HomeMy WebLinkAboutFile Documents.525 E Cooper Ave.0061.2018 (2).ACBK0061-2018-ACBK_BuildingComment2
Subject: PlanCheck
Page Label: 6
Author: justinh
File Name: 0061-2018-ACBK_BuildingComment1 (002).pdf
I do not see where this was
provided, please clarify or submit
documentation of nana wall U
values. We want to avoid a
situation where an wall system
that does not meet IECC
requirements is installed and the
issue is not caught until
inspection.
0061-2018-ACBK_BuildingComment1 (002).pdf (1)
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
No cutsheet was submitted for
fixtures TL1, P1 or P2. I cannot
approve a ComCheck that uses
fixtures that have not been
selected as the lighting plan
indicates. Provide cutsheets for
these fixtures that give max
fixture wattage and NRTL
listings. Lamps and other
fixtures that are plugged in do
not need to be included in the
ComCheck, only permanently
wired fixtures should be
included.
525 Permit Set_revised comments (002).pdf (9)
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
Per the cutsheets submitted
these are 40W fixtures, not 4w.
I cannot accept the wattage of a
proposed bulb, energy code
requires me to use maximum
fixture wattage. If you want to
use the bulb wattage a current
limiting device must be installed
to limit the power consumption to
the desired level. If you wish to
do that please submit a cutsheet
on the proposed current limiting
device and call it out in the
plans.
Subject: PlanCheck
Page Label: 7
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
These doors must each have
one leaf that provides a clear
width of 32" to comply as egress
doors per IBC 1010.1.1. If you
want both leaves to be the same
size the minimum clear width of
the doors (measured with the
doors in open 90 degrees) is 64"
clear. A 5'0" door does not meet
the requirement, previous
comment still stands.
Subject: PlanCheckPage Label: 8.5 1/2" INTERIOR ELEVATIONSAuthor: justinh
File Name: Permit Set.pdf
The horizontal side bar isrequired to extend out 54"minimum from the back wall (see
ANSI fig. 604.5.1), please revisefor both restrooms.
Subject: PlanCheckPage Label: 8.6 HPC ELEVATION STUDYAuthor: justinhFile Name: Permit Set.pdf
This does not match the sliderdoor you show on sheet 10.1,there is an additional slidersection, the overall length does
not match, and you are notshowing the swinging man door.
Please revise.
Subject: PlanCheckPage Label: 10.1 DOOR & WINDOW SCHEDULES
Author: justinhFile Name: Permit Set.pdf
Provide cutsheets on all newproposed fenestration showingcompliant U values per IECCC402.4.
Subject: PlanCheck
Page Label: 10.1 DOOR & WINDOW SCHEDULESAuthor: justinh
File Name: Permit Set.pdf
The swinging man door potion of
the slider door system isrequired to have a compliant 10"
smooth surface at the bottom ofthe door and panic hardware justlike all other required egressdoors. Provide cutsheetsdemonstrating compliance.7'-4"2'-10"
3'-6"6"
5'-8 1/4"
STAINLES GRAB BAR INSTALLED 2003 ANSI
MEN'S205 UH-1
The horizontal sidebar is required toextend out 54"minimum from theback wall (see ANSIfig. 604.5.1), pleaserevise for bothrestrooms.
EXIST. STOREFRONTWINDOW/DOOR SYSTEM
NEW FIXED WINDOW
EXIST. AWNING TOREMAINLINE OF EXIST. ROOF TOREMAINEDGE OF BUILDING
EX
NEW BRICK TO MATCHEXIST.NEW SINGLE TRACKSLIDING WINDOW/DOORSYSTEM
DINING203
MECHANICAL CHASE
EXISTING STOREFRONTWINDOWS TO REMAIN PATIO206BEYOND
MECHANICAL CHASE
1SCALE 1/2" = 1'-0"DINING ROOM - EXTERIOR ELEVATION (EXIST.)
1SCALE 1/2" = 1'-0"DINING ROOM - EXTERIOR ELEVATION (NEW)This does not matchthe slider door youshow on sheet 10.1,there is an additionalslider section, theoverall length does notmatch, and you arenot showing theswinging man door. Please revise.
1 1/2"1 1/2"
5'-0"
7'-0"1 1/2"1 1/2"
5'-0"
3'-6"
1 1/2"1 1/2"3'-6"2 1/2"2 1/2"1 1/2"1 1/2"24'-4 1/2"WINDOW 'B'3/4" = 1'-0"WINDOW 'A'3/4" = 1'-0"
WIDTHHEIGHT101FIXED3'-6"5'-0"7'-0"WOOD A 17.5 0.29102FIXED3'-6"5'-0"7'-0"WOOD A 17.5 0.29103FIXED3'-6"5'-0"7'-0"WOOD A 17.5 0.29104FIXED3'-6"5'-0"7'-0"WOOD A 17.5 0.29105FIXED7'-0"5'-0"7'-0"WOOD B 35 0.29106FIXED7'-0"5'-0"7'-0"WOOD B 35 0.29107FIXED7'-0"5'-0"7'-0"WOOD B 35 0.29
WINDOW SCHEDULEID AREASIZE COMMENTSSTYLEU-VALUEHEAD HEIGHT TYPEFRAME MATERIAL
WIDTHHEIGHT101FIXED4'-0"7'-0"7'-0"WOOD A 17.5 0.29Emergency Egress hardware req.102FIXED 4'-0"7'-0"7'-0"WOOD A 17.5 0.29Emergency Egress hardware req.103FIXED 24'-4 1/2"5'-0"7'-0"WOOD A 17.5 0.29Single Track Slider System w/ man door
DOOR SCHEDULEID AREASIZE COMMENTSSTYLEU-VALUEHEAD HEIGHT TYPEFRAME MATERIAL Provide cutsheets onall new proposedfenestration showingcompliant U valuesper IECC C402.4.5
PROJECT No:DRAWN BY:
DRAWING COPYRIGHT 2018 A CORPS LLC. ALL R
DOOR & W SCHEDULE
10
IFFR PERMITPERMIT SET
24'-4 1/2"
0 1'2'3'
The swinging man door potionof the slider door system isrequired to have a compliant10" smooth surface at thebottom of the door and panichardware just like all otherrequired egress doors. Provide cutsheetsdemonstrating compliance.
I do not see where this was
provided, please clarify or
submit documentation of nanawall U values. We want to
avoid a situation where an wall
system that does not meet
IECC requirements is installedand the issue is not caught
until inspection.
DL1: DL1: Amerlux 4" IC rated: LED A Lamp 9W:1 11
P3: P3: RH 20 Century Factory filament: Other:1 9
Behind Bar linear: L3: AlloyLED Varian 5.5: LED Linear 8W:1 50
Common Space Types:Dining Area - Family Restaurant (1208 sq.ft.)
DL1: DL1: Amerlux 4" IC rated: LED A Lamp 9W:1 45
WS1: WS1: GASLIGHT LENS GRAND SCONCE: Other:1 8
Fireplace linear: L2: AllowLED Varian 5.5: LED Linear 8W:1 8
Coffee Table pendant: P1: Lamp L: LED A Lamp 11W:1 1 2
Living Room Lamps: TL1: Lamp L: LED A Lamp 11W:1 2
Dining Pendant: P2: Lamp L: LED A Lamp 11W:1 1 2
Total Proposed W
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consist
building plans, specifications, and other calculations submitted with this permit application. The proposed interio
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.0.0 and to comply w
applicable mandatory requirements listed in the Inspection Checklist.
Interior Lighting PASSES
Project Title:
Data filename:
525 E Cooper Ave
C:\Users\Michael\Dropbox (Alius Design Corps)\Alius Design Corps Team Folder\1801-BB
Remodel\Documents\Permit\525 E CooperME.cck
Repo
1 compliance-reportLEAX lighting
No cutsheet was submitted for fixtures TL1,
P1 or P2. I cannot approve a ComCheck
that uses fixtures that have not been
selected as the lighting plan indicates.
Provide cutsheets for these fixtures that give
max fixture wattage and NRTL listings.
Lamps and other fixtures that are plugged in
do not need to be included in the
ComCheck, only permanently wired fixtures
should be included.
E
(C X D)
D
Fixture
Watt.
ge Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
sure (463 sq.ft.)
1 11 12 132
1 9 4 40
8W:1 50 6 275
ant (1208 sq.ft.)
1 45 12 540
:1 8 4 36
W:1 8 6 44
1 1 200 200
1 2 20 40
1 1 200 200
1508Total Proposed Watts =
ng alteration project represented in this document is consistent with the
submitted with this permit application. The proposed interior lightingC requirements in COMcheck Version 4.1.0.0 and to comply with any
pection Checklist.
ign Corps)\Alius Design Corps Team Folder\1801-BB
CooperME.cck
07/05/18Report date:
61 ofPage
Project Title:
Data filename:
525 E Cooper Ave
C:\Users\Michael\Dropbox (Alius De
Remodel\Documents\Permit\525 E
e-reportLEAX lighting 2 compliance
Per the cutsheets submitted
these are 40W fixtures, not 4w.
I cannot accept the wattage of a
proposed bulb, energy code
requires me to use maximum
fixture wattage. If you want to
use the bulb wattage a current
limiting device must be installed
to limit the power consumption to
the desired level. If you wish to
do that please submit a cutsheet
on the proposed current limiting
device and call it out in the
plans.
101
101
103
102
104
102
43
3'-6"6'-2"5 1/2"3'-2"9'-4"9 1/2"3 1/2"6'-7/8"3 1/2"9'-5 1/4"5 1/2"
2'-1/2"5 1/2"6"7 1/2"EQ.EQ.1'-7"EXISTING MONTIGO H38D FLUE CLEARANCE - 16" FR 10'-0" FROM CENTERLINE AVENUE, 10'-0" FROM ADJ
EXISTING WEST STAIRWELL
EXISTING ROOFDRAIN & COLUMNTO REMAIN
ICALBOVE
EXIST. COORIDOR DIM.TO BE MAINTAINED
EXIST. BAR WALLTO REMAIN; V.I.F.
QUIP.;DULE
LOUNGE
208ANSI BAR TOPCL
W1
CL
EXISTING COLUMNTO REMAIN; TYP.
These doors must each have one
leaf that provides a clear width of
32" to comply as egress doors per
IBC 1010.1.1. If you want both
leaves to be the same size the
minimum clear width of the doors
(measured with the doors in open90 degrees) is 64" clear. A 5'0"door does not meet the
requirement, previous comment still
stands.
Subject: PlanCheck
Page Label: 8
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
Where seating is back to back a
minimum of 50" is required
between tables to provide
adequate clearance per IBC
1029.12.1 (12" aisle accessway
+ treq'd 19" clearance at each
table). You are not providing
this clearance where the 6 top
tables are provided. See
attached marked up plan for
more info.
Subject: PlanCheck
Page Label: 8
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
Please show the clear travel
path not being encroached by
the stacked door location, it
appears that you should have
plenty of room to re-align it
around this area.
Subject: PlanCheck
Page Label: 15
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
This was not revised as the
response indicated. The
horizontal side grab bar must
extend a total of 54" from the
rear wall, see ANIS figure
604.5.1 for a clear example of
compliant grab bars. This will
need to be brought into
compliance for both restrooms.
Previous comment still stands.
Subject: PlanCheck
Page Label: 15
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
This TP holder needs to be
relocated to a compliant location,
regardless of whether it is
existing or not. The IEBC allows
for up to 20% of a projects
valuation to be required to be put
towards accessibility
improvements, both restrooms
will need to be made fully
compliant during this remodel.
Previous comment still stands.
Subject: PlanCheck
Page Label: 18
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
U values for the french doors
could be as high as .77 for an
entrance door, the sliding wall
system is considered operable
fenestration and has a maximum
U value of .37. Please revise.
01T-R.06.023'-8"3'-10"2'-10"2'-6"4'-0"5'-2 13/16"2'-3 1/16"LINE OF CLEAR TRAVELPATH
30"x48" CLEAR FLOORSPACE
EE SHEET 8.3 FORR ELEVATIONS OFIST. BATHROOMS
ACCESSIBLE TABLE HEIGHT@ 34" A.F.F.
ACCESSIBLE TABLE HEIGHT@ 34" A.F.F.
DOOR STACK LOCATIONS
TO EAST STAIRWELL
DINING ROOM203
WOMEN'S204
PATIO206
LOUNGE208
30
12
40ACCESSIBLE TABLE HEIGHT@ 34" A.F.F.
38.1
18.12
8.22 8.2
20
8.4
1&2
8.5
1&2
3
Where seating is back to back
a minimum of 50" is requiredbetween tables to provideadequate clearance per IBC1029.12.1 (12" aisle accessway+ treq'd 19" clearance at each
table). You are not providingthis clearance where the 6 toptables are provided. Seeattached marked up plan formore info.
3'-10"
LINE OF CLEAR T
SEE SHEET 8.3 FOR
INTERIOR ELEVATIONS OFEXIST. BATHROOMS
DOOR STACK LOCATIONS
TO EAST STAIRWELL
WOMEN'S
204
ACCESSIBLE TABLE H @ 34
8.4
1&2
Please show the clear
travel path not being
encroached by the
stacked door location,
it appears that you
should have plenty of
room to re-align it
around this area.7'-4"2'-10"
3'-6"6"6'-8"3'-5 1/8"5"3'-4"5'-8 1/4"
STAINLESS STEELGRAB BARSINSTALLED PER2003 ANSI A117.1
MEN'S
2051 UH-1
DOOR TOHALLWAY
This was not revised as the response indicated.
The horizontal side grab bar must extend a total of
54" from the rear wall, see ANIS figure 604.5.1 for
a clear example of compliant grab bars. This will
need to be brought into compliance for both
restrooms. Previous comment still stands.
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS7'-4"2'-10"
3'-6"6"1'-3"7/8"
SCALE 1/2" = 1'-0"
EXIST. WOMEN'S RESTROOM
This TP holder needs to be relocated
to a compliant location, regardless of
whether it is existing or not. The
IEBC allows for up to 20% of a
projects valuation to be required to
be put towards accessibility
improvements, both restrooms will
need to be made fully compliant
during this remodel. Previous
comment still stands.
A 35 .38 min.Emergency Egress panic hardware req.
A 35 .38 min.Emergency Egress panic hardware req.
B 243 .38 min.Single Track Slider System w/ man door
B 98 .38 min.Single Track Slider System w/ man door
AREA COMMENTSU-VALUETYPE
U values for the french
doors could be as high
as .77 for an entrance
door, the sliding wall
system is considered
operable fenestration
and has a maximum
U value of .37. Please
revise.
Subject: PlanCheck
Page Label: 19
Author: justinh
File Name: 525 Permit Set_revised comments (002).pdf
Daylight responsive controls are
also required per IECC
C405.2.3. Please show sidelight
and toplight daylight zones on
the lighting plan per IECC
405.2.3.2 and 405.2.3.3 and call
the daylight responsive controls
on the plan.
ES
g Element cans
g Element cans
g Element cans
g Element cans
AH
DATE:
DRAWN BY:
CHECKED BY:
ISSUE:
DESIGN DEVELOPMENT525 EAST COOPERAspen, COLighting Controls
This design provides for lighting control system
allowing for at least 4-8 lighting scenes per area.
The system will be programmed to operate from an
astronomical time clock with scenes to fade from one
to the next very slowly so as to be mostly imperceptible
to the customers.
Dimming of cans down to 1% brightness
Suitable controls would be Lutron/Crestron or Vantage
control.
CJ
Feb 26, 2018
Daylight responsivecontrols are alsorequired per IECCC405.2.3. Please
show sidelight and
toplight daylight zoneson the lighting plan perIECC 405.2.3.2 and
405.2.3.3 and call the
daylight responsivecontrols on the plan.