An occupancy sensor will be
required for the new lighting in
the equipment room, note this on
the plan.
Plan Set.415 E Hyman Ave.2017.09.pdf (4)
Subject: PlanCheck
Page: A2.2
Author: justinh
File Name: Plan Set.415 E Hyman Ave.2017.09.pdf
You must demonstrate that the
new equipment room will have
compliant ventilation per IBC
3005.2.
Subject: PlanCheck
Page: S1.01
Author: justinh
File Name: Plan Set.415 E Hyman Ave.2017.09.pdf
A signed special inspection
agreement is required for
structural steel welding.
Subject: PlanCheck
Page: S1.01
Author: justinh
File Name: Plan Set.415 E Hyman Ave.2017.09.pdf
This is a IIIA building and this
scope of work requires
disturbing the existing fire rated
floor assembly to add structural
elements to the floor to support
the new equipment. Provide a
listed/tested assembly for this
floor that meets the 1 hour fire
rated requirement.
UNIT 16
.:HifiB ·~(WAfll" f-E.fl
'"' 3'-0" 7'-0"3'-11 3/4"7 7/8"4 3/8"
2'-5 1/4"
10'-8"
NEW ELEVATOREQUIPMENT ROOM(IBC 3005.4 EXCEPTION 2.)
NEW EQUIPMENTROOM DOOR (IBC 3005.1)
NEW LINEAR FLUORESCENTLIGHT FIXTURE
POWER UNITTANK
ELEVATOR 1/2"3'-3"1'-5"3"2'-10 1/2"
An occupancy sensor will be
required for the new lighting in the
equipment room, note this on the
plan.3'-0" 7'-0"3'-11 3/4"7
4 3/8"
2'-5 1/4"3'-8 5/8"3 1/2"5'-1/8"10'-8"14'-5/8"
CENTTURE
TANK
SKYLIGHT3'-3"1'-5"3"2'-10 1/2"
You must demonstrate that
the new equipment room will
have compliant ventilation
per IBC 3005.2.
A signed special inspection
agreement is required for structural
steel welding.
This is a IIIA building and this scope of work requires
disturbing the existing fire rated floor assembly to add
structural elements to the floor to support the new
equipment. Provide a listed/tested assembly for this floor
that meets the 1 hour fire rated requirement.
Noted on plan 2/A2.2
See attached letter from Josh Anthe, T&E Marshall Enterprises.
Also noted on plan 2/A2.2.
See attached 415 E Hyman Special Inspection Agreement.
See fire rated beam and floor assembly
details on sheet A0.1.