HomeMy WebLinkAboutFile Documents.845 Meadows Rd.0048.2018 (3).ACBKCOMcheck Software Version 4.0.8.1
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Addition
Construction Site:
845 Meadows Road
Aspen, CO 81611
Owner/Agent:
The Aspen Institute
1000 North 3rd Street
Aspen, CO 81611
Designer/Contractor:
Clanton & Associates, Inc.
4699 Nautilus Court South, Suite
102
Boulder, CO 80301
303-530-7229
Project Information
Energy Code:
Aspen Meadows Reception Renovation and Pavilion Addition
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Dining: Bar Lounge/Leisure 4140 1.01 4181
4181Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-Dining: Bar Lounge/Leisure
LED 1: F1: Surface mounted area light: Other:1 19 26 494
LED 7: F5: Round Surface Area Light: Other:1 6 30 180
LED 8: F6: 4-ft wall mounted stair light: Other:1 1 28 28
LED 9: F2: 2x2 recessed luminaire: Other:1 7 19 133
LED 28: F22: Surface mounted decorative: Other:1 2 60 120
LED 29: F23: Decorative wall sconce: Other:1 5 22 108
LED 31: F25: 8-ft recessed slot light: Other:1 8 72 576
LED 13: F14: 4-in recessed adjustable: Other:1 1 18 18
LED 10: F29: Linear strip light - lf: Other:1 40 6 232
1888Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 55% better than code
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
81 ofPage
Josie Wratten - Senior Designer April 4, 2018
05/
0
4
/
2
0
1
8
nic
k
t
COMcheck Software Version 4.0.8.1
Exterior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Addition
Construction Site:
845 Meadows Road
Aspen, CO 81611
Owner/Agent:
The Aspen Institute
1000 North 3rd Street
Aspen, CO 81611
Designer/Contractor:
Clanton & Associates, Inc.
4699 Nautilus Court South, Suite
102
Boulder, CO 80301
303-530-7229
Project Information
Energy Code:
Aspen Meadows Reception Renovation and Pavilion Addition
2 (Residential mixed use area)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Rooftop Terrace (Plaza area)2513 ft2 0.14 Yes 352
Exterior Stairs 06 (Stairway)69 ft2 1 Yes 69
Doors (Other door (not main entry))23 ft of door 20 Yes 460
Ramps and Walkways around Rooftop Terrace (Walkway < 10 feet wide)492 ft of 0.7 Yes 344
First Floor Terrace (Plaza area)3626 ft2 0.14 Yes 508
Exterior Stairs 03 (Stairway)117 ft2 1 Yes 117
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
1850
1850
600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Rooftop Terrace ( Plaza area 2513 ft2): Tradable Wattage
LED 38: E4: Steplight - per xfr: Other:1 1 75 75
Exterior Stairs 06 ( Stairway 69 ft2): Tradable Wattage
LED 35: E1: Handrail Light - per xfr: Other:1 1 100 100
Doors ( Other door (not main entry) 23 ft of door width): Tradable Wattage
LED 36: E2: Wall Sconce - Downlight: Other:1 7 27 189
Ramps and Walkways around Rooftop Terrace ( Walkway < 10 feet wide 492 ft of walkway length): Tradable Wattage
LED 35: E1: Handrail Light - per xfr: Other:1 1 100 100
First Floor Terrace ( Plaza area 3626 ft2): Tradable Wattage
LED 39: E5: Bollard: Other:1 4 19 76
LED 39: E6: Grill Light - per xfr: Other:1 3 12 36
LED 40: E7: Landscape Light - per xfr: Other:1 1 75 75
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
82 ofPage
05/
0
4
/
2
0
1
8
nic
k
t
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
LED 8: E2: Wall Sconce - Downlight: Other:1 6 27 162
LED 9: E4: Steplight - per xfr: Other:1 1 75 75
Exterior Stairs 03 ( Stairway 117 ft2): Tradable Wattage
LED 10: E4: Steplight - per xfr: Other:1 1 75 75
963Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 61% better than code
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
83 ofPage
Josie Wratten - Senior Designer April 4, 2018
05/
0
4
/
2
0
1
8
nic
k
t
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.8.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
84 ofPage
05/
0
4
/
2
0
1
8
nic
k
t
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.5
[EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
85 ofPage
05/
0
4
/
2
0
1
8
nic
k
t
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
86 ofPage
05/
0
4
/
2
0
1
8
nic
k
t
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
87 ofPage
05/
0
4
/
2
0
1
8
nic
k
t
Section#& Req.IDFinal InspectionComplies?Comments/AssumptionsC303.3,C408.2.5.2[FI17]3Furnished O&M instructions forsystems and equipment to thebuilding owner or designatedrepresentative.CompliesDoes NotNot ObservableNot ApplicableC405.4.1[FI18]1Interior installed lamp and fixturelighting power is consistent with whatis shown on the approved lightingplans, demonstrating proposed wattsare less than or equal to allowedwatts.CompliesDoes NotNot ObservableNot ApplicableSee the Interior Lighting fixture schedule for values.C405.5.1[FI19]1Exterior lighting power is consistentwith what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
CompliesDoes Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1High Impact (Tier 1)2Medium Impact (Tier 2)3Low Impact (Tier 3)
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
87 ofPage
05/
0
4
/
2
0
1
8
nic
k
t
Project Title:
Data filename:
Aspen Meadows Reception Renovation and Pavilion Addition
Z:\16120 Aspen Meadows Pavilion Addition\Calculations\Energy Calcs\Aspen Meadows Pavilion -
Additions.cck
04/04/18Report date:
88 ofPage
05/
0
4
/
2
0
1
8
nic
k
t