Loading...
HomeMy WebLinkAboutFile Documents.COACH RD.0079.2018 (26).ARBK1. THE ELECTRICAL CONTRACTOR SHALL INSTALL FIXTURES SPECIFIED BY 186 LIGHTING DESIGN GROUP, INC. (186). ANY SUBSTITUTIONS MUST BE APPROVED IN WRITING BY 186. UNAPPROVED SUBSTITUTIONS ARE SUBJECT TO REPLACEMENT WITH SPECIFIED FIXTURES AT THE ELECTRICAL CONTRACTOR'S COST. 2. UPON RECEIPT OF DESIGN DOCUMENT SET, THE ELECTRICAL CONTRACTOR IS TO VERIFY ALL FIXTURE LEAD TIMES WITH DISTRIBUTOR, AND GET APPROVAL FROM THE GENERAL CONTRACTOR THAT THESE LEAD TIMES ARE ACCEPTABLE. IF ANY FIXTURE LEAD TIMES ARE NOT APPROVED BY THE GENERAL CONTRACTOR, THE ELECTRICAL CONTRACTOR IS TO CONTACT 186 IMMEDIATELY FOR ASSISTANCE WITH DECREASING LEAD TIMES OR FOR ALTERNATE SPECIFICATION. ELECTRICAL CONTRACTOR IS TO FOLLOW THIS PROTOCOL THROUGHOUT PROJECT AS NEW DRAWINGS AND SPECIFICATION SETS ARE ISSUED. 3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL APPLIANCE OUTLETS, DISPOSALS, AND POWER FOR SYSTEMS NOT SHOWN ON 186 PLANS (IE. POWER FOR HVAC EQUIPMENT, POOL EQUIPMENT, ETC.) INTERIOR DESIGNER IS TO SUPPLY APPLIANCE PACKAGE FOR ELECTRICAL REQUIREMENTS. GENERAL CONTRACTOR IS TO SUPPLY ALL POWER REQUIREMENTS FOR SYSTEMS NOT SHOWN ON PLANS. AUDIO/VIDEO CONTRACTOR IS TO SUPPLY ALL POWER REQUIREMENTS FOR ALL A/V EQUIPMENT. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MEETING ALL APPLICABLE CODES AND GFI REQUIREMENTS. 4. ELECTRICAL AND GENERAL CONTRACTORS ARE RESPONSIBLE FOR VERIFYING ALL FIXTURE COUNTS PRIOR TO ORDERING. 186 IS NOT RESPONSIBLE FOR ANY RESTOCKING CHARGES DUE TO MIS-ORDERING OR CHANGES BY OTHERS AFTER THE INITIAL ORDER. 5. ALL FIXTURES SHALL BE INSTALLED ACCORDING TO MANUFACTURER SPECIFICATIONS AND RECOMMENDATIONS. 6. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL IC, AIRTIGHT, AND NON-IC FIXTURE LOCATIONS PRIOR TO ORDERING FIXTURES. INSULATION TO BE HELD A MINIMUM OF 3" FROM ALL NON-IC FIXTURES. 7. ALL FIXTURE HOUSING SLEEVES AND COLLARS THAT HOLD FIXTURE TRIMS ARE TO BE COMPLETELY FLUSH WITH CEILING AT ELECTRICAL TRIM-OUT. TRIMLESS/FLANGELESS RECESSED LIGHTS ARE TO BE MOCKED UP BY THE ELECTRICAL CONTRACTOR PRIOR TO INSTALLATION. 8. ELECTRICAL CONTRACTOR IS TO NOTIFY 186 IF ANY FIXTURE LOCATIONS MUST MOVE MORE THAN SIX INCHES DUE TO FIELD CONDITIONS. 9. ALL SCONCE AND CLOCK OUTLET LOCATIONS SHOWN ON DRAWINGS ARE APPROXIMATE. EXACT LOCATIONS AND HEIGHTS OF WALL SCONCES AND CLOCK OUTLETS FOR PICTURE LIGHTS ARE TO BE VERIFIED WITH THE INTERIOR DESIGNER AND/OR OWNER. 10. ALL LED STRIP INSTALLATIONS ARE TO BE INDIVIDUALLY FED IN LENGTHS NO LONGER THAN THE MAXIMUM LENGTHS RECOMMENDED BY THE MANUFACTURER. ELECTRICAL AND GENERAL CONTRACTOR ARE TO WORK TOGETHER TO ENSURE THERE ARE NO VISIBLE WIRENUTS OR ELECTRICAL CONNECTIONS. 11. ALL FIXTURES SHALL BE SUPPLIED WITH SPECIFIED LAMPS. WHERE BEAMSPREADS ARE NOT SPECIFIED, SUPPLY WIDEST BEAMSPREAD AVAILABLE FOR PARTICULAR LAMP TYPE. 12. ALL WIRING IS SHOWN SYMBOLICALLY ON PLANS. ACTUAL REMOTE TRANSFORMER/DRIVER LOCATIONS AND HOMERUNS ARE TO BE DETERMINED BY ELECTRICAL CONTRACTOR AND GENERAL CONTRACTOR. ALL REMOTE TRANSFORMERS/DRIVERS SHALL BE TOROIDAL AND MOUNTED IN A LOCATION REMOVED FROM THE ROOM'S AIRSPACE SUCH AS AN ATTIC, CABINET, OR CRAWLSPACE, UNLESS OTHERWISE NOTED. 13. ALL SWITCHED OUTLETS SHOWN ON PLANS SHALL BE WIRED SUCH THAT THE OUTLET MAY BE SWITCHED AT ANY TIME IN THE FUTURE. VERIFY ACTUAL OUTLETS TO SWITCH WITH OWNER. ALL HALF-SWITCHED OUTLETS ARE TO HAVE SWITCHED SIDE AND HOT SIDE FED FROM SAME BREAKER. 14. EXHAUST FAN LOCATIONS ARE SHOWN SYMBOLICALLY ON THE PLANS. VERIFY EXACT EXHAUST FAN LOCATIONS WITH MECHANICAL CONTRACTOR. 15. MOTION SENSORS SHALL BE WALL-MOUNTED AT STANDARD SWITCH HEIGHT UNLESS OTHERWISE NOTED. 16. ALL LOADS TO BE LANDED ON CONTROL DEVICES IN ORDER DRAWN ON PLANS. 17. CENTER LINE OF TYPICAL SWITCH AND WALLBOX DIMMER BOXES TO BE AT 48" A.F.F. CENTER LINE OF TYPICAL CONTROL SYSTEM KEYPADS TO BE AT 54" A.F.F. (EXCEPT AT BEDROOM HEADBOARD LOCATIONS, ABOVE COUNTERS, AND OTHER NON-TYPICAL KEYPAD LOCATIONS) VERIFY WITH OWNER, ARCHITECT, AND INTERIOR DESIGNER. ELECTRICAL CONTRACTOR AND A/V CONTRACTOR TO VERIFY ALL KEYPADS BESIDE BEDS ARE INSTALLED CLEAR OF BED HEADBOARD. 18. ELECTRICAL CONTRACTOR TO VERIFY DIMMER AND CONTROL LOCATIONS. 19. ALL LOADS IN REMOTE DIMMING PANELS TO BE LANDED WHERE SHOWN ON PANEL SCHEDULE PROVIDED BY LIGHTING CONTROL SYSTEM CONTRACTOR. ELECTRICAL CONTRACTOR SHALL NOTIFY LIGHTING CONTROL SYSTEM CONTRACTOR OF ANY LOADS THAT HAVE BEEN MOVED FOR ANY REASON. 20. IN ORDER TO INSURE REMOTE ACCESS TO THE LIGHTING CONTROL SYSTEM PROCESSOR(S), A PHONE OUTLET OR ETHERNET CONNECTION, AS WELL AS AN ELECTRICAL OUTLET IS REQUIRED AT ALL PROCESSOR LOCATIONS. 21. ELECTRICAL CONTRACTOR AND A/V CONTRACTOR ARE TO VERIFY ALL FINISHES OF ELECTRICAL DEVICES, LIGHTING TRIMS, AND WALL-BOX DEVICES WITH THE INTERIOR DESIGNER AND/OR OWNERS PRIOR TO ORDERING. IF THESE COLORS OR FINISHES ARE NOT VERIFIED, ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REPLACING EQUIPMENT AND DEVICES AT NO COST TO THE OWNERS. 22. ELECTRICAL CONTRACTOR TO PROVIDE (10) EXTRA OF 10 DEGREE SPOTS, 25 DEGREE NARROW FLOODS, 40 DEGREE FLOODS, AND 60 DEGREE WIDE FLOODS FOR AIMING AND SPARE STOCK FOR OWNER. PROVIDE FLOOD BEAMSPREADS FOR MR-16 LAMPS WHERE BEAMSPREAD IS NOT DESIGNATED ON 186 BEAMSPREAD DRAWINGS. ELECTRICAL CONTRACTOR TO REQUEST BEAMSPOREAD PLAN FROM 186 PRIOR TO PURCHASE AND ELECTRICAL TRIM OUT OF MR16 LAMPHOLDERS. 23. ALL ADJUSTABLE ACCENTS TO BE AIMED STRAIGHT DOWN AT ELECTRICAL TRIM-OUT. ELECTRICAL CONTRACTOR TO PROVIDE LADDERS AND PERSONNEL TO ASSIST 186 AND CLIENT WITH FINAL AIMING OF ADJUSTABLE FIXTURES WHEN ARTWORK AND FURNITURE ARE IN PLACE. AIMING SESSIONS ARE TYPICALLY AFTER SUNSET. 24. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR APPROPRIATE SIZING OF ALL ELECTRICAL CONDUCTORS. 12-VOLT SYSTEMS SUCH AS MONORAIL, CABLE, AND LOW VOLT TRACK SHALL BE FED WITH STRANDED WIRE OF AN APPROPRIATE GAUGE FOR LIGHTING LOAD SHOWN ON PLANS. WIRING SHALL BE SIZED SUCH THAT VOLTAGE DROP TO LOW VOLTAGE SYSTEMS IS NOT GREATER THAN 10%. IF NECESSARY, USE MULTI-TAP TRANSFORMER TO ACHIEVE REQUIRED VOLTAGE AT EACH LIGHT. ALL REFERENCES TO ELECTRICAL OR LOW VOLTAGE SYSTEMS THAT ARE NOT DIRECTLY RELATED TO LIGHTING ARE ON THE PLANS FOR REFERENCE ONLY. ACTUAL FINAL LOCATIONS AND DIMENSIONS ARE TO BE PROVIDED BY OTHERS. KEYPAD DATA OUTLET CABLE TELEVISION OUTLET THERMOSTAT TRANSFORMER SATELLITE TELEVISION OUTLET TELEPHONE QUAD OUTLET 220V OUTLET DOOR JAMB SWITCH HOT ELECTRICAL OUTLET MOTION SENSOR 1/2 SWITCHED FLOOR OUTLET HOT FLOOR OUTLET FULLY SWITCHED OUTLET 1/2 SWITCHED OUTLET WEATHERPROOF GFI OUTLET GFI PROTECTED OUTLET 3-WAY SWITCH 4-WAY SWITCH 3-WAY DIMMER FULLY SWITCHED FLOOR OUTLET DIMMER SWITCH LEGEND A/V TOUCHSCREEN LINE VOLTAGE CONTROL SYSTEM DIMMERS 220V SPEAKER SATV TS S S S S S S 3 4 JS D TV GD GFI WP GFI SP 1/4 SWITCHED QUAD OUTLET GARAGE DOOR OUTLET RF TABLETOP KEYPAD RF LAMP DIMMER - PLUG INTO HOT OUTLET CIRCUIT NUMBER HOT QUAD FLOOR OUTLET 1/4 SWITCHED QUAD FLOOR OUTLET 1234 T-STAT GENERAL NOTES 3D MR16 LEGEND 10 DEGREE SPOT BEAMSPREAD 25 DEGREE NARROW FLOOD BEAMSPREAD 40 DEGREE FLOOD BEAMSPREAD 60 DEGREE WIDE FLOOD BEAMSPREAD DIFFUSING LENS SOFT FOCUS LENS LINEAR SPREAD LENS FROSTED LENS CLEAR LENS HONEYCOMB LOUVER COLOR LEGEND SYSTEM DIMMER/HYBRID KEYPAD NON-SYSTEM DEVICES SYSTEM HOMERUN LOAD LOW VOLTAGE KEYPAD; FIREPLACE; MOTOR POWER OUTLETS FIBEROPTIC ILLUMINATOR SURFACE-MOUNTED LINEAR LIGHT LANDSCAPE ACCENT EXTERIOR PATH LIGHT UNDERWATER ACCENT WALL-RECESSED STEP LIGHT RECESSED LINEAR LIGHT IN-GROUND WELL LIGHT POST TOP LIGHT T RECESSED WALL WASH, ROUND OR SQUARE LOW VOLTAGE OR LED STRIP SHADE MOTOR / WINDOW MOTOR EXHAUST FAN CEILING FAN 12V OR 24V ROUGH-IN JUNCTION BOX MONOPOINT HEAD DUAL-HEADED MONOPOINT TRACK LIGHTING HANGING PENDANT OR CHANDELIER WALL MOUNTED FIXTURE RECESSED ADJUSTABLE ACCENT, ROUND OR SQUARE MINI-RECESSED DOWNLIGHT OR PUCKLIGHT RECESSED DOWNLIGHT, ROUND OR SQUARE CEILING MOUNTED FIXTURE W P C CLOCK OUTLET FOR PICTURE LIGHTCO 48" FO FP JB POOL LIGHT LONG HANGING PENDANT OR CHANDELIER, VERIFY FEED LOC. FIREPLACE IGNITION 1-HEADED RECESSED MULTIPLE 2-HEADED RECESSED MULTIPLE 3-HEADED RECESSED MULTIPLE P RECESSED LINEAR WALL WASH 12/24V JB JUNCTION BOX JB RGBW 5-CONDUCTOR LOW VOLTAGE ROUGH-IN JUNCTION BOX JB RGB 4-CONDUCTOR LOW VOLTAGE ROUGH-IN JUNCTION BOX WALL MOUNTED SWING-ARM LAMP OR MAKEUP MIRROR WITH INTEGRAL SWITCH XFMR SP NFL FL WFL DIFF SOFT LIN FROST CLR LOUV VERIFY IN FIELDVIF TABLE OF CONTENTS LIGHT.1.001 STANDARD LEGENDS & NOTES LIGHT.2.001 LOWER LEVEL EXT LIGHTING PLAN LIGHT.2.002 MAIN LEVEL EXT LIGHTING PLAN LIGHT.2.003 UPPER LEVEL EXT LIGHTING PLAN. LIGHT.2.004 LANDSCAPE LIGHTING PLAN LIGHT.2.005 DRIVEWAY LIGHTING PLAN LIGHT.2.006 LOWER LEVEL LIGHTING PLAN | A LIGHT.2.007 LOWER LEVEL LIGHTING PLAN | B LIGHT.2.008 MAIN LEVEL LIGHTING PLAN | A LIGHT.2.009 MAIN LEVEL LIGHTING PLAN | B LIGHT.2.010 UPPER LEVEL LIGHTING PLAN ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)LIGHT.0.001I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: STANDARD LEGENDS & NOTES NO SCALE LEGEND & GENERAL NOTES NOT FOR CONSTRUCTION 4/5/2018 STOR. BELOW DW LAUNDRY 008 STAIR 1 007 HALL 011 PDR 2 006 KITCHENETTE 004 BED 1 - PLAYROOM 014BED 2 018 BATH 3 019 BATH 2 016 WIC 2 017 WIC 1 013 MECH 009 PDR 1 003 FAMILY ROOM 002 OUTDOOR PATIO - STAIR 1 001 A4 A4 A4 A4 A4 A4 A4 A4 L8 L8 STEPLIGHT AT RECESSED SEATING LIGHTS DOWN PINSPOT DOWNLIGHTS A1W A1W A1W A1W A1W A1W A1W A1W A1W SPA LIGHTING BY OTHERS L8 STRUCTURE ABOVE A1W A1W ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LIGHT.2.001 LOWER LEVEL EXTERIOR LIGHTING PLAN LOWER LEVEL EXTERIOR LIGHTING PLAN 3/16" = 1'-0" NOT FOR CONSTRUCTION 4/5/2018 EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F.EL. 10'-0" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F.EL. 10'-6" A.F.F. EL. 10'-3" A.F.F. EL. 10'-6" A.F.F. EL. - A.F.F. TO BE V.I.F. REF. A-01 STORAGE KITCHEN 104 HALL 111 LIVING ROOM 102 ENTRY 100 STAIR 1 101GALLERY 106 STAIR 2 107 GARAGE 116 OFFICE 112 PDR 3 109 PANTRY 108 WINE 113 MUDROOM 114 MONOPOINTS HIDDEN AT VERTICAL SKYLIGHT WALL LIGHTS DOWN M1 L8 LED STRIP TOEKICK LIGHTS DOWN AT FIRE Z1 Z1 INGROUND UPLIGHTS - SHIELDED BY CANOPY ABOVE DOWNLIGHT STRIP IN VERTICAL GARAGE DETAIL, HIDDEN SOFT EVEN LIGHTING A1W L8L8 A1W A1W A4 A4 A4 A4 A4 A4 A4 A4 A1W A1W A1W M1M1 M1M1 M1M1 ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LIGHT.2.002 MAIN LEVEL EXTERIOR LIGHTING PLAN MAIN LEVEL EXTERIOR LIGHTING PLAN 3/16" = 1'-0" NOT FOR CONSTRUCTION 4/5/2018 DECK GWB GWB GWB TILE [RE: INT.FOR EL. + FINISH] TILE [RE: INT.FOR EL. + FINISH] GWB GWB DS.DS. W / D REF. EL. 114'-3" [7794.25'] EL. 114'-0" [7794.00'] EL. 122'-5" DECK W/D KITCHEN A12 LIVING A11 ENTRY A10 DECK - BEDROOM A15 WIC A16 BATH A17 HALL A14STORAGE A13 MASTER BED 202 MASTER BATH 203 STEAM SHOWER 204 W.C. 204 MASTER DRESSING 206 STAIR 2 207 HALL 201 A1W A1W A1W A1W A1W A1W A4 A4 A4 A1W A1W ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LIGHT.2.003 UPPER LEVEL EXTERIOR LIGHTING PLAN UPPER LEVEL EXTERIOR LIGHTING PLAN 3/16" = 1'-0" NOT FOR CONSTRUCTION 4/5/2018 B1 B1 B1 B1 B1 B1 B1 B1 SPA LIGHTING BY OTHERS B1 B1 B1 GRADE CHANGE PATHLIGHTS AT STAIRS JB ROUGH-IN FOR POWER AT FLEX PLAY AREA JB SWITCHED OUTLET FOR HOLIDAY LIGHTING SWITCHED OUTLET FOR HOLIDAY LIGHTING L8L8 L8 L8L8L8 L8 L8 L8 L8 FULLY SHIELDED, HIDDEN LOW-OUTPUT LED IN TOEKICK OF PATH FULLY SHIELDED, HIDDEN LOW-OUTPUT LED IN TOEKICK OF PATH M2M2 DOWNLIGHTING TOWARDS PATH FROM TREE; LOWER THAN 8FT MOUNTING HEIGHT M2M2 M2 M2 M2 M2 M2 ST1 CONCRETE RECESSED STEPLIGHT DETAIL AT WINDOW WELL DOWNLIGHTING TOWARDS PATH FROM TREE; LOWER THAN 8FT MOUNTING HEIGHT 1 1 1 JB MATCHLINEMATCHLINE 2 2 2 8FT MAX HEIGHTSOFT LIGHTON SIDEWALKFULLY SHIELDED & HIDDEN, VERY LOW OUTPUT LED ROPELIGHT IN TOEKICK OF PATH 3-4" 1 2LED TOEKICK - TYPE L8 TREE DOWNLIGHT - TYPE M2 I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LIGHT.2.004 LANDSCAPE EXTERIOR LIGHTING PLAN LANDSCAPE LIGHTING PLAN 3/16" = 1'-0" NOT FOR CONSTRUCTION 4/5/2018 B1 B1 B1 B1 B1 SWITCHED OUTLET FOR HOLIDAY LIGHTING PATHLIGHTS AT EM TURNAROUND GRADE CHANGE JB SWITCHED OUTLET FOR HOLIDAY LIGHTING SWITCHED OUTLET FOR HOLIDAY LIGHTING SWITCHED OUTLET FOR HOLIDAY LIGHTING SWITCHED OUTLET FOR HOLIDAY LIGHTING JB ROUGH-IN FOR POWER AT ADDRESS MARKER L8L8 L8 L8L8L8 L8 L8 L8 L8 FULLY SHIELDED, HIDDEN LOW-OUTPUT LED IN TOEKICK OF PATH M2M2 M2M2 1 1 1 JB MATCHLINEMATCHLINE 2 2 ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LIGHT.2.005 LANDSCAPE EXTERIOR LIGHTING PLAN DRIVEWAY LIGHTING PLAN 3/16" = 1'-0" NOT FOR CONSTRUCTION 4/5/2018 STOR. BELOW DW 48"48" 48"48"SMS SSJS JS SSJS JSSSSLAUNDRY 008 STAIR 1 007 HALL 011 PDR 2 006 KITCHENETTE 004 BED 1 - PLAYROOM 014BED 2 018 BATH 3 019 BATH 2 016 WIC 2 017 WIC 1 013 MECH 009 PDR 1 003 A2 S2A2A2A2S2 CC C C P L2L2L2 360° BACKLIT MIRROR. ALT OPTION: SCONCE OR PENDANTS L1 L3L3L3 L1 L1 L1 L3 OPTION: MCM DECORATIVE SCONCE OR PENDANT W L3 A1 A1 A1 A1 UNDER CABINET 360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING 23" L5 L3 SS UNDERCABINET TASK LIGHT L6 RECESSED LINEAR LED. OPTION: TRIMLESS A2S2 A2 A2 HOT OUTLET AT FUTURE BED LOCATION. VERIFY QTY/LOCATION WITH OWNER ON-SITE. A4 A4 A4 A4 A4 A4 LED STRIPS AT SHELVING LED STRIPS AT SHELVING FLOATING VANITY INVERSE COVE 48"MS L1 LED STRIPS AT UNDERCABINET, AND BAR SHELVES. QTY AND TYPE TBD PER FINAL MILLWORK DRAWINGS L1 A1 A1 OPTION: MCM DECORATIVE SCONCE OR PENDANT 360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING L3 INVERSE COVE, GLOWS FROM OUTSIDE P A1 A1 STEPLIGHTS THIS SIDE SHOWN ABOVE JB L1 UPLIGHT ON TOP OF CABINETS STRUCTURE ABOVE JB A2 A2 A2 A2A2A2A2 A2 A2 A2 A2A2 A2 A2 A2A2A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2A2A2A2 L1L1 L1 CC INVERSE COVE L7 WALL WASH TO LIGHT ART WALL ARTA1 A1 A1 A1A1A1A1A1A1A1 EQ EQ EQ 36" C SA2A2 A1 A1 ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LOWER LEVEL LIGHTING PLAN LOWER LEVEL LIGHTING PLAN | A 1/4" = 1'-0" NOT FOR CONSTRUCTION LIGHT.2.006 4/5/2018 SSJS JS FP PDR 2 006 KITCHENETTE 004 WIC 1 013 PDR 1 003 FAMILY ROOM 002 OUTDOOR PATIO - STAIR 1 001 S2 C L2 360° BACKLIT MIRROR. ALT OPTION: SCONCE OR PENDANTS L1 L1 L3 L1L1L1 L1L1L1 OPTION: MCM DECORATIVE SCONCE OR PENDANT W L3 A1 A1 A1 A1 UNDER CABINET 360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING 23" Z1 A4 A4 A4 A4 A4 T1T1 T1 LED STRIPS AT SHELVING LED STRIPS AT SHELVING INVERSE COVE L1 L8 L8 STEPLIGHT AT RECESSED SEATING LIGHTS DOWN LED STRIPS AT UNDERCABINET, AND BAR SHELVES. QTY AND TYPE TBD PER FINAL MILLWORK DRAWINGS PINSPOT DOWNLIGHTS IN-FLOOR HOT OUTLETS. VERIFY QTY AND LOCATIONS ON-SITE WITH OWNER A1W A1W A1W A1W A1W A1W A1W A1W A1W A1WEQEQ A1 A1 TABLE TABLE TH1 TH1 TH1 TH1 TH1 TH1 TH1 TABLE TABLE TABLE DOWN DOWNBAR TH1 BAR TH1 BAR TH1 SEATING TH1 SEATING TH1 SEATING TH1 SEATING TH1 BUILT-IN TH1 SEATING TH1 TH1 TH1 TH1 TH1 TABLE SEATING TH1 SPA LIGHTING BY OTHERS OPTION: MCM DECORATIVE SCONCE OR PENDANT 360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING L3 INVERSE COVE, GLOWS FROM OUTSIDE P A1 A1 L8 L1 LED STRIP INTEGRATED UNDER COUNTER - COORDINATE DETAIL, NOT VISIBLE TO SEATING BELOW. L1 UPLIGHT ON TOP OF CABINETS A2 A2 L1 A1W A1WA1W A1WA1W A1WA1W A1WA1W A1W L7 WALL WASH TO LIGHT ART WALLA1 A1 A1 EQ EQ EQ A2 INGROUND UPLIGHT Z1 A1 A1 360° BACKLIGHT AROUND TV A1W A1W 1 1 1 Z1 Z1 Z1 Z1 Z1 L1 SEE T1/TH1 ALTERNATE SPEC FOR CLG COORDINATION LED STRIPS AT STAIR TREADS ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: LOWER LEVEL LIGHTING PLANLOWER LEVEL LIGHTING PLAN | B 1/4" = 1'-0" NOT FOR CONSTRUCTION LIGHT.2.007 4/5/2018 EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F.EL. 10'-0" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. EL. 10'-3" A.F.F. EL. - A.F.F. TO BE V.I.F. REF. 48" 48" 48" 48" 48" 48" 48"SS S SJS JS JS JS S48"48"48"48"COORDINATE FIXTURE WITH GARAGE DOOR. ALT OPTION: USE L6 RECESSED LINEARS. (~60% COST INCREASE) CRAWL SPACE [4' HIGH / STORAGE] A-01 STORAGE HALL 111 STAIR 2 107 GARAGE 116 OFFICE 112 PDR 3 109 PANTRY 108 WINE 113 MUDROOM 114 A1 L1 OPTION: MCM DECORATIVE SCONCE OR PENDANT W FLOATING VANITY IN-WALL DETAIL WALL RECESSED STEPLIGHT DETAIL; LED STRIP IN WALL DETAIL ST1 SHEETROCK DEPTH TRIMLESS LINEAR LED LED STRIP AT CUBBIES. QTY AND LOCATIONS PER FINAL MILLWORK DESIGN. L5 L5 L5 L5 L5 L5 L6A L6A L6A UNDERCABINET TASK LIGHT AT OFFICE MILLWORK L3 A1 A1 A1 A1 A1 A1 A1 A1 A1A1A1A1 FL1 FL1 FL1 FL1FL1 FL1 FL1 FL1 FL1FL1 FL1 TO STAIRS ABOVE L1 L8 LED STRIP TOEKICK LIGHTS DOWN AT FIRE L1 UPLIGHT FROM MILLWORK - ALT: IN-SHELF-LIGHTING FOR AMBIENT LIGHT A1 A1 A1 A1 36" L5 1/3 1/3 1/3 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 35" A1 A1 NIGHT PATH TO BEDROOMS A1 A1 UPLIGHT AT WINDOW HALLWAY, NOT PATIO) CAN WE FIT DOWNLIGHT IN STAIR LANDING? DOWNLIGHT STRIP IN VERTICAL GARAGE DETAIL, HIDDEN SOFT EVEN LIGHTING L1 L1 L1 L1 INFLOOR UPLIGHTS LED STRIP AT BOTTLE DISPLAY WALL GRAZING BEHIND BOTTLES L8L8 40" L148"48"FL1 FL1 48"48"FL1 FL1 A1WA1W ST1ST1ST1ST1ST1 ST1ST1ST1ST1ST1ST1A4 A4 A4 A4 A4 VERTICAL LED STRIP INTEGRATED INTO WINDOW DETAIL A4 A4 A4 LANDSCAPING BELOW? EQ EQ A1W A1W A1W M1M1 M1 ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: ENTRY LEVEL LIGHTING PLAN | A 1/4" = 1'-0" ENTRY LEVEL LIGHTING PLAN NOT FOR CONSTRUCTION LIGHT.2.008 4/5/2018 EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F.EL. 10'-0" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. EL. 10'-6" A.F.F.EL. 10'-6" A.F.F. EL. 10'-6" A.F.F. REF.SS S SJS JS JS JS FP48"48"COORDINATE FIXTURE WITH GARAGE DOOR. ALT OPTION: USE L6 RECESSED LINEARS. (~60% COST INCREASE) KITCHEN 104 HALL 111 LIVING ROOM 102 ENTRY 100 STAIR 1 101GALLERY 106 STAIR 2 107 GARAGE 116 OFFICE 112 PDR 3 109 PANTRY 108 WINE 113 MUDROOM 114 A1W Z1 Z1 Z1 Z1 Z1 Z1 ART WALL A1A1 L1 L3 OPTION: MCM DECORATIVE SCONCE OR PENDANT W 360° BACKLIT MIRROR FLOATING VANITY 360° ART LIGHT IN-WALL DETAIL LED STRIP UNDER COUNTER LED STRIP UPLIGHT AT HIGH WINDOW IN-FLOOR UPLIGHTS AT COLUMNS RECESSED LINEAR LED: OPTION TRIMLESS L6A L1 L1 L1 ST1 ST1 ST1ST1 WALL RECESSED STEPLIGHT DETAIL; LED STRIP IN WALL DETAIL WALL RECESSED STEPLIGHT DETAIL; LED STRIP IN WALL DETAIL ST1 IN-FLOOR HOT OUTLETS. VERIFY QTY AND LOCATIONS ON-SITE WITH OWNER OPTION: LAMP DIMMER OF USE WITH HOT OUTLET. HIDDEN DEVICE CONNECTS LAMPS TO LIGHTING SYSTEM. ONE PER LAMP ALT: SWITCHED OUTLETS T1T1T1 SHEETROCK DEPTH TRIMLESS LINEAR LED LED STRIP AT CUBBIES. QTY AND LOCATIONS PER FINAL MILLWORK DESIGN. L5 L5 L5 L5 L5 L5 L6A L6A L6A L6 UNDERCABINET TASK LIGHT AT OFFICE MILLWORK L3 A1 A1 A1 A1 A1 MONOPOINTS HIDDEN AT VERTICAL SKYLIGHT WALL LIGHTS DOWN M1 A1W A1W A1W A1 A1 A1 A1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1TH1TH1 TH1 TH1 TH1 TABLE TABLE TABLE TABLE TABLE TABLE FIRE FIRE SEATING SEATING SEATING SEATING DOWNDOWNDOWN DOWN DOWN DOWN TH1 TH1 TH1 TH1 TH1 TH1 TH1 SEATING SEATING SEATING SEATING TABLE SEATING SEATING A1 A1 A1 A1 FL1 FL1 TO STAIRS ABOVE LED STRIP UPLIGHT AT HIGH WINDOW L1 L8 LED STRIP TOEKICK LIGHTS DOWN AT FIRE L1 UPLIGHT FROM MILLWORK - ALT: IN-SHELF-LIGHTING FOR AMBIENT LIGHT A1 A1 A1 A1 36" L5 1/3 1/3 1/3 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 35" A1 A1 NIGHT PATH TO BEDROOMS A1 A1 INGROUND UPLIGHTS - SHIELDED BY CANOPY ABOVE L1 L1 L1L1L1L1L1L1L1 UPLIGHT AT WINDOW SILL UPLIGHT AT WINDOW SILL (LIGHTS HIGH HALLWAY, NOT PATIO) CAN WE FIT DOWNLIGHT IN STAIR LANDING? DOWNLIGHT STRIP IN VERTICAL GARAGE DETAIL, HIDDEN SOFT EVEN LIGHTING L1 L1 L1 L1 INFLOOR UPLIGHTS LED STRIP AT BOTTLE DISPLAY WALL GRAZING BEHIND BOTTLES A1W L8 A1W A1W L1L1L1 40" A1W T1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 TH1 L1 UPLIGHT ABOVE FLOATING STRUCTURE L1 1/3 1/3 1/3 48"48"FL1 FL1 A1WA1W A1WA1WA1W A1WA1WA1WA1WA1WA1W ST1ST1ST1ST1ST1 ST1ST1ST1ST1ST1ST1 ST1 ST1 ST1 ST1 ST1 ST1 TH1 DOWN DOWN EQ EQ EQ A4 A4 A4 OPTION: LIGHT ART WITH TH1 TRACK HEADS - POSSIBLY LESS UNIFORM WALL WASH, BUT CLEANER CEILING VERTICAL LED STRIP INTEGRATED INTO WINDOW DETAIL A4 A4 L1 LED STRIP AT COUNTER HEIGHT CHANGE - TASK LIGHT A4 LANDSCAPING BELOW? EQ EQ A1W A1W A1W M1M1 M1M1 M1M1 ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: ENTRY LEVEL LIGHTING PLAN | B 1/4" = 1'-0" ENTRY LEVEL LIGHTING PLAN NOT FOR CONSTRUCTION LIGHT.2.009 4/5/2018 DECK GWB GWB GWB TILE [RE: INT.FOR EL. + FINISH] TILE [RE: INT.FOR EL. + FINISH] GWB GWB DS.DS. W / D REF. EL. 114'-3" [7794.25'] EL. 114'-0" [7794.00'] EL. 122'-5" DECK W/D FP ART ART ARTGALLERY WALL LED STRIP UPLIGHT AT HIGH WINDOWS VERTICAL LED STRIP INTEGRATED INTO WINDOW DETAIL CLOSET RATED LED STRIPS: QTY AND LOCATION TBD PER FINAL MILLWORK DRAWINGS; STRIPS SHOWN FOR PRICING TO BE UPDATED PER FINAL DESIGN VERTICAL LED STRIP INTEGRATED INTO WINDOW DETAIL UPLIGHT AT WINDOW SILL L5 L5 L5 L5 L5 L5L5 L1L1L1 LED STRIP UPLIGHT AT HIGH WINDOWS L2 L2 L1 L1 L2 L2 LED STRIPS INTEGRATED INTO SAUNA BENCH: UPLIGHT FROM BEHIND BENCH, AND TOEKICK BELOW A2 A2 S2 L2 L3 L1 48"SFL1 S A2 A2 A1W A1W IN-FLOOR HOT OUTLETS. VERIFY QTY AND LOCATIONS ON-SITE WITH OWNER HOT OUTLET AT FUTURE BED LOCATION. VERIFY QTY/LOCATION WITH OWNER ON-SITE. L3 UNDERCABINET LIGHT LED STRIP UPLIGHT AT HIGH WINDOW SILLS L1 A2 A2 A2 A2 A2 A2A2 L1 LED STRIP UPLIGHT AT HIGH WINDOW W WALL MOUNTED READING LIGHTS WITH INTEGRAL CONTROL W 30" L1 L1 WALL RECESSED STEPLIGHT DETAIL; LED STRIP IN WALL DETAIL L1 L1 L1 L1 TO STAIRS BELOW LED STRIP UPLIGHT AT OPENING L1 A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1W A1 A1 L3L3 LIGHTING INTEGRATED INTO BUILT-IN MIRROR L1 L1 LED STRIP TOEKICK, OR FLOATING VANITY PER FINAL DESIGN LED STRIP AT STEP LED STRIP UPLIGHT AT BACK OF CEILING DETAIL A1A1 A1 A1 A1A1 A1 A1 UPLIGHT FROM TOP OF CABINETS L1 SL1 STRIPLIGHT ABOVE HEADER ON JAMB SWITCH S1 S1 A2 SS12" SS SSSKITCHEN A12 LIVING A11 ENTRY A10 DECK - BEDROOM A15 WIC A16 BATH A17 HALL A14STORAGE A13 SSSL1 L1 L1 L1 S3D 3D L1 L1 L1 A2 A2 A1 S2 S2 L1 L1 L1 L1L1 A1W A1W A1WA1WA1WA1W A1WA1WA1WA1W A1WA1WA1WA1W MASTER BED 202 MASTER BATH 203 STEAM SHOWER 204 W.C. 204 MASTER DRESSING 206 STAIR 2 207 HALL 201 UPLIGHT AT WINDOW SILL A1W A1W A1W L1L1 SA1W A1W A1W OPTION: LAMP DIMMER OF USE WITH HOT OUTLET. HIDDEN DEVICE CONNECTS LAMPS TO LIGHTING SYSTEM. ONE PER LAMP ALT: SWITCHED OUTLETS L1 VERIFY TYPE (FLANGED) WITH TILE A4 A4 A4 11" A1W 52" L1 52" MIN DISTANCE TO LIGHT ART @ ~13' CLG A1W A1WA1WA1W A1W A1W A1W A1W A1WA1W 42" S1 S1 S1 S1 S1 S1 S1 S1S1S1S1S1 S1 OPTION: COULD REDUCE QTY OF DOWNLIGHTS DEPENDING ON MILLWORK LED STRIP COVERAGE. ALT OPTION: USE TRIMLESS LINE-OF-LIGHT IN DRESSING INSTEAD OF DOWNLIGHTS. A1WA1WA1WA1W A1W A1W A1WA1W A1W A1W TALK ABOUT ART LIGHTING OPTIONS HERE. ENERGY COMPLIANCE: WHOLE PROJECT 98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT 584 EFFICIENT FIXTURES 9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C . 1200 BANNOCK ST. DENVER, CO 80204 TEL:303.534.5350 www.186group.com DATE REVISION & ISSUE 2018-01-29 MEETING 2018-02-14 PROGRESS 2018-02-28 ACC FINAL SITE PLAN 2018-03-20 PERMIT REVIEW 2018-03-30 PERMIT SET SHEET NUMBER: PAGE TITLE: UPPER LEVEL LIGHTING PLAN 1/4" = 1'-0" UPPER LEVEL LIGHTING PLAN NOT FOR CONSTRUCTION LIGHT.2.010 4/5/2018