controls (dimmers).
AFF DESKS
102
HYMAN MALLDN
SOTHEBY'S ASPENThese lights are
outside and should be
on a exterior lighting
ComCheck, please
submit that document
and remove these
three from the interior
lighting ComCheck.
All offices have manual on auto off dimmer switchesshown on the plans. Switches are labeled "MAD"Added ceiling mounted occupancy sensors in the copy center. See the attached plans for switch revisions.
The com check has been revised, moving the 3 outside down lightsto
the exterior section. See attached revised Co Check report.
Structural details (A-504) and existing photos provided
Knee and toe clearance updated and dimensioned on sheet A-401 per
ANSI 306.2 &306.3.
Cut sheet provided for 20-minute rated window assembly.
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: COMcheck.415 E Hyman.2018.02.pdf
Provide a cutsheet on the track
lighting that verifies the wattage
used on the ComCheck and the
NRTL listing (only the down light
was included in the cutsheets
provided).
COMcheck.415 E Hyman.2018.02.pdf (1)
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Office 2321 0.82 1903
1903Total Allowed Watts =
Proposed Interior Lighting Power
E(C X D)DFixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
BLamps/
Fixture
C# of
Fixtures
Office (2321 sq.ft.)
LED 1: C: LED DOWN LIGHT: LED Linear 10W:1 65 10 650
Track lighting 1: TRACK: TRACK WITH 4 - 9W LED HEADS: Wattage based on 4 feet of track 0 0 120 120
770Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with thebuilding plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.0 and to comply with anyapplicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
SOTHEBY'S ASPEN
Z:\2017 Projects\17108 Sotheby's Aspen\energy - com check\17108 SOTHEBYS ASPENCOMCHECK - REVISED 2-19-18.cck
02/19/18Report date:
51 ofPage
Provide a cutsheet on the track lighting that
verifies the wattage used on the ComCheck
and the NRTL listing (only the down light
was included in the cutsheets provided).
Cutsheet provided on track lighting used on the ComCheck,