HomeMy WebLinkAboutFile Documents.534 E Cooper Ave.0003.2017 (22).ACBKProject Title: 534 E. COOPER STREET, ASPEN Report date: 04/10/18
Data filename: P:\Current Projects\15075.00 - 534 E Cooper Boogies MEP\Calculations\COMcheck\Boogies.cck Page 1 of 4
COMcheck Software Version 4.0.8.0
Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code: 2009 IECC
Project Title: 534 E. COOPER STREET, ASPEN
Project Type: New Construction
Construction Site:Owner/Agent:Designer/Contractor:
534 EAST COOPER
ASPEN, CO 81611
STANTON HUMPHRIES
AEC
AVON, CO 81620
9707488520
STAN@AEC-VAIL.COM
Section 2: Interior Lighting and Power Calculation
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B x C)
CORRIDORS UTILITY AND STORAGE (Retail)5887 1.5 8831
Total Allowed Watts =8831
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
CORRIDORS UTILITY AND STORAGE ( Retail 5887 sq.ft.)
LED 1: A: ACCENT AT BATHRMS: Other:1 6 11.2 67.2
LED 2: A1: ACCENT AT ENTRY: Other:1 2 10.8 21.6
LED 3: D: DOWNLIGHTS STAIR AND ENTRIES: Other:1 27 15.2 410.4
LED 4: F: STRIP LIGHTS: Other:1 1 24 24
LED 5: G: SURFACE LED: Other:1 52 34.9 1814.8
Total Proposed Watts =2338
Section 4: Requirements Checklist
Interior Lighting PASSES: Design 74% better than code.
Lighting Wattage:
q 1.Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies 8831 2338 YES
Controls, Switching, and Wiring:
q 2.Daylight zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to
vertical fenestration.
q 3.Daylight zones have individual lighting controls independent from that of the general area lighting.
Exceptions:
q Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device.
q Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a
separate switch for general area lighting.
Project Title: 534 E. COOPER STREET, ASPEN Report date: 04/10/18
Data filename: P:\Current Projects\15075.00 - 534 E Cooper Boogies MEP\Calculations\COMcheck\Boogies.cck Page 2 of 4
q 4.Independent controls for each space (switch/occupancy sensor).
Exceptions:
q Areas designated as security or emergency areas that must be continuously illuminated.
q Lighting in stairways or corridors that are elements of the means of egress.
q 5.Master switch at entry to hotel/motel guest room.
q 6.Individual dwelling units separately metered.
q 7.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
q 8.Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either
controlling all luminaires, dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps, switching the middle
lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
q Only one luminaire in space.
q An occupant-sensing device controls the area.
q The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
q Areas that use less than 0.6 Watts/sq.ft.
q 9.Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
q Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
q 10.Photocell/astronomical time switch on exterior lights.
Exceptions:
q Lighting intended for 24 hour use.
q 11.Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
q Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC
requirements in COMcheck Version 4.0.8.0 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title Signature Date
Project Notes:
UNFINISHED CORE AND SHELL SPACES WITH TEMPORARY
STRIP LIGHT FIXTURES ARE NOT INCLUDED IN THE COMCHECK.
Stanton O. Humphries, PE 9/27/16
Project Title: 534 E. COOPER STREET, ASPEN Report date: 04/10/18
Data filename: P:\Current Projects\15075.00 - 534 E Cooper Boogies MEP\Calculations\COMcheck\Boogies.cck Page 3 of 4
COMcheck Software Version 4.0.8.0
Exterior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code: 2009 IECC
Project Title: 534 E. COOPER STREET, ASPEN
Project Type: New Construction
Exterior Lighting Zone: 4 (High activity metropolitan commercial district)
Construction Site:Owner/Agent:Designer/Contractor:
534 EAST COOPER
ASPEN, CO 81611
STANTON HUMPHRIES
AEC
AVON, CO 81620
9707488520
STAN@AEC-VAIL.COM
Section 2: Exterior Lighting Area/Surface Power Calculation
A
Exterior Area/Surface
B
Quantity
C
Allowed
Watts
/ Unit
D
Tradable
Wattage
E
Allowed
Watts
(B x C)
F
Proposed
Watts
ENTRIES AT EAST AND SOUTH (Entry canopy)200 ft2 0.4 Yes 80 225
BACK ENTRY (Entry canopy)225 ft2 0.4 Yes 90 108
Total Tradable Watts* =170 333
Total Allowed Watts =170
Total Allowed Supplemental Watts** =1300
* Wattage tradeoffs are only allowed between tradable areas/surfaces.
** A supplemental allowance equal to 1300 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
ENTRIES AT EAST AND SOUTH ( Entry canopy 200 ft2): Tradable Wattage
LED 1: CC: SCONCES: Other:1 9 9 81
LED 2: DD: DOWNLIGHT: Other:1 8 18 144
BACK ENTRY ( Entry canopy 225 ft2): Tradable Wattage
LED 3: DD: DOWNLIGHT: Other:1 6 18 108
Total Tradable Proposed Watts =333
Section 4: Requirements Checklist
Lighting Wattage:
q 1.Within each non-tradable area/surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable
areas/surfaces, total proposed watts must be less than or equal to total allowed watts.
Compliance:Passes using supplemental allowance watts.
Controls, Switching, and Wiring:
q 2.All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting.
q 3.Lighting not designated for dusk-to-dawn operation is controlled by either a a photosensor (with time switch), or an astronomical time
switch.
Project Title: 534 E. COOPER STREET, ASPEN Report date: 04/10/18
Data filename: P:\Current Projects\15075.00 - 534 E Cooper Boogies MEP\Calculations\COMcheck\Boogies.cck Page 4 of 4
q 4.Lighting designated for dusk-to-dawn operation is controlled by an astronomical time switch or photosensor.
q 5.All time switches are capable of retaining programming and the time setting during loss of power for a period of at least 10 hours.
Exterior Lighting Efficacy:
q 6.All exterior building grounds luminaires that operate at greater than 100W have minimum efficacy of 60 lumen/watt.
Exceptions:
q Lighting that has been claimed as exempt and is identified as such in Section 3 table above.
q Lighting that is specifically designated as required by a health or life safety statue, ordinance, or regulation.
q Emergency lighting that is automatically off during normal building operation.
q Lighting that is controlled by motion sensor.
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC
requirements in COMcheck Version 4.0.8.0 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title Signature Date
9/27/16Stanton O. Humphries, PE