HomeMy WebLinkAboutFile Documents.COACH RD.0079.2018 (26).ARBK1. THE ELECTRICAL CONTRACTOR SHALL INSTALL FIXTURES SPECIFIED BY 186 LIGHTING
DESIGN GROUP, INC. (186). ANY SUBSTITUTIONS MUST BE APPROVED IN WRITING BY 186.
UNAPPROVED SUBSTITUTIONS ARE SUBJECT TO REPLACEMENT WITH SPECIFIED FIXTURES
AT THE ELECTRICAL CONTRACTOR'S COST.
2. UPON RECEIPT OF DESIGN DOCUMENT SET, THE ELECTRICAL CONTRACTOR IS TO VERIFY
ALL FIXTURE LEAD TIMES WITH DISTRIBUTOR, AND GET APPROVAL FROM THE GENERAL
CONTRACTOR THAT THESE LEAD TIMES ARE ACCEPTABLE. IF ANY FIXTURE LEAD TIMES ARE
NOT APPROVED BY THE GENERAL CONTRACTOR, THE ELECTRICAL CONTRACTOR IS TO
CONTACT 186 IMMEDIATELY FOR ASSISTANCE WITH DECREASING LEAD TIMES OR FOR
ALTERNATE SPECIFICATION. ELECTRICAL CONTRACTOR IS TO FOLLOW THIS PROTOCOL
THROUGHOUT PROJECT AS NEW DRAWINGS AND SPECIFICATION SETS ARE ISSUED.
3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL APPLIANCE OUTLETS,
DISPOSALS, AND POWER FOR SYSTEMS NOT SHOWN ON 186 PLANS (IE. POWER FOR HVAC
EQUIPMENT, POOL EQUIPMENT, ETC.) INTERIOR DESIGNER IS TO SUPPLY APPLIANCE
PACKAGE FOR ELECTRICAL REQUIREMENTS. GENERAL CONTRACTOR IS TO SUPPLY ALL
POWER REQUIREMENTS FOR SYSTEMS NOT SHOWN ON PLANS. AUDIO/VIDEO CONTRACTOR
IS TO SUPPLY ALL POWER REQUIREMENTS FOR ALL A/V EQUIPMENT. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR MEETING ALL APPLICABLE CODES AND GFI
REQUIREMENTS.
4. ELECTRICAL AND GENERAL CONTRACTORS ARE RESPONSIBLE FOR VERIFYING ALL
FIXTURE COUNTS PRIOR TO ORDERING. 186 IS NOT RESPONSIBLE FOR ANY RESTOCKING
CHARGES DUE TO MIS-ORDERING OR CHANGES BY OTHERS AFTER THE INITIAL ORDER.
5. ALL FIXTURES SHALL BE INSTALLED ACCORDING TO MANUFACTURER SPECIFICATIONS
AND RECOMMENDATIONS.
6. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL IC, AIRTIGHT, AND NON-IC
FIXTURE LOCATIONS PRIOR TO ORDERING FIXTURES. INSULATION TO BE HELD A MINIMUM OF
3" FROM ALL NON-IC FIXTURES.
7. ALL FIXTURE HOUSING SLEEVES AND COLLARS THAT HOLD FIXTURE TRIMS ARE TO BE
COMPLETELY FLUSH WITH CEILING AT ELECTRICAL TRIM-OUT. TRIMLESS/FLANGELESS
RECESSED LIGHTS ARE TO BE MOCKED UP BY THE ELECTRICAL CONTRACTOR PRIOR TO
INSTALLATION.
8. ELECTRICAL CONTRACTOR IS TO NOTIFY 186 IF ANY FIXTURE LOCATIONS MUST MOVE
MORE THAN SIX INCHES DUE TO FIELD CONDITIONS.
9. ALL SCONCE AND CLOCK OUTLET LOCATIONS SHOWN ON DRAWINGS ARE APPROXIMATE.
EXACT LOCATIONS AND HEIGHTS OF WALL SCONCES AND CLOCK OUTLETS FOR PICTURE
LIGHTS ARE TO BE VERIFIED WITH THE INTERIOR DESIGNER AND/OR OWNER.
10. ALL LED STRIP INSTALLATIONS ARE TO BE INDIVIDUALLY FED IN LENGTHS NO LONGER
THAN THE MAXIMUM LENGTHS RECOMMENDED BY THE MANUFACTURER. ELECTRICAL AND
GENERAL CONTRACTOR ARE TO WORK TOGETHER TO ENSURE THERE ARE NO VISIBLE
WIRENUTS OR ELECTRICAL CONNECTIONS.
11. ALL FIXTURES SHALL BE SUPPLIED WITH SPECIFIED LAMPS. WHERE BEAMSPREADS ARE
NOT SPECIFIED, SUPPLY WIDEST BEAMSPREAD AVAILABLE FOR PARTICULAR LAMP TYPE.
12. ALL WIRING IS SHOWN SYMBOLICALLY ON PLANS. ACTUAL REMOTE
TRANSFORMER/DRIVER LOCATIONS AND HOMERUNS ARE TO BE DETERMINED BY
ELECTRICAL CONTRACTOR AND GENERAL CONTRACTOR. ALL REMOTE
TRANSFORMERS/DRIVERS SHALL BE TOROIDAL AND MOUNTED IN A LOCATION REMOVED
FROM THE ROOM'S AIRSPACE SUCH AS AN ATTIC, CABINET, OR CRAWLSPACE, UNLESS
OTHERWISE NOTED.
13. ALL SWITCHED OUTLETS SHOWN ON PLANS SHALL BE WIRED SUCH THAT THE OUTLET
MAY BE SWITCHED AT ANY TIME IN THE FUTURE. VERIFY ACTUAL OUTLETS TO SWITCH WITH
OWNER. ALL HALF-SWITCHED OUTLETS ARE TO HAVE SWITCHED SIDE AND HOT SIDE FED
FROM SAME BREAKER.
14. EXHAUST FAN LOCATIONS ARE SHOWN SYMBOLICALLY ON THE PLANS. VERIFY EXACT
EXHAUST FAN LOCATIONS WITH MECHANICAL CONTRACTOR.
15. MOTION SENSORS SHALL BE WALL-MOUNTED AT STANDARD SWITCH HEIGHT UNLESS
OTHERWISE NOTED.
16. ALL LOADS TO BE LANDED ON CONTROL DEVICES IN ORDER DRAWN ON PLANS.
17. CENTER LINE OF TYPICAL SWITCH AND WALLBOX DIMMER BOXES TO BE AT 48" A.F.F.
CENTER LINE OF TYPICAL CONTROL SYSTEM KEYPADS TO BE AT 54" A.F.F. (EXCEPT AT
BEDROOM HEADBOARD LOCATIONS, ABOVE COUNTERS, AND OTHER NON-TYPICAL KEYPAD
LOCATIONS) VERIFY WITH OWNER, ARCHITECT, AND INTERIOR DESIGNER. ELECTRICAL
CONTRACTOR AND A/V CONTRACTOR TO VERIFY ALL KEYPADS BESIDE BEDS ARE INSTALLED
CLEAR OF BED HEADBOARD.
18. ELECTRICAL CONTRACTOR TO VERIFY DIMMER AND CONTROL LOCATIONS.
19. ALL LOADS IN REMOTE DIMMING PANELS TO BE LANDED WHERE SHOWN ON PANEL
SCHEDULE PROVIDED BY LIGHTING CONTROL SYSTEM CONTRACTOR. ELECTRICAL
CONTRACTOR SHALL NOTIFY LIGHTING CONTROL SYSTEM CONTRACTOR OF ANY LOADS
THAT HAVE BEEN MOVED FOR ANY REASON.
20. IN ORDER TO INSURE REMOTE ACCESS TO THE LIGHTING CONTROL SYSTEM
PROCESSOR(S), A PHONE OUTLET OR ETHERNET CONNECTION, AS WELL AS AN ELECTRICAL
OUTLET IS REQUIRED AT ALL PROCESSOR LOCATIONS.
21. ELECTRICAL CONTRACTOR AND A/V CONTRACTOR ARE TO VERIFY ALL FINISHES OF
ELECTRICAL DEVICES, LIGHTING TRIMS, AND WALL-BOX DEVICES WITH THE INTERIOR
DESIGNER AND/OR OWNERS PRIOR TO ORDERING. IF THESE COLORS OR FINISHES ARE NOT
VERIFIED, ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REPLACING EQUIPMENT AND
DEVICES AT NO COST TO THE OWNERS.
22. ELECTRICAL CONTRACTOR TO PROVIDE (10) EXTRA OF 10 DEGREE SPOTS, 25 DEGREE
NARROW FLOODS, 40 DEGREE FLOODS, AND 60 DEGREE WIDE FLOODS FOR AIMING AND
SPARE STOCK FOR OWNER. PROVIDE FLOOD BEAMSPREADS FOR MR-16 LAMPS WHERE
BEAMSPREAD IS NOT DESIGNATED ON 186 BEAMSPREAD DRAWINGS. ELECTRICAL
CONTRACTOR TO REQUEST BEAMSPOREAD PLAN FROM 186 PRIOR TO PURCHASE AND
ELECTRICAL TRIM OUT OF MR16 LAMPHOLDERS.
23. ALL ADJUSTABLE ACCENTS TO BE AIMED STRAIGHT DOWN AT ELECTRICAL TRIM-OUT.
ELECTRICAL CONTRACTOR TO PROVIDE LADDERS AND PERSONNEL TO ASSIST 186 AND
CLIENT WITH FINAL AIMING OF ADJUSTABLE FIXTURES WHEN ARTWORK AND FURNITURE ARE
IN PLACE. AIMING SESSIONS ARE TYPICALLY AFTER SUNSET.
24. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR APPROPRIATE SIZING OF ALL
ELECTRICAL CONDUCTORS. 12-VOLT SYSTEMS SUCH AS MONORAIL, CABLE, AND LOW VOLT
TRACK SHALL BE FED WITH STRANDED WIRE OF AN APPROPRIATE GAUGE FOR LIGHTING
LOAD SHOWN ON PLANS. WIRING SHALL BE SIZED SUCH THAT VOLTAGE DROP TO LOW
VOLTAGE SYSTEMS IS NOT GREATER THAN 10%. IF NECESSARY, USE MULTI-TAP
TRANSFORMER TO ACHIEVE REQUIRED VOLTAGE AT EACH LIGHT.
ALL REFERENCES TO ELECTRICAL OR LOW VOLTAGE SYSTEMS THAT ARE NOT DIRECTLY
RELATED TO LIGHTING ARE ON THE PLANS FOR REFERENCE ONLY. ACTUAL FINAL LOCATIONS
AND DIMENSIONS ARE TO BE PROVIDED BY OTHERS.
KEYPAD
DATA OUTLET
CABLE TELEVISION OUTLET
THERMOSTAT
TRANSFORMER
SATELLITE TELEVISION OUTLET
TELEPHONE
QUAD OUTLET
220V OUTLET
DOOR JAMB SWITCH
HOT ELECTRICAL OUTLET
MOTION SENSOR
1/2 SWITCHED FLOOR OUTLET
HOT FLOOR OUTLET
FULLY SWITCHED OUTLET
1/2 SWITCHED OUTLET
WEATHERPROOF GFI OUTLET
GFI PROTECTED OUTLET
3-WAY SWITCH
4-WAY SWITCH
3-WAY DIMMER
FULLY SWITCHED FLOOR OUTLET
DIMMER
SWITCH
LEGEND
A/V TOUCHSCREEN
LINE VOLTAGE CONTROL SYSTEM DIMMERS
220V
SPEAKER
SATV
TS
S
S
S
S
S
S
3
4
JS
D
TV
GD
GFI
WP
GFI
SP
1/4 SWITCHED QUAD OUTLET
GARAGE DOOR OUTLET
RF TABLETOP KEYPAD
RF LAMP DIMMER - PLUG INTO HOT OUTLET
CIRCUIT NUMBER
HOT QUAD FLOOR OUTLET
1/4 SWITCHED QUAD FLOOR OUTLET
1234
T-STAT
GENERAL NOTES
3D
MR16 LEGEND
10 DEGREE SPOT BEAMSPREAD
25 DEGREE NARROW FLOOD BEAMSPREAD
40 DEGREE FLOOD BEAMSPREAD
60 DEGREE WIDE FLOOD BEAMSPREAD
DIFFUSING LENS
SOFT FOCUS LENS
LINEAR SPREAD LENS
FROSTED LENS
CLEAR LENS
HONEYCOMB LOUVER
COLOR LEGEND
SYSTEM DIMMER/HYBRID KEYPAD
NON-SYSTEM DEVICES
SYSTEM HOMERUN LOAD
LOW VOLTAGE KEYPAD; FIREPLACE; MOTOR
POWER OUTLETS
FIBEROPTIC ILLUMINATOR
SURFACE-MOUNTED LINEAR LIGHT
LANDSCAPE ACCENT
EXTERIOR PATH LIGHT
UNDERWATER ACCENT
WALL-RECESSED STEP LIGHT
RECESSED LINEAR LIGHT
IN-GROUND WELL LIGHT
POST TOP LIGHT
T
RECESSED WALL WASH, ROUND OR SQUARE
LOW VOLTAGE OR LED STRIP
SHADE MOTOR / WINDOW MOTOR
EXHAUST FAN
CEILING FAN
12V OR 24V ROUGH-IN JUNCTION BOX
MONOPOINT HEAD
DUAL-HEADED MONOPOINT
TRACK LIGHTING
HANGING PENDANT OR CHANDELIER
WALL MOUNTED FIXTURE
RECESSED ADJUSTABLE ACCENT, ROUND OR SQUARE
MINI-RECESSED DOWNLIGHT OR PUCKLIGHT
RECESSED DOWNLIGHT, ROUND OR SQUARE
CEILING MOUNTED FIXTURE
W
P
C
CLOCK OUTLET FOR PICTURE LIGHTCO
48"
FO
FP
JB
POOL LIGHT
LONG HANGING PENDANT OR CHANDELIER, VERIFY FEED LOC.
FIREPLACE IGNITION
1-HEADED RECESSED MULTIPLE
2-HEADED RECESSED MULTIPLE
3-HEADED RECESSED MULTIPLE
P
RECESSED LINEAR WALL WASH
12/24V
JB JUNCTION BOX
JB
RGBW
5-CONDUCTOR LOW VOLTAGE ROUGH-IN JUNCTION BOX
JB
RGB
4-CONDUCTOR LOW VOLTAGE ROUGH-IN JUNCTION BOX
WALL MOUNTED SWING-ARM LAMP
OR MAKEUP MIRROR WITH INTEGRAL SWITCH
XFMR
SP
NFL
FL
WFL
DIFF
SOFT
LIN
FROST
CLR
LOUV
VERIFY IN FIELDVIF
TABLE OF CONTENTS
LIGHT.1.001 STANDARD LEGENDS & NOTES
LIGHT.2.001 LOWER LEVEL EXT LIGHTING PLAN
LIGHT.2.002 MAIN LEVEL EXT LIGHTING PLAN
LIGHT.2.003 UPPER LEVEL EXT LIGHTING PLAN.
LIGHT.2.004 LANDSCAPE LIGHTING PLAN
LIGHT.2.005 DRIVEWAY LIGHTING PLAN
LIGHT.2.006 LOWER LEVEL LIGHTING PLAN | A
LIGHT.2.007 LOWER LEVEL LIGHTING PLAN | B
LIGHT.2.008 MAIN LEVEL LIGHTING PLAN | A
LIGHT.2.009 MAIN LEVEL LIGHTING PLAN | B
LIGHT.2.010 UPPER LEVEL LIGHTING PLAN
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)LIGHT.0.001I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
STANDARD LEGENDS & NOTES
NO SCALE
LEGEND
& GENERAL NOTES
NOT FOR
CONSTRUCTION
4/5/2018
STOR.
BELOW
DW
LAUNDRY
008
STAIR 1
007
HALL
011
PDR 2
006
KITCHENETTE
004
BED 1 - PLAYROOM
014BED 2
018
BATH 3
019
BATH 2
016
WIC 2
017
WIC 1
013
MECH
009
PDR 1
003
FAMILY ROOM
002
OUTDOOR PATIO
-
STAIR 1
001
A4 A4 A4 A4 A4 A4 A4 A4
L8
L8
STEPLIGHT AT RECESSED
SEATING LIGHTS DOWN
PINSPOT DOWNLIGHTS
A1W
A1W
A1W
A1W
A1W
A1W
A1W
A1W
A1W
SPA LIGHTING
BY OTHERS
L8
STRUCTURE ABOVE
A1W A1W
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LIGHT.2.001
LOWER LEVEL
EXTERIOR LIGHTING PLAN
LOWER LEVEL EXTERIOR LIGHTING PLAN
3/16" = 1'-0"
NOT FOR
CONSTRUCTION
4/5/2018
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.EL. 10'-0" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.EL. 10'-6" A.F.F.
EL. 10'-3" A.F.F.
EL. 10'-6" A.F.F.
EL. - A.F.F. TO BE V.I.F.
REF.
A-01
STORAGE
KITCHEN
104
HALL
111
LIVING ROOM
102
ENTRY
100 STAIR 1
101GALLERY
106
STAIR 2
107
GARAGE
116
OFFICE
112
PDR 3
109
PANTRY
108
WINE
113
MUDROOM
114
MONOPOINTS HIDDEN AT VERTICAL
SKYLIGHT WALL LIGHTS DOWN
M1
L8
LED STRIP TOEKICK
LIGHTS DOWN AT FIRE
Z1 Z1
INGROUND UPLIGHTS -
SHIELDED BY CANOPY
ABOVE
DOWNLIGHT STRIP IN VERTICAL GARAGE DETAIL,
HIDDEN SOFT EVEN LIGHTING
A1W
L8L8
A1W
A1W
A4
A4
A4
A4
A4
A4 A4 A4
A1W
A1W
A1W
M1M1 M1M1 M1M1
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LIGHT.2.002
MAIN LEVEL
EXTERIOR LIGHTING PLAN
MAIN LEVEL EXTERIOR LIGHTING PLAN
3/16" = 1'-0"
NOT FOR
CONSTRUCTION
4/5/2018
DECK
GWB
GWB
GWB
TILE [RE: INT.FOR EL. + FINISH]
TILE [RE: INT.FOR EL. + FINISH]
GWB
GWB
DS.DS.
W / D
REF.
EL. 114'-3" [7794.25']
EL. 114'-0" [7794.00']
EL. 122'-5"
DECK
W/D
KITCHEN
A12
LIVING
A11
ENTRY
A10
DECK
-
BEDROOM
A15
WIC
A16
BATH
A17
HALL
A14STORAGE
A13
MASTER BED
202
MASTER BATH
203
STEAM SHOWER
204
W.C.
204
MASTER DRESSING
206
STAIR 2
207
HALL
201
A1W
A1W
A1W
A1W
A1W
A1W
A4
A4
A4
A1W
A1W
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LIGHT.2.003
UPPER LEVEL
EXTERIOR LIGHTING PLAN
UPPER LEVEL EXTERIOR LIGHTING PLAN
3/16" = 1'-0"
NOT FOR
CONSTRUCTION
4/5/2018
B1
B1 B1 B1 B1
B1 B1 B1
SPA LIGHTING
BY OTHERS
B1
B1
B1
GRADE CHANGE
PATHLIGHTS AT
STAIRS
JB
ROUGH-IN FOR
POWER AT FLEX
PLAY AREA
JB
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
L8L8 L8
L8L8L8
L8
L8 L8
L8
FULLY SHIELDED, HIDDEN
LOW-OUTPUT LED IN
TOEKICK OF PATH
FULLY SHIELDED, HIDDEN
LOW-OUTPUT LED IN
TOEKICK OF PATH
M2M2
DOWNLIGHTING
TOWARDS PATH FROM
TREE; LOWER THAN 8FT
MOUNTING HEIGHT
M2M2
M2
M2
M2
M2
M2
ST1
CONCRETE RECESSED
STEPLIGHT DETAIL AT
WINDOW WELL
DOWNLIGHTING
TOWARDS PATH FROM
TREE; LOWER THAN 8FT
MOUNTING HEIGHT
1
1
1
JB
MATCHLINEMATCHLINE
2
2
2
8FT MAX HEIGHTSOFT LIGHTON SIDEWALKFULLY SHIELDED & HIDDEN, VERY
LOW OUTPUT LED ROPELIGHT IN
TOEKICK OF PATH
3-4"
1 2LED TOEKICK - TYPE L8 TREE DOWNLIGHT - TYPE M2
I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LIGHT.2.004
LANDSCAPE
EXTERIOR LIGHTING PLAN
LANDSCAPE LIGHTING PLAN
3/16" = 1'-0"
NOT FOR
CONSTRUCTION
4/5/2018
B1
B1
B1
B1
B1
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
PATHLIGHTS AT
EM TURNAROUND
GRADE CHANGE
JB
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
SWITCHED
OUTLET FOR
HOLIDAY LIGHTING
JB
ROUGH-IN FOR POWER
AT ADDRESS MARKER
L8L8 L8
L8L8L8
L8
L8 L8
L8
FULLY SHIELDED, HIDDEN
LOW-OUTPUT LED IN
TOEKICK OF PATH
M2M2
M2M2
1
1
1
JB
MATCHLINEMATCHLINE
2
2
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LIGHT.2.005
LANDSCAPE
EXTERIOR LIGHTING PLAN
DRIVEWAY LIGHTING PLAN
3/16" = 1'-0"
NOT FOR
CONSTRUCTION
4/5/2018
STOR.
BELOW
DW
48"48"
48"48"SMS SSJS
JS
SSJS JSSSSLAUNDRY
008
STAIR 1
007
HALL
011
PDR 2
006
KITCHENETTE
004
BED 1 - PLAYROOM
014BED 2
018
BATH 3
019
BATH 2
016
WIC 2
017
WIC 1
013
MECH
009
PDR 1
003
A2 S2A2A2A2S2
CC C C
P
L2L2L2
360° BACKLIT MIRROR. ALT
OPTION: SCONCE OR PENDANTS
L1
L3L3L3
L1
L1
L1
L3
OPTION: MCM DECORATIVE SCONCE OR PENDANT
W
L3
A1
A1
A1
A1
UNDER CABINET
360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING
23"
L5
L3
SS
UNDERCABINET
TASK LIGHT
L6
RECESSED LINEAR LED.
OPTION: TRIMLESS
A2S2 A2 A2
HOT OUTLET AT FUTURE
BED LOCATION. VERIFY
QTY/LOCATION WITH
OWNER ON-SITE.
A4 A4 A4 A4 A4 A4
LED STRIPS AT SHELVING
LED STRIPS AT SHELVING
FLOATING VANITY
INVERSE COVE
48"MS
L1
LED STRIPS AT UNDERCABINET, AND BAR
SHELVES. QTY AND TYPE TBD PER FINAL
MILLWORK DRAWINGS
L1
A1
A1
OPTION: MCM DECORATIVE SCONCE OR PENDANT
360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING
L3
INVERSE COVE, GLOWS
FROM OUTSIDE
P
A1
A1
STEPLIGHTS THIS
SIDE SHOWN ABOVE
JB
L1
UPLIGHT ON TOP OF
CABINETS
STRUCTURE ABOVE
JB
A2
A2
A2
A2A2A2A2
A2 A2 A2
A2A2 A2 A2
A2A2A2
A2 A2 A2 A2
A2
A2
A2 A2
A2
A2 A2 A2 A2
A2A2A2A2
L1L1
L1
CC
INVERSE COVE
L7
WALL WASH TO
LIGHT ART WALL
ARTA1
A1
A1
A1A1A1A1A1A1A1
EQ
EQ
EQ
36"
C
SA2A2
A1 A1
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LOWER LEVEL
LIGHTING PLAN
LOWER LEVEL LIGHTING PLAN | A
1/4" = 1'-0"
NOT FOR
CONSTRUCTION
LIGHT.2.006
4/5/2018
SSJS JS
FP
PDR 2
006
KITCHENETTE
004
WIC 1
013
PDR 1
003
FAMILY ROOM
002
OUTDOOR PATIO
-
STAIR 1
001
S2
C
L2
360° BACKLIT MIRROR. ALT
OPTION: SCONCE OR PENDANTS
L1
L1
L3 L1L1L1
L1L1L1
OPTION: MCM DECORATIVE SCONCE OR PENDANT
W
L3
A1
A1
A1
A1
UNDER CABINET
360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING
23"
Z1
A4 A4 A4 A4 A4
T1T1
T1
LED STRIPS AT SHELVING
LED STRIPS AT SHELVING
INVERSE COVE
L1
L8
L8
STEPLIGHT AT RECESSED
SEATING LIGHTS DOWN
LED STRIPS AT UNDERCABINET, AND BAR
SHELVES. QTY AND TYPE TBD PER FINAL
MILLWORK DRAWINGS
PINSPOT DOWNLIGHTS
IN-FLOOR HOT OUTLETS.
VERIFY QTY AND LOCATIONS
ON-SITE WITH OWNER
A1W
A1W
A1W
A1W
A1W
A1W
A1W
A1W
A1W
A1WEQEQ
A1
A1
TABLE
TABLE
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TABLE
TABLE
TABLE
DOWN
DOWNBAR
TH1
BAR
TH1
BAR
TH1
SEATING
TH1
SEATING
TH1
SEATING
TH1
SEATING
TH1
BUILT-IN
TH1
SEATING
TH1
TH1
TH1
TH1
TH1
TABLE
SEATING
TH1
SPA LIGHTING
BY OTHERS
OPTION: MCM DECORATIVE SCONCE OR PENDANT
360° BACKLIT MIRROR PROVIDES FUNCTIONAL LIGHTING
L3
INVERSE COVE, GLOWS
FROM OUTSIDE
P
A1
A1
L8
L1
LED STRIP INTEGRATED UNDER
COUNTER - COORDINATE DETAIL,
NOT VISIBLE TO SEATING BELOW.
L1
UPLIGHT ON TOP OF
CABINETS
A2
A2
L1
A1W
A1WA1W
A1WA1W
A1WA1W
A1WA1W
A1W
L7
WALL WASH TO
LIGHT ART WALLA1
A1
A1
EQ
EQ
EQ
A2
INGROUND UPLIGHT
Z1
A1 A1
360° BACKLIGHT AROUND TV
A1W A1W
1
1
1
Z1 Z1 Z1 Z1 Z1
L1
SEE T1/TH1 ALTERNATE
SPEC FOR CLG
COORDINATION
LED STRIPS AT STAIR TREADS
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
LOWER LEVEL
LIGHTING PLANLOWER LEVEL LIGHTING PLAN | B
1/4" = 1'-0"
NOT FOR
CONSTRUCTION
LIGHT.2.007
4/5/2018
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.EL. 10'-0" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-3" A.F.F.
EL. - A.F.F. TO BE V.I.F.
REF.
48"
48"
48"
48"
48"
48"
48"SS
S
SJS
JS
JS
JS
S48"48"48"48"COORDINATE FIXTURE WITH
GARAGE DOOR. ALT OPTION:
USE L6 RECESSED LINEARS.
(~60% COST INCREASE)
CRAWL SPACE
[4' HIGH / STORAGE]
A-01
STORAGE
HALL
111
STAIR 2
107
GARAGE
116
OFFICE
112
PDR 3
109
PANTRY
108
WINE
113
MUDROOM
114
A1
L1
OPTION: MCM
DECORATIVE SCONCE
OR PENDANT
W
FLOATING VANITY
IN-WALL DETAIL
WALL RECESSED STEPLIGHT DETAIL;
LED STRIP IN WALL DETAIL
ST1
SHEETROCK DEPTH
TRIMLESS LINEAR LED
LED STRIP AT CUBBIES. QTY
AND LOCATIONS PER FINAL
MILLWORK DESIGN.
L5
L5
L5
L5
L5
L5
L6A L6A L6A
UNDERCABINET TASK LIGHT
AT OFFICE MILLWORK
L3
A1
A1
A1
A1 A1
A1 A1 A1 A1A1A1A1
FL1
FL1
FL1
FL1FL1
FL1 FL1
FL1
FL1FL1
FL1
TO STAIRS
ABOVE
L1
L8
LED STRIP TOEKICK
LIGHTS DOWN AT FIRE
L1
UPLIGHT FROM MILLWORK - ALT:
IN-SHELF-LIGHTING FOR AMBIENT LIGHT
A1
A1
A1
A1
36"
L5
1/3
1/3
1/3
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
35"
A1 A1
NIGHT PATH TO BEDROOMS
A1
A1
UPLIGHT AT WINDOW
HALLWAY, NOT PATIO)
CAN WE FIT
DOWNLIGHT IN
STAIR LANDING?
DOWNLIGHT STRIP IN VERTICAL GARAGE DETAIL,
HIDDEN SOFT EVEN LIGHTING
L1
L1 L1
L1
INFLOOR
UPLIGHTS
LED STRIP AT
BOTTLE
DISPLAY
WALL
GRAZING
BEHIND
BOTTLES
L8L8
40"
L148"48"FL1
FL1 48"48"FL1
FL1
A1WA1W
ST1ST1ST1ST1ST1
ST1ST1ST1ST1ST1ST1A4
A4
A4
A4
A4
VERTICAL LED STRIP INTEGRATED
INTO WINDOW DETAIL
A4 A4 A4
LANDSCAPING BELOW?
EQ
EQ
A1W
A1W
A1W
M1M1 M1
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
ENTRY LEVEL LIGHTING PLAN | A
1/4" = 1'-0"
ENTRY LEVEL
LIGHTING PLAN
NOT FOR
CONSTRUCTION
LIGHT.2.008
4/5/2018
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.EL. 10'-0" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.EL. 10'-6" A.F.F.
EL. 10'-6" A.F.F.
REF.SS
S
SJS
JS
JS
JS
FP48"48"COORDINATE FIXTURE WITH
GARAGE DOOR. ALT OPTION:
USE L6 RECESSED LINEARS.
(~60% COST INCREASE)
KITCHEN
104
HALL
111
LIVING ROOM
102
ENTRY
100 STAIR 1
101GALLERY
106
STAIR 2
107
GARAGE
116
OFFICE
112
PDR 3
109
PANTRY
108
WINE
113
MUDROOM
114
A1W
Z1 Z1 Z1 Z1 Z1 Z1
ART WALL
A1A1
L1
L3
OPTION: MCM
DECORATIVE SCONCE
OR PENDANT
W
360° BACKLIT
MIRROR
FLOATING VANITY
360° ART LIGHT
IN-WALL DETAIL
LED STRIP UNDER
COUNTER
LED STRIP UPLIGHT
AT HIGH WINDOW
IN-FLOOR UPLIGHTS
AT COLUMNS
RECESSED LINEAR
LED: OPTION
TRIMLESS L6A
L1
L1
L1
ST1 ST1
ST1ST1
WALL RECESSED STEPLIGHT DETAIL;
LED STRIP IN WALL DETAIL
WALL RECESSED STEPLIGHT DETAIL;
LED STRIP IN WALL DETAIL
ST1
IN-FLOOR HOT OUTLETS.
VERIFY QTY AND LOCATIONS
ON-SITE WITH OWNER
OPTION: LAMP DIMMER OF USE WITH HOT
OUTLET. HIDDEN DEVICE CONNECTS
LAMPS TO LIGHTING SYSTEM. ONE PER
LAMP ALT: SWITCHED OUTLETS
T1T1T1
SHEETROCK DEPTH
TRIMLESS LINEAR LED
LED STRIP AT CUBBIES. QTY
AND LOCATIONS PER FINAL
MILLWORK DESIGN.
L5
L5
L5
L5
L5
L5
L6A L6A L6A
L6
UNDERCABINET TASK LIGHT
AT OFFICE MILLWORK
L3
A1
A1
A1
A1 A1
MONOPOINTS HIDDEN AT VERTICAL
SKYLIGHT WALL LIGHTS DOWN
M1
A1W A1W A1W
A1 A1 A1 A1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1TH1TH1
TH1 TH1 TH1
TABLE
TABLE
TABLE
TABLE
TABLE
TABLE
FIRE
FIRE
SEATING
SEATING
SEATING
SEATING
DOWNDOWNDOWN
DOWN DOWN DOWN
TH1
TH1
TH1
TH1
TH1
TH1
TH1
SEATING
SEATING
SEATING
SEATING
TABLE
SEATING
SEATING
A1 A1 A1 A1
FL1
FL1
TO STAIRS
ABOVE
LED STRIP UPLIGHT
AT HIGH WINDOW
L1
L8
LED STRIP TOEKICK
LIGHTS DOWN AT FIRE
L1
UPLIGHT FROM MILLWORK - ALT:
IN-SHELF-LIGHTING FOR AMBIENT LIGHT
A1
A1
A1
A1
36"
L5
1/3
1/3
1/3
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1 Z1
35"
A1 A1
NIGHT PATH TO BEDROOMS
A1
A1
INGROUND UPLIGHTS -
SHIELDED BY CANOPY
ABOVE
L1
L1
L1L1L1L1L1L1L1
UPLIGHT AT WINDOW SILL
UPLIGHT AT WINDOW
SILL (LIGHTS HIGH
HALLWAY, NOT PATIO)
CAN WE FIT
DOWNLIGHT IN
STAIR LANDING?
DOWNLIGHT STRIP IN VERTICAL GARAGE DETAIL,
HIDDEN SOFT EVEN LIGHTING
L1
L1 L1
L1
INFLOOR
UPLIGHTS
LED STRIP AT
BOTTLE
DISPLAY
WALL
GRAZING
BEHIND
BOTTLES
A1W
L8
A1W
A1W
L1L1L1
40"
A1W
T1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
TH1
L1
UPLIGHT ABOVE
FLOATING STRUCTURE
L1
1/3
1/3
1/3
48"48"FL1
FL1
A1WA1W
A1WA1WA1W
A1WA1WA1WA1WA1WA1W
ST1ST1ST1ST1ST1
ST1ST1ST1ST1ST1ST1
ST1
ST1
ST1
ST1
ST1
ST1
TH1
DOWN
DOWN
EQ EQ EQ
A4
A4
A4
OPTION: LIGHT ART WITH TH1 TRACK HEADS - POSSIBLY LESS
UNIFORM WALL WASH, BUT CLEANER CEILING
VERTICAL LED STRIP INTEGRATED
INTO WINDOW DETAIL
A4
A4
L1
LED STRIP AT COUNTER
HEIGHT CHANGE - TASK LIGHT
A4
LANDSCAPING BELOW?
EQ
EQ
A1W
A1W
A1W
M1M1 M1M1 M1M1
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
ENTRY LEVEL LIGHTING PLAN | B
1/4" = 1'-0"
ENTRY LEVEL
LIGHTING PLAN
NOT FOR
CONSTRUCTION
LIGHT.2.009
4/5/2018
DECK
GWB
GWB
GWB
TILE [RE: INT.FOR EL. + FINISH]
TILE [RE: INT.FOR EL. + FINISH]
GWB
GWB
DS.DS.
W / D
REF.
EL. 114'-3" [7794.25']
EL. 114'-0" [7794.00']
EL. 122'-5"
DECK
W/D
FP
ART
ART
ARTGALLERY WALL
LED STRIP UPLIGHT
AT HIGH WINDOWS
VERTICAL LED STRIP INTEGRATED
INTO WINDOW DETAIL
CLOSET RATED LED STRIPS: QTY AND LOCATION TBD
PER FINAL MILLWORK DRAWINGS; STRIPS SHOWN
FOR PRICING TO BE UPDATED PER FINAL DESIGN
VERTICAL LED STRIP
INTEGRATED INTO
WINDOW DETAIL
UPLIGHT AT WINDOW SILL
L5
L5 L5 L5
L5
L5L5
L1L1L1
LED STRIP UPLIGHT
AT HIGH WINDOWS L2
L2
L1
L1
L2
L2
LED STRIPS INTEGRATED INTO
SAUNA BENCH: UPLIGHT FROM
BEHIND BENCH, AND TOEKICK
BELOW
A2
A2
S2
L2
L3
L1
48"SFL1
S
A2
A2
A1W A1W
IN-FLOOR HOT OUTLETS.
VERIFY QTY AND LOCATIONS
ON-SITE WITH OWNER
HOT OUTLET AT FUTURE BED
LOCATION. VERIFY QTY/LOCATION
WITH OWNER ON-SITE.
L3
UNDERCABINET LIGHT
LED STRIP UPLIGHT AT HIGH
WINDOW SILLS
L1
A2
A2
A2
A2
A2
A2A2
L1
LED STRIP UPLIGHT AT HIGH WINDOW
W
WALL MOUNTED READING
LIGHTS WITH INTEGRAL
CONTROL
W
30"
L1
L1
WALL RECESSED STEPLIGHT DETAIL;
LED STRIP IN WALL DETAIL
L1 L1 L1 L1
TO STAIRS BELOW
LED STRIP UPLIGHT AT OPENING
L1
A1W A1W
A1W A1W
A1W A1W
A1W A1W
A1W A1W
A1W A1W
A1W A1W
A1W A1W
A1 A1
L3L3
LIGHTING
INTEGRATED INTO
BUILT-IN MIRROR
L1
L1
LED STRIP TOEKICK,
OR FLOATING VANITY
PER FINAL DESIGN
LED STRIP AT STEP
LED STRIP UPLIGHT AT
BACK OF CEILING
DETAIL
A1A1 A1 A1
A1A1 A1 A1
UPLIGHT FROM TOP OF CABINETS
L1
SL1
STRIPLIGHT ABOVE
HEADER ON JAMB SWITCH
S1
S1
A2
SS12"
SS
SSSKITCHEN
A12
LIVING
A11
ENTRY
A10
DECK
-
BEDROOM
A15
WIC
A16
BATH
A17
HALL
A14STORAGE
A13
SSSL1 L1 L1 L1 S3D
3D
L1
L1
L1
A2
A2
A1
S2
S2
L1
L1
L1
L1L1
A1W
A1W
A1WA1WA1WA1W
A1WA1WA1WA1W
A1WA1WA1WA1W
MASTER BED
202
MASTER BATH
203
STEAM SHOWER
204
W.C.
204
MASTER DRESSING
206
STAIR 2
207
HALL
201
UPLIGHT AT WINDOW SILL
A1W
A1W
A1W
L1L1
SA1W
A1W
A1W
OPTION: LAMP DIMMER OF USE WITH HOT
OUTLET. HIDDEN DEVICE CONNECTS
LAMPS TO LIGHTING SYSTEM. ONE PER
LAMP ALT: SWITCHED OUTLETS
L1
VERIFY TYPE
(FLANGED)
WITH TILE
A4
A4
A4
11"
A1W
52"
L1
52" MIN DISTANCE TO
LIGHT ART @ ~13' CLG
A1W
A1WA1WA1W
A1W
A1W
A1W A1W
A1WA1W
42"
S1 S1
S1
S1
S1
S1
S1
S1S1S1S1S1
S1
OPTION: COULD REDUCE QTY OF DOWNLIGHTS
DEPENDING ON MILLWORK LED STRIP COVERAGE.
ALT OPTION: USE TRIMLESS LINE-OF-LIGHT IN
DRESSING INSTEAD OF DOWNLIGHTS.
A1WA1WA1WA1W
A1W A1W A1WA1W
A1W
A1W
TALK ABOUT ART LIGHTING OPTIONS HERE.
ENERGY COMPLIANCE: WHOLE PROJECT
98.4% OF ALL FIXTURES AND LIGHT BULBS ARE EFFICIENT
584 EFFICIENT FIXTURES
9 NON-EFFICIENT FIXTURES (ALL TYPES W, P AND C)I I BAR X RESIDENCE110 + 112 COACH ROADASPEN, CO 816111 8 6 L I G H T I N G D E S I G N G R O U P ,I N C .
1200 BANNOCK ST.
DENVER, CO 80204
TEL:303.534.5350
www.186group.com
DATE REVISION & ISSUE
2018-01-29 MEETING
2018-02-14 PROGRESS
2018-02-28 ACC FINAL SITE PLAN
2018-03-20 PERMIT REVIEW
2018-03-30 PERMIT SET
SHEET NUMBER:
PAGE TITLE:
UPPER LEVEL LIGHTING PLAN
1/4" = 1'-0"
UPPER LEVEL
LIGHTING PLAN
NOT FOR
CONSTRUCTION
LIGHT.2.010
4/5/2018