HomeMy WebLinkAboutFile Documents.515 E Hopkins Ave.0120.2018 (9).ACBKBootsyBellows_BuildingComment2 Subject: PlanCheck Page Label: 3 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf That is a 2009 IBC code reference, please revise to be 1004.4 which is the correct code section reference in the 2015 edition. 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf (13) Subject: PlanCheck Page Label: 3 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf I recalculated the occupant load for the green room and VIP room by using room SF minus an accessible route at the unconcetrated assembly rate (15 SF per occupant which assumes a mix of tables and chairs, I thought that seemed fair as there will be some furniture in place). I came up with an occupant load of 10 in the VIP room and 6 in the green room. Please revise the numbers for these two spaces on the seating count table, we want to give you the maximum occupant load that the space allows. This would increase the total seating count to 84, please revise the occupant load table using the 84 seats + 120 occupants + 10 employees for a total occupant load of 214. Be sure to revise the accessible table row as well, 84 x .05 = 74.2 which we would round up to 5 required accessible seats. You will want to show an additional accessible seat at one of the tables in the main area but now that you don't have raised platforms that shouldn't be an issue. Subject: PlanCheck Page Label: 4 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf OCCUPANT LOAD: SQFT (PER 1004.4) / 15 WITH 'RESIDENTIAL FURNITURE'SQFT / 5 WHEN FURNITURE REMOVED +FIXED SEATING AREAS (1004.7) 1 PERSON / 24" OF BOOTH SEAT LOUNGE 120 O 195 O That is a 2009 IBC code reference, please revise to be 1004.4 which is the correct code section reference in the 2015 edition. All ideas, designs, arrangements and 119 South Spring St Suite 203Aspen, CO 81611 970-925-3444 970-920-2186TEL FAX FIRE SEPARATION KEY: SEATING COUNTS:BAR STANDING ONLYLOUNGE (FIXED SEATING)VIPGREEN ROOMTOTALACCESSIBLE TABLES 76 X .05 = 4 686276 6 7 EXIT ACCESS TRAVEL DISTANCE3' TO NEAREST EXIT 1 HR RATED WALL 1 HR RATED FLOOR/CEILING/ROOF ASSEMBLY 1/2 HR RATED WALLB A A.3 OCCUPANT LOAD:SQFT (PER 1004.4) / 15 WITH 'RESIDENTIAL FURNITURE'SQFT / 5 WHEN FURNITURE REMOVED+FIXED SEATING AREAS (1004.7)1 PERSON / 24" OF BOOTH SEAT LOUNGE 602SQFT /5120 OCCUPANTS+ 89195 OCCUPANTS I recalculated the occupant load for the green room andVIP room by using room SF minus an accessible route at the unconcetrated assembly rate (15 SF per occupant which assumes a mix of tables and chairs, I thought thatseemed fair as there will be some furniture in place). Icame up with an occupant load of 10 in the VIP room and6 in the green room. Please revise the numbers for these two spaces on the seating count table, we want to give you the maximum occupant load that the space allows. Thiswould increase the total seating count to 84, please revisethe occupant load table using the 84 seats + 120occupants + 10 employees for a total occupant load of 214. Be sure to revise the accessible table row as well, 84 x .05 = 74.2 which we would round up to 5 required accessibleseats. You will want to show an additional accessible seatat one of the tables in the main area but now that you don't have raised platforms that shouldn't be an issue.2'-0"4'-0" F F 7'-0"<-30"x48" Revised. Thanks for the ruling here. The table has been updated and an additional accessible seat has been added to the plan. Assuming you want the sink clearance here 11/19/2018 Subject: PlanCheck Page Label: 4 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf Show the required forward approach at one of your urinals and reference your standard details on G1.07 for urinal height. Subject: PlanCheck Page Label: 4 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf For the new sinks in each restroom please note that they will have compliant knee and toe clearance per you standard accessibility details on sheet G1.07. Show a 30"x48" forward approach at one sink basin in each restroom, this should be drawn tucked in 17" demonstrating compliant knee and toe clearance. Subject: PlanCheck Page Label: 4 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf Show that you have compliant forward approach at the sink. This is a new restroom and must comply fully, it does not appear that you have the required clear space at the sink for accessibility or the required fixture clearance from the wall to center of the fixture as required by IPC 405 (15"). Subject: PlanCheck Page Label: 4 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf Approaches at the accessible seats should be shown as forward approaches as required by A117.1 902.2 (similar to what is shown at the bar). Subject: PlanCheck Page Label: 4 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf In the accessible stalls show the required water closet clearances per A117.1 section 604.3 (60" wide and 56"deep) rather than a 60" turn around. C D 1'-10"1'-8"2'-0"4'-0" R 2'-6" R 2'-6" R 2'-6" R 2'-6" DW C F F F F 1'-6" 1'-6"7'-0"4'-91/4"<-30"x48"<-30"x48" RE:G1.04-1.07 NO CHANGES TOLAYOUT, FIXTURES ORCLEARANCES. ASEXISTS. EXISTS. Show the required forward approach at one of your urinals and reference your standard details on G1.07 for urinal height. C 11/4" 3'-0" 34" max typ. 34" max typ. R 2'-6" R 2'-6" R 2'-6" R 2'-6" R 2'-6" C C C C C F F B 1'-6 " 1'-6"1'-10" 1'-6"7'-0"4'-91/4"<-30"x48"30"x48"-> 30 " x 4 8 " 30" x 4 8 " 30"x48" <-30"x48" 30"x48" RE:G1.04-1.07 NO CHANGES TOLAYOUT, FIXTURES ORCLEARANCES. ASEXISTS. NO CHANGES TOLAYOUT, FIXTURES ORCLEARANCES. ASEXISTS. 2. ALL DOORS SERVING TYPE A UNIT MUST HAVE HARDW OR TWISTING OF THE WRIST TO OPERATE. EXISTING COMP COMPLY WITH:A117.1-2009 1003.5 & 1004.5.1 For the new sinks in each restroom please note that they will have compliant knee and toe clearance per you standardaccessibility details on sheet G1.07. Show a 30"x48" forward approach at one sink basin in each restroom, this should bedrawn tucked in 17" demonstratingcompliant knee and toe clearance. D E1'-10"1'-8"2'-0"4'-0" R 2'-6" R 2'-6" DW C C F F F F 1'-6"7'-0"4'-91/4" <-30"x48" RE:G1.04-1.07 Show that you have compliant forward approach at the sink. This is a new restroom and must comply fully, it does not appear that you have the required clear space at the sink for accessibility or the required fixture clearance from the wall to center of the fixture as required by IPC 405 (15"). 5'-11/4" 8" 3'-0" 34" max typ. 34" max typ. 34" max typ. R 2'-6" C C C C C 1'-6"1'-10" 1'-6"1'-6"<-30"x48"<-30"x48"30"x48"->30"x48"-> 30"x48"-> 30"x 4 8 " 30"x 4 8 " 30"x48" 30"x48 " 30"x48" 60" ADJUSTABLE BARTOP @ 34" A.F.F. W/30X48 CLEAR FOWARDAPPROACHRE: G1.03 & A7.01 COMMISSIONED SPACE OUTSIDE OF LEASE Approaches at the accessible seats should be shown as forward approaches as required by A117.1 902.2 (similar to what is shown at the bar). C R 2'-6" R 2'-6" R 2'-6" F F 6"7'-0"4'-91/4" RE:G1.04-1.07 NO CHANGES TOLAYOUT, FIXTURES ORCLEARANCES. ASEXISTS. NO CHANGES TOLAYOUT, FIXTURES ORCLEARANCES. ASEXISTS. In the accessible stalls show the required water closet clearances per A117.1 section 604.3 (60" wide and 56"deep) rather than a 60" turn around. Forward approach shown and detail referenced. Forward approach shown and detail referenced. Revised Revised to be compliant with fixture clearance shown and dimensioned. Revised 11/19/2018 Subject: PlanCheck Page Label: 11 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf This does not appear to be an existing walk in cooler per the demo plan, provide cutsheets on the walk in cooler that show compliance with IECC C403.2.15 or C403.2.16. If this is a relocated walk in you must still demonstrate that it complies with code. Subject: PlanCheck Page Label: 11 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf These doors cannot be locked as they provide exit access to the spaces around yours. Are you proposing any method of securing your unit from the common area here? Please verify that the door from the exit vestibule to the elevator lobby has panic hardware. Subject: PlanCheck Page Label: 11 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf You are using this door tag twice. Please identify note that panic hardware is required on this door on the schedule. Subject: PlanCheck Page Label: 13 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf Be sure you are consistently taging you sheets, this does not match what is shown on the plan title under your RCP. Please double check that all sheets are labeled consistently. Subject: PlanCheck Page Label: 14 Author: justinh File Name: 204 Galena St. Bootsy Bellows. Permit Drawings.2018.10 marked up round 2.pdf The relocated lighting is considered to be altered luminaires, which puts you over the 10% limit for the exception to IECC C503.6. Please remove this table as well as all references to the 10% alteration exception. I will create the ComCheck for your space using your layout and the luminaire schedule from the previous tenant's permit set. Show your theatrical lighting on this plan and provide me with a cutsheet or more information on it. It is exempt but should still be shown on the plan and recorded as an exempt fixture on the ComCheck. (2 FR R 3 FR R 9" R5" RE 3 FR G 10" RLO W S 5" L3 FR (M 5" WRTAG QUANI 1 2 3 4 5 6 7 8 10 C D 103 2 400020304 05 5WR 5WR1 5 3/4 5 9DW SEE G1.03-05 FORACCESSIBLE BATHDETAILS C C C C C F F F F MEN'S122 128STAFF BATH 129DRY STROAGE 133GREEN RM.WALK IN(EXISTING)126DISH PIT 119OFFICE 124AUDIO/VISUAL This does not appear to be an existing walk in cooler per the demo plan, provide cutsheets on the walk in cooler that show compliance with IECC C403.2.15 or C403.2.16. If this is a relocated walk in you must still demonstrate that it complies with code. 5 6 7 07 2 11 ELEV. 104 ELEV. LOBBY103 EXIT VESTIBULE102 SPRINKLER107 123COAT CHECK These doors cannot be locked as they provide exit access to the spaces around yours. Are you proposing any method of securing your unit from the common area here? Please verify that the door from the exit vestibule to the elevator lobby has panic hardware. E F E.7 400 015 5 1 1 07 C C C TEMPERED GLASSINSTALLED PER MANUFACTURER'S SPECSEE A7.01 GREASE INTERCEPTOR EGRESS STAIR116 133 GREEN RM. HALL101 NOTES/REMARKS LOCATED TO NEW POSITION LOCATED TO NEW POSITION LOCATED TO NEW POSITION LOCATED TO NEW POSITION You are using this door tag twice. Please identify note that panic hardware is required on this door on the schedule. DRAWN BY: PROJECT No:1801 CPF A1.07 LOWER LEVEL FLOORPLAN DEMO Sheet No. 0 4'8'12' Be sure you are consistently taging you sheets, this does not match what is shown on the plan title under your RCP. Please double check that all sheets are labeled consistently. All ideas, designs, arrangemen indicated or represented by this owned by and are the property of D Architects, PC and developed fo conjunction with the specified of the ideas, designs, arrangem shall be used by or disclosed fo whatsoever without the written 119 South Sprin Suite 203Aspen, CO 81 970-925-3 970-920-2 TELFAX LIGHTING FIXTURE COUNTS:FIXTURE TYPE EXISTING NEW DELTAA 15 15 0B 7 7 0C 26 24 2D 1 0 1E 4 4 0F 6 5 1TOTAL 59 55 4PERCENTAGE OF CHANGE 7% 6 7 GRID SYSTEM A.C.T.CEILING TILE WALL STUD8" - 18GA. CSJ8" - 18GA. CSJ@ 24" O.C. SCALE:SUSPENSION SYSTEM DETAILN.T.S.1 B A A.3 EXISTING FIXTURE IN NEW LOCATION.LESS THAN 10% CHANGE. EXISTING FIXTURE IN NEW LOCATION.LESS THAN 10% CHANGE. The relocated lighting is considered tobe altered luminaires, which puts you over the 10% limit for the exception to IECC C503.6. Please remove this tableas well as all references to the 10% alteration exception. I will create the ComCheck for your space using your layout and the luminaire schedule fromthe previous tenant's permit set. Show your theatrical lighting on this plan and provide me with a cutsheet or more information on it. It is exempt butshould still be shown on the plan and recorded as an exempt fixture on the ComCheck. This is really a strange software issue. I tried to clean this up a little. The existing walk in is to remain, but it is mirrored on axis so its door flips to the other end. I noted on the plans that these are doors are to remain unlocked and have shown a proposed location for a portable security gate Revised. This is now door 8 and panic hardware requirement is noted in the door schedule on A1.05 Revised. Revised. Thank you for your efforts here! 11/19/2018