Loading...
HomeMy WebLinkAboutFile Documents.COACH RD.0079.2018 (17).ARBKAir System Sizing Summary for DGQ Project Name: 18003-DBX 7 10/19/2018 Prepared by: RADER ENGINEERING INC.01:38PM Air System Information Air System Name DGQ Equipment Class UNDEF Air System Type SZCAV Number of zones 1 Floor Area 653.0 ft² Location Eagle, Colorado Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads Central Cooling Coil Sizing Data Total coil load 1.3 Tons Total coil load 15.6 MBH Sensible coil load 13.4 MBH Coil CFM at Aug 1400 754 CFM Max block CFM 754 CFM Sum of peak zone CFM 754 CFM Sensible heat ratio 0.859 CFM/Ton 581.7 ft²/Ton 503.6 BTU/(hr·ft²)23.8 Water flow @ 10.0 °F rise 3.11 gpm Load occurs at Aug 1400 OA DB / WB 88.9 / 64.7 °F Entering DB / WB 73.1 / 58.5 °F Leaving DB / WB 51.2 / 49.8 °F Coil ADP 48.8 °F Bypass Factor 0.100 Resulting RH 46 % Design supply temp.50.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F Central Heating Coil Sizing Data Max coil load 14.6 MBH Coil CFM at Des Htg 754 CFM Max coil CFM 754 CFM Water flow @ 20.0 °F drop 1.46 gpm Load occurs at Des Htg BTU/(hr·ft²)22.3 Ent. DB / Lvg DB 68.6 / 92.5 °F Humidifier Sizing Data Max steam flow at Des Htg 0.59 lb/hr Airflow Rate 754 CFM Air mass flow 2540.49 lb/hr Moisture gain .00023 lb/lb Supply Fan Sizing Data Actual max CFM 754 CFM Standard CFM 565 CFM Actual max CFM/ft²1.16 CFM/ft² Fan motor BHP 0.15 BHP Fan motor kW 0.12 kW Fan static 0.75 in wg Outdoor Ventilation Air Data Design airflow CFM 0 CFM CFM/ft²0.00 CFM/ft² CFM/person 0.00 CFM/person Hourly Analysis Program 5.11 Page 1 of 2 10/19/18 10/30/2018 Zone Sizing Summary for DGQ Project Name: 18003-DBX 7 10/19/2018 Prepared by: RADER ENGINEERING INC.01:38PM Air System Information Air System Name DGQ Equipment Class UNDEF Air System Type SZCAV Number of zones 1 Floor Area 653.0 ft² Location Eagle, Colorado Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads Zone Terminal Sizing Data Zone Name Design Supply Airflow (CFM) Minimum Supply Airflow (CFM) Zone CFM/ft² Reheat Coil Load (MBH) Reheat Coil Water gpm @ 20.0 °F Zone Htg Unit Coil Load (MBH) Zone Htg Unit Water gpm @ 20.0 °F Mixing Box Fan Airflow (CFM) DGQ 754 754 1.16 0.0 0.00 0.0 0.00 0 Zone Peak Sensible Loads Zone Zone Zone Cooling Time of Heating Floor Sensible Peak Sensible Load Area Zone Name (MBH)Cooling Load (MBH)(ft²) DGQ 13.4 Aug 1400 15.4 653.0 Space Loads and Airflows Zone Name / Space Name Mult. Cooling Sensible (MBH) Time of Peak Sensible Load Air Flow (CFM) Heating Load (MBH) Floor Area (ft²) Space CFM/ft² DGQ DGQ-01 Flex Room 1 10.5 Aug 1400 591 12.3 286.0 2.07 DGQ-02 Sitting 1 1.3 Jul 1500 76 1.3 181.0 0.42 DGQ-03 Bedroom 1 1.0 Jul 1500 58 1.3 125.0 0.46 DGQ-04 Bath 1 0.5 Jul 1500 29 0.5 61.0 0.48 Hourly Analysis Program 5.11 Page 2 of 2 10/30/2018