HomeMy WebLinkAboutFile Documents.525 E Cooper Ave.0061.2018.ACBK0061-2018-ACBK_BuildingComment1
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: ComCheck.pdf
Provide cutsheets on all light
fixtures that give maximum
fixture wattage (not bulb) and
NRTL listing.
ComCheck.pdf (4)
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: ComCheck.pdf
This sf is much more than the
area that I measure for what you
are showing on your lighting
plan. If you are using the sf of
the entire restaurant you must
show all existing lighting in the
entire space and include it on
your ComCheck. Please reduce
this number to only account for
the dining space where lighting
is being altered. Any existing
lighting to remain after this
remodel in that area should also
be included on your ComCheck.
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: ComCheck.pdf
You need to be using the space
by space method as you are not
doing a ComCheck for the entire
building. Please revise, this
watt/sf should only be .89 per
IECC table C405.4.2(2).
Subject: PlanCheck
Page Label: 1
Author: justinh
File Name: ComCheck.pdf
I agree with the fixture count for
fixture A, but am unsure
regarding the pendant and
sconce. I count 10 of fixture C
on the lighting plan which
appears to be a sconce, but you
show 20 on this report. I do not
see 10 pendant lights shown on
your lighting plan and I do not
see where the 6 lights marked B
are shown on this report. Please
clarify and revise the ComCheck
and lighting plan as needed.
Signature Date
E Cooper.cck
R
Provide cutsheets on all light
fixtures that give maximum
fixture wattage (not bulb)
and NRTL listing.
Interior Lighting Compliance Certifica
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
525 E Cooper Ave
Aspen, CO 81611
Owner/Agent:
Aspen Grove Associates LLP
51027 Highway 6 & 24
Suite 100
Glenwood Springs, CO 81611
970.945.1200
Designer/Contractor:
Michael Edinger
A.D.C.
1331 East Sopris Creek Roa
Basalt, CO 81621
719.331.9211
michael@aliusdc.com
Project Information
Energy Code:
525 E Cooper Ave
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
A
1-Existing Rest. (Dining: Family)2722 0 .95
Total Allowed Watts =
Proposed Interior Lighting Power
D
Fixtu
Watt
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
This sf is much more than the area that I
measure for what you are showing on
your lighting plan. If you are using the sf
of the entire restaurant you must show all
existing lighting in the entire space and
include it on your ComCheck. Please
reduce this number to only account for the
dining space where lighting is being
altered. Any existing lighting to remain
after this remodel in that area should also
be included on your ComCheck.
e Associates LLP
way 6 & 24
Springs, CO 81611
00
Designer/Contractor:
Michael Edinger
A.D.C.
1331 East Sopris Creek Road
Basalt, CO 81621
719.331.9211
michael@aliusdc.com
ve
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
2722 0 2586.95
2586Total Allowed Watts =
E
(C X D)
D
Fixture
Watt.
er Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
You need to be using
the space by space
method as you are not
doing a ComCheck for
the entire building.
Please revise, this
watt/sf should only be
.89 per IECC table
C405.4.2(2).
Proposed Interior Lighting Power
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
Existing Rest. ( Dining: Family 2722 sq.ft.)
LED 1: LED A Lamp 9W:
Incandescent 1: PENDANT: Incandescent 40W:
Incandescent 2: SCONCE: Incandescent 40W:
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project rep
building plans, specifications, and other calculations submitted with this per systems have been designed to meet the 2015 IECC requirements in COMch
mandatory requirements listed in the Inspection Checklist.
Name - Title Signature
Interior Lighting PASSES
Project Title:
Data filename:
525 E Cooper Ave
C:\Users\Michael\Desktop\525 E Cooper.cck
I agree with the fixture count for fixture A, but am
unsure regarding the pendant and sconce. I count
10 of fixture C on the lighting plan which appears to
be a sconce, but you show 20 on this report. I do
not see 10 pendant lights shown on your lighting
plan and I do not see where the 6 lights marked B
are shown on this report. Please clarify and revise
the ComCheck and lighting plan as needed.
I spoke to Alex from LEAX about this at length. We will verify the bulbs
match my wattage though I don't feel I should have to compromise the
lighting design because the fixture can support a different bulb. We will
use the bulbs we spec. Let's discuss.
I have adjusted the sq. ft. calculation to only
include the area we are affecting.
The revised COmCheck is using the space
by space method
I believe I have all counts accurate and
matching on plan and commcheck
Subject: PlanCheck
Page Label: 3.3 UPPER LEVEL PLAN NEW
Author: justinh
File Name: Permit Set.pdf
Please clarify how this door
system stacks and provide
cutsheets that show more
information. I had assumed that
the panels stack over the
swinging man door when the
sliders are in the open position
but this seems to show that the
entire system would slide over
this portion of wall.
Permit Set.pdf (27)
Subject: PlanCheck
Page Label: 3.3 UPPER LEVEL PLAN NEW
Author: justinh
File Name: Permit Set.pdf
These doors do not comply as
egress doors. IBC 1010.1.1
requires egress doors with 2
leaves without a mullion to have
at least one leaf be 32" wide.
Please revise.
Subject: PlanCheck
Page Label: 3.4 UPPER LEVEL R.C.P.-EXISTING
Author: justinh
File Name: Permit Set.pdf
If this work is not proposed in the
scope of your permit then please
remove it from your plans. If you
are proposing exterior lighting
anywhere with this permit then
you must submit an exterior
lighting ComCheck.
Subject: PlanCheck
Page Label: 3.6 UPPER LEVEL FURNITURE PLAN
Author: justinh
File Name: Permit Set.pdf
You are showing 108 seats not
counting the bar seating. 5% of
your seating is required to be
accessible which means that 6
accessible seats distributed
throughout the entire space are
required. Clearly identify these
six seats and demonstrate that
they meet ANSI requirements for
accessibility. All accessible
seating shall be on an
accessible route.
Subject: PlanCheck
Page Label: 3.6 UPPER LEVEL FURNITURE PLAN
Author: justinh
File Name: Permit Set.pdf
This elevation legend does not
match what is actually shown on
sheet 8.4, please revise so that
the numbering corresponds to
the correct elevations.
103
EXISTINGCOLUMNS TOREMAIN; TYP.
LINE OF EXISTINGMECHANICAL CHASE ABOVEEXISTINGELECTRICALPANEL
FLOOR DRAINFLOOR DRAIN
EXISTING INSOROLLSHADE SYSTEM
OPEN TO BELOW
NEW SINGLETRACK SLIDINGDOOR SYSTEMSTACKINGLOCATION
NEW MILLWORK WRAP @COLUMN TYP.
THROOMS
OUTSIDE
RK SCOPE
TO EAST STAIRWELL
DININGROOM203
WOMEN'S
204 SHELVING ABOVERESINVINYLPlease clarify how this door system
stacks and provide cutsheets that
show more information. I had
assumed that the panels stack over
the swinging man door when the
sliders are in the open position but
this seems to show that the entire
system would slide over this portion
of wall.
101
101
103
102
102
104
43
73/4"
4'-81/2"8'-101/2"103/4"3'-81/4"61/8"2'-2"2'-2"61/8"3'-75/8"31/2"7'-8"EXISTING MONTIGO H38DF TO FLUE CLEARANCE - 16" FROM W 10'-0" FROM CENTERLINE OF C AVENUE, 10'-0" FROM ADJACEN
EXISTING WEST STAIRWELL
EXISTING ROOFDRAIN & COLUMN
EXIST. COORIDOR DIM.TO BE MAINTAINED
DININGROOM208
COAT ROOM202
CL
W1
EXISTINGCOLUMNS TOREMAIN; TYP.
These doors do not
comply as egress
doors. IBC 1010.1.1
requires egress doors
with 2 leaves without
a mullion to have at
least one leaf be 32"
wide. Please revise.
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
COEAST COOPER24'-7 1/16"
WEST STAIRWELL P6
P6
P6P6
P6
P6
P6
FIELD OF LIGHT - LANTERNSTO CREATE ENTRY
EXPERIENCE
TV AWNINGR+B TO WORK WITH CITY OF
ASPEN AND BUILDING OWNER
TO GET OUTDOOR LIGHTINGAPPROVED
A
4
DININGROOM208
05
BAR209
If this work is notproposed in the scope
of your permit then
please remove it from
your plans. If you areproposing exteriorlighting anywhere with
this permit then you
must submit an
exterior lightingComCheck.
DE
A
You are showing 108 seats not
counting the bar seating. 5% of
your seating is required to be
accessible which means that 6
accessible seats distributed
throughout the entire space are
required. Clearly identify these six
seats and demonstrate that they
meet ANSI requirements for
accessibility. All accessible seating
shall be on an accessible route.
DININGROOM
208
28.4
1
4
3
This elevation legend
does not match what
is actually shown on
sheet 8.4, please
revise so that the
numbering
corresponds to the
correct elevations.
the stacking is clarified on plan sheets and
door detail sheets
the doors have been changed to 5'-0" wide
it is not in the scope and has been
eliminated from the drawing set
6 accessible seats are shown
irrelevant elevations have been removed and
tags coordinated with remaining elevations
Subject: PlanCheck
Page Label: 3.6 UPPER LEVEL FURNITURE PLAN
Author: justinh
File Name: Permit Set.pdf
11 bar seats requires 1
accessible space with a
companion space. This does
not comply as drawn, clear
space must be forward facing
and pulled into the accessible
portion of the bar demonstrating
proper knee and toe clearance.
Both the required accessible
space and the companion space
must have the forward facing
30"x48" clear space.
Subject: PlanCheck
Page Label: 3.6 UPPER LEVEL FURNITURE PLAN
Author: justinh
File Name: Permit Set.pdf
Clearly show the existing doors
to remain on all proposed floor
plans.
Subject: PlanCheck
Page Label: 3.6 UPPER LEVEL FURNITURE PLAN
Author: justinh
File Name: Permit Set.pdf
Accessible clear spaces at
tables must be drawn forward
facing to demonstrate you have
the required clearance to sit at a
table, parallel clear spaces do
not work. The forward facing
clear space should also be
drawn tucked into the table a
minimum of 17" to demonstrate
the required knee and toe
clearance.
Subject: PlanCheck
Page Label: 3.6 UPPER LEVEL FURNITURE PLAN
Author: justinh
File Name: Permit Set.pdf
Show a 3' wide accessible route
through your tenant space that
connects all required exits, the
restrooms, and all accessible
seating. Required clear spaces
at accessible seating cannot
overlap into this 3' wide
accessible route.
Subject: PlanCheck
Page Label: 8.1 1/2 " INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Your detail references have the
wrong sheet, these are provided
on 7.2, please revise on all
elevation sheets.3/64"2'-2 43/64"
30"x48" CLEAR FLOORSPACE
DUMB WAITER BAR202
KITCHEN205
BACK BAR
COAT ROOM202
W
1&2
8.3
58.18.24
8.11
2
3
X
2 8.2
11 bar seats requires 1 accessible
space with a companion space. Thisdoes not comply as drawn, clearspace must be forward facing andpulled into the accessible portion ofthe bar demonstrating proper knee
and toe clearance. Both the required
accessible space and the companion
space must have the forward facing30"x48" clear space.
208
05
3
Clearly show the
existing doors to
remain on all proposed
floor plans.3'-0 33/64"TO EAST STAIRWELL
DININGROOM203
MEN'S204 WOMEN'S204
KITCHEN205
DININGROOM203
4
Accessible clearspaces at tables must
be drawn forward
facing to demonstrateyou have the required
clearance to sit at a
table, parallel clearspaces do not work.
The forward facing
clear space should
also be drawn tuckedinto the table a
minimum of 17" to
demonstrate therequired knee and toe
clearance.
BAR202
BACK BAR
Show a 3' wide accessible route through your tenant
space that connects all required exits, the restrooms,
and all accessible seating. Required clear spaces at
accessible seating cannot overlap into this 3' wide
accessible route. 6 1/4"47.5
Your detail references
have the wrong sheet,
these are provided on
7.2, please revise on
all elevation sheets.
accessible seating has been clarified and
shown in accordance with code
requirements. See furniture plan
the existing doors are shown
the required 17" is shown on the furniture
plan
the accessible route is shown on the
furniture plan
the tags have been revised to reflect the
accurate detail
Subject: PlanCheck
Page Label: 8.1 1/2 " INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Egress doors in spaces with
occupant loads greater that 50
are required to have compliant
panic/fire exit hardware per IBC
1010.1.10, this applies to doors
101, 102 and 103. Provide
cutsheets on the hardware and
show this on your elevations and
schedule.
Subject: PlanCheck
Page Label: 8.1 1/2 " INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Egress doors (doors 101, 102,
and 103) are required to have a
smooth surface on the bottom
10" of the push side per ANSI
404.2.9, provide cutsheets on all
swinging egress doors that
shows compliance with this
requirement.
Subject: PlanCheck
Page Label: 8.1 1/2 " INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Please verify that the coat room
will be for employee use rather
than patrons. If patrons are
hanging up their own coats then
an additional rack at a max
height of 48" must be provided
for accessibility.
Subject: PlanCheck
Page Label: 8.2 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
This is not an existing elevation,
you are showing the proposed
slider door. Please re-title the
elevation to accurately depict
what you are showing.
Subject: PlanCheck
Page Label: 8.3 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
This detail and page are not
included in this set. Provide
them or remove the reference.
67.557.5
47.5
FIXED MILLWORKFIXED GLAZINGFIXED GLAZINGFIXED MILLWORK
NEW FIXED GLAZING
FIXED MILLWORK
LLWORK
MOLDING
BASEG
N MOLDING
VATION
Egress doors in spaces with occupant loads
greater that 50 are required to have
compliant panic/fire exit hardware per IBC
1010.1.10, this applies to doors 101, 102and 103. Provide cutsheets on the hardware
and show this on your elevations and
schedule.
47.5
NEW FIXED GLAZING
FIXED MILLWORK
FIXED GLAZING
FIXED MILLWORK
G
ELEVATION Egress doors (doors
101, 102, and 103) are
required to have a
smooth surface on the
bottom 10" of the push
side per ANSI 404.2.9,
provide cutsheets on
all swinging egress
doors that shows
compliance with this
requirement.
57.5
47.5
OM 202 - ELEVATION 2 SCALE 1/2" = 1'-0"
COAT ROOM 202 - ELEVATION
Please verify that thecoat room will be for
employee use rather
than patrons. Ifpatrons are hanging
up their own coats
then an additional rackat a max height of 48"
must be provided for
accessibility.8'-9 1/2"8'-3"PAINTEDMILLWORK
OPEN AIRCORRIDOR
3 SCALE 1/2" = 1'-0"
DINING ROOM - EXISTING FOR HPC REFERENCE
This is not an existing
elevation, you are
showing the proposedslider door. Please
re-title the elevation to
accurately depict what
you are showing.
X7.5
This detail and page
are not included in this
set. Provide them or
remove the reference.
cutsheet has been provided and doors
revised in drawings to show
compliance
the 10" is dimensioned on the
elevations
see revised elevations and plans. Coat
room has been eliminated.
Elevation tags and labels have been updated
on furniture plans and elevation sheets
Tags have been revised and coordinated
Subject: PlanCheck
Page Label: 8.3 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Provide a side view elevation for
the accessible portion of the bar
demonstrating the required knee
and toe clearance. The
accessible portion of the bar will
need to be at least 60" long to
accommodate the one required
space plus a companion.
Revise and dimension the length
of the accessible bar top on all
applicable floor plans and
elevations.
Subject: PlanCheck
Page Label: 8.5 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
TP dispenser is required to be a
minimum of 18" above the floor
and the outer end must be within
42" of the back wall (see ANSI
fig. 604.7), please revise for both
restrooms.
Subject: PlanCheck
Page Label: 8.5 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Please dimension the size of the
knee and toe clearance you've
drawn for both restrooms to
show compliance with ANSI 306.
Subject: PlanCheck
Page Label: 8.5 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Bottom edge of the mirror can
only be a maximum of 40" above
the floor (ANSI 603.3), please
revise for both restrooms.
Subject: PlanCheck
Page Label: 8.5 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Operable part of the toilet must
be on the side facing the open
restroom, show this to
demonstrate compliance for both
restrooms. 2'-10"4'-2"
E 1/2" = 1'-0"
R 202 ELEVATION Provide a side view elevation for the
accessible portion of the bar demonstrating the
required knee and toe clearance. The
accessible portion of the bar will need to be at
least 60" long to accommodate the one
required space plus a companion. Revise and
dimension the length of the accessible bar top
on all applicable floor plans and elevations.1'-3"2'-4 7/8"TP HOLDERMOUNTING
1 MEN'S RESTROOM
SCALE 1/2" = 1'-0"1
TP dispenser is
required to be a
minimum of 18" above
the floor and the outer
end must be within 42"
of the back wall (see
ANSI fig. 604.7),
please revise for both
restrooms.5'-7"2'-3 1/2"6 1/2"1'-10"3'-4 7/8"7'-4"PAPERTOWE +TRAS
ANSI CLEARANCE
1 SCALE 1/2" = 1'-0"1 S
MEN'S RESTROOM M
Please dimension the
size of the knee and
toe clearance you've
drawn for both
restrooms to show
compliance with ANSI
306.
2'-11 3/4"
11 3/4"2'-0"1'-6"6"
7'-1 3/4"
STAINLESS STEELGRAB BARSINSTALLED PER2003 ANSI A117.1
3" MEDIUM CHER WOOD FRAME
MIRROR
BATH 6 -LIGHTBRONZE, 7'-0" AFF
LAMINATE VANITYAND BACKSPLASHWITH SOLID COLORCORE
Bottom edge of the
mirror can only be a
maximum of 40"
above the floor (ANSI
603.3), please revise
for both restrooms.3'-0"1'-6WALLCOVERING
1 SCALE 1/2" = 1'-0"1MEN'S RESTROOM
Operable part of the
toilet must be on the
side facing the open
restroom, show this to
demonstrate
compliance for both
restrooms.
Bar location changed and section
through ANSI bartop provided
Exist. TP holder shown with compliant
dimensions
Knee and toe clearance dimensioned
revised
operable handle shown
Subject: PlanCheck
Page Label: 8.5 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
Please dimension the height of
the paper towel dispenser at the
point where the towels are
dispensed. Maximum height is
48", please revise for both
restrooms.
Subject: PlanCheck
Page Label: 8.5 1/2" INTERIOR ELEVATIONS
Author: justinh
File Name: Permit Set.pdf
The horizontal side bar is
required to extend out 54"
minimum from the back wall (see
ANSI fig. 604.5.1), please revise
for both restrooms.
Subject: PlanCheck
Page Label: 8.6 HPC ELEVATION STUDY
Author: justinh
File Name: Permit Set.pdf
This does not match the slider
door you show on sheet 10.1,
there is an additional slider
section, the overall length does
not match, and you are not
showing the swinging man door.
Please revise.
Subject: PlanCheck
Page Label: 10.1 DOOR & WINDOW SCHEDULES
Author: justinh
File Name: Permit Set.pdf
Provide cutsheets on all new
proposed fenestration showing
compliant U values per IECC
C402.4.
Subject: PlanCheck
Page Label: 10.1 DOOR & WINDOW SCHEDULES
Author: justinh
File Name: Permit Set.pdf
The swinging man door potion of
the slider door system is
required to have a compliant 10"
smooth surface at the bottom of
the door and panic hardware just
like all other required egress
doors. Provide cutsheets
demonstrating compliance.5'-7"6'-8"2'-3 1/2"6 1/2"4 7/8"1'-10"3'-4 7/8"7'-1 3/4"7'-4"5'-8 1/4"
3'-5"4 3/4"3'-4"5"WALLCOVERING
PAPERTOWEL+TRASH
4" BASE PAINTED TOMATCH DINING ROOM,TYP.
DOOR TOHALLWAY
WALLCOVERING
3" MEDIUM CHERRYWOOD FRAME
ANSI CLEARANCE
1 SCALE 1/2" = 1'-0"1 SCALE 1/2" = 1'-0"
MEN'S RESTROOM MEN'S RESTROOMPlease dimension the
height of the paper
towel dispenser at the
point where the towelsare dispensed.
Maximum height is
48", please revise for
both restrooms.7'-4"2'-10"
3'-6"6"
5'-8 1/4"
STAINLES GRAB BAR INSTALLED 2003 ANSI
MEN'S
205 UH-1
The horizontal side
bar is required to
extend out 54"
minimum from the
back wall (see ANSI
fig. 604.5.1), please
revise for both
restrooms.
EXIST. STOREFRONTWINDOW/DOOR SYSTEM
NEW FIXED WINDOW
EXIST. AWNING TOREMAIN
LINE OF EXIST. ROOF TOREMAIN
EDGE OF BUILDING
EX
NEW BRICK TO MATCHEXIST.NEW SINGLE TRACKSLIDING WINDOW/DOORSYSTEM
DINING203
MECHANICAL CHASE
EXISTING STOREFRONTWINDOWS TO REMAIN PATIO206
BEYOND
MECHANICAL CHASE
1 SCALE 1/2" = 1'-0"DINING ROOM - EXTERIOR ELEVATION (EXIST.)
1 SCALE 1/2" = 1'-0"DINING ROOM - EXTERIOR ELEVATION (NEW)This does not matchthe slider door youshow on sheet 10.1,there is an additionalslider section, theoverall length does notmatch, and you arenot showing theswinging man door. Please revise.1 1/2"1 1/2"
5'-0"
7'-0"1 1/2"1 1/2"5'-0"3'-6"1 1/2"1 1/2"3'-6"
2 1/2"
2 1/2"1 1/2"1 1/2"24'-4 1/2"
WINDOW 'B'3/4" = 1'-0"WINDOW 'A'3/4" = 1'-0"
WIDTH HEIGHT
101FIXED 3'-6"5'-0"7'-0"WOOD A 17.5 0.29
102FIXED 3'-6"5'-0"7'-0"WOOD A 17.5 0.29
103FIXED 3'-6"5'-0"7'-0"WOOD A 17.5 0.29
104FIXED 3'-6"5'-0"7'-0"WOOD A 17.5 0.29105FIXED7'-0"5'-0"7'-0"WOOD B 35 0.29106FIXED7'-0"5'-0"7'-0"WOOD B 35 0.29107FIXED7'-0"5'-0"7'-0"WOOD B 35 0.29
WINDOW SCHEDULE
ID AREASIZE COMMENTSSTYLEU-VALUEHEAD HEIGHT TYPEFRAME MATERIAL
WIDTH HEIGHT
101FIXED 4'-0"7'-0"7'-0"WOOD A 17.5 0.29 Emergency Egress hardware req.
102FIXED 4'-0"7'-0"7'-0"WOOD A 17.5 0.29 Emergency Egress hardware req.
103FIXED 24'-4 1/2"5'-0"7'-0"WOOD A 17.5 0.29 Single Track Slider System w/ man door
DOOR SCHEDULE
ID AREASIZE COMMENTSSTYLEU-VALUEHEAD HEIGHT TYPEFRAME MATERIAL
Provide cutsheets onall new proposedfenestration showingcompliant U valuesper IECC C402.4.5
PROJECT No:DRAWN BY:
DRAWING
COPYRIGHT 2018 A CORPS LLC. ALL R
DOOR & W
SCHEDULE
10
IFFR PERMIT
PERMIT SET
24'-4 1/2"
0 1'2'3'
The swinging man door potionof the slider door system isrequired to have a compliant
10" smooth surface at thebottom of the door and panichardware just like all other
required egress doors. Provide cutsheetsdemonstrating compliance.
Dimensions provided.
Revised
revised and coordinated
nana door correspondence provided
10" compliant smooth surface and note
regarding panic hardware exception
provided
I do not see where this was
provided, please clarify or
submit documentation of nana
wall U values. We want to
avoid a situation where an wall
system that does not meet
IECC requirements is installed
and the issue is not caught
until inspection.
Subject: PlanCheck
Page Label: 10.1 DOOR & WINDOW SCHEDULES
Author: justinh
File Name: Permit Set.pdf
This door does not match any
door shown on your schedule or
applicable elevations. Please
revise.
Subject: PlanCheck
Page Label: 10.1 DOOR & WINDOW SCHEDULES
Author: justinh
File Name: Permit Set.pdf
Door type B is not referenced on
your schedule, please revise
your schedule for consistency.1 1/2"1 1/2"7'-0"3'-6"
2 1/2"2 1/2"1 1/2"1 1/2"7'-0"WINDOW 'B'
3/4" = 1'-0"
WINDOW 'A'
3/4" = 1'-0"
DOOR 'A'
3/4" = 1'-0"
DOOR 'B'
3/4" = 1'-0"
SCALE: 3/4" = 1'-0"1 DOOR AND WINDOW ELEVATIONS
This door does not
match any door shown
on your schedule or
applicable elevations. Please revise.7'-0"DOOR 'B'
3/4" = 1'-0"VATIONS
Door type B is not
referenced on your
schedule, please revise your
schedule for consistency.
door dimensioned coordinated
notes and dimensions and tags
coordinated