HomeMy WebLinkAboutFile Documents.533 E Main St.0004.2017 (40).ACBKFUSIBLE DISCONNECT
SOLID BRICK
ENCLOSURE WALL
PERFORATED BRICK
ENCLOSURE WALL
GRADE SLOPES EAST TO WEST 5'-7"17'-2"6'-0"5'-7"BRICK ENCLOSURE WALL
GRADE SLOPES AWAY
10'-3"
METERING CABINET
FUSIBLE DISCONNECT
BRICK ENCLOSURE WALL
10'-2"1'-0"6'-0"1'-6"A0.11
1
A0.112
A0.11 3
3 YD DUMPSTERXFMR
METERING
CABINET
FUSIBLE
DISCONNECT
9'-11"PERFORATED BRICK WALL
A0.11
5
17'-2"
3'-0"
1'-0"
3'-0"3'-0"DUMPSTER
TRANSFORMER
METERING CABINET
WITH FUSIBLE
DISCONNECT BEYOND
CMU WALL W/ BRICK
EXTERIOR FACE
PERFORATED
BRICK WALL
5'-7"6'-0"1'-6"CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
610 EAST HYMAN AVE.
ASPEN, CO 81611
TEL: 970.925.5590
FAX: 970.920.4557
cunniffe.com
SHEET NO.
JOB NO.4/20/2017 4:51:09 PMA0.11
1511
ENCLOSURE
ELEVATIONSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COISSUE: DATE:
PERMIT RESUB. 04/17/17
1/2" = 1'-0"1 ENCLOSURE NORTH
1/2" = 1'-0"2 ENCLOSURE EAST
1/2" = 1'-0"
3 ENCLOSURE WEST
1/4" = 1'-0"4 ENLARGED ENCLOSURE PLAN
1/2" = 1'-0"5 ENCLOSURE SOUTH
City of Aspen
Received
5/2/17
Building Department
Please submit a complete
plan set.
Provide a letter or email from City of
Aspen Electric approving this
transformer installation and surround.
Sheet S0.1 was never submitted with the original submission.
Please provide it. Must show general notes and design load
specifications.
Submit all 8.5x11 documents as separate pdf files, including the
special inspection agreement and remp worksheet.
DNUP1234567892A4.21A4.11A4.2STORAGESTORAGEBOILERROOMCRAWLSPACECRAWLSPACECRAWLSPACEELEV EQUIP002ELEVLOBBY001REFER TO STRUCTURALDRAWINGS FOR NEW FOOTINGAND COLUMN LOCATIONS INTHIS AREAEL.= 88'-0"EL.= 89'-7 1/2"COORDINATE WALL PENETRATIONSWITH DUCTWORK, RE: MECHREFER TO ELECDWGS THIS AREACHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.2/16/2017 7:46:52 AMA2.4PROPOSEDCONSTRUCTIONPLANSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"1PROPOSED BASEMENT LEVELCONSTRUCTION PLANISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/1730" x 30" access30" x 30" access30" x 30" access30" x 30" access30" x 30" accessRESPONSE TO BUILDINGDEPARTMENT COMMENT #4 City of Aspen Received 5/2/17Building Department
DNUP1234567892A4.21A4.11A4.2STORAGESTORAGEBOILERROOMCRAWLSPACECRAWLSPACECRAWLSPACEELEV EQUIP002ELEVLOBBY001REFER TO STRUCTURALDRAWINGS FOR NEW FOOTINGAND COLUMN LOCATIONS INTHIS AREAEL.= 88'-0"EL.= 89'-7 1/2"COORDINATE WALL PENETRATIONSWITH DUCTWORK, RE: MECHREFER TO ELECDWGS THIS AREA001NEW HM DOOR & FRAME3CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.5/1/2017 10:16:43 AMA2.4PROPOSEDCONSTRUCTIONPLANSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"1PROPOSED BASEMENT LEVELCONSTRUCTION PLANISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17PERMIT RESUB 4/17/173City of Aspen Received 5/2/17Building Department
DNC1234567892A4.2A8.341321A4.11A4.2ENTRY100MEETINGRM102MEETINGRM103MEETINGRM104MEETINGRM105KITCHEN109WOMEN110HALLWAY111MEN116OFFICE113OFFICE114HALL115HALL117RECEPT118OFFICE119VEST.120120B120A117119114111B109A109B113A110111A116A8.38657100EABDMEETINGRM101OFFICE122122101A102A103A104A105A101B101C102C103C104C102B103B104B105BMEETINGRM107CONF RM112A6.11112105C106BMEETINGRM106106A107A113B107BSTOR121A3.61A3.71A3.51EL.= 100'-0"EL.= 100'-6"EL.= 100'-0"2022032172192382202182212222332'-1 7/16"12'-5"12'-5"12'-5"11'-11"13'-0"9'-3 3/4"5'-0"ALIGN6'-0 1/4"ALIGN10'-3 1/4"5'-2"3'-7"3'-8"4'-4"213ALIGN107C234234232244244BAAAAAAAAAABAAA2382372371'-8"8A9.16"4'-1 1/4"6"4'-1 1/4"6"6'-7 3/4"5'-7 1/2"EXIST3'-6 1/8" +/-EXIST3'-6 1/8" +/-DISPLAYREFDISPLAY4'-5 1/2"1'-0"5'-4 1/4"4'-1 1/2"4'-10"2462461'-0" 3'-6"1'-0"EQ3'-5"EQ4"AAA8.3171'-8"8"7'-2 3/8" +/-4"121LINE OF LOW CEILING ABOVEA9.1122602602602012011'-3"255255ALIGN3'-8"4"4"111WALL CONSTRUCTION TO CONFORM TOUL U309 RATED ASSEMBLY OR SIM TOPROVIDE 1 HR RATED ENCLOSURE.3WALL CONSTRUCTION TO CONFORM TOUL U309 RATED ASSEMBLY OR SIM TOPROVIDE 1 HR RATED ENCLOSURE.31. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BUILD-OUT. NOTIFY ARCHITECT OF ANYDISCREPANCIES BETWEEN FIELD CONDITIONS AND DRAWINGS PRIOR TO ALL WORK.2. PROVIDE NEW INTERIOR PARTITIONS AS INDICATED ON PLANS RE: A10.1. TYPICAL PARTITIONCONSTRUCTION: 2X WD 16" O.C. W/ (1) LA. 5/8" TYPE-X GYP. BD. EA. SIDE WITH LEVEL 4 FINISH.3. ROUTE FULL HEIGHT PARTITIONS AROUND EXISTING DUCTWORK AND PIPING AS NECESSARY TOSTRUCTURE ABOVE. PROVIDE 1” PLENUM-RATED GASKET BETWEEN ALL NEW AND EXISTINGPARTITION CONSTRUCTION AND NEW OR EXISTING DUCTWORK TO MINIMIZE VIBRATION, ANDMAINTAIN ACOUSTIC SEPARATION.4. IF FIRE-RESISTIVE RATED PROTECTION (GYP BD, SPRAY-ON, ETC.) IS MODIFIED ABOVE CEILINGSFOR OF NEW PARTITIONS, NEW CEILING FRAMING, OR NEW ATTCHMENTS SUCH AS HANGER RODS,GC SHALL PATCH AND REPLACE TO MAINTAIN UNIFORM THICKNESS AND APPLICATION.5. CONTRACTOR SHALL PATCH ANY PENETRATIONS IN EXISTING FIRE-RATED CONSTRUCTION TOMAINTAIN FIRE RATING.6. REPAIR WALLS AT ALL ABANDONED J-BOX LOCATIONS. BLANK COVERPLATES ARE NOTACCEPTABLE.7. CONTRACTOR TO PATCH AND REPAIR ALL DAMAGED SURFACES INCLUDING PARTITIONS,WINDOWS, WINDOW FRAMES, DOORS, DOOR FRAMES TO AS-NEW CONDITION.8. CONTRACTOR TO PATCH ALL SURFACES AT AREAS OF DEMOLITION THAT ARE TO RECEIVE NEWFINISHES.9. PATCH AREAS OF DAMAGE FOLLOWING REMOVAL OF WALL BASE. PREPARE WALL SMOOTH TORECEIVE NEW BASE.10. ALL PERIMETER DIMENSIONS ARE FROM FACE OF FINISHED WALL, UNLESS NOTED OTHERWISE.11. ALL INTERIOR DIMENSIONS ARE TAKEN FROM FACE OF FINISHED SURFACE, UNLESS NOTEDOTHERWISE.12. PRIOR TO FRAMING, CONTRACTOR SHALL VERIFY DIMENSIONS AND VISUALLY INSPECT ALL ITEMSTO BE SALVAGED OR REUSED, INCL DOORS, FRAMES, TRIM, HARDWARE, ETC.13. VERIFY CONDITION OF SUBFLOOR. PREPARE FLOOR LEVEL TO BE NO GREATER THAN 1” VARIATIONIN 10'-0”.14. AT REMODEL AREAS, PATCH EXISTING ABNORMALITIES IN FLOOR AND PREPARE FLOOR FLAT TORECEIVE NEW FINISHES. FLOOR FLATNESS MUST MEET MANUFACTURER'S REQUIREMENTS FOREACH FLOOR FINISH MATERIAL.15. PROVIDE NEW FRT WOOD BLOCKING AS REQUIRED FOR ALL ITEMS ANCHORED TO NEW ANDEXISTING WALLS.16. NEW PAINT ON ALL WALLS WITHIN AREA OF WORK (EXCEPT KITCHEN). 1 COAT PRIMER, 2 COATS OFFINISH COLOR. REFER TO FINISH PLANS.CONSTRUCTION GENERAL NOTESALTERNATE A - DECORATIVE PAINTINGA1: CEILING MURALSREFER TO CEILING PLANS AND INTERIOR ELEVATIONS.A) GC SCOPE - ADD ALTERNATE: AT (12) LOWER COFFERPANELS PROVIDE SCAFFOLDING FOR MURAL INSTALLATION BYDECORATIVE ARTS VENDOR. BASE BID SHALL INCLUDE PRIME AND BASECOAT OF PAINT ON ALL SURFACES.B) OWNER VENDOR SCOPE - PAINTED MURALS ON (12) LOWERCOFFER AREAS OF NAVE CEILING, AS NOTED ON DRAWINGS. MURALS TOBE EXECUTED IN STUDIO, INSTALLED AS CANVAS APPLIED TO GYP BDSURFACES ON SITE.A2: BEAMS AND CEILING DECORATIVE PAINT.PREFER TO CEILING PLANS AND INTERIOR ELEVATIONSA) GC SCOPE - ADDALTERNATE: PROVIDE SCAFFOLDING FORDECORATIVE PAINT WORK BY DECORATIVE ARTS VENDOR. BASE BIDSHALL INCLUDE PRIME AND BASE COAT OF PAINT ON ALL SURFACES.B) OWNER VENDOR SCOPE - FAUX WOOD FINISH ON CEILING BEAMS,STENCILING ON CEILING COFFER BORDERS AND CENTER MEDALLIONS,STENCIL ELEMENTS ON NAVE SIDE WALLS, AND PAINTING ON CURVEDFRIEZE BAND AT WALL CEILING TRANSITION.A3: OTHER DECORATIVE CEILINGS.REFER TO CEILING PLANS.A) GC SCOPE- ADD ALTERNATE: PROVIDE SCAFFOLDING IN AREASNOTED BELOW. PROVIDE SURFACE PREP (LEVEL 5 FINISH) TO RECEIVEDECORATIVE PAINT AT CEILING AREAS NOTED BELOW. ALL CEILINGTRIMWORK SHOWN ON DRAWINGS IS PART OF BASE BID: CROWNMOULDING, ETC.B) OWNER VENDOR SCOPE - PAINTED STENCIL/MURAL ON CEILINGSIN SACRISTY 208, NARTHEX 204, ENTRY 100, AND STAIR 201 & 203.ALTERNATE B - BELLSA) GC SCOPE - ADD ALTERNATE: REMOVE ONE BELFRY VENT, ANDHOIST AND SET BELLS AND FRAMES IN PLACE IN BELFRY AS SHOWN ONDRAWINGS. ALLOW FOR MISC. BLOCKING/FRAMING. PRIMARYSTRUCTURAL FRAMING WILL BE SAME WITH OR WITHOUT NEW BELLS.REINSTALL VENT AFTER INSTALLATION IS COMPLETE. PROVIDEELECTRICAL CONDUIT AND BOXES FOR NEW ELECTRONIC RINGERSYSTEM WITH CONTROLS IN (2) LOCATIONS: CHOIR LOFT AND SACRISTY.ROUTE POWER AND LOW VOLTAGE CABLE TO EACH BELL (SYSTEMPROVIDED BY OWNER).B) OWNER VENDOR SCOPE - PROVIDE TWO REFURBISHED BELLS WITHNEW WOOD AND STEEL FRAMES. PROVIDE ELECTRONIC BELL RINGERSYSTEM FOR THREE BELLS.ALTERNATE C - OFFICE AREA MILLWORKA) GC SCOPE - ADD ALTERNATE: PROVIDE AND INSTALL BOOKCASESIN PRIVATE OFFICES, AND DISPLAY CASES IN ENTRY AREA, PERLOCATIONS AND DESIGNS SHOWN ON DRAWINGS. INCLUDE COSTS FORSHOP DRAWINGS SUBMITTAL AND APPROVAL. COSTS FOR DISPLAY CASELIGHTING TO REMAIN AS PART OF BASE BID SCOPE.B) OWNER SCOPE - NONEALTERNATE D - OPERABLE PARTITIONSA) GC SCOPE - ADD ALTERNATE: PROVIDE AND INSTALL SPECIFIEDPARTITIONS, TRACK AND HARDWARE IN MEETING ROOMS 101-107 ASSHOWN ON DRAWINGS AND SPECIFICATIONS.B) OWNER'S SCOPE - NONEALTERNATE E - CARPET AT STAIRSA) GC SCOPE - ADD ALTERNATE: PROVIDE CUSTOM SPECIFIED ~ 48"WIDE CARPET RUNNER WITH 48" BRASS CARPET RODS ON STAIRS ANDLANDINGS. INSTALL NEW 3/4" OAK WOOD ON ALL TREADS FROM MAINLEVEL TO CHURCH LEVEL AND OAK VENEER PLYWOOD RISERS. STAINEXPOSED TREADS TO MATCH ADJACENT WOODWORK B) OWNER'S SCOPE - NONE.ALTERNATE F - EXISTING CHURCH DOORSA) GC SCOPE - ADD ALTERNATE: REUSE EXISTING DOORS REFURBISHAND REFINISH AND PROVIDE NEW HARDWARE. INSTALL HEADER ABOVEDOOR ACROSS ENTIRE NARTHEX ELEVATION. PROVIDE TRANSOMWINDOW ABOVE DOORS AND ADJACENT WINDOWS.B) OWNER'S SCOPE - NONEALTERNATE G - FINISHESA) GC SCOPE - PROVIDE SEPARATE PRICING FOR ALTERNATEFINISHES CPT-1A FOR CPT-1, CPT-2A FOR CPT-2, & CPT-6A FOR CPT-6 ASLISTED IN FINISH SCHEDULE. PROVIDE DEDUCT ALTERNATE FOR"STANDARD RED" TILE COLOR WHERE NOTED FOR TILES T-13 THRU T-28.B) OWNER'S SCOPE - NONE1CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:03 PMA2.5PROPOSEDCONSTRUCTIONPLANSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"1PROPOSED MAIN LEVEL CONSTRUCTION PLANCONSTRUCTION KEYNOTES201 NEW SOLID STAINED WD DISPLAY CASE WITH WOOD SHELVES, ACCENT LIGHTING, RE: ELEC. REFER TOALTERNATE C.202 3CM GRANITE TRANSACTION TOP W. WOOD TRIM SURROUND AT OPENING. RE: ELEVS.203 3CM GRANITE COUNTER WITH 4" BACKSPLASH. STAINED WD BASE CABINETS W. RAISED PANEL DOORS.213 3CM GRANITE COUNTER TOP W. CUSTOM WOOD BASE CABIENTS AND UPPER CABINETS.217 DUAL-HEIGHT ADA DRINKING FOUNTAIN218 EXTEND (E) LANDING WITH 2X WD FRAMING AND PLYWOOD SUBSTRATE TO ALIGN WITH EDGE OF DOOR TRIM.MATCH EXISTING HEIGHT.219 P.LAM UPPER CABINETS, RE: ELEV.220 NEW OPERABLE PARTITION AND TOP TRACK, TYP OF (6). BASIS OF DESIGN: HUFCOR-642. UTILIZE (E) STRUCT.SUPPORTS ABOVE CEILING. REFER TO ALTERNATE D.221 (E) ROLL DOWN GRILLE AT KITCHEN TO REMAIN.222 INFILL STUD WALL. MATCH ADJACENT CONSTRUCTION AND WALL TEXTURE.232 NEW DRYWALL PILASTER.233 NEW GRANITE COFFEE COUNTER.234 RECONSTRUCT UPPER FLIGHT OF STAIR, RE: STRUC. REFER TO ALTERNATE E FOR FINISHES.237 STRIP, SAND & REFINISH (E) WDW FRAMES AND WDW SASHES, INSIDE AND OUT AND DOOR CASING/TRIM.REPLACE NON-HISTORIC HDWARE W. ACCURATE HDWARE, TYP.238 NEW STORM WDWS ON EXTERIOR OF ALL WINDOWS, BOTH LEVELS.241 NEW CONCRETE STEPS AND SIDEWALK. RE: SITEPLAN244 LAVATORY COUNTER (ST-2)246 (4) 18" DEEP WOOD SHELVES (PAINT GRADE)AT 16" O.C. VERTICALLY.255 WALL MOUNTED WOOD HANDRAIL.260 BUILT-IN BOOKCASE AND BASE CABINET. REFER TO ALTERNATE C.ISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/17113City of Aspen Received 5/2/17Building DepartmentDraw and dimensionclear spaces for thesink and fridge at thecoffeecounter/kitchenette.Sink clear space mustbe centered forparallel approach. Thecolumn appears tooverlap.Print the UL U309installation instructionson the plan set.
UPC123456789A8.224312A4.21A4.11A4.2STAIR201STOR202STAIR203NARTHEX204VEST205NAVE206SANCTUARY207(E) ROOF BELOW205EABDCONFESSIONALA8.313A8.39141516111012BCCAA204B204AA9.13A3.61A3.71A3.51EL.= 114'-0 1/2"EL.= 115'-2 1/2"EL.= 114'-0 1/2"CONFESSIONALEL.= 114'-0 1/2"202A2132152132142132152122502122082092092092042052062112112572082102103'-8" 1'-9"2'-7"4'-6"7 1/4"ALIGN208209239239236236238237237238234234240EL.= 112'-10 1/2"3'-9 1/4"25'-5 7/8"25'-5 7/8"4'-5"8'-4"8'-4"4'-5"EL.= 113'-4 1/2"EL.= 113'-4 1/2"2042'-4"1'-8"2'-4"4'-4"204204EL.= 112'-10 1/2"202B212ALIGNALIGN5A8.4257EQ.EXIST3'-0 3/4"5'-10"1'-2"3'-3"1'-2"2'-5 1/2"3'-4"4'-8"REFV.I.F.50'-11 3/4"A9.21A9.11021224921221211A7.102452452'-6"2'-6"2482484'-0"AAA237237237237237237251252252AAAA2.73254254254AVAVAV2582583A4.2ALTARSERVERVESTING209VESTING /SACRISTY208MATCH EXISTINGA7.10152592592366'-11 1/2"6'-11 1/2"212212T.O. (E) GYPCRETE1MATCH (E) GYPCRETE111333333331. MILLWORKER TO PROVIDE SHOP DRAWINGS AND CONTROL SAMPLES SHOWING COMPLETE FINISH APPEARANCE FOR ALLSTANDARD AND CUSTOM FINISHES, AND OBTAIN APPROVAL PRIOR TO COMMENCING FABRICATION. FIELD VERIFY ALLCONDITIONS, AND DIMENSIONS, AFTER WALLS HAVE BEEN ERECTED.2. INTERIOR SURFACES OF PLAM CABINET TO BE WHITE MELAMINE; AT WOOD CABINETS BLACK MELAMINE. BACKER SHEET ISREQUIRED AT ALL CONCEALED SURFACES, UNO.3. PROVIDE AND COORDINATE SETTING OF BLOCKING AS REQUIRED FOR MOUNTING CLEATS, SHELF STANDARDS AND ALLWALL MOUNTED MILLWORK.4. REQUEST CLARIFICATION FROM ARCHITECT FOR BLOCKING LOCATIONS AT OWNER'S ARTWORK PER ELEVATIONS.5. PROVIDE CONCEALED CABINET HINGES AND CATCHES TO ACCOMMODATE EACH CABINET DOOR SIZE.6. ALL MDF SHALL BE 3/4" HIGH DENSITY, UNLESS NOTED OTHERWISE.7. ALL STANDARDS, BRACKETS AND ACCESSORIES TO BE KNAPE AND VOGT, HEAVY DUTY DOUBLE SLOT, WHITE FINISH.LOCATE STANDARDS AT STUDS WHERE POSSIBLE, OTHERWISE PROVIDE BLOCKING IN WALL.8. ALL CASEWORK DOORS AND DRAWERS TO HAVE 4" WIRE PULLS WITH DARK BRONZE FINISH, UNO.9. CASEWORK DESIGN TO BE FLUSH OVERLAY UNO.10. ALL DRAWERS SHALL BE ON FULL EXTENSION SLIDES, RATED FOR 100 LBS OR MORE.11. ALL SHELVES TO BE 3/4" HIGH DENSITY MDF WITH WHITE MELAMINE FINISH AND WHITE VINYL "T" EDGE ON K&V (#333 ZC)SUPPORTS UNLESS NOTED OTHERWISE ON PLAN.12. TYPICAL DRAWER CONSTRUCTION IS AS FOLLOWS: FACE- PLASTIC LAMINATE ON 3/4" MDF. SIDES, AND BACKS, ANDBOTTOMS- MELAMINE ON 1/2" MDF.13. THE QUIALITY STANDARDS OF THE ARCHITECTURAL WOODWORK INSTITUTE SHALL APPLY AND BY REFERENCE ARE HEREBYMADE A PART OF THIS SPECIFICATION. ALL PLASTIC LAMINATE WORK SHALL BE AWI CUSTOM GRADE AS DEFINED IN THELATEST EDITION OF THE AWI STANDARDS. ALL WOOD OR VENEER WORK SHALL BE AWI PREMIUM GRADE AS DEFINED INTHE LASTEST EDITION OF THE AWI STANDARDS.14. MILLWORKER SHALL BE RESPONSIBLE FOR COORDINATING OPENINGS FOR ANY APPLIANCES WITH THE APPLIANCESUPPLIER.15. ALL EDGES OF RUNNING TRIM TO BE EASED TO 1/16" RADIUS.16. REFER TO MILLWORK DETAILS ON SHEET A802.CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:07 PMA2.6PROPOSEDCONSTRUCTIONPLANSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"1SANCTUARY LEVEL CONSTRUCTION PLANCONSTRUCTION KEYNOTES204 FRAME CHASE FOR HVAC DUCTWORK. PROVIDE CAST BRASS DECORATIVE RETURN GRILLE. RE: INT. ELEVS, AND MECH.205 CUSTOM MILLWORK CONFESSIONAL. RE: INTERIOR ELEVATIONS AND DETAILS.206 INFILL FLOOR CONSTRUCTION, RE: STRUC.208 NEW WD FRAMED STEPS, RE: DETAIL. REFER TO HVAC PLANS FOR SUPPLY DUCTWORK BELOW SANCTUARY FLOOR.209 REMOVE, REPAIR, REINSTALL HISTORIC WD BEADBOARD WAINSCOT. CAP RAIL TO REMAIN. COORD. PEW ATTACHMENTTO WALLS.210 STAINED WD WINDOW FRAMES WITH DECORATIVE LEADED GLASS AND DECORATIVE STAINED WOOD TRIM.211 STAINED WD WALL CAP. MATCH EXISTING PROFILE IF UNABLE TO SALVAGE FROM EXISTING.212 LITURGICAL ELEMENTS BY OWNER.213 3CM GRANITE COUNTER TOP W. CUSTOM WOOD BASE CABIENTS AND UPPER CABINETS.214 8'-8" HIGH PREMIUM-GRADE WOOD CABINETS. RE: INTERIOR ELEVS.215 SINK, RE: PLUMB234 RECONSTRUCT UPPER FLIGHT OF STAIR, RE: STRUC. REFER TO ALTERNATE E FOR FINISHES.236 SANCTUARY PLATFORM: TILE FLOORING ON CEMENT BOARD, OVER T&G PLYWD SUBFLOOR, ON 2X JOISTS @ 12" OC. RE:STRUC DWGS. ** PROVIDE SEPARATE LINE ITEM PRICING FOR UNCOUPLING MATTE BELOW ALL FLOOR TILE LOCATIONS.**237 STRIP, SAND & REFINISH (E) WDW FRAMES AND WDW SASHES, INSIDE AND OUT AND DOOR CASING/TRIM. REPLACENON-HISTORIC HDWARE W. ACCURATE HDWARE, TYP.238 NEW STORM WDWS ON EXTERIOR OF ALL WINDOWS, BOTH LEVELS.239 REMOVE SACRISTY DOORS AND FRAMES. MODIFY R.O. TALLER TO ACCOMODATE HIGHER FLOOR LEVEL.240 PROVIDE AND INSTALL NEW 3/8" INTERIOR GLASS PANE FOR ENERGY EFFICIENCY AT ROUND WDW. STAINED WDREMOVEABLE STOP.245 INFILL EXISTING WINDOW ARCH AT STAIR LANDING WITH WOOD BEAD BOARD. MATCH EXISTING WAINSCOT MATERIAL.248 NEW PLYWOOD SUBFLOOR IN THIS AREA TO MATCH EXISTING DEPTH. ADD LEVELING COMPOUND AS REQUIRED TOACHIEVE LEVEL TRANSITION WITH NEW FINISHES IN AISLES. COORDINATE WITH DEMOLITION PLANS AND MECHANICALDRAWINGS FOR SCOPE IN THIS AREA.249 MODIFY EXISTING REREDOS AND HIGH ALTAR. RE: DETAILS. REPAINTING BY OWNER'S VENDOR.250 NEW ALTAR, RE: DETAILS. PAINTING BY OWNER'S VENDOR.251 EXISTING ENTRY CANOPY TO REMAIN.252 STAINED WOOD CASED OPENING254 PROVIDE APPROX 3/8" LEVELING COMPOUND UNDER PEW AREA TO ACHIEVE LEVEL TRANSITION WITH NEW TILE FINISHESIN AISLES. COORDINATE WITH FINISH PLANS.257 EXISTING SIDE ALTAR TO BE REMOVED AND PROTECTED DURING CONSTRUCTION BY GC. REFURBISHING SCOPE BY GCINCLUDES REMOVAL OF EXISTING TOP AND REPLACE WITH 1-1/4" PAINT GRADE WOOD. REPAINT ENTIRE BASE & SHELVESBY OWNER'S VENDOR. COLOR SCHEME IS TBD.258 REPAINT WINDOW TRIM (2 TOTAL) BY OWNER'S VENDOR.259 PROVIDE NEW SAND TEXTURE FINISH TO MATCH EXISTING ADJACENT WALLS.ISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/17GENERAL CONSTRUCTION NOTESSEE SHEET A2.5MILLWORK GENERAL NOTES113City of Aspen Received 5/2/17Building DepartmentNote on the plans thata portable ramp will beprovided toaccommodate anaccessible route to thesanctuary.3,919 sf
DNC891A4.11A4.2ORGANCHAMBER301OPEN TONAVE BELOWOPEN TOBELOWORGANEABDOPEN TOBELOWBALCONY303301225224223243CHOIRLOFT302STAIR3043A7.1126'-0"13'-0"13'-0"3'-4"4'-2 1/2"4'-2 1/2"1'-3"1'-3"4'-2 1/2"4'-2 1/2"3'-4"3'-4" 4'-2 1/2"1A7.11302OPEN TOBELOWAAAAA7.10925525610"261113'-5 3/4"C891A4.11A4.2BD230227227229228247253ALTERNATE BC78BDA8.44321NARTHEX204BCCAA204B204A2042062102103'-8" 1'-9"2'-7"4'-6"7 1/4"ALIGN4'-5"8'-4"8'-4"4'-5"204EL.= 112'-10 1/2"ALIGNALIGN2'-3"6'-1"6'-1"2'-3"EQ.EQ.EQ.EQ.EQEQ3"1'-0"5 1/2"2'-0"5 1/2"1'-0"3"EQEQA10.18A10.19A7.1111A8.3181CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:08 PMA2.7PROPOSEDCONSTRUCTIONPLANSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"1PROPOSED CHOIR LOFTCONSTRUCTION PLAN 3/16" = 1'-0"2PROPOSED BELFRY LEVELCONSTRUCTION PLANCONSTRUCTION KEYNOTES204 FRAME CHASE FOR HVAC DUCTWORK. PROVIDE CAST BRASS DECORATIVE RETURN GRILLE. RE: INT.ELEVS, AND MECH.206 INFILL FLOOR CONSTRUCTION, RE: STRUC.207 NEW CARVED WOOD ALTAR RAIL. RE: DETAIL.208 NEW WD FRAMED STEPS, RE: DETAIL. REFER TO HVAC PLANS FOR SUPPLY DUCTWORK BELOWSANCTUARY FLOOR.209 REMOVE, REPAIR, REINSTALL HISTORIC WD BEADBOARD WAINSCOT. CAP RAIL TO REMAIN. COORD.PEW ATTACHMENT TO WALLS.210 STAINED WD WINDOW FRAMES WITH DECORATIVE LEADED GLASS AND DECORATIVE STAINED WOODTRIM.211 STAINED WD WALL CAP. MATCH EXISTING PROFILE IF UNABLE TO SALVAGE FROM EXISTING.212 LITURGICAL ELEMENTS BY OWNER.213 3CM GRANITE COUNTER TOP W. CUSTOM WOOD BASE CABIENTS AND UPPER CABINETS.214 8'-8" HIGH PREMIUM-GRADE WOOD CABINETS. RE: INTERIOR ELEVS.215 SINK, RE: PLUMB223 STAINED WOOD RAILING. MATCH HISTORIC RAILING AT CHOIR LOFT.224 NEW STEEL LADDER TO BELFRY LEVEL ABOVE, PAINT.225 REUSE HISTORIC WOOD RAILING SALVAGED FROM EXISTING CHOIR LOFT.227 (2) REFURBISHED BELLS PURCHASED BY OWNER. GC TO COORD REQM'TS FOR HOISTING ANDPLACEMENT. REFER TO ALTERNATE B.228 CEILING ACCESS HATCH.229 3' X 3' ACCESS TO ATTIC.230 (E) BELL TO BE CLEANED AND REFURBISHED BY OWNER'S VENDOR. INCLUDE ELEC SCOPE FORNEW MECHANICAL RINGING SYSTEM.236 SANCTUARY PLATFORM: TILE FLOORING ON CEMENT BOARD, OVER T&G PLYWD SUBFLOOR, ON 2XJOISTS @ 12" OC. RE: STRUC DWGS. ** PROVIDE SEPARATE LINE ITEM PRICING FOR UNCOUPLINGMATTE BELOW ALL FLOOR TILE LOCATIONS. **237 STRIP, SAND & REFINISH (E) WDW FRAMES AND WDW SASHES, INSIDE AND OUT AND DOORCASING/TRIM. REPLACE NON-HISTORIC HDWARE W. ACCURATE HDWARE, TYP.238 NEW STORM WDWS ON EXTERIOR OF ALL WINDOWS, BOTH LEVELS.239 REMOVE SACRISTY DOORS AND FRAMES. MODIFY R.O. TALLER TO ACCOMODATE HIGHER FLOORLEVEL.240 PROVIDE AND INSTALL NEW 3/8" INTERIOR GLASS PANE FOR ENERGY EFFICIENCY AT ROUND WDW.STAINED WD REMOVEABLE STOP.243 ORGAN TO BE REASSEMBLED BY OWNER'S VENDOR.245 INFILL EXISTING WINDOW ARCH AT STAIR LANDING WITH WOOD BEAD BOARD. MATCH EXISTINGWAINSCOT MATERIAL.247 MECHANICAL DUCTWORK, RE: MECH253 INFILL EXISTING ATTIC ACCESS.255 WALL MOUNTED WOOD HANDRAIL.256 HANDRAIL WITH WOOD BALLUSTERS.261 ADD 1 LAYER 1/2" PLYWD AND 1 LAYER 5/8" GYP. BD. ON ALL 3 SIDES AND CEILING OF ORGANCHAMBER. 3/8" = 1'-0"3ENLARGED NARTHEXCONSTRUCTION PLANISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/1711City of Aspen Received 5/2/17Building DepartmentProvide an updateddoor scheduleshowing the new widthof door 302 (min 32"clear required).
MAIN LEVEL100'-0"SANCTUARY LEVEL112'-10 1/2"1234567892A4.21A4.2HALLWAY111NAVE206SANCTUARY207NARTHEX204STOR202ENTRY100CHOIR LOFT LEVEL122'-4 1/2"ORGANCHAMBER301A7.102CRAWLSPACECRAWLSPACEEXIST. BELFRY LEVEL136'-3 1/2"EXISTING TRUSS PACKS IN ATTICNEW WD TRIM AT COFFERED CEILING, RE: DETAILSRECESSED SLOT FOR CONCEALED LIGHT FIXTURENEW CEILINGRECONSTRUCT CURVED SANCTUARY ARCH, RE: 1/A4.2 FOR DETAILSDEMO AND RECONSTRUCT CURVED CEILING, 3 SIDESPROVIDE LEVEL 5 FINISH, PRIMED, W/ BASE COATHIGH ALTAR TO BE DISASSEMBLED, PROTECTED, AND RE-INSTALLED.RE: 1/A9.2NEW PLATFORM FRAMING,RE: STRUCINFILL WALL WHERE DOOR WAS REMOVED.MATCH ADJACENT SURFACESEXTEND LANDING, RE: PLANEXISTING BELL TO BEREFURBISHED BY OWNERALTERNATE B(2) NEW BELLS BY OWNER. GC TOCOORDINATE REQUIREMENTSFOR HOISTING AND PLACEMENTNEW CHOIR LOFT ,RE: STRUC & FLOOR PLANSINFILL FRAMING ABOVE ENTRYRE: STRUCT.EXISTING PORCH ROOFTO REMAINPROVIDE BATT INSULATION OVER SPRAY APPLIEDINSULATION (R-60 TOTAL) THROUGHOUT ENTIRE ATTICSPACE ABOVE CEILING AIR BARRIER. INCLUDING NAVE,SANCTUARY, AND SACRISTIESBATT INSULATION OVER SPRAY APPLIEDINSULATION FOR R-60 TOTAL.11'-10"A7.106A7.1013MECH GRILLE,RE: MECHMECH DUCTWORK,RE: MECHA7.119A7.105MECH DUCTWORK, RE: MECHSLOPED DRYWALLA7.1010OPEN TOBEYONDLINE OF EXISTING CURVED CEILINGCRITICAL DIM5'-1 3/4"4'-0"NEW CURVED CEILING HEIGHT AT THIS POINTIS CRITICAL TO ACCOMODATE LITURGICAL ELEMENTR 8'-6"SIMA7.1014A7.1011O.H.O.H.3A4.2NEW GYP BD CEILINGELEMENTS, RE: CEILINGPLANS19'-2 1/2"A7.101611WALL MOUNTED WOODHANDRAIL, STAIN111'-9 7/8"33CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:12 PMA4.1BUILDINGSECTIONSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"1BUILDING SECTION - FACING EASTISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/1713City of Aspen Received 5/2/17Building Department
MAIN LEVEL100'-0"SANCTUARY LEVEL112'-10 1/2"C1A4.1CHOIR LOFT LEVEL122'-4 1/2"EABDNAVE206MEETINGRM104HALLWAY111MEN116OFFICE113CRAWLSPACECRAWLSPACEA7.103A7.101A7.104REFRAME SANCTUARY ARCHW/ NEW PROFILE AS SHOWNSTATUE SURROUNDS BY OWNER VENDORMAINTAIN HISTORIC WOOD TRIM AT DOORSAND WINDOWSPROVIDE BATT INSULATIONOVER SPRAY APPLIEDINSULATION (R-60 TOTAL)THROUGHOUT ENTIRE ATTICSPACE, RE: SPECS.MECH DUCTWORK SHOWN DASHED,RE: MECH11'-6"9'-6 3/4"1'-6"12'-1 7/8"9"MAIN LEVEL100'-0"SANCTUARY LEVEL112'-10 1/2"C1A4.1CHOIR LOFT LEVEL122'-4 1/2"EABDENTRY100STAIR203STAIR201CRAWLSPACESTOR202BALCONY303STOR121MODIFY EXISTING CEILINGTO ACCOMODATE NEWDOOR TO CHOIR LOFTNEW 42" WOOD GUARDRAILAND OPEN BALUSTERSSIM TO CHOIR LOFT RAILINGNEW INFILL FRAMING ATBELFRY LEVEL, RE: STRUCNEW CEILINGNEW GYP. BD. SHAFTENCLOSURE FOR HVACDUCTWORKINSTALL (2) HISTORIC FXITURESFROM CHURCHNEW STAIR AND HANDRAILNEW FLOOR STRUC, RE: STRUCNEW FIN. ON EXISTING STAIRFINISH AND PROTECT UNDERSIDEOF STAIR AS STORAGE SPACE,(2) LA OF GYP. BD.A7.108A7.112A7.113(E) WD WAINSCOT TO REMAINNEW WALL MNT'D STAINEDWD HANDRAILATTIC ACCESS DOOR,PAINTED PLYWD W/ LOCKABLECLASP(2) LA. 5/8" TYPE X GYP.BD AT UNDERSIDE OFSTAIRS(2) LA. 5/8" TYPE X GYP.BD AT UNDERSIDE OFSTAIRSPROVIDE BATT INSULATIONOVER SPRAY APPLIEDINSULATION (R-60 TOTAL)THROUGHOUT ENTIRE ATTICSPACE, RE: SPECS.16 R @ 6.7" EA.9'-0"15 TR @ 11" EA.13'-10"CEABDSANCTUARY20719'-6"R 13'-0 1/2"FLAT3'-9"1'-10 1/2"WD TRIM AT SANCTUARY ARCH BEYONDOUTLINE OF ALTAR & REREDOSCURVED FRAMED CEIILNG WITHBATT INSULATION OVER SPRAYAPPLIED INSULATION (R-60 TOTAL)THROUGHOUT ENTIRE ATTIC SPACE,RE: SPECS.NEW RAISED PLATFORMPER STRUC DWGSATTICATTICALTARSERVERVESTING209VESTING /SACRISTY2081CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:15 PMA4.2BUILDINGSECTIONSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 3/16" = 1'-0"2BUILDING SECTION - FACING SOUTH 3/16" = 1'-0"1BUILDING SECTION - FACING SOUTHISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/17 3/16" = 1'-0"3BUILDING SECTION - LOOKING NORTH13City of Aspen Received 5/2/17Building DepartmentAll handrail extensionsmust return.
TA-1 SEMI RECESSED TOILET TISSUE DISPENSOR BOBRICK B-3888TA-2 42" GRAB BAR BOBRICK B-5806 X 42TA-3 RECESSED SANITARY NAPKIN DISPOSAL BOBRICK B-353TA-4 PARTITION MNTD DUAL SANITARY NAPKIN DISPOSAL BOBRICK B-354TA-5 PARTITION MNTD DUAL TOILET TISSUE DISPENSOR BOBRICK B-386TA-6 36" GRAB BAR BOBRICK B-5806 X 36TA-7 MIRROR, POLISHED EDGES, FRAMELESS BOBRICK B-290TA-8 SEMI RECESSED PAPER TOWEL DISPENSOR BOBRICK B-359TA-9 RECESSED BABY CHANGING STATION BOBRICK KB110TA-10 18" GRAB BAR BOBRICK B-5806 X 18TA-11 VENEER PLYWOOD PARTITIONTOILET ACCESSORIES SCHEDULEMEN116WOMEN110A6.18976A6.152341'-7" EQ EQ5'-0" CLR.6'-10 3/8"5'-0" CLR 3'-1" 3'-1"7'-1 3/4" 5'-0" CLR.11'-3"2'-1 1/2" 3'-6" 3'-6" 2'-1 1/2"1'-3" 2'-6" 1'-3"TA-7TA-6TA-2TA-5TA-4TA-10TA-1TA-3TA-9TA-8TA-8TA-10TA-1TA-2TA-6TA-8TA-7TA-9TA-11TA-11TA-9PARTITION PER PLAN, RE: ELEVATIONSFOR MIRRORSMOUNT OUTLETS 4" ABOVE COUNTERTOPTO BOT OF COVER PLATE. RE: ELEC.BACKSPLASH TRIM AT SIDES AND BACK.PROVIDE SEALANT WHERE MEETS TILE.SINK, RE: SPECS.COUNTERTOP, RE: FINISH SCHEDREMOVEABLE WD APRONPER ADA CLEARANCESPROVIDE PLYWD BACKING IN WALL FORANCHORAGE OF WALL MOUNTED ITEMS.NOTE BACKERBOARD AND TILE WALLFINISH, PER ELEVATIONS2'-10" TO RIM OF SINK4"2"2"10 1/2"2"1 3/4"1'-6"9"3'-10"A6.110RE: TILE ELEVATIONFOR PATTERN & HEIGHT4'-3"PARTITION ASSCHEDULED2'-10"1'-7"RE: TILE ELEVATIONFOR PATTERN & HEIGHT2'-10"1'-7"2'-4"3'-10"10A6.1WALL SCONCE, RE: ELERE: TILE ELEVATIONFOR PATTERN & HEIGHTREMOVEABLEARPON WD PANEL2'-10"TILE T-93'-4"3'-10"10A6.1RE: TILE ELEVATIONFOR PATTERN & HEIGHTPARTITION AS SCHEDULEDREMOVEABLEAPRON WD PANEL2'-10"1'-3"1'-3" 2'-6"TILE T-93'-4"RE: TILE ELEVATIONFOR PATTERN & HEIGHT2'-10"1'-7"MAX1'-5"3'-3"A6.110RE: TILE ELEVATIONFOR PATTERN & HEIGHT2'-10"RE: TILE ELEVATIONFOR PATTERN &HEIGHT2'-10"T-8T-6T-5T-36'-0 3/8"T-2T-4T-7CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:17 PMA6.1ENLARGEDFLOOR PLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 1/4" = 1'-0"1ENLARGED RESTROOM PLAN 1" = 1'-0"10SECTION AT LAVATORY 1/4" = 1'-0"2WEST ELEVATIONWOMEN 110 1/4" = 1'-0"3NORTH ELEVATIONWOMEN 110 1/4" = 1'-0"4EAST ELEVATIONWOMEN 110 1/4" = 1'-0"5SOUTH ELEVATIONWOMEN 110 1/4" = 1'-0"7WEST ELEVATIONMEN 116 1/4" = 1'-0"8WEST ELEVATIONMEN 116 1/4" = 1'-0"9NORTH ELEVATIONMEN 116 1/4" = 1'-0"6SOUTH ELEVATIONMEN 116ISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17PERMIT RESUB 4/17/1711ENLARGED TILE ELEVATION3333City of Aspen Received 5/2/17Building DepartmentProvide horizontal andvertical grab bars onside wall of accessibletoilet stall in women'srestroom.Provide depthdimensions for kneeand toe clearanceunder lavatory.
DIFFUSER BOX, RE: MECH.CONT. SLOT FOR AIRFLOW,RE: HVACRIGID FOAM EXTRUSIONBATT INSULATION OVERSPRAY APPLIED INSUL,(R-60 TOTAL) RE: SPECSACOUSTIC PANEL,RE: SPECSRECESSED LIGHTFIXTURE, RE: ELEC9"1'-6"9"2 1/2"2 1/2"2"IGNITIONBARRIER(E) STL. ANGLE TRUSS,RE: STRUC(E) WD TRUSS PACK,RE: STRUCRIGID FOAM EXTRUSION,RE: SPECSRECESSED LIGHTFIXTURE, RE: ELEC2 1/2"2 1/2"2"EXISTING CEILINGSUBSTRATEACOUSTIC PANEL,RE: SPECS9" 9" 9" 9"BATT INSUL OVER SPRAYAPPLIED INSUL, (R-60TOTAL), RE: SPECSIGNITION BARRIERDIFFUSER, RE: MECHRIGID FOAM EXTRUSION,RE: SPECSCURVED WALL/CEILINGTRANSITIONSTRIP LIGHT FIXTURE,RE: ELECEXISTING EXTERIOR WALLRIGID FOAM EXTRUSION,RE: SPECSELEVATION9"1'-6"4"R 2'-4"2 1/2"2 1/2"2"EXISTING CEILING SURFACEBATT INSULATION OVERSPRAY APPLIED INSUL,(R-60 TOTAL) RE: SPECSIGNITIONBARRIERCURVED BEAM SUPPORTBEYONDAPPROX LINE OFORGAN PIPESACOUSTIC PANEL,RE: SPECS3 /4 "2 1 /2 "2 "9"9"9"9"EXISTING CEILINGSUBSTRATERIGID FOAM EXTRUSION,RE SPECSBATT INSULATION OVERSPRAY APPLIED INSUL,(R-60 TOTAL) RE: SPECSIGNITIONBARRIER7 1/4"ORGAN CHAMBERCEILING - (2) LA 5/8" GYP.BD. W/ 1/2" PLYWDBETWEENCASED OPENINGBATT INSULATION OVERSPRAY APPLIEDINSULATION, (R-60 TOTAL)RE: SPECSRIGID FOAM EXTRUSION,RE: SPECSPLANE OF (E)CEILINGIGNITIONBARRIERLIGHT FIXTURE,RE: ELEC - MOUNTAS CLOSE TO BEAMAS POSSIBLE(E) WD TRUSS PACK,RE: STRUCRIGID FOAM EXTRUSION,RE: SPECACOUSTICAL PANEL,RE: SPECRECESSED LIGHT FIXTURE,RE: ELEC9" 9" 9" 9"7"BATT INSULATION OVERSPRAY APPLIED INSUL,(R-60 TOTAL) RE: SPECSIGNITIONBARRIER9" 9"RIGID FOAM EXTRUSION,RE: SPECSPAINTED COFFER BYOWNER'S VENDOR9" 9"FAUX FINISH BYOWNER'S VENDORDIFFUSER, RE: MECHPT-5 BY GC, TYPPT-4 BY GC, TYPRE: FINISH SCHED.JOIST, RE: STRUCSTL. BEAM, RE: STRUC(E) WD JOIST, RE: STRUCGYP. BD. CEILING,RE: PLANRE: CLG PLANRE: CLG PLAN1'-1" 1'-1"5 1/2"STL CHANNEL, RE: STRUC9 1/4"4"1"10 3/4" +/- MATCH EXISTINGMATCH (E) WD CAPMATCH (E) WOOD RAILINGAND BALUSTERSCARPET, RE: FINISH SCHEDWD FLOOR,RE: FINISH SCHED5 1/2"10"MATCH (E) TRIMMATCH (E)WD TRIMA10.110SEMI-RECESSEDVIDEO CAMERA.3'-6"PLANRE:PLANRE:PLYWD OVER WOOD FRAMINGRE: STRUCRE: PLANRE: PLANFIELD TILE, RE: FINISH PLANACCENT NOSING,RE: FINISH PLANDUCTWORK & GRILLE, RE: MECHMORTAR BED1/4" CEMENT BOARDCAULK JOINT, TYP.BATT INSULATIONOVER SPRAY APPLIEDINSUL, RE: SPECSRIGID FOAM EXTRUSION,RE: SPECS1x4 WD TRIM, STAINRE: PLANCURVED SANCTUARY CEILINGWITH LEVEL 5 FINISH, PRIMEDWITH BASE COAT9"1'-2" 9" 9" 9"EXISTING CEILINGSURFACE3/8" RADDECORATIVE STENCIL BYOWNER'S VENDORPROVIDE NEW LEVEL 5FINISH, PRIMED WITHBASE COAT1/4" RADMATCH (E) SANDTEXTURE FINISHEXIST WALLRE: INT ELEVRE: INT ELEVACOUSTICAL PANEL,RE: SPECS2 1/2"2 1/2"2"IGNITION BARRIERNEW WALL, RE: PLANSCASED WD TRIMOPENING, STAIN1X WD TRIM,STAIN5/8" GYP. BD. ON MTL.STUD FURRING9"3"ADD 1/2" PLYWD &(1) LA. 5/8" GYP.BD.PLANRE:PLANRE:RE: PLANTILE, RE: FINISH PLANWD BASE, STAIN2 x 4 WD POSTS, STAINSOLID WD TOP, STAIN2 x 2 DECORATIVE WD ARCH, STAIN1/2"2 X 6 WD BASE, STAIN1-1/2" X 5" WD CAP, STAIN2 X 6 WD POSTS BEYOND, STAIN5 1/2"3 1/2"1/4"1/4"1/4"1/4"7"7 1/4"2"1 1/2"1/4" RADIUS, TYP.1'-2"3/4"TILE3/8" MORTAR BED1/4" BACKER BOARD(2) LA. 3/4" PLYWD,RE: STRUCCOORD W/ STRUC2'-7"DUCTWORK, RE: MECHWD STUD FRAMING,RE: STRUC1'-0 3/4"3/8" RAD1X4 WD TRIM, STAINDECORATIVE STENCIL BYOWNER'S VENDORPROVIDE NEW LEVEL 5FINISH, PRIMED WITHBASE COAT1/4" RADMATCH (E) SANDTEXTURE FINISHPROVIDE NEW LEVEL 5FINISH, PRIMED WITHBASE COAT1X4 WD TRIM, STAIN1X2 WD TRIM, STAIN1/4" X 1/4" GROOVE1X4 WD TRIM, STAINLINE OF ARCH ABOVERE: PLAN FOR WALL TYPE(E) WALL SHOWNSHADED1'-9 3/4" +/-1'-9 3/4" +/-MATCH EXISTING2'-6 3/4" +/-RE: FINISH SCHEDTRANSITION STRIP, RE: SPECSCARPET, RE: FINISH PLAN3/4" PLYWD, MATCH (E) HEIGHT2X WD FRAMING3/4" PLYWD SUBSTRATE1/4" BACKER BOARDTILE, RE: FINISH PLANCHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:18 PMA7.10INTERIOR DETAILSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 1" = 1'-0"1CEILING DETAIL @LONGITUDINAL BEAMS 1" = 1'-0"2CEILING DETAIL@ EXISTING TRUSS 1" = 1'-0"3CEILING DETAIL @ EXTERIOR WALL 1" = 1'-0"4CEILING DETAIL @ RIDGE 1" = 1'-0"5CEILING DETAILAT ORGAN CHAMBER 1" = 1'-0"6CEILING DETAIL@ EXISTING TRUSS 1" = 1'-0"7SOFFIT DETAIL @ INTERSECTIONLONGITUDINAL BEAMS 1" = 1'-0"8DETAIL AT EXIST FLOOR 1" = 1'-0"13SECTION AT CHOIR LOFT 1" = 1'-0"11SECTION AT SANCTUARY STEPSISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/17 1" = 1'-0"10CEILING DETAIL@ SANCTUARY ARCH 1" = 1'-0"9JAMB DETAILAT ORGAN CHAMBER 1" = 1'-0"12SECTION AT ALTAR RAIL 1" = 1'-0"14RAISED FLOOR DETAIL 1" = 1'-0"15PLAN DETAIL AT ARCH 1 1/2" = 1'-0"16SECTION AT STEP111133City of Aspen Received 5/2/17Building DepartmentThe batt insulation inthe attic must bemineral fiber to complywith the exception tothe thermal barrierrequirements of 2015IBC 2603.4.1.6.Specify the type of battinsulation.Note the requirementto provide sprinklerheads or fill withnon-combustibleinsulation incombustibleconcealed spaces perNFPA 13 section8.15.1.2.3.
C1234567892A4.21A4.11A4.2EABD2A7.104A7.103A7.10STAIR201STAIR203STOR202NAVE206SANCTUARY207ORGANCHAMBER301VEST2055A7.106A7.10308309309310310311311312313318312317319321321321321322322323316329329329329329329329329329329301301319319319319319319319319319329319319319319319329A7.1071A7.10EL.= 16'-9"EL.= 16'-9"EL.= 25'-9 1/2"EL.= 12'-2"EL.= 12'-2"SLOPESLOPE3193197'-1 1/2"30110A7.106A7.10*** GC TO COORDINATEFINISHED CEILING HEIGHT ATTHIS LOCATION TOACCOMODATE HEIGHTOF LITURGICAL ELEMENT. RE:SECTION5'-1 3/4"TYP.1'-6"3313313333333123123123323A4.2PT-4, TYPPT-4, TYPPT-5, TYPPRIMED ONLY, TYPPT-4, TYPPT-7SANCTUARYARCH, PT-8ALTERNATE A3ALTERNATE A3PRIMED ONLY, TYP10A7.111111A10.1633C891A4.11A4.2BDOPEN TOABOVEOPEN TOABOVEOPEN TOABOVEOPEN TOABOVENARTHEX204EL.= 8'-5"312325326326312EL.= 8'-5"1'-6"1'-6"1'-6"1'-6"4A7.1110A10.11A10.16CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/27/2017 10:15:12 AMA7.2REFLECTEDCEILING PLANSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO2PROPOSED REFLECTED CEILING PLANSANCTUARY LEVEL1PROPOSED REF. CEILING PLANAT NARTHEXRCP KEYNOTES301 (E) PLASTER / GYP. BD. CEILING TO REMAIN THIS AREA.308 NEW GYP. BD. COVE CEILING TRANSITION, TYP.309 MILLWORK BEAMS AND COFFER DETAILS310 CUSTOM PENDANT FIXTURE, TYP. OF 10. G.C. ALLOWANCE OF $3500 TO ELEC CONTRACTOR. GCTO INCLUDE COSTS FOR FULL MOCK-UP FIXTURE FOR OWNER AND ARCHITECT REVIEW.311 CUSTOM SEMI-PENDANT FLUSH FIXTURE, TYP OF 2. G.C. ALLOWANCE OF $1800 TO ELEC.CONTRACTOR.312 WOOD CROWN MOLDING, PAINT.313 RECONSTRUCT SANCTUARY ARCH, RE: ELEV.316 2" PAINTED WOOD CEILING TRIM.317 RECONSTRUCT CURVED CEILING, 3 SIDES.318 SLOT IN DRYWALL FOR PROJECTOR SCREEN, TYP. OF 2.319 NEW GYP. BD. CEILING. REFER TO ALTERNATE A1321 RECESSED SLOT TO CONCEAL LIGHT FIXTURES, TYP OF 12.322 RELOCATED HISTORIC FIXTURES FROM CHURCH, TYP. OF 2323 EXANDED OPENING IN EXISTING WALL FOR ORGAN CHAMBER.325 1" PAINTED WOOD TRIM.326 CASED WOOD OPENING.329 1/2" NOVAWALL ACOUSTIC SURFACE.331 ACCESS HATCH. COORD SIZE & LOCATION WITH MECH.332 RECESSED EMERGENCY FIXTURE, RE: ELEC.333 MECHANICAL SLOT DIFFUSER, RE: MECH.ISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/1713City of Aspen Received 5/2/17Building Department
NEW CARPET AND BRASS RODHARDWARE ON REFINISHEDWOOD STAIRSOPEN TORECEPTIONALTERNATE C MILLWORK DISPLAYCABINETS W. ADJ. SHELVESALL WOOD SOLID CHERRY BASECABINETS, PREMIUM GRADE W/RAISED PANEL CONST.7A7.116A7.118A7.118A9.18'-6 1/2"WD TRIM, STAIN,MATCH (E)GRANITE COUNTERTOP,RE: FINISH SCHED.ARTWORK NICHENEW CARPET AND BRASS RODHARDWARE ON REFINISHEDWOOD STAIRSSCHEDULED BASE9A9.1WD BASE CABINET WITHGRANITE COUNTERTOPEXISTING ENTRY DOORGYP. BD. SOFFITWOOD TRIMMATCH EXISTADAREF.SOFFIT BEYONDCUSTOM WOOD FRONT FORREFRIGERATORSCHEDULE BASESINK, RE: PLUMB DWGS12'-10"3A9.11OPEN TOBEYOND1A9.12'-9"2'-9"FINISHED END PANELGRANITE COUNTERTOP &BACKSPLASHRAISED PANEL WD DOORSIMROLL DOWN SECURITY GRILLEBASE CABINETROLL DOWN SECURITY GRILLECONCEALED IN CEILINGCOPIER LOCATIONWOOD CASED OPENINGWD BASE, MATCH (E)2'-6"4'-6"1'-0"1'-0"4'-10"OPEN TOBEYOND4'-6"1'-0"2'-6"WD BASE CABINET8'-8" 2'-0"10'-8"2A9.1SEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSMODIFY AS REQUIRED TOACCOMMODATE AV EQUIP,RE: AV DWGSSEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSPAINTED WDTRIMSEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSPAINTED WOODTRIM2'-0"3'-6"2'-4"2'-10"8'-8"2A9.11A9.12'-0"EQ.3'-0" 3'-0" 3'-0"EQ.SEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSMODIFYDEPTH OFCABINETSMODIFY CABINET TOACCOMODATE AVEQUIP, RE: AV DWGS8'-8"4" CROWN MOLDINGALL WOOD SOLID CHERRYCABINETRY, PREMIUM GRADEQUALITY, RAISED PANELCONST. W/ 4" CROWNMOLDING, TYP.GRANITE COUNTERTOPS3'-0" 2'-2" 3'-6" 2'-0"24" DEEP CABINET24" DEEP CABINET12" DEEP CABINET1A9.1SIM2A9.13'-0"EQ.3'-0"EQ.3'-0"SEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSSTAINED WDTRIM2'-0"3'-6"2'-2"3'-0"8'-8"2'-0"2'-0"1'-0"3'-0"1'-0"1A9.12A9.1SEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSREF2'-3 3/16"FALSE PANEL,COORD EQUIPW/ AV DWGSSIMSEE DETAIL 13/A8.2 FORADDITIONAL NOTES & DIMSSTAINED WOODTRIM2'-9"2'-9"3'-0" 4"1CROWN MOLDING, STAINLEADED GLASS IN WDFRAMEGYP. BD, PAINTSCHEDULED BASE1X WD TRIM, STAINVENEER PLYWD, STAINMODIFY & REINSTALL HISTORICWOOD WORK FROM EXISTINGCHOIR PLATFORMCHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:19 PMA8.3INTERIORELEVATIONSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 1/4" = 1'-0"3EAST ELEVATION - ENTRY 101 1/4" = 1'-0"2SOUTH ELEVATION - ENTRY 101 1/4" = 1'-0"4WEST ELEVATION - ENTRY 101 1/4" = 1'-0"1NORTH ELEVATION - ENTRY 101 1/4" = 1'-0"8EAST ELEVATIONRECEPTIONIST 118 1/4" = 1'-0"7SOUTH ELEVATIONRECEPTIONIST 118 1/4" = 1'-0"5WEST ELEVATIONRECEPTIONIST 118 1/4" = 1'-0"6NORTH ELEVATIONRECEPTIONIST 118 1/4" = 1'-0"9ALTAR SERVER'SVESTING 209 1/4" = 1'-0"10ALTAR SERVER'SVESTING 209 1/4" = 1'-0"11ALTAR SERVER'SVESTING 209 1/4" = 1'-0"12ALTAR SERVER'SVESTING 209 1/4" = 1'-0"13VESTING /SACRISTY 208 1/4" = 1'-0"14VESTING / SACRISTY 208 1/4" = 1'-0"15VESTING /SACRISTY 208 1/4" = 1'-0"16VESTING /SACRISTY 208 1/4" = 1'-0"17MEETING RM 107ISSUE: DATE:50% DD SET 09/02/16100% DD SET 10/11/16DD ADDENDUM #1 11/14/1650% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17ADDENDUM #1 3/7/17PERMIT RESUB 4/17/17 1/4" = 1'-0"18WEST ELEVATION ATAT CHOIR LOFT1City of Aspen Received 5/2/17Building DepartmentProvide the height ofthe reception counter.Max 36" foraccessibility.
CLEADED GLASS INFIXED WD FRAMEDOOR AS SCHEDULEDWOOD BASE,RE: SCHED.WD TRIM, STAINWOOD BASE.RE: SCHEDWOOD CASEDOPENINGWALL SCONCE,RE: ELECCROWN MOLDING,RE: FINISH SCHEDOPEN TOBEYONDREFER TO EAST ELEVATIONFOR ADDITIONAL NOTESOPEN TOBEYONDREFER TO EAST ELEVATIONFOR ADDITIONAL NOTESEXISTING STAIR LANDINGNEW STEP, RE: PLAN3'-6"MODIFY EXISTING WALL HEIGHTAND WOOD WALL CAP TO MATCHNEW FLOOR STEP CONFIGURATIONEDGE OF EXISTING WALL TO REMAINMATCH (E) WD BASEREMOVE PORTION OF EXISTINGWALL TO ACCOMODATE NEWWALL HEIGHT3'-0"WD HANDRAIL & MTLBRACKET, MATCH EXIST.CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.4/20/2017 1:08:20 PMA8.4INTERIORELEVATIONSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO 1/4" = 1'-0"1SOUTH ELEVATIONNARTHEX 204 1/4" = 1'-0"2EAST ELEVATIONNARTHEX 204 1/4" = 1'-0"3WEST ELEVATIONNARTHEX 2044NORTH ELEVATIONNARTHEX 2045ELEVATION AT STAIR LANDINGISSUE: DATE:50% CD SET 12/20/16PERMIT DRAWINGS 1/12/17100% CD 2/15/17PERMIT RESUB 4/17/17City of Aspen Received 5/2/17Building DepartmentHandrail extensionsmust return.
WIRING SCHEDULE - ALUMINUMAMPS(2WG) (3WG) (4WG)1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND100(2#1 & 1#6 G) 1 1/4"C (3#1 & 1#6 G) 1 1/2"C (4#1 & 1#6 G) 1 1/2"C200(2-250 KCMIL & 1#4 G) 2"C (3-250 KCMIL & 1#4 G) 2 1/2"C (4-250 KCMIL & 1#4 G) 3"C300(2-500 KCMIL & 1#2 G) 2 1/2"C (3-500 KCMIL & 1#2 G) 3"C (4-500 KCMIL & 1#2 G) 3 1/2"C8003[(2-400 KCMIL & 1#3/0 G) 2 1/2"C] 3[(3-400 KCMIL & 1#3/0 G) 3"C] 3[(4-400 KCMIL & 1#3/0 G) 3 1/2"C]CONDUCTOR SIZES ARE BASED ON 75° TERMINATIONS.CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).WIRING SCHEDULE - COPPERAMPS(2WG) (3WG) (4WG)1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND20(2#12 & 1#12 G) 3/4"C (3#12 & 1#12 G) 3/4"C (4#12 & 1#12 G) 3/4"C30(2#10 & 1#10 G) 3/4"C (3#10 & 1#10 G) 3/4"C (4#10 & 1#10 G) 3/4"C40(2#8 & 1#10 G) 3/4"C (3#8 & 1#10 G) 3/4"C (4#8 & 1#10 G) 1"C50(2#6 & 1#10 G) 3/4"C (3#6 & 1#10 G) 1"C (4#6 & 1#10 G) 1"C60(2#4 & 1#10 G) 1"C (3#4 & 1#10 G) 1"C (4#4 & 1#10 G) 1 1/4"C70(2#4 & 1#8 G) 1"C (3#4 & 1#8 G) 1 1/4"C (4#4 & 1#8 G) 1 1/4"C80(2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C (4#2 & 1#8 G) 1 1/2"C90(2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C (4#2 & 1#8 G) 1 1/2"C100(2#1 & 1#8 G) 1 1/4"C (3#1 & 1#8 G) 1 1/2"C (4#1 & 1#8 G) 1 1/2"C200(2#3/0 & 1#6 G) 1 1/2"C (3#3/0 & 1#6 G) 2"C (4#3/0 & 1#6 G) 2"CCONDUCTOR SIZES ARE BASED ON 60° TERMINATIONS LESS THAN 100A AND 75° TERMINATIONS GREATER THAN 100ACONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).SERVICE WIRING SCHEDULEAMPSALUMINUM(4W)GROUNDING ELECTRODE CONDUCTOR3Ø, 4 WIRE W.P. M.F. C.E.C. G.RING G. ROD8003[(4-400 KCMIL) 3"C]#3/0 CU #3/0 CU #3/0 CU #3/0 CU #6 CUCONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).ABBREVIATIONS: W.P. - WATER PIPE; M.F. - METAL FRAME OR STRUCTURE; C.E.C. - CONCRETE ENCASED ELECTRODE;G.RING. - GROUND RING; G.ROD - GROUND ROD, PIPE OR PLATE ELECTRODEDISTRIBUTION PANEL:VOLTAGE:120/208V, 3PH, 4W(N)MDPMINIMUM BUS:800LOCATION:MAIN:ELEV LOBBY 001MLOMOUNTING:MINIMUM AIC:RECESSED22,000PANELS/RISERSMOTORS/EQUIPMENTPANELSUBTOTALDEMAND PANEL TOTALMARK:P0P1AM0 SPAREEL-1CH-1OCPD:100/3 CB 300/3 CB 300/3 CB 100/3 CB 200/3 CB 175/3 CBLIGHTING1200 1585595 0 0 17150125%21438RECEPTACLES3240 23040 1920 0 0 28200 NEC 220 19100LARGEST MOTOR0 166266009 41382 51817 5181725%12954MOTORS0 17634 32337 0 0 143170100%143170EQUIPMENT6428 1349614064 0 0 33988100%33988APPLIANCES0 12416 4992 0 0 17408 6 11315PANEL TOTAL (KVA):242.0GENERAL NOTES:1.PROVIDE LOCKABLE HANDLES ON CIRCUIT BREAKERS.PANEL TOTAL (A):6722.PANEL:(N)P0VOLTAGE:120/208V, 3PH, 4WMINIMUM BUS:100LOCATION:ELEV LOBBY 001MAIN:MLOMOUNTING:RECESSEDMINIMUM AIC:22,000NO.LOADTYPE LOAD DESCRIPTIONBREAKERBUSBREAKERTYPE LOAD DESCRIPTIONLOADNO.ABCPOLETRIP A BCTRIPPOLEABC1 1200 L(E)BASEMENT LIGHTS120+20 1 R ELEV LOBBY 001 720 23 1664 E(E)ORGAN BLOWER220+20 1 R BASEMENT STORAGE 900 45 1664 E -- -- --+20 1 R BOILER ROOM 720 67 1500 E MEN 116 HAND DRYER 1 20+20 1 R EXTERIOR REC 360 89 100 E MEN 116 URINALS 1 20+20 1 R MEN 116/WOMEN 110 540 1011 1500 E WOMEN 110 HAND DRYER 1 20+20 1 SPARE 1213 SPARE 1 20+20 1 SPARE 1415 SPARE 1 20+20 1 SPARE 1617 SPARE 1 20+20 1 SPARE 1819 SPARE 1 20+SPACE 2021 SPACE+SPACE 2223 SPACE+SPACE 2425 SPACE+SPACE 2627 SPACE+SPACE 2829 SPACE+SPACE 30LOAD TYPE PANEL TOTALFEED THRUTOTALSUBFEEDTOTALFEEDERSUBTOTALDEMAND FEEDER TOTALGENERAL NOTES:A.ALL CIRCUITS WITH (E) ARE EXISTING TO REMAIN.(L) LIGHTING12001200125%1500B.(R) RECEPTACLES32403240NEC 2203240C.(LM) LARGEST MOTOR0025%0D.(M) MOTORS (ALL)00100%0E.(E) EQUIPMENT64286428100%6428SPECIFIC NOTES:(A) APPLIANCES0000(1)PANEL TOTAL (KVA):11.2(2)(3)PANEL TOTAL (A):54(4)(5)PANEL:(N)M0VOLTAGE:120/208V, 3PH, 4WMINIMUM BUS:400LOCATION:BOILER ROOMMAIN:MLOMOUNTING:RECESSEDMINIMUM AIC:10,000NO.LOADTYPE LOAD DESCRIPTIONBREAKERBUSBREAKERTYPE LOAD DESCRIPTIONLOADNO.ABCPOLETRIP A BCTRIPPOLEABC1 2496 A(E)STOVE230+20 1 E(E)WASHER1920 23 2496 A -- -- --+60 2 E(E)DRYER4992 45 1920 R(E)PHONE REC120+-- -- E -- 4992 67 2003 LM AHU-1 3 30+30 2 M FC-1 1144 89 2003 LM -- -- --+-- -- M -- 1144 1011 2003 LM -- -- --+20 1 SPARE 1213 2003 M AHU-2 3 30+20 1 SPARE 1415 2003 M -- -- --+20 1 SPARE 1617 2003 M -- -- --+20 1 SPARE 1819 400 ECUH-1 (x4)120+25 1 M FC-7 1536 2021 200 ECUH-2 (x2)120+20 2 M FC-8 894 2223 200 ECUH-3 (x3)120+-- -- M -- 894 2425 450 ECUH-4 (x4)120+20 1 E B-1 180 2627 1144 M P-1 2 20+20 1 E B-1 180 2829 1144 M -- -- --+20 1 MEF-1 (x2)360 3031 1144 M P-1 2 20+20 1 M EF-2 144 3233 1144 M -- -- --+20 1 MGF-1 (x3)150 3435 221 M P-2 2 20+20 1 E MOTORIZED LOUVER 150 3637 221 M -- -- --+20 1 E BASEMENT DAMPERS 300 3839 221 M P-2 2 20+20 1 E MAIN LEVEL DAMPERS 100 4041 221 M -- -- --+20 1 L(E)TIME CLOCK95 4243 1656 M P-3 1 30+20 1 M EF-3 264 4445 75 M P-4 1 20+20 1 SPARE 4647 1176 M P-5 1 20+20 1 SPARE 4849 1030 M P-6 2 20+20 1 SPARE 5051 1030 M -- -- --+20 1 SPARE 5253 1030 M P-6 2 20+SPACE 5455 1030 M -- -- --+SPACE 5657 651 M P-7 2 20+SPACE 5859 651 M -- -- --+SPACE 6061 SPARE 1 20+SPACE 6263 SPARE 1 20+SPACE 6465 SPARE 1 20+SPACE 6667 SPARE 1 20+SPACE 6869 SPACE+SPACE 7071 SPACE+SPACE 72LOAD TYPE PANEL TOTALFEED THRUTOTALSUBFEEDTOTALFEEDERSUBTOTALDEMAND FEEDER TOTALGENERAL NOTES:A.ALL CIRCUITS WITH (E) ARE EXISTING TO REMAIN.(L) LIGHTING9595125%119B.(R) RECEPTACLES19201920NEC 220 1920 C.(LM) LARGEST MOTOR6009600925%1502D.(M) MOTORS (ALL)3233732337100%32337E.(E) EQUIPMENT1406414064100%14064SPECIFIC NOTES:(A) APPLIANCES4992499214992(1)PANEL TOTAL (KVA):54.9(2)(3)PANEL TOTAL (A):153(4)(5)PANEL:(N)P1AVOLTAGE:120/208V, 3PH, 4WMINIMUM BUS:400LOCATION:HALL 117MAIN:MLOMOUNTING:RECESSEDMINIMUM AIC:22,000NO.LOADTYPE LOAD DESCRIPTIONBREAKERBUSBREAKERTYPE LOAD DESCRIPTIONLOADNO.ABCPOLETRIP A BCTRIPPOLEABC1 1664 A(E)KITCHEN DISPOSAL220+20 1 L(E)LTG MEETING R 101120 23 1664 A -- -- --+20 1 L(E)LTG MEETING R 102120 45 1440 L(E)KITCHEN LIGHTS120+20 1 L(E)LTG MEETING R 103120 67 1920 R(E)PASS WINDOW REC120+20 1 L(E)LTG MEETING R 104120 89 1920 R(E)PASS WINDOW REC120+20 1 L(E)LTG MEETING R 105120 1011 1664 A(E)KITCHEN STEAM TABLE220+20 1 L(E)LTG MEETING R 106120 1213 1664 A -- -- --+20 1 L(E)LTG MEETING R 107120 1415 1920 A(E)KITCHEN COFFEE120+20 1 E(E)MEETING ROOM FANS540 1617 1920 A(E)ANSUL & OVEN120+20 1 E(E)MAG DOOR HOLDER500 1819 1920 E(E)KITCHEN REC120+20 1 L HALLWAY 111 265 2021 1920 E(E)KITCHEN UC REF120+20 1 L MAIN LEVEL OFFICE 1585 2223 1920 E(E)FREEZER120+20 1 L MAIN LEVEL ENTRY 1810 2425 1920 E(E)REFRIGERATOR120+20 1 L SANCTUARY ENTRY 1055 2627 1920 A(E)DISHWASHER120+20 1 L VESTING 208/ALTER 209 642 2829 1920 E(E)KITCHEN ICE120+20 1 L SANCTUARY/NAVE 1800 3031 1008 M(E)MUA UNIT120+20 1 L SANCTUARY/NAVE 1800 3233 1200 L SANCT. TRACK LTG 1 20+20 1 L SANCTUARY/NAVE 1000 3435 1200 L SANCT. TRACK LTG 1 20+20 1 L SANCTUARY/NAVE 1218 3637 5542 LM(E)KITCHEN HOOD FAN3100+100 3 E(E)PANEL 'P1B'3839 5542 LM -- -- --+-- -- E -- 4041 5542 LM -- -- --+-- -- E -- 42LOAD TYPE PANEL TOTALFEED THRUTOTALSUBFEEDTOTALFEEDERSUBTOTALDEMAND FEEDER TOTALGENERAL NOTES:A.ALL CIRCUITS WITH (E) ARE EXISTING TO REMAIN.(L) LIGHTING15855 015855125%19819B.(R) RECEPTACLES3840 1920023040NEC 220 16520 C.(LM) LARGEST MOTOR16626 01662625%4157D.(M) MOTORS (ALL)17634 017634100%17634E.(E) EQUIPMENT10640 285613496100%13496SPECIFIC NOTES:(A) APPLIANCES12416 0124165 8691(1)PANEL TOTAL (KVA):80.3(2)(3)PANEL TOTAL (A):223(4)(5)PANEL:(N)P1BVOLTAGE:120/208V, 3PH, 4WMINIMUM BUS:100LOCATION:HALL 117MAIN:MLOMOUNTING:RECESSEDMINIMUM AIC:10,000NO.LOADTYPE LOAD DESCRIPTIONBREAKERBUSBREAKERTYPE LOAD DESCRIPTIONLOADNO.ABCPOLETRIP A BCTRIPPOLEABC1 540 R STORAGE 121 1 20+20 1 R HALLWAY 111 540 23 540 R ENTRY 100 COFFE BAR 1 20+20 1 R OFFICE 119 900 45 900 R STORAGE 122 1 20+20 1 R OFFICE 114 900 67 1080 R MEETING R 1/2 1 20+20 1 R OFFICE 113 900 89 1080 R MEETING R 3/4/5 1 20+20 1 R HALL 115/117/118 1080 1011 1260 R MEETING R 6/7 1 20+20 1 R CONF RM 112 900 1213 1000 R COPIER REC. 1 20+20 1 R MEETING RM PROJ. 540 1415 720 R WEST NAVE 1 20+20 1 R ALTER SERVER 209 900 1617 900 R EAST NAVE 1 20+20 1 R VESTING 208 540 1819 720 R SANCTUARY 207 1 20+20 1 R CHOIR LOFT/ORGAN 720 2021 1296 E SANCT. SPEAKERS 1 20+20 1 R BELFRY REC 180 2223 1200 E SANCT. SUBWOOFER 1 20+20 1 R COFFEE BAR UC REF 1000 2425 360 E CHOIR LOFT PROJ. 1 20+20 1 R VESTING 208 REF 1000 2627 360 R ALTER SERVER 209 AV 1 20+20 1 SPARE 2829 SPARE 1 20+20 1 SPARE 3031 SPARE 1 20+20 1 SPARE 3233 SPARE 1 20+20 1 SPARE 3435 SPARE 1 20+20 1 SPARE 3637 SPARE 1 20+20 1 SPARE 3839 SPARE 1 20+20 1 SPARE 4041 SPARE 1 20+20 1 SPARE 42LOAD TYPE PANEL TOTALFEED THRUTOTALSUBFEEDTOTALFEEDERSUBTOTALDEMAND FEEDER TOTALGENERAL NOTES:A.(L) LIGHTING00125%0B.(R) RECEPTACLES1920019200NEC 220 14600 C.(LM) LARGEST MOTOR0025%0D.(M) MOTORS (ALL)00100%0E.(E) EQUIPMENT28562856100%2856SPECIFIC NOTES:(A) APPLIANCES0000(1)PANEL TOTAL (KVA):17.5(2)(3)PANEL TOTAL (A):48(4)(5)SHORT CIRCUIT / VOLTAGE DROP CALCULATION SUMMARYPOINTTAGVOLTAGE /PHASELENGTH(FT)COPPER /ALUMINUMCONDUITWIRESIZE# OFSETSFEEDERVOLTAGEDROP (%)TOTALVOLTAGEDROP (%)IscAVAILABLEUPSTREAMIsc (FAULT)F1DISCONNECT208V, 3Ø10AN400 30.1% 0.1%59,600 54,709F2 MDP208V, 3Ø65AN400 30.7% 0.8%17,471 14,928F3 M0208V, 3Ø75AS50010.4% 1.2%14,928 9,971F4P0208V, 3Ø10AS110.1% 0.9%14,928 11,777F5P1A208V, 3Ø50AS50010.4% 1.2%14,928 11,212F6P1B208V, 3Ø10AS110.1% 1.3%11,212 9,336** FOR DESIGN PURPOSES, A 300KVA UTILITY TRANSFORMER WITH A MAXIMUM AVAILABLE (SYMMETRICAL) FAULT AT THE SECONDARY OF 59,600 AMPSHAS BEEN ASSUMED. ACTUAL TRANSFORMER AND FAULT CURRENT INFORMATION SHALL BE PROVIDED TO THE ELECTRICAL ENGINEER, PRIOR TOPURCHASING ANY ELECTRICAL EQUIPMENT, TO ALLOW VERIFICATION OF THESE CALCULATIONS. SHORT CIRCUIT CALCULATIONS ARE FURNISHED FORALL FAULT LEVELS ABOVE 10,000 AMPS @ 208 VOLT. ANY FAULT CURRENT BELOW THIS LEVEL IS CONSIDERED SAFE FOR THE ELECTRICAL SYSTEM TOCLEAR OR EQUIPMENT IS BUILT TO WITHSTAND THIS LEVEL OF FAULT SAFELY.T200/3300/3200/3100/3300/3(N) MDP800A MLO208Y/120V, 3P, 4WMNG20 L.F. OF #3/0 CU ENCASEDIN MIN. 2" OF CONCRETE.I.A.W. N.E.C. 205-52(C)WATER SERVICE I.A.W.N.E.C. 250-52(A)BUILDING STEEL I.A.W.N.E.C. 250-52(B)GROUNDING ELECTRODECONDUCTORS SIZED PERSERVICE WIRING SCHEDULE.SPACEPANEL'P1A'(N)PANEL'M0'(N)PANEL'P0'(N)300A(4WG)AL300A(4WG)ALSPACE100/3200A(3WG)CU800A(4WG)AL800A, 208V/3 FUSED SERVICEDISCONNECT SWITCH WITHUTILITY METERING AND NEMA3R ENCLOSURE800A(4W)ALBASEMENTMAIN LEVELPANEL'P1B'(N)100A(4WG)ALSPARECH1EL1100A(4WG)ALSPDF1F2F3F4F5F6BUSSMANN KRP-C_SP800A FUSE(E)RECONNECT EXISTINGFEEDER TO NEW CIRCUITBREAKERALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:02:40 PME0.1ELECTRICALONE-LINEDIAGRAMST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: NONE1ELECTRICAL ONE-LINE DIAGRAM33City of Aspen Received 5/2/17Building Department
LUMINAIRE SCHEDULETYPE DESCRIPTION MOUNTINGRECESSDEPTHLAMPSINPUT WATTS VOLT MANUFACTURER CATALOG NUMBERSPECIFICNOTESQTY TYPEDP1 DECORATIVE CUSTOM LED PENDANT IN SANCTUARY PENDANT -LED AS SUPPLIED,3000KALLOW 100WATTS120 RAMBUSCHCUSTOM FIXTURE WITH A MINIMUM OF6000 LUMEN OUTPUT5DP2EXISTING PENDANT FROM SANCTUARY, REFURBISHEDAND RELOCATED TO STAIRPENDANT - 6ARCHIPELAGOCA10 3.5W LAMP360 120 - -DP3 DECORATIVE PENDANT IN MEETING ROOMS PENDANT -LED AS SUPPLIED,3000K60 120SCOTTARCHITECTURALLIGHTING24" S2355-L60-30K-PC (BRONZEMETALLIC)-LF06-OA24"DP4 DECORATIVE PENDANT IN OFFICE CEILING - 3 CREE 16.5W A19 60 120 HINKLEY SUSSEX 4791EZ 6DS1 DECORATIVE SURFACE MOUNT IN VESTING CEILING - 3 CREE 16.5W A19 225 120 HINKLEY SUSSEX 4791EZDW1 DECORATIVE WALL SCONCE IN RESTROOMS WALL -LED AS SUPPLIED,3000K13.5 120 ELK 66170-1-LED OILED BRONZEDW2DECORATIVE CUSTOM WALL SCONCE IN NARTHEXCOMPLIMENTARY TO PENDANT IN SANCTUARY, ADACOMPLIANTWALL -LED AS SUPPLIED,3000K8 120 RAMBUSCHCUSTOM FIXTURE WITH MINIMUM OF800 LUMEN OUTPUT5(E)EXISTING FIXTURE TO REMAINE1EXTERIOR DUAL HEAD ADJUSTABLE LED BULLET LIGHTWITH INTEGRAL TRANSFORMERSURFACE -LED AS SUPPLIED,3000K14 120/12 BK LIGHTINGDS-LED-E66-MFL-A9-BZP-A-360SLBC5-BZP MB3-BZP TRSS-75-120E2WALL MOUNTED EXTERIOR LED DOWNLIGHT WITHEMERGENCY BATTERY BACKUPWALL -LED AS SUPPLIED,4000K17 120 DUAL-LITE PGN-ZE3EXTERIOR DECORATIVE LED WALL SCONCE WITHREMOTE EMERGENCY BATTERY BACK UPWALL -LED AS SUPPLIED,2700K15 120 HINKLEY PULLMAN 2210OZ-LED 4R1RECESSED 6" APERTURE LED WALL WASHER, 2000LUMENSRECESSED 7 9/16"LED AS SUPPLIED,3000K23.2 120 GOTHAM LIGHTING EVO-WW-30/20-6AR-LD-MVOLTR2 RECESSED 6" APERTURE LED DOWNLIGHT, 2000 LUMENS RECESSED 7 9/16"LED AS SUPPLIED,3000K23.2 120 GOTHAM LIGHTING EVO-30/20-6AR-WD-LD-MVOLTR2ERECESSED 6" APERTURE LED DOWNLIGHT, 2000 LUMENSWITH EMERGENCY BATTERY BACKUPRECESSED 7 9/16"LED AS SUPPLIED,3000K23.2 120 GOTHAM LIGHTING EVO-30/20-6AR-WD-LD-MVOLT-ELR3 RECESSED 2" APERTURE LED DOWNLIGHT, 1000 LUMENS RECESSED 7 1/4"LED AS SUPPLIED,3000K13 120 GOTHAM LIGHTINGICO-30/10-2AR-LED-50D-MVOLT-UGZ-NCHR4SEMI-RECESSED ADJUSTABLE LED DOWNLIGHT WITHFINISH TO MATCH BEAMRECESSED 5" 1SORAA MR16 9WSM16-09-25D- 930-0335 120CONTRASTLIGHTINGT7124-05 IT7000E PROVIDE UL LABELFOR 35W MAX WATTAGER4WSEMI-RECESSED ADJUSTABLE LED DOWNLIGHT WITHWHITE FINISHRECESSED 5" 1SORAA MR16 9WSM16-09-25D- 930-0335 120CONTRASTLIGHTINGT7124-05 IT7000E PROVIDE UL LABELFOR 35W MAX WATTAGE WHITE FINISHR5 RECESSED LED PUCK LIGHT IN MILLWORK/NICHERECESSED 0.73"LED AS SUPPLIED,3000K1 12 EDGE LIGHTING DOT-RD-1W-30D-30K-BZ TE-60L-12 1R6RECESSED ADJUSTABLE LED DOWNLIGHT, 2200 LUMENSWITH IC HOUSINGRECESSED 7 3/16"LED AS SUPPLIED,3000K25 120 WAC LIGHTING R4RAT-F-930-HZ R4RNT-25R6RRECESSED REMODELER ADJUSTABLE LED DOWNLIGHTWITH 2200 LUMENSRECESSED 7 3/16"LED AS SUPPLIED,3000K25 120 WAC LIGHTING R4RAT-F-930-HZ R4BRT-25R7 RECESSED 2 3/8" LED ADJUSTABLE LED DOWNLIGHT RECESSED 3 1/4"LED AS SUPPLIED,3000K5 12 JUNO LIGHTING MG1LG2-930-FL-SN TL602E-60-WH 1S112'" LONG LED GRAZING FIXTURE MOUNTED IN BASE OFSCULPTURE STANDSURFACE -LED AS SUPPLIED,3000K5.2 24 LUMINIIKENDO M GRAZE-12"-30K- HO-11-A-WHLTEA4U1UKL-CV2401S2 4' LONG LENSED LED SURFACE -LED AS SUPPLIED,3000K42 120 LITHONIAZL1N-L48-5000LM-FST-MVOLT-30K-80CRI-WHS3SURFACE MOUNTED LINEAR LED TAPE LIGHT WITHMINIMUM CRI OF 98SURFACE -LED AS SUPPLIED,3000K2.5 W/FT 24 LUMINII LL30-3OK HST PSD-96-24 1S4 SURFACE MOUNTED LINEAR UNDER CABINET LIGHT SURFACE -LED AS SUPPLIED,3000K8 W/FT 120 WAC LIGHTINGLEDME PRO AC-LED SERIESBA-ACLED-*-930-BZ2T1SURFACE MOUNTED LINE VOLTAGE TRACK WITH TWOCIRCUIT WITH TWO NEUTRALSSURFACE -LED AS SUPPLIED,3000K17 W/2FT 120 TIMES SQUAREAXT13-98-30-B-120-*-TA1/TE2 -LEE-SERIES TRACK3W1 2' LONG WALL MOUNTED LENSED LED SURFACE -LED AS SUPPLIED,3000K22 120 LITHONIAZL1N-L24-2500LM-FST-MVOLT-30K-80CRI-WHW2 SMALL LED WALL SCONCE IN CONFESSIONAL WALL -LED AS SUPPLIED,AMBER16 120 HINKLEY AVENUE 61222OZW3CONFESSIONAL INDICATOR LIGHT WITH RED AND GREENMARKER ON SEPARATE SWITCHRECESSED 2.5" LED AS SUPPLIED 8 120 WINONAMARKER06-RECT-CPTN-INT-2/LSR1-RED-GRN-MVOLT-RG1-*-MOD DUALCIRCUITX1TRADITIONAL STYLE, CEILING MOUNTED, LED EXIT SIGNWITH RED LETTERING, SANDBLASTED FACE, ANDEMERGENCY BATTERY BACKUPCEILING - LED AS SUPPLIED 1 120 COLE KCL-612-RED-120-EMX1WTRADITIONAL STYLE, WALL MOUNTED, LED EXIT SIGNWITH RED LETTERING, SANDBLASTED FACE, ANDEMERGENCY BATTERY BACKUPWALL - LED AS SUPPLIED 1 120 COLE KWL-612-RED-120-AR-EMX2CONCEALED EMERGENCY EGRESS LIGHT WITHBATTERY BACK UPRECESSED 3 5/8" 2 LED AS SUPPLIED 10 120 CONCEALITE F5000-LED30-90-SD-NCX3THERMOPLASTIC LED EXIT SIGN WITH RED LETTERING,EGRESS LIGHTS, AND BATTERY BACKUPWALL - LED AS SUPPLIED 5 120 EVENLITE TCXCOM-R-U-WX4EXTERIOR LED EGRESS LIGHT WITH BATTERY BACK UPAND HEATERWALL - LED AS SUPPLIED 15.2 120 DUAL-LITE PG-Z-HTRGENERAL NOTES:A.THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTEPRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS ANDSPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.B.REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.C. ALL FLUORESCENT LAMPS ARE TO BE 3000° KELVIN COLOR TEMPERATURESPECIFIC NOTES:(1)REMOTE DRIVER REQUIRED.(2)PROVIDE DIFFERENT LENGTHS MOUNTED END TO END TO PROVIDE LENGTHS SHOWN ON PLANS.(3)PROVIDE A 20 AND 40 DEGREE REFLECTOR FOR EACH TRACK HEAD.(4)PROVIDE REMOTE INVERTER FOR EGRESS LIGHTING, BODINE ELI-S-20. LOCATE IN CLOSEST STORAGE UNDER STAIRS.(5)APPROVED ALTERNATE BIDDER: ST. LOUIS LIGHTING.(6)PROVIDE FACTORY INSTALLED LABEL INDICATING MAX WATTAGE PER SOCKET IS 20 WATTS.MECHANICAL EQUIPMENT SCHEDULEMARK DESCRIPTIONVOLT /PHASEHP WATTS FLA MCA MOCPDISCONNECT/FUSE SIZEFEEDER SPECIFIC NOTESAHU-1 AIR HANDLING UNIT 208/3 5 6009 15.7 19.6 30A3P 30A, 3P, NF30A(4WG)CUM0-7,9,11AHU-2 AIR HANDLING UNIT 208/3 5 6009 15.7 19.6 30A3P 30A, 3P, NF30A(4WG)CUM0-13,15,17CH-1 CHILLER 208/3 - 51817 - 144.0 200A3P 200A, 3P, NF200A(3WG)CUMDPFC-1 FAN COIL UNIT 208/1 1 1/2 2288 11.0 13.8 30A1P 30A, 2P, NF30A(2WG)CUM0-8,10FC-7 FAN COIL UNIT 120/1 1 1536 12.8 16.0 25A1P1P MOTORRATED SWITCH30A(2WG)CUM0-20FC-8 FAN COIL UNIT 208/1(2)1/21788 8.6 10.8 20A2P 30A, 2P, NF20A(2WG)CUM0-22,24CUH-1 CABINET UNIT HEATER 120/1 - 100 0.8 1.0 20A1P INTEGRAL20A(2WG)CUM0-19CUH-2 CABINET UNIT HEATER 120/1 - 100 0.8 1.0 20A1P INTEGRAL20A(2WG)CUM0-21CUH-3 CABINET UNIT HEATER 120/1 - 66.8 0.6 0.7 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-23CUH-4 CABINET UNIT HEATER 120/1 - 50 0.4 0.5 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-25B-1 BOILER 120/1 - 180 1.5 1.9 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-26 M0-28P-1 BOILER INJECTION PUMP 208/1 1 1/2 2288 11.0 13.8 20A2P 30A, 2P, NF20A(2WG)CUM0-27,29 M0-31,33P-2 HWS/R CIRC PUMP 208/1 - 442 2.1 2.7 20A2P 30A, 2P, NF20A(2WG)CUM0-35,37 M0-39,41P-3 WATER HEATER CIRC PUMP 120/1 3/4 1656 13.8 17.3 30A1P1P MOTORRATED SWITCH30A(2WG)CUM0-43P-4 DHW RE-CIRC PUMP 120/1 1/25 72 0.6 0.8 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-45P-5 SMS/R CIRC PUMP 120/1 1/2 1176 9.8 12.3 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-47P-6 CHS/R PUMP 208/1 1 1/4 2059 9.9 12.4 20A2P 30A, 2P, NF20A(2WG)CUM0-49,51 M0-53,55P-7 CHILLED WATER PUMP 208/1 - 1301 6.3 7.8 20A2P 30A, 2P, NF20A(2WG)CUM0-57,59EF-1 EXHAUST FAN 120/1 - 180 1.5 1.9 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-30EF-2 EXHAUST FAN 120/1 - 144 1.2 1.5 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-32EF-3 EXHAUST FAN 120/1 - 264 2.2 2.8 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-44GF-1 GLYCOL FEEDER 120/1 - 50 0.4 0.5 20A1P1P MOTORRATED SWITCH20A(2WG)CUM0-34GENERAL NOTES:A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.D.WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.SPECIFIC NOTES:(1)(2)(3)(4)ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 3:58:26 PME0.2ELECTRICALSCHEDULESST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADO33333City of Aspen Received 5/2/17Building Department
JJJJJJJACEBD123456789ELEV EQUIP002STORAGESTORAGEBOILERROOMCRAWLSPACECRAWLSPACECRAWLSPACEELEV LOBBY001+48"+48"+48"+48"+48"'MDP'+48"1123B1B1+48"(E)(E)(E)(E)(E)DRYER(E)WASHER'M0''P0'M0-2M0-2M0-5M0-5M0-4,6M0-4,6P0-2P0-2P0-2P0-2P0-2P0-2P0-4P0-4P0-4P0-4P0-4P0-4P0-4P0-4P0-4P0-4P0-6P0-6P0-6P0-6P0-6P0-6P0-6P0-6P0-2P0-2(E)(E)FC1111113333333ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 3:58:28 PME2.4BASEMENTLEVELELECTRICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOFLAG NOTES:1PROVIDE 20A, 120V CIRCUIT FORMOTORIZED DAMPERS.EXISTING ELEVATOR TO REMAIN.RECONNECT EXISTING FEEDER TONEW PANEL 'MDP' PER ONE-LINEDIAGRAM ON SHEET E0.1.PROVIDE ELECTRICAL CONNECTIONSTO (2) P-1, (2) P-2, (1) P-3, (1) P-4, (1) P-5,(2) P-6, (1) P-7, AND (3) GF-1 PUMPS INTHIS AREA. COORDINATE WITHMECHANICAL CONTRACTOR.23SCALE: 3/16" = 1'-0"BASEMENT LEVEL ELECTRICAL PLANALL MOTORIZED DAMPERS THIS SHEETSHALL BE CIRCUITED TO M0-38.1.POWER NOTES:City of Aspen Received 5/2/17Building Department
TVJJJJJTVTVJJHHHHHJACEBD123456789KITCHEN109ENTRY100MEETING RM102MEETING RM103MEETING RM104MEETING RM105HALLWAY111WOMEN110OFFICE113MEN116HALL115OFFICE114OFFICE119HALL117RECEPT118VEST.120MEETING RM101OFFICE122MEETING RM107CONF RM112CCCCCCC'P1A'+42"+42"'P1B'COPIER1222EF1EF1FC7FC833CUH3CUH3+42"CUH4CUH4CUH4CUH2CUH2CUH4CUH4CUH4CUH4CUH1CUH3CUH4CUH144455(E) (E) (E) (E) (E) (E) (E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)WP(E)(E)(E)(E)(E)P0-8P0-8STOR121P1B-1P1B-1P1B-1P1B-1P1B-1P1B-1P1B-3P1B-3P1B-3P1B-3P1B-3P1B-3P1B-5P1B-5P1B-5P1B-5P1B-5P1B-5P1B-5P1B-5P1B-5P1B-5P1B-7P1B-7P1B-7P1B-7P1B-7P1B-7P1B-7P1B-7P1B-7P1B-7P1B-9P1B-9 P1B-9P1B-9P1B-9P1B-9 P1B-9P1B-9 P1B-9P1B-9P1B-9P1B-9P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-11P1B-2P1B-2P1B-2P1B-2P1B-2P1B-2P1B-4P1B-4P1B-4P1B-4P1B-4P1B-4P1B-4P1B-4P1B-6P1B-6P1B-6P1B-6P1B-6P1B-6P1B-6P1B-6P1B-8P1B-8P1B-8P1B-8P1B-8P1B-8P1B-8P1B-8P1B-10P1B-10P1B-10P1B-10 P1B-10P1B-10P1B-10P1B-10P1B-10P1B-10P1B-10P1B-10P1B-13P1B-13P0-10P0-10P1B-12P1B-12P1B-12P1B-12P1B-12P1B-12P1B-12P1B-12P1B-12P1B-12P0-10P0-10P0-10P0-10P0-7P0-7P0-9P0-9 P0-9P0-9P0-11P0-11P1B-14P1B-14P1B-14P1B-14P1B-14P1B-14REFP1B-24P1B-24MEETING RM10643CUH43ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 3:58:32 PME2.5MAIN LEVELELECTRICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"MAIN LEVEL POWER PLANFLAG NOTES:1RECONNECT EXISTING KITCHENCIRCUITS TO PANEL 'P1A'. REFER TOPANEL SCHEDULE ON SHEET E0.1.PROVIDE CEILING MOUNTED DUPLEXRECEPTACLE FOR PROJECTOR.PROVIDE 20A, 120V CIRCUIT FOR HANDDRYER.PROVIDE 120V POWER CONNECTIONTO MOTORIZED DAMPER. COORDINATEEXACT LOCATION WITH MECHANICALCONTRACTOR PRIOR TO ROUGH-IN.PROVIDE 20A, 120V CIRCUIT FORURINAL.2345ALL MOTORIZED DAMPERS THIS SHEETSHALL BE CIRCUITED TO M0-40.PROVIDE FIRE ALARM SYSTEM TOCOMPLY WITH NATIONAL, STATE, ANDLOCAL CODES. SYSTEM SHALL BEDESIGN/BUILD BY CONTRACTOR ANDCONTRACTOR SHALL OBTAIN LICENSEDENGINEER OF RECORD FOR SYSTEM.FIRE ALARM DEVICES SHOWN ON PLANARE FOR DESIGN INTENT. FINAL DESIGNRESPONSIBILITY BY DESIGN/BUILDCONTRACTOR.1.2.POWER NOTES:City of Aspen Received 5/2/17Building Department
ACEBD123456789STAIR201STOR202STAIR203NARTHEX204VEST205NAVE206SANCTUARY207VESTING /SACRISTY208ALTARSERVERVESTING209CC122CCC33CUH1CUH1AHU1AHU2C(E)(E)(E)(E)(E)(E)P1B-15P1B-15P1B-15P1B-15P1B-15P1B-15P1B-15P1B-15P1B-17P1B-17P1B-17P1B-17P1B-17P1B-17P1B-17P1B-17P1B-17P1B-17P1B-16P1B-16P1B-16P1B-16P1B-16P1B-16P1B-27P1B-27P1B-18P1B-18P1B-18P1B-18P1B-18P1B-18P1B-19P1B-19P1B-19P1B-19P1B-21P1B-21P1B-21P1B-21P1B-21P1B-21P1B-21P1B-21P1B-21P1B-21P1B-23P1B-23P1B-23P1B-23CP1B-16P1B-16P1B-26P1B-26REFEF333ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 3:58:35 PME2.6SANCTUARYLEVELELECTRICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"SANCTUARY LEVEL POWER PLANPROVIDE STAGE FLOOR BOX WITH (1)DUPLEX RECEPTACLE AND (1) DATAOUTLET. REFER TO TECHNOLOGYPLANS AND TECHNOLOGY DIAGRAMSFOR MORE INFORMATION.PROVIDE DUPLEX RECEPTACLE FORSPEAKER. COORDINATE EXACTLOCATION WITH AV INSTALLER.PROVIDE DUPLEX RECEPTACLE FORSUBWOOFER. MOUNT RECEPTACLE INSUBWOOFER ENCLOSURE.COORDINATE EXACT LOCATION WITHAV INSTALLER.FLAG NOTES:123PROVIDE FIRE ALARM SYSTEM TOCOMPLY WITH NATIONAL, STATE, ANDLOCAL CODES. SYSTEM SHALL BEDESIGN/BUILD BY CONTRACTOR ANDCONTRACTOR SHALL OBTAIN LICENSEDENGINEER OF RECORD FOR SYSTEM.FIRE ALARM DEVICES SHOWN ON PLANARE FOR DESIGN INTENT. FINAL DESIGNRESPONSIBILITY BY DESIGN/BUILDCONTRACTOR.1.POWER NOTES:City of Aspen Received 5/2/17Building Department
ocSSocDDDDDJJJocococococSSoc ococococococSoSSSSSSSSSSocococSSSSo SSocSSACEBD123456789DP4DP4S3R3R3R3R1R1DP4R2R2R1R1DW1DW1R2ER2R2DP4DP4DP4DP4DW1DW1DW1DW1R2R2ER2R2(E)(E)(E)(E)DP4DP4DP4DP3DP3DP3DP3DP3DP3DP3DP3DP3DP3DP3DP3DP3DP3S2S2R5R5X1X1X3X3X312R3R3DP4KK3311R2(E)R2R2ER2ER2(E)R5R5R2EDP43333333444456677R2ER2EHALLWAY111WOMEN110MEN116OFFICE113CONF RM112KITCHEN109OFFICE114OFFICE119STOR121ENTRY100MEETING RM101MEETING RM102MEETING RM103MEETING RM104MEETING RM105MEETING RM106MEETING RM107OFFICE122VEST.120S3S38339RECEPT1181313131313133TOLIGHTSIN STAIRABOVETO LIGHTSIN STAIRABOVE151010P1A-24P1A-22P1A-2P1A-4P1A-6P1A-8P1A-10P1A-12P1A-14(E)P1A-5P1A-20R2ER2R4WR4W1414111212R2R21X233333ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 3:58:40 PME3.2MAIN LEVELLIGHTING PLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"MAIN LEVEL LIGHITNG PLANFLAG NOTES:J-BOX FOR CEILING FAN.LIGHTING IN THE KITCHEN TO REMAINAS INSTALLED.REMOVE EXISTING SWITCH FORLIGHTS AND REPLACE WITH SWITCHWITH WIRELESS COMMUNICATION(LUTRON MRF2-8ANS-120-*). PROVIDECEILING MOUNTED OCCUPANCYSENSOR WITH WIRELESSCOMMUNICATIONS IN THIS ROOM ASWELL (LUTRON LRF2-OCR2B-P-WH).PROVIDE WALL BOX DIMMER ANDCEILING OCCUPANCY SENSOR WITHWIRELESS COMMUNICATIONS (LUTRONMRF2-6CL-* LRF2-VCR2B-P-WH).PROVIDE COMPANION WALL BOXDIMMER (LUTRON MA-R-*).PROVIDE DUAL TECHNOLOGYOCCUPANCY SENSOR (LUTRONLOS-CDT-500-WH).PROVIDE NUMBER OF WALL SWITCHESAS SHOWN IN THIS ROOM AND CEILINGOCCUPANCY SENSOR WITH WIRELESSCOMMUNICATIONS (LUTRONMRF2-8ANS-120-* LRF2-VCR2B-P-WH).PROVIDE ASTRONOMICAL TIMESWITCH (INTERMATIC EJ600A).PROGRAM LIGHTS TO COME ON ATSUNSET AND TURN OFF AT 1AM.CONNECT THIS FIXTURE TO EXISTINGCIRCUIT FEEDING LIGHTS IN HALL.EXIT SIGN WITH INTEGRAL EGRESSLIGHTING.MOUNT FIXTURE ABOVE DOOR JAMB INBOTTOM OF ARCHING WINDOW.PROVIDE BLOCKING AS NEED TOCONCEAL FIXTURE FROM VIEW.CONNECT THIS SWITCH AND LIGHT ONSWITCH LEG TO THE CIRCUITINDICATED FOR THE LIGHTS IN THEUPPER STAIR.REMOVE EXISTING LAMP AND REPLACEWITH 8W CREE BR30 LAMP.REFER TO SHEET E4.1 FOR MOUNTINGDIAGRAM FOR LIGHT IN DISPLAYWINDOW.EXIT SIGN WITH INTEGRAL EGRESSLIGHTING.12CIRCUIT EXIT SIGNS AND EGRESSLIGHTS TO NEAREST UNSWITCHEDCIRCUIT.ALL EXTERIOR LIGHTING IS EXISTING TOREMAIN.1.2.LIGHTING NOTES:34567891011121314153City of Aspen Received 5/2/17Building Department123456789101112123456789101112131412345678910111213141516171819202112341231234123456451212123
DRF/SF/S14x1214øDUCTWORK LEGENDDESCRIPTIONROUNDRECTANGULARDUCT RISERDUCT DROP90° ELBOW DN.(NEGATIVE PRESSURE)90° ELBOW DN.(POSITIVE PRESSURE)90° ELBOW UP(NEGATIVE PRESSURE)90° ELBOW UP(POSITIVE PRESSURE)SIZE OR SHAPE TRANSITIONROUND FLEXIBLE DUCTCONNECTION90° RADIUS ELBOW90° MITERED ELBOWW/ TURNING VANES90° STRAIGHT TEE90° CONICAL TEE3DPLANPLAN3D45° BRANCH45° CONICAL BRANCH--COMBINATION FIRE ANDSMOKE DAMPERFIRE DAMPERSMOKE DAMPEROFFSET TO CHANGE ELEVATIOND = DROP R=RISEDUCT SIZE TAG:FIRST NUMBER = PLAN WIDTHMANUAL BALANCING DAMPERMOTORIZED DAMPERBACKDRAFT DAMPER--AAVAIR ADMITTANCE VALVEAFFABOVE FINISHED FLOORAFGABOVE FINISHED GRADEAUTOAUTOMATICABVABOVEBCSBUILDING CONTROL SYSTEMBDDBACK DRAFT DAMPERBLDGBUILDINGBFGBELOW FINISHED GRADEBOPBOTTOM OF PIPE FROM FINISHED FLOORB/NBETWEENCCOMMONCACOMBUSTION AIRCCCONTROLS CONTRACTORCFMCUBIC FEET PER MINUTE (AIR FLOW RATE)CIPCAST IN PLACECLGCEILING (OR COOLING)CONCCONCRETECONDCONDENSATECONNCONNECT (OR CONNECTION)CONTR'RCONTRACTORCOCLEANOUTCOTGCLEANOUT TO GRADECWDOMESTIC COLD WATERDNDOWN(E)EXISTINGEATENTERING AIR TEMPERATUREECELECTRICAL CONTRACTOREXHEXHAUSTEWTENTERING WATER TEMPERATUREEAEXHAUST AIRPLAN ABBREVIATIONS PIPING DESIGNATIONSHYDRONIC PIPINGCHS CHILLED WATER SUPPLYCHS CHILLED WATER SUPPLYHWS HEATING WATER SUPPLYHWR HEATING WATER RETURNGF GLYCOL FEEDSMS SNOWMELT SUPPLYSMR SNOWMELT RETURNPLUMBING PIPINGG NATURAL GASMG MEDIUM PRESSURE GASD DRAIN PIPEDOMESTIC COLD WATER (CW)DOMESTIC HOT WATER (HW)HOT WATER RECIRCULATION (HWC)FIRE LINEFPW PUMPED WASTEWWASTEVENTVGREASE WASTEGWGREASE VENTGVSTORM DRAINSTSTORM DRAIN OVERFLOWST(OF)SECONDARY DRAINSDSAND AND OIL WASTESOBDDBDDFIXTURE CONNECTION SCHEDULEWCWATER CLOSET (FLUSH VALVE)ABBREV.-HW1"CW4"WASTE2"VENTNOTES:1.2.3.4.5.6.7.8.9.WATER CLOSET (FLUSH TANK)URINAL (BLOWOUT)URINAL (WASHDOWN)URINAL (WATERLESS)LAVATORYHAND SINKSERVICE SINKMOP SERVICE BASINDRINKING FOUNTAIN / E.W.C.KITCHEN SINK W/ OR W/O DISPOSERBATHTUB / SHOWERCLOTHES WASHER ROUGH-INDISH MACHINE ROUGH-INDISHWASHER ROUGH-INBAR SINKFLOOR SINKFLOOR DRAINTROUGH DRAINWORK SINKHOSE BIBWCT - 1/2" 4" 2"UR 1" 2" 1-1/2"UR 3/4" 2" 1-1/2"UR - 2" 1-1/2"LAV 1/2" 1-1/2" 1-1/2"HS 1-1/2" 1-1/2"SS 3" 2"MSB 3/4" 3" 2"DF - 1/2"KS 1/2" 1/2" 2"SH 3/4" 3/4" 2"CW 1/2" 1/2" 2"DMDWBSFSFDTDWSHB---1/2"1/2"1/2"3/4"1/2"1/2"1-1/2" 1-1/2"1-1/2"1-1/2"1-1/2"-1/2"1/2" 1/2"3/4" 3/4" 2" 1-1/2"2" 1-1/2"1-1/2"1-1/2"---------3/4"3/4"3/4"3"3"2"2"2"2"1-1/2"1-1/2"SIZES SHOWN ARE MINIMUM PIPE SIZES TO A SINGLE FIXTURE. LARGER SIZESMAY BE INDICATED ON PLANS WHERE REQUIRED.MINIMUM DOMESTIC PIPE SIZE TO 2 OR MORE FIXTURES IS 3/4".RE: MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR INDIRECT WASTESIZES.WASTE AND VENT SIZES SHOWN ABOVE APPLY TO INDIVIDUAL VENTING ONLY.WHERE ALLOWED, INDIVIDUAL VENT CONNECTIONS MAY BE OMITTED OR SIZESMAY VARY WHEN CIRCUIT VENTS, COMMON VENTS, WASTE STACK VENTS,WET VENTS, OR COMBINATION DRAIN AND VENT SYSTEMS ARE USED. PRIORAPPROVAL FROM THE ENGINEER IS REQUIRED TO USE THESE ALTERNATIVEVENTING METHODS.PROVIDE TRAP PRIMER FOR ALL FLOOR DRAINS AND FLOOR SINKS NOTLOCATED IN FOOD SERVICE AREAS.MINIMUM SIZE FOR WASTE AND VENT PIPING BENEATH SLAB IS 2".ALL FIXTURES LISTED ARE NOT NECESSARILY USED ON THIS PROJECT.REFER TO APPLIANCE SCHEDULES (BY OTHERS) FOR ADDITIONAL PLUMBINGFIXTURE CONNECTIONS SUCH AS INST-HOTS, COFFEE MAKERS, AND GARBAGEDISPOSALS.PROVIDE ICE MAKER BOX ROUGH IN W/ 1/2"CW CONNECTION FOR ALLREFRIGERATOR LOCATIONS.-PLAN SYMBOLSCONTROL PANEL/RADIANT MANIFOLDT---P---SHCOPEPOCO2SPCARBON DIOXIDE SENSORCARBON MONOXIDE SENSORFIRE RISERDIAGRAM CONTINUATION REFERENCEPLUMBING RISERHEATING WATER RISERTHERMOSTATHVAC RISERPOINT OF NEW CONNECTIONDUCT STATIC PRESSURE SENSORROOM PRESSURE SENSORHUMIDISTATREMOTE TEMPERATURE SENSOREMERGENCY POWER OFF SWITCHACCESS PANELSNOWMELT MANIFOLDSECTION CUT LETTER/SHEET SHOWN ONPOINT OF DISCONNECTIONA15012x6XFR12x6TYPE OF AIR DEVICERE: GRD SCHEDULE.AIR DEVICEDESIGNATION KEY# = AIR QUANTITY(CFM)CA = COMB. AIROSA = OUTSIDE AIRRET = RETURNEXH = EXHAUSTXFR = TRANSFERSIZE (INCHES) OR MINIMUMFREE AREA REQUIRED INSQUARE FEETINDICATES AIR INLET DEVICEREFERENCE SAMPLERE: B/M400 FFINOTES1.2.FFI = FOR FURTHER INFORMATIONFCT = FOR CONTINUATIONSHEET NUMBERDRAWING NUMBER ORDIAGRAM LETTERREFER TO:ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS ONLEGEND SHEET ARE NOT NECESSARILY USED ON THISPROJECT.THIS DRAWING SET CONSISTS OF DATA GENERATED, IN PART,BY OTHER PARTIES. NOT ALL SYMBOLOGIES AND NOTATIONCONVENTIONS OCCURRING IN THIS DRAWING SET ARENECESSARILY DEFINED ON THESE LEGENDS. CONSULT THEENGINEER IN THE EVENT SYMBOLOGY OR NOTATIONINTERPRETATION IS REQUIRED.NOTE:FOR STANDARD MODULE SIZEREGISTERS, SIZE GIVEN IS NECK SIZE.REFER TO GRD SCHEDULE FORMODULE SIZE.BFBOFURNISHED BY OWNERFCOFLOOR CLEANOUTFCTFOR CONTINUATIONFFIFOR FURTHER INFORMATIONGCGENERAL CONTRACTORGHXGROUND HEAT EXCHANGERGPMGALLONS PER MINUTE (WATER FLOW RATE)HPHORSE POWERHWDOMESTIC HOT WATERLATLEAVING AIR TEMPERATURELFLINEAR FOOTLWTLEAVING WATER TEMPERATUREMCMECHANICAL CONTRACTORMFGMANUFACTURERMODMOTOR OPERATED DAMPER(N)NEWNCNORMALLY CLOSEDNECNATIONAL ELECTRIC CODENICNOT IN CONTRACTNONORMALLY OPENKWKILOWATTSOAOUTSIDE AIROBDOPPOSED BLADE VOLUME DAMPEROCON CENTEROSAOUTSIDE AIRRARETURN AIRREQ'DREQUIREDREQ'MTSREQUIREMENTSSASUPPLY AIRSFSQUARE FOOT (FEET)SPSTATIC PRESSURESSSTAINLESS STEELTATHROW-AWAY (OR TRANSFER AIR)TYPTYPICALUNOUNLESS NOTED OTHERWISEVTRVENT THROUGH ROOFW/WITHW/OWITHOUTRE:REFER TO:WCOWALL CLEANOUTXFRTRANSFERFSDCOMBINATION FIRE/SMOKE DAMPERFACPFIRE ALARM CONTROL PANELFAFREE AREASH B W HFSPRESSURE REDUCING VALVESHOCK ABSORBERSTRAINER W/ BLOW-OFF VALVEROOF DRAINSAFETY RELIEF VALVEFLOOR DRAINFLOOR SINKHORIZONTAL CLEANOUTVACUUM BREAKERVERTICAL CLEANOUTPRESSURE GAUGE W/ PIG TAIL & COCKTHERMOMETERPRESSURE - TEMP. TAPAIR VENTPIPE ANCHORFLEXIBLE CONNECTORPIPE EXPANSION JOINTPIPE UNIONDOUBLE CHECK BACKFLOW PREVENTERPUMP & EQUIPMENT CONNECTORTEMPERATURE CONTROL VALVE (2-WAY)DRAIN VALVE W/ HOSE ENDPLUG VALVE IN RISERFLOW BALANCING VALVEGATE OR GLOBE VALVE IN RISERFLOW CONTROL VALVEBALL VALVEPLUG OR BALANCING VALVECHECK VALVEGLOBE VALVEBUTTERFLY VALVEVENTURI/FLOW INDICATORTEMPERATURE CONTROL VALVE (3-WAY)SOLENOID VALVE90° ELBOW UPTEE UPTEE DOWNPIPING SYMBOLS90° ELBOW DNSHUT OFF (BALL, GATE, BUTTERFLY)FLOW SWITCHHOSE BIBB or WALL HYDRANTTEMPERATURE CONTROLLER OR SENSORSTEAM TRAP TEST CHAMBERSTEAM TRAP:FT-FLOAT & THERMOSTATICTD-THERMODYNAMICIB-INVERTED BUCKETTS-THERMOSTATICBP-BALANCED PRESSURETCEQUIPMENT ABBREVIATIONSAIR HANDLING UNITAHUAIR SEPARATORASBOILER (HOT WATER)BBASE BOARDBBBUFFER TANKBTCONSTANT VOLUME BOXCVDISHWASHER EXHAUST FANDEFELECTRIC BASEBOARD HEATEREBHFURNACEFFAN COILFCFAN POWERED BOXFPGLYCOL FEEDERGFHUMIDIFIERHC HEATING COILHP HEAT PUMPHX HEAT EXCHANGERKITCHEN EXHAUST FANKEFMAKE-UP AIR UNITMAUMOTOR CONTROL CENTERMCCMIXING VALVEMVPUMP (SEE PIPING LEGEND FOR DETAILS)PRETURN (OR RELIEF) AIR FANRFRADIANT ZONERZSNOWMELT AREASASUMP BASINSBSUPPLY FANSFSTORAGE TANKSTTHERMOSTATIC MIXING VALVETMVUNIT HEATERUHVARIABLE VOLUME BOXVVWATER HEATERWHHCHILLERCHCOOLING COILCCCIRC PUMPCPCABINET UNIT HEATERCUHCOOLING TOWERCTDUCT COILDCELECTRIC WATER HEATEREWHEVAPORATIVE COOLING UNITECUENERGY RECOVERY UNITERUEXHAUST FANEFEXPANSION TANKETVARIABLE VOLUME BOX W/ REHEATVRHWCHOT WATER RECIRCULATIONALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:26 PMM0.0MECHANICALCOVER SHEETST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOMECHANICAL SHEET INDEX#TITLEISSUE LOG 50% DD - 10.11.2016 100% DD - 11.14.2016 50% CD's - 12.20.2016 PERMIT DRAWINGS - 01.12.17 100% CD - 02.15.2017M0.0 MECHANICAL COVER SHEET √ √ √ √ √M0.1 MECHANICAL SCHEDULES √ √ √ √ √M0.2 MECHANICAL SCHEDULES √ √ √ √ √M2.0 SITE MECHANICAL PLAN √ √ √ √M2.1 BASEMENT LEVEL DEMOLITION MECHANICAL PLAN √ √ √ √ √M2.2 MAIN LEVEL DEMOLITION MECHANICAL PLAN √ √ √ √ √M2.3 SANCTUARY LEVEL DEMOLITION MECHANICAL PLAN √ √ √ √ √M2.4 BASEMENT LEVEL MECHANICAL PLAN √ √ √ √ √M2.5 MAIN LEVEL MECHANICAL PLAN √ √ √ √ √M2.6 SANCTUARY LEVEL MECHANICAL PLAN √ √ √ √ √M2.7 CHOIR LOFT & BELFRY LEVEL MECHANICAL PLAN √ √ √ √ √M4.0 MECHANICAL DIAGRAMS √ √ √ √ √M5.0 PIPING DIAGRAMS & CONTROL SCHEMATICS √ √ √ √M5.1 MECHANICAL CONTROLS √ √ √ √P2.2 MAIN LEVEL DEMOLITION PLUMBING PLAN √ √ √ √P2.3 SANCTUARY LEVEL DEMOLITION PLUMBING PLAN √ √ √ √P2.4 BASEMENT LEVEL PIPING PLAN √ √ √ √P2.5 MAIN LEVEL PLUMBING PLAN √ √ √ √ √P2.6 SANCTUARY LEVEL PLUMBING PLAN √ √ √ √P4.0 PLUMBING DIAGRAMS AND ISOMETRIC √ √ √ √ √PROJECT ALTITUDEABOVE SEA LEVEL8,000'GENERAL NOTES:1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.20.21.These drawing notes accompany the published construction document specification book (Project Manual).All work of all trades must be in strict compliance, or exceed the minimum material and method requirements of the 2015 version of the InternationalBuilding, Mechanical, Plumbing, Energy Conservation, and Fire Codes and the 2014 National Electrical Code, most current NFPA, all local ordinances andamendments and manufacturer’s installation recommendations. If a conflict between those publications exists, the most stringent requirement shall apply.Do not scale drawings. Verify dimensions in field prior to commencement of work. Refer to architectural drawings for all dimensions.All subcontractors shall be licensed, experienced, and thoroughly knowledgeable in their respective areas of the construction industry and shall perform in aresponsible manner with established construction sequence, shall recognize the priority of the construction documents, and shall inform the primecontractor of potential problems when the construction documents are unclear or inconsistent.Inasmuch as design for remodel and/or rehabilitation requires that certain assumptions be made regarding [existing] conditions, and because some of theseassumptions cannot be verified without destroying otherwise adequate or serviceable portions of the building, the Engineer cannot assure the Owner or thecontractor that the professional consulting services herein encompass all contingencies. Field coordination during construction is imperative. Makereasonable allowances for unseen conditions.The existing building will be occupied by the Owner during construction. Continued operation of the facility shall not be hindered by this work. Account forall additional costs which may be incurred due to the difficulty of working over and around employees, furniture, equipment, etc.; and due to the hours of theday in which an area may be accessible when compiling his bid.Be responsible to field verify existing equipment or ductwork remaining to be connected to new or existing systems. Provide ductwork, piping, controls,diffusers, etc., as required to restore continuity of system (s), or to make new work meet existing conditions, whether indicated or not.Provide mechanical demolition as required. Refer to architectural demolition drawings for location and extent of demolition required. Visit site prior to bid todetermine extent of work involved. Existing fixtures, mechanical equipment, etc., being removed shall be returned to the Owner. Dispose of all removedpiping, ductwork, etc. unless noted otherwise. Pipes, ductwork, equipment, etc. To be removed, are shown hatched, unless otherwise noted.Verify exact locations of existing underground utilities, piping, and raceway systems prior to trenching. Contractor shall obtain and verify exact utilitycompany drawings and requirements.All ductwork, diffusers, piping, fixtures, and equipment shown in light line weight is existing, new indicated by heavier line weight, except where noted.Pipes, ductwork, equipment, etc. o be removed, are shown hatched.Offset piping, ductwork, etc. As necessary to accommodate structure, beams, and columns, and existing equipment.All existing support rods and straps now supporting ducts, pipes, air tubing, electrical conduit, etc. that are removed to allow room for installation of [new]equipment shall be relocated and reinstalled, or replaced if damaged.All “capped” sanitary and vent lines shall be reconnected or re-routed as necessary to prevent “dead-ends” in the piping. All piping shall drain to activesanitary waste lines and all branches with traps shall be adequately vented.Work shall be performed in a workmanlike manner to the satisfaction of the architect, Owner, and Engineer.Submittals shall include, but not be limited to: equipment, fixtures, insulation, diffusers, pumps, fans, piping, valves, boilers, furnaces, controls, and fireprotection.Provide necessary trenching, backfill, excavation, supports, sawcutting and patching, concrete/paving, etc., as required. Backfill trenches in 6” layers andto 90% compaction and patch to match existing grade.Provide 4” high concrete equipment pads beneath floor mounted mechanical equipment, in addition to any base assemblies required or recommended bythe manufacturer.See architectural reflected ceiling plan for all ceiling penetrations and air device locations.Coordinate architectural, structural, mechanical, fire protection, electrical, landscaping, and interior design drawings prior to installation.Mount all stats at 48” AFF In “accessible” areas, 4’6” AFF In other areas, unless noted otherwise. Coordinate location with wall finish, and to avoidcasework, furniture, door swings, heat sources, and exterior walls. Notify Engineer of any conflicts prior to beginning thermostat installation.Full test and balance required. Refer to specifications, section 230010 FFI.ISSUE LOG KEY:'√ ' ISSUED AS PART OF SET' ' NOT PART OF SET' * ' ISSUED FOR INFORMATION ONLYCity of Aspen Received 5/2/17Building Department
RADIANT MANIFOLD SCHEDULEZONE DESCRIPTIONAREA(SQ. FT.)GPMESTIMATED #OF LOOPSLOOPSPACING @EXT.WALLMAX LOOPPRESSURELOSS(FT H2O)FLOORCOVERINGACCESSORIES REMARKSRZ-1WESTSANCTUARYPERIMETER270 0.5 3 6 0.6 CARPET, TILE - -RZ-2EASTSANCTUARYPERIMETER270 0.5 3 6 0.6 CARPET, TILE - --------- - -MANUFACTURERS: *GENERAL NOTES:A:B:BOILER SCHEDULEMARK SERVICEBOILERTYPEFUELTYPETURNDOWNRATIOHEATING CAPACITYL.W.T.(°F)E.W.T.(°F)BURNERVENTTYPEMANUFACTURER*& MODEL #ACCESSORIES REMARKSINPUT@ S.L.(MBH)OUTPUT@ ALT.MINIMUMA.F.U.E.HPVOLT/PHB-1BLDGHEAT,SNOWMELT,DHWCONDENSINGNATURALGAS5:1 600 456 95 130 11015 ACIRCUIT120/1 IVTRIANGLE TUBEKS-600CONDENSATENEUTRALIZER-- - - - - - - - ----- - - -MANUFACTURERS: * LOCHINVAR, PATTERSON KELLY, VIESSMANN OR BUDERUSGENERAL NOTES:A: EQUIPPED FOR HIGH ALTITUDE OPERATION; 30% P.G. HEATING WATERB:HEAT EXCHANGER SCHEDULEMARK SERVICE TYPE SIDE GPM FLUIDE.W.T.(°F)L.W.T.(°F)MAXPRESSUREDROP (PSI)FOULINGFACTORHEATTRANSFER(MBH)MANUFACTURER* &MODEL #ACCESSORIES REMARKSHX-1 SNOWMELTBRAZEDPLATEHOT 23 30% P.G. 130 110 1.20.0001 217TACOTFP10X20L-20(1-1/2"TMPT)--COLD 16 50% P.G. 70 100 0.6---HOT---- ------COLD---- -MANUFACTURERS: * B&G, PATTERSON-KELLY, TACO, TRANTERGENERAL NOTES:A:B:AIR COOLED CHILLER SCHEDULEMARK TYPEDUTYCAPACITY(TONS)AMBIENTTEMP.DB (°F)L.W.T. (°F)E.W.T.(°F)GPMHEADLOSS(FT.)ELECTRICAL CONDENSING FANEERAPPROX.OPER.WEIGHT(LBS)MANUFACTURER*& MODEL #ACCESSORIES REMARKSMCAVOLT/PHMOCP QTY CFMMAXRPMCH-1 SCROLL 30 95 45 55 65.4 19.8 144 208/3 200 2 22000 1150 9.8 2300MULTI-STACKASP030X--- - - - ----------- - - - -MANUFACTURERS: * TRANE, YORK, TEMPTROL, CARRIERGENERAL NOTES:A: SOUND-ATTENUATION MODULE, INCLUDING: COMPRESSOR BLANKETS, AIRFOIL FAN BLADES, VFD CONDENSER FAN MOTORS.B:PUMP SCHEDULEMARK SERVICE TYPE GPM TDH (FT) FLUIDMOTORMANUFACTURER* & MODEL #ACCESSORIES REMARKSHP(WATT)VOLT/PHP-1BOILERINJECTIONINLINE 58 52 30% P.G. 1-1/2 208/1GRUNDFOSTP 40-240--P-2HEATINGWATERCIRCINLINE 55 25 30% P.G. (442) 208/1GRUNDFOSMAGNA3 40-120INTEGRAL VFD -P-3WATERHEATERCIRCINLINE 28 31 30% P.G. 3/4 120/1GRUNDFOSUPS 32-160/2- SPEED 2P-4DHWRECIRCINLINE 5 8 WATER 1/25 120/1GRUNDFOSUP 15-18 B7--P-5SNOWMELTCIRCINLINE 16 26 50% P.G. 1/2 120/1GRUNDFOSUPS 26-150- SPEED 2P-6CHILLERCIRC PUMPINLINE 65 37 50% P.G. 1-1/4 208/1GRUNDFOSUPS 75-69/2- SPEED 3P-7CHILLEDWATERPUMPINLINE 80 46 50% P.G. (1301) 208/1GRUNDFOSMAGNA3 65-150 FINTEGRAL VFD ------ --- - - -MANUFACTURERS: * B&G, GRUNDFOS, TACO OR AURORA EQUIVALENTGENERAL NOTES:A:MISCELLANEOUS MECHANICAL EQUIPMENT SCHEDULEMARK SERVICE TYPE CAPACITYELECTRICALMANUFACTURER*& MODEL #ACCESSORIES REMARKSHPVOLT/PHGF-1HWS/R,CHS/R,SMS/RGLYCOLFEEDER6 GAL15 ACIRCUIT120/1AXIOMMF-200- 3 QTY TOTALBT-1CHILLEDWATERVERTICALBUFFERTANK80 GAL - - RAYPAK - ---- --- - - -MANUFACTURERS: *GENERAL NOTES:A:WATER HEATER SCHEDULEMARK SERVICE TYPE SIDE GPM FLUIDE.W.T.(°F)L.W.T.(°F)MAXPRESSUREDROP(FT H2O)STORAGECAPACITY(GAL.)TANKDIMENSIONSL x DMANUFACTURER* &MODEL #ACCESSORIES REMARKSWH-1 DHW INDIRECTHOT 28 30% P.G. 145 110 2.5120 72x32TRIANGLE TUBESMART 120--COLD - WATER 40 120 ----HOT---- --- - -COLD---- -MANUFACTURERS: *GENERAL NOTES:A:B:SNOWMELT MANIFOLD SCHEDULEZONE DESCRIPTIONAPPROXAREA(SQ. FT.)GPMESTIMATED #OF LOOPSMAX LOOPPRESSURELOSS(FT H2O)ACCESSORIES REMARKSSZ-1COURTYARDSIDEWALKS385 4.2 3 6.0 - -SZ-2FRONTSIDEWALKS &ENTRY1064 12 7 9.6SLAB TEMP/MOISTURESENSOR------ - - -MANUFACTURERS: *GENERAL NOTES:A: CONFIRM FINAL LOCATION OF SLAB SENSOR WITH ARCHITECT AND ENGINEER PRIOR TO INSTALL.B:PLUMBING FIXTURE SCHEDULESYMBOL TYPE A.D.A. FINISHMANUFACTURER*& MODEL #FAUCET TRIM MFR.* &MODEL #ACCESSORIES REMARKSFLOOR DRAIN -POLISHEDNICKELBRONZEZURNZ415-B- TRAP PRIMER -WALL HYDRANT -POLISHEDBRONZEZURNZ1334-C-INTEGRAL BACKFLOWPREVENTERKEYED OPERATION;AUTOMATIC DRAININGDRINKINGFOUNTAINYES BRONZEELKAYEDFPBV117C-WALL HANGERMPW200;SUPPORT LEGS ML100TWO-LEVEL FOUNTAIN;VANDAL-RESISTANTLAVATORY YESBRUSHEDNICKEL;DUNEKOHLERK-2339DANZEFAIRMONT D304140THERMOSTATICMIXINGVALVE1.2 GPMWATER CLOSET YES DUNEKOHLERK-3817-TOILET SEAT K-4650;BRUSHED NICKELLEVER1.28 GPFURINAL NOCHROME;WHITEKOHLERK-4989-RSLOAN195-0.125 ES-SWALL CARRIERHARD-WIRED AUTO SENSOR;0.125 GPFVESTINGSACRARIUMSINKYESCHROME;STAINLESSSTEELINSTITUTIONAL GROUPCH-2233-A-GR-_DELTA26C3944-A.1.5 GPM AERATORVESTINGSINKYESCHROME;STAINLESSSTEELKOHLERK-3325-HCFDELTA26C3944-UNDERMOUNT SINK;1.5 GPM AERATOR--- - - - -MANUFACTURERS:FIXTURE: AMERICAN STANDARD, UNIVERSAL RUNDLE, FIAT STERN WILLIAMSFAUCET: SPEAKMAN, DELTA, AMERICAN STANDARD, CHICAGODRAIN: JOSAM, WADE SMITHGENERAL NOTES:A:SACRARIUM BOWL DRAINED TO GRADE; REGULAR BOWL DRAINED TO BUILDING WASTE. CUSTOM PUNCH SINK FOR APPROPRIATE FAUCET HOLECONFIGURATION.B:P1P2P3P4P5P6P7P8P9ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:27 PMM0.1MECHANICALSCHEDULESST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOALL STARTERS AND VFD'S FOR MECHANICALEQUIPMENT SHALL BE FURNISHED UNDERTHIS CONTRACT AND SET IN PLACE ANDWIRED BY EC. EACH SHALL BE OF ONEMANUFACTURER OR AVAILABLE THROUGHONE MANUFACTURER TO FACILITATE EASEOF MAINTENANCE.NOT ALL EQUIPMENT REQUIRED UNDERTHIS CONTRACT IS NECESSARILY SPECIFIEDON THE SCHEDULE SHEETS. PLAN &DIAGRAM NOTATIONS AND PROJECT MANUALCONTAIN EQUIPMENT SPECIFICATIONS ASWELL.(ASHRAE 90.1-2004 & 2007)MECHANICAL EQUIPMENT THAT IS NOTCOVERED BY THE U.S. NATIONAL APPLIANCEENERGY CONSERVATION ACT (NAECA) OF1987 SHALL CARRY A PERMANENT LABELINSTALLED BY THE MANUFACTURERSTATING THAT THE EQUIPMENT COMPLIESWITH THE REQUIREMENTS OF STANDARD90.1.(ASHRAE 62.1)ALL AIR MOVING EQUIPMENT SUBJECT TOTHE SCOPE OF ASHRAE 62.1 AND SHALLCOMPLY WITH CONSTRUCTION REQ'MTSTHEREIN.NOT ALL CAPACITIES, CHARACTERISTICS,AND CONSTRUCTION FEATURES REQUIREDARE NECESSARILY INDICATED IN THEEQUIPMENT SCHEDULES. RE: PLANS ANDSPECIFICATIONS FOR ADDITIONAL REQ'MTS.CAPACITIES, CHARACTERISTICS, ANDCONSTRUCTION FEATURES OF THESCHEDULED EQUIPMENT ARE HEREBYINCORPORATED INTO THE PROJECTREQUIREMENTS. EQUIVALENT PRODUCTSPERFORMANCE AND CONSTRUCTIONFEATURES SHALL MEET OR EXCEED THATOF THE SPECIFIED EQUIPMENT WHETHERSCHEDULED OR NOT.NOT ALL EQUIPMENT AVAILABLE FROMLISTED "EQUIVALENT" MANUFACTURERSLISTED IS NECESSARILY EQUIVALENT TOTHE BASIS OF DESIGN EQUIPMENTSPECIFIED. CONTRACTOR SHALL BESOLELY RESPONSIBLE FOR ANY COSTS,RESULTANT CHANGES TO OTHER DIVISIONS,AND SPATIAL REQ'MTS FOR EQUIPMENTOTHER THAN SCHEDULED.1.2.3.4.5.6.7.SCHEDULE NOTES:City of Aspen Received 5/2/17Building Department
GRILLE, REGISTER, DIFFUSER & LOUVERSYMBOL USE PATTERN FINISHMANUFACTURER* & MODEL #ACCESSORIES REMARKSFLOORSUPPLY/RETURNBAR GRILLEANODIZEDALUMINUMTITUSCT-PP-0-- WALL-MOUNTEDSUPPLYLOUVEREDSUPPLYGRILLESTD.WHITETITUS271FL--WALL-MOUNTEDRETURNLOUVEREDRETURNGRILLESTD.WHITETITUS23RL--CEILINGSUPPLY/RETURNLINEAR SLOTBLACKINTERIORTITUSFLMUD-IN FRAME TYPEA., B.RE: PLANS FORSLOT SIZESFLOOR &WALLSUPPLY &RETURNCUSTOMSCROLLGRILLERE: ARCH REGGIO -FREE AREAREQUIRED NOTEDON PLANSEXTERIORLOUVERDRAINABLESTATIONARYSTDRUSKINELF6375DX--MANUFACTURERS:GRD KRUEGER, METALAIRE, TITUSLOUVER GREENHECK, L&D, RUSKINGENERAL NOTES:A: RETURN: JETTHROW. EXTERIOR WALL-ADJACENT SUPPLY: JETTHROW. INTERIOR SUPPLY: HIGHTHROW.B: ACTIVE LENGTH GIVEN ON PLAN. MATCH TOTAL LENGTH (ACTIVE+INACTIVE) TO ARCHITECTURAL FEATURES.ABCDEFAIR HANDLING UNIT SCHEDULEMARKAREASERVEDTYPEMIN.OUTSIDEAIR (CFM)AIR DELIVERY CAPACITY COOLING COILPREHEAT COILSOUND POWER LEVEL (dB re. 10-12 WATT)VOLT/PHASEFILTERAPPROX.OPER.WEIGHT(LBS)MANUFACTURER*& MODEL #ACCESSORIES REMARKSSUPPLY FAN AIR CONDITIONS WATER CONDITIONS COIL AIR CONDITIONS WATER CONDITIONS COILCFME.S.P. @ALT(IN W.C.)MOTOR(HP)E.A.T.DB/WB(°F)L.A.T.DB/WB(°F)TOTALMBHSENSIBLEMBHE.W.T.(°F)L.W.T.(°F)GPMMAX.WTRP.D.(FT.)MAX.AIR P.D.(IN.)E.A.T.DB (°F)L.A.T.DB (°F)SENSIBLEMBHE.W.T.(°F)L.W.T.(°F)GPMMAX.WTRP.D. (FT.)MAX.AIR P.D.(IN.)LOCATION125 HZ250 HZ500 HZ1000HZ2000HZ4000HZ8000HZAHU-1NAVE,SANCTUARY(PERIMETER)VERT 1200 3800 1.14 5 81 /55 55 /46 79 79 45 51 32 25.5 0.51 41 85 133 130 112 16 2.4 0.17INLET 85777474736872208/3FLATMERV 8PLEATED890DAIKINLAH007ARE: GENERAL NOTES -ALL APPLYALL APPLYDISCHARGE86858684827973RADIATED 81 73 71 68 66 60 51AHU-2NAVE,SANCTUARY(INTERIOR)VERT 1200 3800 0.9 5 81 /55 55 /46 79 79 45 51 32 25.5 0.51 41 85 133 130 112 16 2.40.17INLET 84777474726872208/3FLATMERV 8PLEATED890DAIKINLAH007ARE: GENERAL NOTES -ALL APPLYALL APPLYDISCHARGE85848683817972RADIATED 80 72 71 67 65 59 50- - - - - - - - - - - --- - - -- - --- - -INLET-- - - - -DISCHARGERADIATEDMANUFACTURERS: * TRANE, YORK, TEMPTROL, CARRIERGENERAL NOTES:A: DOUBLE WALL CONSTRUCTION WITH FOAM INJECTED INSULATION D: FACTORY-MOUNTED STARTER AND DISCONNECT. G: VIBRATION ISOLATION PER SPECIFICATIONS, RE: SECTION 230548 FFI. J: AHU-1: MFTR RA PLENUM. AHU-2: CUSTOM PLENUM. MOTORIZED DAMPER ON OSA DUCT, BALANCE DAMPER ON RA DUCT.B: HINGED, KEYLESS ACCESSE: 4" HOUSEKEEPING PAD. H: 2-ROW HEATING COIL, 6-ROW COOLING COIL.K:C: PROVIDE CUSTOM MIXING BOX WHERE NECESSARY FOR SPECIFIC DUCT SIZES REQUIRED. F: DRAIN PAN.I: PROVIDE SMOKE DETECTOR IN RA DUCT UPSTREAM OF OSA CONNECTION.L:EXHAUST FAN SCHEDULEMARK TYPEFANSOUND POWER (dB re. 10-12 WATT)MOTORMANUFACTURER* & MODEL #ACCESSORIESVENTILATIONRATECALCULATIONREMARKSCFM SONESESPHP/(WATT)VOLT/PHASE@ S.L.(IN WC)@ ALT(IN WC)63HZ125HZ250HZ500HZ1000HZ2000HZ4000HZ8000HZEF-1 CEILING 220 2.5 0.4 0.3 60 59 54 45 51 38 37 35 (73) 120/1COOKGC-520FAN SPEEDCONTROLLER;STEEL GRILLE3 WC OR UR x70 CFM PER WC-UR =210 CFM MINA., B.EF-2 INLINE 50 0.7 0.34 0.25 45 45 43 45 37 32 25 16 (30) 120/1COOKGN-142FAN SPEED CONROLLER2 PER x 5 CFM/PER +20FT² x 0.06 CFM/FT² =11.2 CFM MINA., B.EF-3 CEILING 120 1.2 0.27 0.2 61 58 48 42 37 32 30 30 (67) 120/1COOKGC-340FAN SPEEDCONTROLLER;STEEL GRILLE5300 FT² x 0.02CFM/FT² =106 CFM MINB.MANUFACTURERS: * ACME, COOK, GREENHECK, PANASONIC, PENNGENERAL NOTES:A: ESP ESTIMATED, MAY DIFFER DUE TO UNKNOWN DUCT ROUTING OR EXTERIOR TERMINATION. PROVIDE BALANCE DAMPER IN ASSOCIATED DUCT TO AID IN ACHIEVING REQUIRED PERFORMANCE POINT.B: VIBRATION ISOLATION PER SPECIFICATIONS, RE: SECTION 230050 FFI.UNIT AND CABINET HEATER SCHEDULE (HYDRONIC)MARK TYPEHEATING COIL ELECTRICALMANUFACTURER*& MODEL #ACCESSORIES REMARKSSENSIBLEMBHWATER CONDITIONS AIR CONDITIONSHP/(WATTS)VOLT/PHE.W.T.(°F)GPMMAX. WTR.P.D. (FT.)E.A.T(°F)L.A.T.(°F)CFMCUH-1 WALL 13.5 130 1.4 10.0 68 98 290 (26) 120/1JAGABZMW 055-145INTEGRALTHERMOSTAT21.7"H x 57.1"L x 5.12"DPROVIDE 36 W MFTR POWERSUPPLYCUH-2 WALL 4.1 130 0.5 1.0 68 98 100 (17) 120/1JAGABZMW 055-075INTEGRALTHERMOSTAT21.7"H x 29.5"L x 5.12"DPROVIDE 36 W MFTR POWERSUPPLYCUH-3KICKSPACE4.5 130 0.5 0.43 68 112 127 (66.8) 120/1BEACON-MORRISK-120A. -CUH-4FLOORRECESS2.0 130 0.5 0.03 68 9885 MAX;65 MIN- 120/1SMITH'SFL-100A., B. --- ---- -- - - -MANUFACTURERS: * BEACON MORRIS, TRANE, MCQUAY, MODINE EQUIVALENTGENERAL NOTES:A: REMOTE WALL-MOUNTED THERMOSTATB: REMOVABLE WALKING-RATED FLOOR GRILLEBASEBOARD RADIATOR SCHEDULEMARKBTUHPER L.F.@ S.L.BTUHPER L.F.@ ALTAVERAGEWATERTEMP. (°F)ENTERINGAIR TEMP.(°F)TUBESIZE(IN.)FINSIZE(IN.)ENCLOSURESIZE (IN.)H x WMANUFACTURER* & MODEL #ACCESSORIES REMARKSBB-1 - 312 120 68 N/A N/A 9" x 2-7/8"RUNTALTHERMOTOUCH-3F------ --- - - - -MANUFACTURERS: * STERLING, VULCAN, RUNTAL, JAGAGENERAL NOTES:A:B:SILENCERS SCHEDULEMARK TYPE SERVICELENGTH(IN)CFMMAXPRESSUREDROP W/OGRILLESINSERTION LOSS (dB re. 20 mPascals)MANUFACTURE& MODEL #ACCESSORIES REMARKS63HZ125HZ250HZ500HZ1000HZ2000HZ4000HZ8000HZS-1STRAIGHTINLINEDISSIPATIVEAHU-1SUPPLY36 3800 0.06 3 5 8 14 14 11 8 5VIBROACOUSTICS24x22 RD-HV-F4x36--S-2 ELBOWINLINEDISSIPATIVEAHU-1RETURN66 3800 0.29 1623343740383024VIBROACOUSTICSEXRED-ULV-FE-14x48 FACEDIMENSIONSS-3ELBOWINLINEDISSIPATIVEAHU-2RETURN36 3800 0.30 1221273341342426VIBROACOUSTICSTRED-HV-FX-16x24 FACEDIMENSIONS- - - - - - -------- - - -MANUFACTURERS: *GENERAL NOTES:A: INSERTION LOSS BASED ON 200 FPM FACE VELOCITY.B:FAN COIL SCHEDULE (HYDRONIC)MARK SERVICE TYPEFAN COOLING COIL HEATING COILFILTERMANUFACTURER* & MODEL #ACCESSORIES REMARKSCFMO.S.A.CFMESP ELECTRICAL AIR CONDITIONS WATER CONDITIONS AIR CONDITIONS WATER CONDITIONS@ S.L.(IN WC)@ ALT(IN WC)HPVOLT/PHE.A.T.DB(°F)L.A.T.DB(°F)TOTALMBHSENSIBLEMBHE.W.T.(°F)L.W.T.(°F)GPMMAX.WTRP.D.(FT.)E.A.T.DB (°F)L.A.T.DB (°F)SENSIBLEMBHE.W.T.(°F)L.W.T.(°F)GPMMAX.WTRP.D.(FT.)FC-1THROUGH5MEETINGROOM101-105CEILINGHUNGHORIZ3200 550 0.8 0.6 1-1/2 208/1 80 55 80 64 45 55 16 5 53 90 94.5 130 110 5 0.5 2" T.A.CARRIER42BHE40-ALL APPLY;BOTTOM-ACCESSFC-2THROUGH6NOT USEDFC-7 OFFICESCEILINGHUNG1700 110 0.8 0.6 1 120/1 79 55 33 29 45 55 6.8 2.2 63 85 30.0 130 110 3.0 0.5 2" T.A.DAIKINHHDB120-ALL APPLY; ZONED;BOTTOM-ACCESSFC-8 ENTRYAIRCURTAIN2752 - N/A N/A (2) 1/2 208/1 N/A 65 100 77 130 110 9 2.4 -BERNERARC12-2072--- - ---- ---- -- - ---- - - - --- - - - - -- - ---- ---- -- - ---- - - - --- - - - - -MANUFACTURERS: * CARRIER, ENVIROTEC, MCQUAY, TRANEGENERAL NOTES:A: FULL ECONOMIZER CONTROLC: DOUBLE-WALL, INSULATED CONSTRUCTION. E.B: VIBRATION ISOLATION PER SPECIFICATIONS, RE: SECTION 230050 FFI. D: TOOL-LESS, HINGED ACCESS.F.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:28 PMM0.2MECHANICALSCHEDULESST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOALL STARTERS AND VFD'S FOR MECHANICALEQUIPMENT SHALL BE FURNISHED UNDERTHIS CONTRACT AND SET IN PLACE ANDWIRED BY EC. EACH SHALL BE OF ONEMANUFACTURER OR AVAILABLE THROUGHONE MANUFACTURER TO FACILITATE EASEOF MAINTENANCE.NOT ALL EQUIPMENT REQUIRED UNDERTHIS CONTRACT IS NECESSARILY SPECIFIEDON THE SCHEDULE SHEETS. PLAN &DIAGRAM NOTATIONS AND PROJECT MANUALCONTAIN EQUIPMENT SPECIFICATIONS ASWELL.(ASHRAE 90.1-2004 & 2007)MECHANICAL EQUIPMENT THAT IS NOTCOVERED BY THE U.S. NATIONAL APPLIANCEENERGY CONSERVATION ACT (NAECA) OF1987 SHALL CARRY A PERMANENT LABELINSTALLED BY THE MANUFACTURERSTATING THAT THE EQUIPMENT COMPLIESWITH THE REQUIREMENTS OF STANDARD90.1.(ASHRAE 62.1)ALL AIR MOVING EQUIPMENT SUBJECT TOTHE SCOPE OF ASHRAE 62.1 AND SHALLCOMPLY WITH CONSTRUCTION REQ'MTSTHEREIN.NOT ALL CAPACITIES, CHARACTERISTICS,AND CONSTRUCTION FEATURES REQUIREDARE NECESSARILY INDICATED IN THEEQUIPMENT SCHEDULES. RE: PLANS ANDSPECIFICATIONS FOR ADDITIONAL REQ'MTS.CAPACITIES, CHARACTERISTICS, ANDCONSTRUCTION FEATURES OF THESCHEDULED EQUIPMENT ARE HEREBYINCORPORATED INTO THE PROJECTREQUIREMENTS. EQUIVALENT PRODUCTSPERFORMANCE AND CONSTRUCTIONFEATURES SHALL MEET OR EXCEED THATOF THE SPECIFIED EQUIPMENT WHETHERSCHEDULED OR NOT.NOT ALL EQUIPMENT AVAILABLE FROMLISTED "EQUIVALENT" MANUFACTURERSLISTED IS NECESSARILY EQUIVALENT TOTHE BASIS OF DESIGN EQUIPMENTSPECIFIED. CONTRACTOR SHALL BESOLELY RESPONSIBLE FOR ANY COSTS,RESULTANT CHANGES TO OTHER DIVISIONS,AND SPATIAL REQ'MTS FOR EQUIPMENTOTHER THAN SCHEDULED.1.2.3.4.5.6.7.SCHEDULE NOTES:33City of Aspen Received 5/2/17Building Department
(E) 3" W EXIT PROVIDE PRICINGFOR DEMO OF 3" W MAIN FROMBLDG TO UTILITY MAIN.CHILLER LOCATED ADJACENT TO(N) TRASH ENCLOSURE IN (N)CHILLER ENCLOSURE. PROVIDEALL MFTR REQD CLEARANCES.CHS/R TO BASEMENT MECHROOM, RE: P2.4 FCT.RE:M5.0 FFI.(N) COMBINED BOILER VENTTHROUGH (E) CHIMNEY, FASNSEALFLEX TYPE OR EQUIVALENT,ESTIMATED 14"ø MAX, TO BEFINALIZED WITH VENDORENGINEERED BREECHING DESIGN.(E) BOILER COMBUSTIONAIR INTAKE AREA WELL.TO REMAIN.(N) OSA INTAKE AREAWELL.SM ZONE 2SM ZONE 1SZ-2 MANIFOLD INLANDSCAPE BOX.(E) PAVEMENT AND TUBINGTO BE REUSED IF POSSIBLE.RE: ARCH FFI.AT DISCONNECT POINT, SAW-CUT PAVING, CUT ANDSPLICE (E) TUBING TO CREATE SHORTER LOOPS.(E) SM AREA SOUTH OF DISCONNECTION POINT TOBE DRAINED AND ABANDONED IN PLACE.CH-1(E) SZ-1 MANIFOLD BASEMENT, TO BEREPLACED WITH (N) MANIFOLD PIPING ANDVALVES, RE-CONNECTED TO (E) LOOPS.EXTENTS OF (E) SNOWMELT,ABONDONED IN PLACE.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:28 PMM2.0SITEMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 1/8" = 1'-0"SITE MECHANICAL PLANCity of Aspen Received 5/2/17Building Department
ACEBD123456789ELEV EQUIP002STORAGESTORAGEBOILERROOMCRAWLSPACECRAWLSPACEELEV LOBBY001CRAWLSPACE(E) DX FAN COIL UNIT SERVINGOFFICES. DEMO UNIT AND ALLDUCTWORK.(E) WATER ENTRYTO REMAIN.(E) COMBUSTION AIR DUCTED TOBOILER ROOM, TERMINATING ~10"ABOVE FLOOR.(E) EXPANSION TANK.(E) BOILERSDEMO (E) SNOWMELTHX AND PUMPS.DEMO (E) RADIANTBASEBOARD ZONE VALVEBANKS.ESTIMATED (E)RADIANT ZONE.(E) EXPOSEDRADIANT FLOORPIPING MANIFOLDS.(E) (E) RADIANT BASEBOARDZONE VALVE BANKS.(E) WATER HEATER.(E) SM MANIFOLDS IN BASEMENT. FIELD-VERIFY WHICHMANIFOLDS SERVE WHICH AREAS OF (E) SNOWMELT.MEASURE CURRENT FLOW AND PD PRIOR TOCONSTRUCTION START. DRAIN AND CAP LOOPS ATMANIFOLD FOR LATER CONNECTION TO (N) MANIFOLD.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:31 PMM2.1BASEMENTLEVELDEMOLITIONMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"BASEMENT LEVEL DEMOLITION MECHANICALPLANADDITIONAL STORM, HYDRONIC,DOMESTIC, WASTE AND VENT PIPING MAYBE ROUTED IN SPACE THAT IS NOTREPRESENTED, BUT IS TO REMAIN.OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ONTHESE DRAWINGS; MODIFICATIONS TOTHESE SYSTEMS ARE NOT ANTICIPATED.FIELD VERIFY ALL COMPONENTS PRIORTO DEMOLITION. THE INFORMATION ONTHIS SHEET WAS OBTAINED, IN PART,FROM HISTORIC DESIGN DRAWINGS. ONLYPORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATIONDURING DESIGN PROCESS.PROVIDE PRELIMINARY TESTING OFEXISTING HYDRONIC SYSTEMS. MEASURECURRENT FLUID FLOW RATE THROUGHALL EXISTING COILS, RADIANT, ANDSNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OFMEASURED VALUES TO ENGINEER FORREVIEW AND CONFIRMATION OF SYSTEMDESIGN ASSUMPTIONS PRIOR TODEMOLITION.(E) WASTE SYSTEM SERVING SPACE ISLOCATED IN THE CEILING OF THE SPACEBELOW.REMOVE ALL MECHANICAL ITEMSINDICATED.TEMPORARILY SEAL OR CAP PIPING TO BERE-USED FOR LATER CONNECTION.SEAL ALL OPEN DUCTS DURINGCONSTRUCTION TO MITIGATE DUST ANDDEBRIS FROM SYSTEM. CAP DUCTWORKIN LOCATIONS THAT ARE NOT BEINGRECONNECTED.REMOVE ALL DEMOLISHED COLD WATER,HOT WATER AND HOT WATERRECIRCULATION PIPING BACK TO BRANCHFROM MAIN TO ELIMINATE ALL DEADENDS IN DOMESTIC WATER PIPING.NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATIONREPRESENTED IN THE DOCUMENTSVERSUS WHAT IS FOUND IN THE FIELD.COORDINATE PATCHING AND REPAIRS OFWALLS, CEILINGS AND FLOORS WITHARCHITECT.PATCH STRUCTURAL OPENINGS INFLOORS, WALLS AND ROOFS THAT WEREPREVIOUSLY OCCUPIED BY SYSTEMSAND EQUIPMENT DEMOLISHED UNDERTHIS CONTRACT IN ACCORDANCE WITHSTRUCTURAL ENGINEER'SREQUIREMENTS.1.2.3.4.5.6.7.8.9.10.11.DEMOLITION NOTES:City of Aspen Received 5/2/17Building Department
ACEBD123456789KITCHEN109ENTRY100MEETING RM102MEETING RM103MEETING RM104MEETING RM105HALLWAY111VEST.120MEETING RM101OFFICE122MEETING RM107ALL (E) BASEBOARDS,DIFFUSERS, EXHAUSTFANS, ETC. TO BEREMOVED, THIS AREA.(E) HOOD EXH.FAN.(E) BATH EXH FANS TOBE REMOVED. RETAINDUCT ROUTING FORFUTURE CONNECTION.(E) OSA INTAKE GRATEAT GRADE TO REMAIN.(E) HYDRONICBASEBOARD, TYP.(E) KITCHEN MAU SYSTEM TOREMAIN. PRIOR TO COMMENCINGANY CONSTRUCTION, MEASURE(E) HWS/R TEMP, FLOW AND PD AT(E) KITCHEN MAU, AND REPORTTO ENGINEER FOR REVIEW.ALL (E) KITCHEN EQUIPMENTAND APPLIANCES TO REMAIN.ESTIMATED (E)RADIANT ZONETO REMAIN.(E) CONDENSING UNIT.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:35 PMM2.2MAIN LEVELDEMOLITIONMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"MAIN LEVEL DEMOLITION MECHANICAL PLANADDITIONAL STORM, HYDRONIC,DOMESTIC, WASTE AND VENT PIPING MAYBE ROUTED IN SPACE THAT IS NOTREPRESENTED, BUT IS TO REMAIN.OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ONTHESE DRAWINGS; MODIFICATIONS TOTHESE SYSTEMS ARE NOT ANTICIPATED.FIELD VERIFY ALL COMPONENTS PRIORTO DEMOLITION. THE INFORMATION ONTHIS SHEET WAS OBTAINED, IN PART,FROM HISTORIC DESIGN DRAWINGS. ONLYPORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATIONDURING DESIGN PROCESS.PROVIDE PRELIMINARY TESTING OFEXISTING HYDRONIC SYSTEMS. MEASURECURRENT FLUID FLOW RATE THROUGHALL EXISTING COILS, RADIANT, ANDSNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OFMEASURED VALUES TO ENGINEER FORREVIEW AND CONFIRMATION OF SYSTEMDESIGN ASSUMPTIONS PRIOR TODEMOLITION.(E) WASTE SYSTEM SERVING SPACE ISLOCATED IN THE CEILING OF THE SPACEBELOW.REMOVE ALL MECHANICAL ITEMSINDICATED.TEMPORARILY SEAL OR CAP PIPING TO BERE-USED FOR LATER CONNECTION.SEAL ALL OPEN DUCTS DURINGCONSTRUCTION TO MITIGATE DUST ANDDEBRIS FROM SYSTEM. CAP DUCTWORKIN LOCATIONS THAT ARE NOT BEINGRECONNECTED.REMOVE ALL DEMOLISHED COLD WATER,HOT WATER AND HOT WATERRECIRCULATION PIPING BACK TO BRANCHFROM MAIN TO ELIMINATE ALL DEADENDS IN DOMESTIC WATER PIPING.NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATIONREPRESENTED IN THE DOCUMENTSVERSUS WHAT IS FOUND IN THE FIELD.COORDINATE PATCHING AND REPAIRS OFWALLS, CEILINGS AND FLOORS WITHARCHITECT.PATCH STRUCTURAL OPENINGS INFLOORS, WALLS AND ROOFS THAT WEREPREVIOUSLY OCCUPIED BY SYSTEMSAND EQUIPMENT DEMOLISHED UNDERTHIS CONTRACT IN ACCORDANCE WITHSTRUCTURAL ENGINEER'SREQUIREMENTS.1.2.3.4.5.6.7.8.9.10.11.DEMOLITION NOTES:City of Aspen Received 5/2/17Building Department
ACEBD123456789STAIR201STOR202STAIR203NARTHEX204VEST205NAVE206SANCTUARY207VESTING /SACRISTY208ALTARSERVERVESTING209(E) BASEBOARDTO BE REMOVED.(E) RADIANT ZONE TO REMAINPENDING CONFIRMATION OFOXYGEN BARRIER-EQUIPPEDTUBING.(E) NAVE RADIANT ZONE TO BE DRAINEDAND ABONDONED IN PLACE IN ROOMCENTER, AND REMOVED AT PERIMETERWHERE (N) RADIANT ZONES ARE TO BEINSTALLED. RE: ARCH. FFI.(E) RADIANT MANIFOLD ANDACCESS DOOR.(E) RADIATOR TOBE REMOVED.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:38 PMM2.3SANCTUARYLEVELDEMOLITIONMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"SANCTUARY LEVEL DEMOLITION MECHANICALPLANADDITIONAL STORM, HYDRONIC,DOMESTIC, WASTE AND VENT PIPING MAYBE ROUTED IN SPACE THAT IS NOTREPRESENTED, BUT IS TO REMAIN.OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ONTHESE DRAWINGS; MODIFICATIONS TOTHESE SYSTEMS ARE NOT ANTICIPATED.FIELD VERIFY ALL COMPONENTS PRIORTO DEMOLITION. THE INFORMATION ONTHIS SHEET WAS OBTAINED, IN PART,FROM HISTORIC DESIGN DRAWINGS. ONLYPORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATIONDURING DESIGN PROCESS.PROVIDE PRELIMINARY TESTING OFEXISTING HYDRONIC SYSTEMS. MEASURECURRENT FLUID FLOW RATE THROUGHALL EXISTING COILS, RADIANT, ANDSNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OFMEASURED VALUES TO ENGINEER FORREVIEW AND CONFIRMATION OF SYSTEMDESIGN ASSUMPTIONS PRIOR TODEMOLITION.(E) WASTE SYSTEM SERVING SPACE ISLOCATED IN THE CEILING OF THE SPACEBELOW.REMOVE ALL MECHANICAL ITEMSINDICATED.TEMPORARILY SEAL OR CAP PIPING TO BERE-USED FOR LATER CONNECTION.SEAL ALL OPEN DUCTS DURINGCONSTRUCTION TO MITIGATE DUST ANDDEBRIS FROM SYSTEM. CAP DUCTWORKIN LOCATIONS THAT ARE NOT BEINGRECONNECTED.REMOVE ALL DEMOLISHED COLD WATER,HOT WATER AND HOT WATERRECIRCULATION PIPING BACK TO BRANCHFROM MAIN TO ELIMINATE ALL DEADENDS IN DOMESTIC WATER PIPING.NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATIONREPRESENTED IN THE DOCUMENTSVERSUS WHAT IS FOUND IN THE FIELD.COORDINATE PATCHING AND REPAIRS OFWALLS, CEILINGS AND FLOORS WITHARCHITECT.PATCH STRUCTURAL OPENINGS INFLOORS, WALLS AND ROOFS THAT WEREPREVIOUSLY OCCUPIED BY SYSTEMSAND EQUIPMENT DEMOLISHED UNDERTHIS CONTRACT IN ACCORDANCE WITHSTRUCTURAL ENGINEER'SREQUIREMENTS.1.2.3.4.5.6.7.8.9.10.11.DEMOLITION NOTES:City of Aspen Received 5/2/17Building Department
ELEV EQUIP002ACEBD123456789ELEV LOBBY001STORAGESTORAGEBOILERROOMCRAWLSPACECRAWLSPACECRAWLSPACEB -1B -1WH-1SPACE FORHWS/RPUMPS. GF,ET, HX, ETC.SA & RA PLENUM BOX TOFLOOR GRILLE ABOVE,TYP.FAN COIL UNIT, CEILING-HUNGORCRAWLSPACE -FLOOR MOUNTED,PENDING FEASIBLITY OF CRAWLSPACEIMPROVEMENTS TO ACCOMODATE,TYP.6"TYP.6"ø TYP.6"ø TYP.8"ø TYP.8"ø TYP.OSA INTAKE IN (N) AREA WELL.12x1222x12 SA12x10 SA12x10 SA12x1012x10 SASPACE FORCHW PUMPS.GF, ET, ETC.FIELD COORDINATE DUCT ANDPIPE ROUTING WITH ELECTRICALTO AVOID ROUTING ABOVEELECTRICAL PANELS.BT -1x920F32 324900BREACHED BOILER FLUE, SLOPED TODRAIN SECTION IN MECH. RM. PROVIDEENGINEERED SHOP DRAWINGS OF FLUEDESIGN FROM VENDOR.FLEXIBLE BOILER FLUE MATERIAL,FASNSEAL FLEX OR EQUIVALENT,THROUGH (E) CHIMNEY.(E) BOILER COMBUSTION AIRPATH AND DUCT TO REMAIN.(E) CRAWLSPACE VENILATIONTO REMAIN, TYP.6"ø TYP.12x1012x1012x1020x1226x1426x1226x1226x14FC -126x1810"ø TYP.414x1632x1820x1232x188"ø TYP.8"ø TYP.22222222222222222ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:49 PMM2.4BASEMENTLEVELMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADORE: M4.0 FOR ALL APPLICABLE DIAGRAMS.COORDINATE ROUTING OF CONDENSATEDRAIN LINES WITH ARCHITECT PRIOR TOINSTALLATION.CEILING COORDINATION OF ALL MEPSYSTEMS (LIGHTING, DUCTWORK,DIFFUSERS, ELECTRICAL, FIREPROTECTION, ETC.) MUST BE COMPLETEDBY THE CONTRACTOR PRIOR TO THESTART OF ANY INSTALLATIONS.AVOID ROUTING DUCTWORK OVERELECTRICAL ROOMS OR ELECTRICALPANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITH ELECTRICALCONTRACTOR.PROVIDE FLEXIBLE DUCT AND PIPECONNECTIONS TO ALL MOTORIZEDEQUIPMENT.VERIFY ALL EQUIPMENT ACCESS PANELSWITH MANUFACTURER AND ARCHITECT.ALL SOURCES OF IGNITION ON MECHANICALEQUIPMENT SHALL BE MOUNTED 18" AFF.PROTECT PIPING ROUTED ALONGCOLUMNS, WALLS, ETC. FROM DAMAGE ASNECESSARY WITH CAGES. COORDINATEWITH ARCHITECT.ALL RETURN AIR GRILLES SHALL BEPROVIDED WITH SOUND BOOT WITH 1"LINER.T-STATS SHALL BE LOCATED NEAR THELIGHT SWITCH WITHIN THE ROOM SHOWN.COORDINATE WITH ARCHITECT &ELECTRICAL ENGINEER TO MATCH HEIGHTAND LOCATION.ALL DUCTWORK SHALL BE ROUTED AS HIGHAS POSSIBLE IN THE CEILING SPACE.UTILIZE JOIST SPACE WHEN POSSIBLE,ESPECIALLY WHERE CROSSING OTHERDUCTS, PIPES, AND ELECTRICAL.ALL RA & SA RECTANGULAR DUCT TOINCLUDE 1" INTERNAL LINER, UNO. OSA ANDEXH DUCT SHALL BE UNLINED.CONNECT ALL SA AND RA DEVICES WITHINACOUSTIC FLEX DUCT, 5' MIN. & 8' MAXLENGTH.UTILIZE REMOTE BALANCE DAMPERS ILOOBD OR BALANCE DAMPERS AT GRILLE.FLEX DUCT TO BE LOCATED BETWEENDEVICE AND BALACE DAMPER, AS SHOWN.1.2.3.4.5.6.7.8.9.10.11.12.13.14.HVAC NOTES:SCALE: 3/16" = 1'-0"BASEMENT LEVEL MECHANICAL PLANFLAG NOTES:1WHERE BALANCE DAMPER IS LOCATED INCRAWLSPACE, PROVIDE WITH REMOTECABLE - OPERATION ACCESIBLE FROMASSOCIATED AIR DEVICE FACE IN MEETINGROOM ABOVE.City of Aspen Received 5/2/17Building DepartmentIndicateheadroomheights underductwork inbasement andmain level onthe plans.
ACEBD123456789KITCHEN109ENTRY100MEETING RM102MEETING RM103MEETING RM104MEETING RM105HALLWAY111MEETING RM101OFFICE122MEETING RM1070.7 SFFASUPPLY & RETUENFLOOR GRILLES, TYP.222222222222222221.08 SFFA1.29 SFFA1.1 SFFA320ETYP. 4WOMEN110OFFICE113MEN116HALL115OFFICE114OFFICE119RECEPT118VEST.120CONF RM1121FC -7EF -1EF -1x150B66FC -86ø3312x1016x1216x1222x1412x10x400C14 610ø10øx380B12 610ø10øx380B12 6x380B12 610ø12ø10ø10øx400B14 6x380B12 6x380B12 6x360B12 624x144444380ETYP. 5430ETYP. 3380ETYP. 536x12CUH -1CUH -2CUH -3CUH -2CUH -3CUH -3CUH -4CUH -4CUH -4CUH -4CUH -4CUH -4CUH -4CUH -4CUH -1TTTTTTTTTTTTTTTTTTTTTTTTTT11111118ø8øFIELD COORDINATE DUCTROUTING WITH ELECTRICAL TOAVOID ROUTING ABOVEELECTRICAL PANELS.TT1TT11518x12BDDBAROMETRIC DAMPERFC-7 MASTER CONTROLLERLOCATED IN RECEPTION AREA,COORDINATE EXACT PLACEMENTWITH OWNER AND ARCHITECT.STOR121CUH -433333ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:47:57 PMM2.5MAIN LEVELMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"MAIN LEVEL MECHANICAL PLANRE: M4.0 FOR ALL APPLICABLE DIAGRAMS.COORDINATE ROUTING OF CONDENSATEDRAIN LINES WITH ARCHITECT PRIOR TOINSTALLATION.CEILING COORDINATION OF ALL MEPSYSTEMS (LIGHTING, DUCTWORK,DIFFUSERS, ELECTRICAL, FIREPROTECTION, ETC.) MUST BE COMPLETEDBY THE CONTRACTOR PRIOR TO THESTART OF ANY INSTALLATIONS.AVOID ROUTING DUCTWORK OVERELECTRICAL ROOMS OR ELECTRICALPANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITH ELECTRICALCONTRACTOR.PROVIDE FLEXIBLE DUCT AND PIPECONNECTIONS TO ALL MOTORIZEDEQUIPMENT.VERIFY ALL EQUIPMENT ACCESS PANELSWITH MANUFACTURER AND ARCHITECT.ALL SOURCES OF IGNITION ON MECHANICALEQUIPMENT SHALL BE MOUNTED 18" AFF.PROTECT PIPING ROUTED ALONGCOLUMNS, WALLS, ETC. FROM DAMAGE ASNECESSARY WITH CAGES. COORDINATEWITH ARCHITECT.ALL RETURN AIR GRILLES SHALL BEPROVIDED WITH SOUND BOOT WITH 1"LINER.T-STATS SHALL BE LOCATED NEAR THELIGHT SWITCH WITHIN THE ROOM SHOWN.COORDINATE WITH ARCHITECT &ELECTRICAL ENGINEER TO MATCH HEIGHTAND LOCATION.ALL DUCTWORK SHALL BE ROUTED AS HIGHAS POSSIBLE IN THE CEILING SPACE.UTILIZE JOIST SPACE WHEN POSSIBLE,ESPECIALLY WHERE CROSSING OTHERDUCTS, PIPES, AND ELECTRICAL.ALL RA & SA RECTANGULAR DUCT TOINCLUDE 1" INTERNAL LINER, UNO. OSA ANDEXH DUCT SHALL BE UNLINED.CONNECT ALL SA AND RA DEVICES WITHINACOUSTIC FLEX DUCT, 5' MIN. & 8' MAXLENGTH.UTILIZE REMOTE BALANCE DAMPERS ILOOBD OR BALANCE DAMPERS AT GRILLE.FLEX DUCT TO BE LOCATED BETWEENDEVICE AND BALACE DAMPER, AS SHOWN.1.2.3.4.5.6.7.8.9.10.11.12.13.14.HVAC NOTES:FLAG NOTES:WALL-MOUNTED THERMOSTATADJACENT TO LIGHT SWITCH,COORDINATE EXACT LOCATION ANDAPPEARANCE WITH ARCHITECT.CUSTOM DECORATIVE GRILLE, EITHER(1) CONTINUOUS WITH MULTIPLE DUCTCONNECTIONS, OR MULTIPLEMATCHING CONNECTION QTY. BELOW.TBD IN ARCH. COORD.CONNECT (N) EF-1 TO (E) EXHAUSTDUCT, WITH BDD.DUCT ROUTED IN JOIST SPACE TODIFFUSER.PROVIDE CLEAR LOCKBOX COVER.12345City of Aspen Received 5/2/17Building Department
1ACEBD123456789STAIR201STOR202STAIR203NARTHEX204VEST205NAVE206SANCTUARY207VESTING /SACRISTY208ALTARSERVERVESTING2091SA RISER FROM AHU-2,DN IN CHASE.SA DIFFUSERS INTEGRATED INSANCTUARY RISERS, TYP. 6.LINEAR SLOT CEILING SUPPLYDIFFUSERS, TYP., INTEGRATEDWITH ARCHITECTURAL CEILING.OPTION: PERIMETER RADIANTFLOOR HEATING ZONES.OPTION: PERIMETERRADIANT FLOORHEATING ZONES.9.0 SFFA3800E32x14 RA RISER FROMAHU-1, DN IN CHASE.TRNSITION TO 48x14 INCHASE PRIOR TO GRILLECONNECTION.RM-1RM-21900ETYP. 24.5 SFFABB -1BB -1RZ-1RZ-2x475D96 1TYP. 4x325D96 1TYP. 48ø18x1010"ø,TYP 8.10"ø,TYP 8.24x1224x1820x1822x20AHU -224x1224x228ø8ø8ø8ø8ø26x2422x14CUH -1CUH -120x1620x1622x18 RA IN CHASE.24x26 RA DN IN CHASE.x50D12 14"ø EXH UP INSTUD SPACE.S -1S-1 (IN SA DUCT)S-2 SILENCER INVERTICAL RA DUCT INCHASE.S-3 SILENCER INVERTICAL RA DUCT INCHASE.20x18BOTTOM OF RA GRILLEFLUSH WITH FLOOR, TYP. 2RA DUCT UNDER STAGE TOBE UNLINED.18x10SS200ETYP. 60.58 SFFATT10x810x88"ø,TYP 7.8"ø,TYP 7.SA DUCTS CONNECTEDTO 24x12 SA TRUNKUNDER STAGE.S2M2.63M2.7ø8ø8x325D96 1TYP. 4x475D96 1TYP. 4RE: 2/M2.7 FCT.20x18HEF -36øATTIC VENTILATION FAN MOUNTEDAT LOCATION ACCESSIBLE FROMATTIC WALKWAYHUMIDISTAT MOUNTED TOTRUSS AT LOCATIONACCESSIBLE FROM ATTIC WALKWAY, WITHIN SOUTH THIRD OFATTIC AREA TO AVOIDNORTHERN AREA SUSCEPTIBLETO OUTDOOR CONDITIONS ATBELFRY.3AHU -2S -3CUSTOM RETURN AIR PLENUMBY CONTRACTOR. MATCH RA& OSA DUCT CONNECTIONSIZES AS NECESSARY.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:11 PMM2.6SANCTUARYLEVELMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"1SANCTUARY LEVEL MECHANICAL PLANRE: M4.0 FOR ALL APPLICABLE DIAGRAMS.COORDINATE ROUTING OF CONDENSATEDRAIN LINES WITH ARCHITECT PRIOR TOINSTALLATION.CEILING COORDINATION OF ALL MEPSYSTEMS (LIGHTING, DUCTWORK,DIFFUSERS, ELECTRICAL, FIREPROTECTION, ETC.) MUST BE COMPLETEDBY THE CONTRACTOR PRIOR TO THESTART OF ANY INSTALLATIONS.AVOID ROUTING DUCTWORK OVERELECTRICAL ROOMS OR ELECTRICALPANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITH ELECTRICALCONTRACTOR.PROVIDE FLEXIBLE DUCT AND PIPECONNECTIONS TO ALL MOTORIZEDEQUIPMENT.VERIFY ALL EQUIPMENT ACCESS PANELSWITH MANUFACTURER AND ARCHITECT.ALL SOURCES OF IGNITION ON MECHANICALEQUIPMENT SHALL BE MOUNTED 18" AFF.PROTECT PIPING ROUTED ALONGCOLUMNS, WALLS, ETC. FROM DAMAGE ASNECESSARY WITH CAGES. COORDINATEWITH ARCHITECT.ALL RETURN AIR GRILLES SHALL BEPROVIDED WITH SOUND BOOT WITH 1"LINER.T-STATS SHALL BE LOCATED NEAR THELIGHT SWITCH WITHIN THE ROOM SHOWN.COORDINATE WITH ARCHITECT &ELECTRICAL ENGINEER TO MATCH HEIGHTAND LOCATION.ALL DUCTWORK SHALL BE ROUTED AS HIGHAS POSSIBLE IN THE CEILING SPACE.UTILIZE JOIST SPACE WHEN POSSIBLE,ESPECIALLY WHERE CROSSING OTHERDUCTS, PIPES, AND ELECTRICAL.ALL RA & SA RECTANGULAR DUCT TOINCLUDE 1" INTERNAL LINER, UNO. OSA ANDEXH DUCT SHALL BE UNLINED.CONNECT ALL SA AND RA DEVICES WITHINACOUSTIC FLEX DUCT, 5' MIN. & 8' MAXLENGTH.UTILIZE REMOTE BALANCE DAMPERS ILOOBD OR BALANCE DAMPERS AT GRILLE.FLEX DUCT TO BE LOCATED BETWEENDEVICE AND BALACE DAMPER, AS SHOWN.1.2.3.4.5.6.7.8.9.10.11.12.13.14.HVAC NOTES:FLAG NOTES:1ACOUSTIC IMPACTS OF CUSTOMGRILLE TO BE EVALUATED, EXACT SIZE,AND CONFIGURATION TBD.PROVIDE 20X30 ACCESS HATCHADJACENT TO AHU, LOCATED SO AS TOMAINTAIN 30X30 WORKING SERVICESPACE AT SERVICE SIDE OF AHU, PER2015 IMC RQTS. RE: ARCH FFI.SCALE: NONE2AHU-2 ELEVATION123223City of Aspen Received 5/2/17Building Department
DNACEBD89RA DUCT INARCH CHASE.EF -24"ø EXH UP.EF-2 IN ATTIC SPACEABOVE STAIRS.4"ø EXH DN.AHU -122x16OSA INTAKE ROUTED TOBELFRY LOUVERS, RE:M2.7 FCT.S -13M2.7CBD89EXH 5025005.75 SFFABUILD SHEET METAL PLENUMBOX ON BACK OF (E)HISTORICAL WOOD LOUVER.SIZE ASSUMING 50% NFA OF(E) LOUVER.BUILD SHEET METAL PLENUMBOX ON BACK OF (E)HISTORICAL WOOD LOUVER.SIZE ASSUMING 50% NFA OF(E) LOUVER.20x16RELIEFMOTORIZED RELIEFDAMPER IN VERTICALOF 20x16 DUCT.2400E5.7 SFFA0.3 SFFA5.75 SFFAEXH 500.3 SFFA3ROUTE DUCT INSPACE BETWEENFRAMING MEMBERS.S -2AHU -1S -1ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:17 PMM2.7CHOIR LOFT &BELFRY LEVELMECHANICALPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADORE: M4.0 FOR ALL APPLICABLE DIAGRAMS.COORDINATE ROUTING OF CONDENSATEDRAIN LINES WITH ARCHITECT PRIOR TOINSTALLATION.CEILING COORDINATION OF ALL MEPSYSTEMS (LIGHTING, DUCTWORK,DIFFUSERS, ELECTRICAL, FIREPROTECTION, ETC.) MUST BE COMPLETEDBY THE CONTRACTOR PRIOR TO THESTART OF ANY INSTALLATIONS.AVOID ROUTING DUCTWORK OVERELECTRICAL ROOMS OR ELECTRICALPANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITH ELECTRICALCONTRACTOR.PROVIDE FLEXIBLE DUCT AND PIPECONNECTIONS TO ALL MOTORIZEDEQUIPMENT.VERIFY ALL EQUIPMENT ACCESS PANELSWITH MANUFACTURER AND ARCHITECT.ALL SOURCES OF IGNITION ON MECHANICALEQUIPMENT SHALL BE MOUNTED 18" AFF.PROTECT PIPING ROUTED ALONGCOLUMNS, WALLS, ETC. FROM DAMAGE ASNECESSARY WITH CAGES. COORDINATEWITH ARCHITECT.ALL RETURN AIR GRILLES SHALL BEPROVIDED WITH SOUND BOOT WITH 1"LINER.T-STATS SHALL BE LOCATED NEAR THELIGHT SWITCH WITHIN THE ROOM SHOWN.COORDINATE WITH ARCHITECT &ELECTRICAL ENGINEER TO MATCH HEIGHTAND LOCATION.ALL DUCTWORK SHALL BE ROUTED AS HIGHAS POSSIBLE IN THE CEILING SPACE.UTILIZE JOIST SPACE WHEN POSSIBLE,ESPECIALLY WHERE CROSSING OTHERDUCTS, PIPES, AND ELECTRICAL.ALL RA & SA RECTANGULAR DUCT TOINCLUDE 1" INTERNAL LINER, UNO. OSA ANDEXH DUCT SHALL BE UNLINED.CONNECT ALL SA AND RA DEVICES WITHINACOUSTIC FLEX DUCT, 5' MIN. & 8' MAXLENGTH.UTILIZE REMOTE BALANCE DAMPERS ILOOBD OR BALANCE DAMPERS AT GRILLE.FLEX DUCT TO BE LOCATED BETWEENDEVICE AND BALACE DAMPER, AS SHOWN.1.2.3.4.5.6.7.8.9.10.11.12.13.14.HVAC NOTES:SCALE: 3/16" = 1'-0"1CHOIR LOFT LEVEL MECHANICAL PLANSCALE: 3/16" = 1'-0"2BELFRY LEVEL MECHANICAL PLANSCALE: 1/4" = 1'-0"3AHU-1 ELEVATION3FLAG NOTES:1ACOUSTIC IMPACTS OF CUSTOMGRILLE TO BE EVALUATED, EXACT SIZE,AND CONFIGURATION TBD.PROVIDE 20X30 ACCESS HATCHADJACENT TO AHU, LOCATED SO AS TOMAINTAIN 30X30 WORKING SERVICESPACE AT SERVICE SIDE OF AHU, PER2015 IMC RQTS. RE: ARCH FFI.22City of Aspen Received 5/2/17Building Department
AIR FLOWUSE DUCT SEALANT ORGASKETED FITTING ON HIGHVELOCITY DUCT.CONICAL SPIN-IN FITTING W/MANUAL DAMPER, HANDLE,& LOCK NUT.FLEX DUCT.WORM DRIVE S.S. CLAMP.NOTE:DIAGRAM FOR LOW & HIGH VELOCITYDUCTWORK EXCEPT UPSTREAM OFVAV BOXES. OMIT DAMPER & FLEXDUCT UPSTREAM OF VAV BOXES.NO SCALEROUND DUCT TAKE-OFF DIAGRAMA45° DUCT TAKE-OFF DIAGRAMNO SCALE45°WH1/4 OF "W" OR6" MINIMUM.ENDBEARING.SINGLE BLADE DAMPERIF H<8" OPPOSEDBLADE DAMPER IF H>=8"SEAL AIRTIGHT AROUNDENTIRE TAKE-OFF.BSUPPLY DIFFUSER REMOTE BALANCE DAMPER DIAGRAMNO SCALEINSULATED SUPPLYAIR PLENUM.24" STANDARD CABLEOR AS REQUIRED.ROUNDDAMPER.TAKE-OFF ASREQUIRED.PLENUMADJUSTABLEMOUNTING CLAMP.DIFFUSER.ADJUSTS WITH 1/4"NUTDIRVER, SPECIFYOPTIONAL SCREWDRIVERTIP IF LESS THAN 3/8"NON-ACCESSIBLE BRANCH DUCT DAMPERNOTE:CEILING DIFFUSER SHOWN.FLOOR DIFFUSER SIMILAR.DWALLDUCT SOUND CONTROL DIAGRAM(DUCT THRU WALL)NO SCALECAULK PENETRATION CONTINUOUSAROUND PERIMETER OF DUCT ONBOTH SIDES OF LEAD WOOL.DUCT.MINERAL FIBER; FILL CAVITYAROUND PERIMETER OF DUCT.EXTEND ACOUSTICAL DUCT WRAPBEYOND INSULATION. TAPE ENDSTO DUCT W/ CONTINUOUS SEALAROUND PERIMETER OF DUCT,TYP.SOUND ATTENUATOR(WHERE SHOWN ONPLANS.)DUCT WRAP OR EQUIV.LOADED VINYL ACOUSTICAL DUCT LAGGINGWITH FIBROUS GLASS SCRIM REINFORCEDALUMINUM FOIL FACING 1.0 LB/SF, 0.090" THICK.1" THICK QUILTED FIBERGLASS (0.2 LB/SF)DECOUPLER/ABSORBER TO FORM A TIGHTFITTING "FLOATING" NOISE BARRIER.WHERE REQUIRED R VALUE EXCEEDS R-4UTILIZE 2" THICK (0.04 LB/SF) DECOUPLERFOR R-8 TOTAL.E(ROOF OR FLOOR)DUCT SOUND CONTROL DIAGRAMNO SCALEDUCT.CAULK PENETRATION CONTINUOUSAROUND PERIMETER OF DUCT ONBOTH SIDES OF MINERAL FIBER.EXTEND ACOUSTICAL DUCT WRAPBEYOND INSULATION. TAPE ENDSTO DUCT WITH CONTINUOUS SEALAROUND PERIMETER OF DUCT,TYP.STRUCTURE (ROOF OR FLOOR).MINERAL FIBER; FILL CAVITYAROUND PERIMETER OFDUCT.PROVIDE EXTRA INSULATION ATCORNERS TO ENSURE THAT DUCTWRAPDOES NOT TOUCH DUCT.LOADED VINYL ACOUSTICAL DUCT LAGGINGWITH FIBROUS GLASS SCRIM REINFORCEDALUMINUM FOIL FACING 1.0 LB/SF, 0.090"THICK.1" THICK QUILTED FIBERGLASS (0.2 LB/SF)DECOUPLER/ABSORBER TO FORM ATIGHT FITTING "FLOATING" NOISEBARRIER. WHERE REQUIRED R VALUEEXCEEDS R-4 UTILIZE 2" THICK (0.04LB/SF) DECOUPLER FOR R-8 TOTAL.SOUND ATTENUATOR;WHERE SHOWN ON PLANS.RETURN AIR GRILLESOUND BOOT DIAGRAMNO SCALE22 GA. SHEET METALBOOT W/ 1" DUCTINSULATION. MINIMUMSIZE = 12x24.NO TURNINGVANES.RETURN GRILLE3'-0"SUPPORT FROMOVERHEADSTRUCTURE.CNO SCALEFLOOR SA/RA DIFFUSER/PLENUM DIAGRAMFLOOR SA OR RA DIFFUSER.SA PLENUM WITH 1/2" DUCT LINER. SAPLENUM SHALL BE 1/2" LARGER THAN SADIFFUSER IN ALL DIMENSIONS TOACCOUNT FOR DUCT LINER.ADDITIONAL ROUND SA OR RADUCTS AS NECESSARY.PROVIDE MINIMUM 3FT AND MAXIMUM 8FTOF INSULATED ACOUSTIC FLEX DUCT ATTRANSITION TO ALL INSULATED S.A./R.A.PLENUMS.NOTES:1.REFER TO MECHANICAL PLANS FORROUND DUCT OR ACOUSTIC FLEXDUCT SIZE AND SA/RA DIFFUSER SIZE.PAN SA/RA PLENUM AROUND FLOORJOISTS AS REQUIRED.2.GCEILINGSAFAN COIL UNITOSAFILTER W/ ACCESSPANEL.ACOUSTICAL LINING.VOLUME DAMPER.RA DUCT.CONDENSATE DRAIN. PIPEINDIRECT TO APPROVEDRECEPTOR (PROVIDEMIN. 2" DEEP TRAP).SHEET METAL DRAINPAN.3/4" SECONDARY DRAIN TOAPPROVED RECEPTOR.PIPE INDIRECT TO FLOORDRAIN ON SINK TAIL PIECE,TYP.ROUND HANGER ROD TYP.WITH EXCEPTION OF FANCOILS LOCATED IN ATTIC.SPRING VIBRATIONISOLATORS, TYP.DOUBLE LOCKNUT.NOTES:1.RETURN AIR PLENUM FULLSIZE OF UNIT CONNECTION.2.THIS SUPPORT SYSTEM IS NOTALLOWED IN THE ATTIC.3.LOCATE ATTIC FAN COILS ON4" HOUSEKEEPING PAD WITHSPRING VIBRATIONISOLATORS.MOTORIZED DAMPER.FAN COIL UNIT INSTALLATIONNO SCALEDDHVERTICAL FAN COIL UNIT INSTALLATIONNO SCALEDSARASEALED FAN COIL UNIT CLOSET TOMINIMIZE NOISE TRANSFER ANDCREATE A RETURN AIR PLENUM.FLEX CONNECTION, TYP.CONDENSATE DRAIN W/ 2" DEEPTRAP. PIPE INDIRECT TO APPROVEDRECEPTOR (SINK TAILPIECE ORWASHERBOX). PROVIDE FLOATSWITCH IN DRAIN PAN TO DISABLEFAN IF CONDENSATE LEVEL RISESABOVE THE PRIMARY DRAIN LEVEL.FILTER W/ ACCESS PANEL.INSULATED RETURN PLENUM FULLSIZE OF UNIT INLET.VIBRATION ISOLATOR, TYP.INSULATED RETURN DUCTSTUBBED INTO EQUIPMENTCLOSET, OR DUCTED DOWNTO 12" A.F.F., ORCONNECTED TO FAN COILUNIT AS INDICATED ONPLANS.OSA DUCT.MOTORIZED DAMPER.FAN COILUNITJRETURNSUPPLY2-WAY COIL PIPING DIAGRAMNO SCALEKCOILNOTES:1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENTCONTAINING FANS OR COMPRESSORS, NOT REQ'D FOREQUIPMENT SUCH AS DUCT COILS.2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATERENTERS MOST DOWNSTREAM COIL, LEAVES MOST UPSTREAMCOIL).3. REFER TO CONTROLS DRAWINGS FOR ADDITIONALINFORMATIO.4. 2-WAY VALVE NORMALLY OPEN FOR HEATING AND NORMALLYCLOSED FOR COOLING.STRAINERWITHBLOWDOWNAND CAP.MANUAL AIR VENTAT HIGHESTPOINT IN PIPING.NO SCALEL3-WAY (DIVERTING VALVE)COIL PIPING DIAGRAMCOILNOTES:1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT CONTAININGFANS OR COMPRESSORS, NOT REQ'D FOR EQUIPMENT SUCH ASDUCT COILS.2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER ENTERSMOST DOWNSTREAM COIL, LEAVES MOST UPSTREAM COIL).3. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION.4. 3-WAY VALVE WITH COIL RETURN PIPED TO NORMALLY OPENPORT FOR HEATING AND NORMALLY CLOSED PORT FOR COOLING.MANUAL AIR VENTAT HIGHESTPOINT IN PIPING.STRAINERWITHBLOWDOWNVALVE ANDCAP.SUPPLYRETURNNO SCALEBASEBOARD RADIATION DIAGRAMHWSHWR( UPFEED )HWRMANUAL AIR VENTS ATHIGH POINTSCONTINUE AS PERPLANSALTERNATE ROUTING & MANUAL AIRVENT LOCATION FOR SAME ENDCONNECTIONS.RISE IN DIRECTIONOF FLOWTHRU FLOOR (IN WALL)CONTROL VALVE INENCLOSURE ONRETURN SIDE (ASAPPLICABLE)CONTINUE AS PERPLANSMOUNTING HEIGHTAS PER EQUIPMENT LISTOR MANUFACTURER'SLISTINGLENGTH AS PER PLANSMRADIANT/SNOWMELT MANIFOLD PIPING DIAGRAMNO SCALECONTROL VALVE.MANIFOLD BOX (WALLMOUNTED FORRADIANT; LOCATED INSLAB FORSNOWMELT).MANUFACTURER'SMANIFOLD ASSY.LOOPBALANCE/ISOLATIONVALVEMANUFACTURER'SMANIFOLD ASSEMBLYWITH REVERSERETURN PIPING.RADIANT/SNOWMELTTUBING. LOOPQUANTITY ASREQUIRED.NOTES:1. PROVIDE MANUFACTURER'S MAINFOLDS ANDISOLATION VALVES WITH PIPING.2. FOR EXTERIOR MANIFOLD LOCATIONS PROVIDEWATERPROOF MANIFOLD BOX OR WATERPROOFCONTROL VALVE.TO PIPING MAINSSMSSMRAIR VENT AT HIGHPOINTS, TYPICAL.MANIFOLD BALANCEVALVE.NSNOWMELT CONNECTION: STAIR TO WALK DIAGRAMNO SCALESTAIR #2STAIR #1 & 32-1/2" MAX5/8" POLYETHYLENE HEATPIPE.5/8" POLYETHYLENE ATSTAIRS & LANDINGS.3" SANDSTONE AT STAIR& LANDING.CONCRETE AT STAIR &LANDING.NOTE:1. REFER TO ARCH FORSTAIR DIMENSIONS.2. RE: CIVIL FOR MATREIAL &CONSTRUCTION DETAIL.3. PROVIDE MIN R-10 SLABINSULATION UNDER SMTUBING. RE: CIVIL FOR EXACTPLACMENT IN ASSEMBLY,MATERIAL, ECT.9" O.C. TYP. FOR ALLLANDINGS & WALKS.3-1/2"4-1/2"4"3"1-1/4"4-1/2"4-1/2"3-1/2"P(FC-1-5, AHU-1 & 2, ALL CUH)(FC-6, FC-7, FC-8)FSNOWMELT TUBING IN CONCRETE DIAGRAMNO SCALECOMPACTED GRADEUNDER-SLAB INSULATION,R-10 MINIMUM.WIRSBO TUBINGWIRE MESH OR REBARCONCRETE SLAB BY OTHERS, RE:ARCH DRAWINGS.WIRE TIEMINIMUM 1.5" OF CONCRETEOVER TUBINGEDGE INSULATION DEPTH TOFROST LINE IF NO HORIZONTALINSULATION IS UTILIZED INASSEMBLYQNOTES:1.CONTRACTOR TO DIP TUBINGBELOW SLAB INTO SUBSOIL ATSLAB CONSTRUCTION JOINTS.2.PROVIDE PIPE INSULATION ONSMOWMELT TUBINGPENETRATING EXPANSIONJOINTS FOR 6 INCHES ONEITHER SIDE OF JOINT, OR DIPTUBING BELOW THE SLAB INTOTHE SUBSOIL.3.SECURE SNOWMELT TUBING 6INCHES ON EITHER SIDE OFCONTROL JOINTS.4.PRESSURE TEST SNOWMELTTUBING WITH 60 PSI OR AIRFOR 24H. TUBING TO REMAIN UNDERPRESSURE DURING CONCRETEPOUR.5.BASE MATERIAL TO BECOMPACTED PRIOR TOINSTALLING ASSEMBLYCOMPONENTS.6. RE: CIVIL FOR EXACTCONSTRUCTION DETAIL,MATERIALS,ECT.33ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:22 PMM4.0MECHANICALDIAGRAMSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOCity of Aspen Received 5/2/17Building Department
SCALE:SCALE:DSMRSMSDSDSHWRHWSHWRHWSGSCHYDRONIC HEATING PLANT PIPING DIAGRAM & CONTROL SCHEMATICHYDRONIC CHILLED WATER PIPING DIAGRAM & CONTROL SCHEMATIC12SDDSDDCHSCHRCHSCHRCHSFSP-7P-6CAPPED DRAIN ATLOW POINT.LOCKING HANDLEOUTDOORCHILLER PADMECHANICALROOMCH-1P-3HWS/R TO BUILDINGDISTRIBUTION.AIR VENT ALL HIGHPOINTS, TYP.TO GLYCOLFEEDER GF-1.HWS/R EXPANSIONTANK, TACO CBX-130OR EQUIVALENT.DOMESTIC WATEREXPANSION TANK, TACOPAX-30 OR EQUIVALENT.CW, HW, HWR TO PIPERACK.SMS/R TO SNOWMELTMANIFOLDS.SNOWMELT EXPANSION TANK,TACO CBX-30 OR EQUIVALENT.VIBRATIONISOLATION.CONCRETE PAD.EXPANSION TANK,TACO CBX-30 OREQUIVALENT.CHS/R TODISTRIBUTIONSYSTEM.GLYCOL FEEDER,GF-1.CLOSELY-SPACEDTEES.AIR VENT ALL HIGHPOINTS, TYP.CONNECT (N) 2"GAS TO (E) GASMAIN IN MECH RM.1-1/2"1-1/2"1-1/2"1-1/2"1-1/2"1-1/2"3"3"3"3"2-1/2"2-1/2"2-1/2"2-1/2"1-1/2"3/4"1-1/2"2"2"3"3"3"3"1"AISEQUENCE OF OPERATION - CENTRAL CHILLED WATERDESCRIPTION:THE SYSTEM CONSISTS OF ONE AIR COOLED CHILLER AND TWO BUILDING CHILLEDWATER PUMPS.CHILLED WATER GENERATIONUPON A CALL FOR COOLING, PUMP P-6 SHALL ENABLE AND CHILLER SHALLOPERATE VIA MANUFACTURER PACKAGED CONTROLS TO MAINTAIN CHSTEMPERATURE AT SETPOINT OF 45°F (ADJ.).CHILLED WATER CIRCULATION PUMP P-7 SHALL OPERATE WHENEVER A CALL FORCOOLING IS PRESENT FROM ANY CONNECTED LOAD (AHU OR FCU). PUMP SHALLMODULATE PER MANUFACTURER CONTROLS TO MAINTAIN SYSTEM DIFFERENTIALPRESSURE.TECPCPVFDWH-1B-1B-1P-1P-1ETP-2P-2ASETP-4NONEHX-1ASP-5ETNONEBT-1NCDDDDESCRIPTION - THE CENTRAL PLANT CONSISTS OF TWO MODULATING, CONDENSING GAS BOILERS SERVING BUILDING HEAT ANDHOT WATER, SNOWMELT SYSTEM, INDIRECT-FIRED WATER HEATER SERVING DOMESTIC HOT WATER HEATING, AND ASSOCIATEDPUMPS AND CONTROLS COMPONENTS.HEATING WATERENABLE BOILERS AND ASSOCIATED BOILER INJECTION PUMPS UPON A CALL FOR HEAT FROM SPACE HEATING, SNOWMELT, ORDOMESTIC WATER HEATING. THE BOILERS SHALL BE STAGED AND OPERATE ONLY AS NEEDED THROUGH THE BOILERMANUFACTURER'S CONTROL SYSTEM. DISABLE BOILERS AND ASSOCIATED BOILER INJECTION PUMPS WHEN A CALL FOR HEAT IS NOLONGER PRESENT.UPON A CALL FOR HEAT FROM ANY SYSTEM (FCU, AHU, CUH, SNOWMELT, OR RADIANT ZONE), HEATING WATER CIRCULATION PUMPSP-1 SHALL ENABLE AND MODULATE PER MANUFACTURER-INTEGRAL CONTROLS TO MAINTAIN SYSTEM DIFFERENTIAL PRESSURE ANDTEMPERATURE. WHEN CALL FOR HEAT HAS BEEN SATISFIED, PUMPS P-1 SHALL BE OFF. ALTERNATE LEAD/LAG PUMP PERMANUFACTURER CONTROLS TO ACHIEVE EQUAL RUN TIME ON BOTH PUMPS.DOMESTIC HOT WATERON A CALL FOR DOMESTIC HOT WATER PRIORITY FROM A TANK MOUNTED AQUASTAT SET AT 120°F (ADJ), THE DOMESTIC HOTWATER PRIORITY BOILER SHALL ENABLE AND MODULATE PER MANUFACTURER CONTROLS TO SATISFY THE DOMESTIC HOT WATERLOAD BY SUPPLYING 145°F (ADJ) HEATING WATER. THE WATER HEATER CIRCULATION PUMP P-3 SHALL RUN TO DIVERT ALL HEATINGWATER TO WATER HEATER, AND BOILER INJECTION PUMP P-1 OF ASSOCIATED BOILER SHALL BE OFF. INCREASE BOILER HWSSETPOINT TO 160°F MAX BASED ON DEVIATION OF WATER HEATER TANK TEMPERATURE FROM SETPOINT.DISABLE BOILERS AND WATER HEATER CIRCULATION PUMPS WHEN A CALL FOR DOMESTIC HOT WATER HEATING IS NO LONGERPRESENT.DOMESTIC HOT WATER RECIRCULATION PUMP P-5 SHALL CYCLE TO MAINTAIN A DOMESTIC HOT WATER RECIRCULATIONTEMPERATURE OF 110°F (ADJ).SNOWMELTUPON A CALL FROM AN IN-SLAB TEMPERATURE/MOISTURE SENSOR (TEKMAR 090 OR EQUIVALENT), OPEN HEATING WATER CONTROLVALVE, ENABLE PUMP P-5, CYCLE HX CONTROL VALVE TO MAINTAIN SMS TEMPERATURE OF 100°F (ADJ.)PLANT PIPING NOTES:1FLAG NOTES:SPIROVENT MICROBUBBLE AIR ELIMINATOR, OREQUIVALENT. MATCH PIPE SIZE.PIGTAIL PRESSURE GAUGE.2NOTES:SEQUENCE OF CONTROL1. COALESCING TYPE AIR SEPARATOR WITH WITH AUTOMATIC RELIEF FLOAT. 1 -1/2" PIPEAND SMALLER: SPIROTHERM SPIROVENT JR, B&G EASB JR, OR TACO VORTEC. 2" PIPE AND LARGER: SPIROTHERM SPIROVENT SR, B&G CRS, OR TACO 4900. OR EQUIVALENT.2. EXTEND DRAIN TO NEAREST FLOOR SINK FOR INDIRECT CONNECTION. DO NOT COMBINE DRAIN WITH OTHERS.3. PROVIDE ALL STRAINERS WITH BLOWDOWN BALL VALVE, HOSE END THREAD, GASKETED CAP AND CHAIN.4. PROVIDE GASKETED CAP AND CHAIN FOR DRAINS.5. EXTEND ALL SAFETY RELIEF VALVES TO DRAIN PER VALVE MFG's RECOMMENDATIONS WITHOUT PIPE BELLIES OR UPWARD SLOPE. DO NOT COMBINE WITH OTHERS.6. INDICATES UNION OR FLANGE CONNECTION FOR SERVICE PURPOSES. DIELECTRIC UNIONS NOT PERMITTED EXCEPT AT DOMESTIC WATER CONNECTIONS TO WATER HEATERS. PROVIDE DIELECTRIC NIPPLES OR FLANGES AT FERROUS TO NON-FERROUS PIPING MATERIAL TRANSITIONS.7. THREE-WAY VALVE WITH PORTS IDENTIFIED: C = COMMON NC = NORMALLY CLOSED NO = NORMALLY OPEN8. DIAGRAM IS SCHEMATIC IN NATURE. NOT ALLAPPURTENANCES REQ'D ARE NECESSARILY SHOWN.PROVIDE SYSTEM ACCESS, VALVING, AND DRAINAGEAS REQ'D FOR PROPER SYSTEM MAINTENANCE ANDPURGE/FILL PROCEDURES.9. PROVIDE MANUAL AIR VENT AT ALL HIGH POINTS ANDMANUAL DRAIN VALVES AT ALL LOW POINTS. PIPEDRAIN VALVES TO A SUITABLE LOCATION WHENDRAINS ARE IN A LOCATION IN WHICH THEIRDRAINAGE WILL BE A NUISANCE OR CAUSE DAMAGE.10. ALL PARALLEL EQUIPMENT SUCH AS BOILERS, PUMPS,TANKS, ETC. SHALL BE PIPED IN TRUE REVERSEDRETURN FASHION FOR AUTOMATIC FLOW BALANCINGBETWEEN THE PARALLEL ITEMS.11. PROVIDE 4" HIGH CONCRETE SHOP KEEPING PAD INADDITION TO MFG's BASE FOR ALL FLOOR MOUNTEDEQUIPMENT. COORDINATE EXACT PAD SIZES ANDLOCATIONS WITH PIPING SHOP DRAWINGS ANDCONCRETE CONTRACTOR.12. ALL ISOLATION VALVES SHALL BE FULL PORT VALVESEQUIVALENT TO PIPE SIZE SHOWN.13. ROUTE COMBUSTION EQUIPMENT AND VENT STACKTEE CONDENSATE DRAIN LINES AND INDIRECTCONNECT TO CONDENSATE NEUTRALIZATION BASINSIZED PER COMBUSTION EQUIPMENT MFG'sRECOMMENDATIONS. INDIRECT CONNECT BASINOUTLET TO NEAREST WASTE RECEPTOR.14. RE: R/M301 FOR POT FEEDER CONNECTION.15. REFER TO CONTROLS DRAWINGS FOR ADDITIONALDEVICE REQUIREMENTS SUCH AS PRESSURE ANDTEMPERATURE PICKUP LOCATIONS.16. RE: X/M## FOR PIGTAIL PRESSURE GAUGECONNECTION.17. PROVIDE DOWNWARD GAS FLOW INTOSEDIMENT/DRIP LEG TEES.NCCNO1. PROVIDE ALL DRAIN OUTLETS WITH HOSE ENDTHREAD, GASKETED CAP & CHAIN.2. PROVIDE 4" HIGH SHOP KEEPING PAD INADDITION TO MFG'S BASE BENEATH ALL FLOORMOUNTED EQUIPMENT.3. PROVIDE STOP COCK FOR ALL PRESSUREGAUGES.4. SIGNIFIES BALL VALVE FOR PIPE 2" & LESS,BUTTERFLY FOR 2-1/2" & ABOVE.5. NOT ALL APPURTENANCES REQUIRED ARENECESSARILY SHOWN. PROVIDE VALVING ANDACCESS AS DESIRED FOR FLUSH/FILL/PURGEOPERATIONS.6. PROVIDE PRESSURE GAUGES WITH STOP COCKFOR EASE OF REPLACEMENT.7. STATUS VIA CURRENT SWITCH IS DEEMEDACCEPTABLE PROVIDED SWITCH WILL TRIP INTHE EVENT OF LOCKED ROTOR AMPS ANDSHAFT OR BELT FAILURE.222212222SEQUENCE OF CONTROLCPALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:23 PMM5.0PIPINGDIAGRAMS &CONTROLSCHEMATICSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOCity of Aspen Received 5/2/17Building Department
SCALE:SCALE:SCALE:SCALE:SCALE:SCALE:HWSHWRHWSHWRHWSHWRBDDUNIT HEATER CONTROL DIAGRAMVERTICAL AND HORIZONTAL CABINET4 PIPE FAN COIL UNIT WITH OSA CONTROL DIAGRAMTHERMOSTAT CONTROL SCHEMATICEXHAUST FANAUXILIARY SYSTEMSCONTROL SEQUENCESDUAL-CONTROL 4 PIPE AIR HANDLING UNIT WITH OSA CONTROL DIAGRAMUNIT HEATER CONTROL DIAGRAMVERTICAL AND HORIZONTAL CABINET325614APPLIES TO ALL CUH-1 AND CUH-2 CABINET UNIT HEATERS, ANDFC-8 AIR CURTAIN.UPON A DROP IN TEMPERATURE BELOW SETPOINT MINUSDIFFERENTIAL, THERMOSTAT SHALL ENERGIZE FAN AND OPENHEATING WATER CONTOL VALVE. CONVERSELY UPON A RISE INTEMPERATURE ABOVE SETPOINT PLUS DIFFERENTIAL FAN SHALLBE DE-ENERGIZED AND CONTROL VALVE SHALL CLOSE.APPLIES TO ALL CUH-3 AND CUH-4 CABINET UNIT HEATERS.UPON A DROP IN TEMPERATURE BELOW SETPOINT MINUSDIFFERENTIAL, THE SPACE-MOUNTED THERMOSTAT SHALLENERGIZE FAN AND OPEN HEATING WATER CONTOL VALVE.CONVERSELY UPON A RISE IN TEMPERATURE ABOVE SETPOINTPLUS DIFFERENTIAL FAN SHALL BE DE-ENERGIZED AND CONTROLVALVE SHALL CLOSE.WHERE MULTIPLE HEATERS ARE CONTROLLED VIA A SINGLETHERMOSTAT, A SINGLE CONTROL VALVE SHALL BE PROVIDEDFOR ALL ASSOCIATED HEATERS, WHICH SHALL OPEN AND ALLHEATERS SHALL BE CONTROLLED SIMULTANEOUSLY FOLLOWINGTHE ABOVE SEQUENCE.CHSCHRCHSCHRCHSCHRHWRHWSWALL SWITCHINTEGRALTHERMOSTAT.WALL-MOUNTEDTHERMOSTAT.WALL-MOUNTEDTHERMOSTAT.TSTATMMTSTATDMOSARAZONE (ORMASTER)THERMOSTATFRZAPPLIES TO FC-1, 2, 3, 4, 5, 6, AND 7THE SYSTEM CONSISTS OF A FAN COIL UNIT WITH HOT WATER COIL, CHILLED WATER COIL, SUPPLY FAN, AND OSAMOTORIZED DAMPER.A SPACE-MOUNTED 7-DAY PROGRAMMABLE THERMOSTAT WITH PROGRAMMABLE OCCUPIED/UNOCCUPIED SETTINGSHALL BE PROVIDED FOR EACH FCU. WHEN IN OCCUPIED MODE, FAN IS ON AND MOTORIZED OSA DAMPER SHALL BEIN POSITION TO SUPPLY OSA CFM LISTED IN FCU SCHEDULE. WHEN IN UNOCCUPIED MODE, OSA DAMPER IS CLOSED,AND FCU OPERATES TO MAINTAIN SPACE UNOCCUPIED SETPOINTS.OPTIMAL START: CONTROLLER SHALL AUTOMATICALLY ADJUST THE DAILY START TIME OF THE FCU TO BRING THESPACE TO DESIRED OCCUPIED TEMPERATURE IMMEDIATELY PRIOR TO SCHEDULED OCCUPANCY.FREEZESTAT TRIP: FREEZESTAT SERPENTINED ON THE DOWNSTREAM SIDE OF THE HEATING COIL (PREFERABLE) ORCOOLING COIL (LESS PREFERRED) SHALL SHUT OFF FAN AND CLOSE OUTDOOR AIR DAMPER WHEN TRIPPED.HEATING VALVE SHALL OPEN WHEN FREEZESTAT IS TRIPPED. FREEZESTATS ARE TO BE THE AUTOMATIC RESETTINGTYPE INITIALLY SET TO TRIP AT 35°F.TEMPERATURE CONTROL:SPACE TEMPERATURE SHALL BE MAINTAINED AT SETPOINT BY OPENING OR CLOSING THE HOT AND CHILLED WATERVALVES IN SEQUENCE AS REQUIRED. SIMULTANEOUS HEATING AND COOLING WATER FLOW SHALL BE PROHIBITED.SPACE TEMPERATURE SETPOINT SHALL BE INITIALLY SET AT 70°F FOR HEATING, AND 75°F FOR COOLING, ADJ.UNOCCUPIED SETPOINT SHALL BE INITIALLY SET AT 65°F HEATING AND 80°F COOLING, ADJ.ZONED FAN COIL UNIT, FC-7:IN ADDITION TO ABOVE SEQUENCE: PROVIDE MOTORIZED ZONE DAMPERS WHERE SHOWN ON PLANS. PROVIDETHERMOSTATS AND CENTRAL CONTROLLER CAPABLE OF POLLING MULTIPLE ZONES TO SET OPERATION MODE(HEATING VS. COOLING), TRANE TRACKER OR EQUIVALENT. OCCUPANCY SHALL BE SCHEDULED THROUGH MASTERTHERMOSTAT. ZONE THERMOSTATS SHALL BE CAPABLE OF SETTING SPACE SETPOINT TEMPERATURE. CENTRALCONTROLLER SHALL DETERMINE HEATING VS. COOLING MODE, AND ZONE MOTORIZED DAMPER SETTINGS BASED ONZONE TEMPERATURE DEVIATION FROM ZONE THERMOSTAT SETPOINT.NOTES:1. SOME COILS REQUIRE 3-WAY DIVERTING VALVES. RE: M4.0 COIL PIPING DIAGRAMS FFI. ALL VALVES SHALL BE2-POSITION.2. RE: M4.0 COIL PIPING DIAGRAMS FOR ALL PIPING CONFIGURATION, VALVES, AND APPURTENANCES REQUIRED.SAOCCMSAPPLIES TO EF-1, BATHROOM EXHAUST FANS.FAN SHALL BE CONTROLLED BY INDIVIDUAL SPACE MOUNTED OCCUPANCYSENSOR. UPON DETECTION OF OCCUPANCY, EXHAUST FANS SHALL ENABLE. WHENOCCUPANCY HAS NOT BEEN SENSED FOR 10 MINUTES (ADJ.), EXHAUST FANS SHALLDISABLE.MANUAL OVERRIDE-ON WALL SWITCH TO BE PROVIDED, ADJACENT TO LIGHTSWITCH IN SPACE BEING SERVED. WHEN SWITCH IS IN ON POSITION, FAN SHALLOPERATE. WHEN SWITCH IS IN OFF POSITION, FAN SHALL BE CONTROLLED BYSPACE MOUNTED OCCUPANCY AS DESCRIBED ABOVE.(E) EXHAUST DUCT,TO EXTERIORTERMINATION.GRAVITY OPERATEDNON-MOTORIZEDBACK DRAFTDAMPER.UNIT MOTORSTARTERDMOSARAZONETHERMOSTATFRZSAAHU-1DMOSARAFRZSAAHU-2RM-1 & 2TSTATMTSTATMSADMZONE T-STAT,TYP.FC-7, ZONEDFAN COIL UNIT,ONLY. TYP. ALLZONES.THE SYSTEM CONSISTS OF TWO AIR HANDLING UNITS WITH HOT WATER COIL, CHILLED WATER COIL, SUPPLY FAN, ANDMIXING DAMPERS, AND TWO RADIANT FLOOR HEATING ZONES.A SPACE-MOUNTED 7-DAY PROGRAMMABLE THERMOSTAT WITH PROGRAMMABLE OCCUPIED/UNOCCUPIED SETTINGSHALL BE PROVIDED FOR THE SANCTUARY/NAVE SPACE, AND SHALL CONTROL AHU-1, AHU-2, AND RADIANT ZONES ASFOLLOWS.VENTILATION CONTROL:1. STAGE 1 OCCUPIED MODE: AHU-1 FAN IS ON AND MOTORIZED OSA DAMPER SHALL BE IN POSITION TO SUPPLYOSA CFM LISTED IN AHU SCHEDULE.2. STAGE 2 OCCUPIED MODE: AHU-1 & AHU-2 FANS ARE ON, BOTH MOTORIZED OSA DAMPERS SHALL BE IN POSITIONTO SUPPLY OSA CFM LISTED IN AHU SCHEDULE.3. UNOCCUPIED MODE: BOTH OSA DAMPERS ARE CLOSED, AND AHU OPERATES TO MAINTAIN SPACE UNOCCUPIEDSETPOINTS.BUILDING RELIEF AIR PATH: UPON A RISE IN BUILDING PRESSURE ABOVE OUTDOOR AMBIENT PRESSURE, OPENMOTORIZED RELIEF DAMPER IN RELIEF AIR DUCTWORK IN BELFRY. UPON A DROP IN BUILDING PRESSURE TO OUTSIDEAIR PRESSURE, CLOSE MOTORIZED RELIEF DAMPER. RELIEF DAMPER TO BE FOAM INJECTED THERMALLY ISOLATEDLOW TEMPERATURE CONTROL DAMPER, RUSKIN CDTI-50 OR EQUIVALENT.OPTIMAL START: CONTROLLER SHALL AUTOMATICALLY ADJUST THE DAILY START TIME OF THE AHU TO BRING THESPACE TO DESIRED OCCUPIED TEMPERATURE IMMEDIATELY PRIOR TO SCHEDULED OCCUPANCY.FREEZESTAT TRIP: FREEZESTAT SERPENTINED ON THE DOWNSTREAM SIDE OF THE HEATING COIL (PREFERABLE) ORCOOLING COIL (LESS PREFERRED) SHALL SHUT OFF FAN AND CLOSE OUTDOOR AIR DAMPER WHEN TRIPPED. HEATINGVALVE SHALL OPEN WHEN FREEZESTAT IS TRIPPED. FREEZESTATS ARE TO BE THE AUTOMATIC RESETTING TYPEINITIALLY SET TO TRIP AT 35°F.TEMPERATURE CONTROL:SPACE TEMPERATURE SHALL BE MAINTAINED AT SETPOINT BY OPENING OR CLOSING THE HOT AND CHILLED WATERVALVES IN SEQUENCE AS REQUIRED. SIMULTANEOUS HEATING AND COOLING WATER FLOW SHALL BE PROHIBITED.SPACE TEMPERATURE SETPOINT SHALL BE INITIALLY SET AT 70°F FOR HEATING, AND 75°F FOR COOLING, ADJ.UNOCCUPIED SETPOINT SHALL BE INITIALLY SET AT 65°F HEATING AND 80°F COOLING, ADJ. STAGE HEATING ANDCOOLING AS FOLLOWS:HEATING1. STAGE 1: OPEN RADIANT MANIFOLD 1 & 2 CONTROL VALVES.2. STAGE 2: ENABLE AHU-1 HEATING IN ADDITION TO RADIANT HEAT.3. STAGE 3: ENABLE AHU-2 HEATING IN ADDITION TO AHU-1 AND RADIANT HEAT.COOLING:1. STAGE 1: ENABLE AHU-1 COOLING.2. STAGE 2: ENABLE AHU-2 COOLING IN ADDITION TO AHU-1 COOLING.AS SPACE TEMPERATURE REACHES SETPOINT, DISABLE THE ABOVE STAGES IN REVERSE SEQUENCE.NOTES:1. SOME COILS REQUIRE 3-WAY DIVERTING VALVES. RE: M4.0 COIL PIPING DIAGRAMS FFI. ALL VALVES SHALL BE2-POSITION.2. RE: M4.0 COIL PIPING DIAGRAMS FOR ALL PIPING CONFIGURATION, VALVES, AND APPURTENANCES REQUIRED.SMK1. RELIEF AIR DUCT SYSTEM: UPON DETECTION OFINTERIOR PRESSURE GREATER THAN AMBIENTOUTDOOR PRESSURE, OPEN MOTORIZED DAMPERAT RELIEF AIR DAMPER. UPON EQUALIZATION OFINTERIOR AND EXTERIOR PRESSURES, DAMPERSHALL CLOSE.2. EF-2, CONFESSIONAL EXHAUST FAN: UPON CLOSEOF A ROOM-MOUNTED ON/OFF SWITCH, FAN SHALLENABLE. FAN SHALL DISABLE ON OPEN OF ON/OFFSWITCH.3. HYDRONIC RADIANT BASEBOARD, BB-1: BASEBOARDASSOCIATED HEATING WATER CONTROL VALVESHALL OPEN UPON A CALL FOR HEAT FROM ASPACE-MOUNTED THERMOSTAT. CONVERSELY,VALVE SHALL CLOSE WHEN CALL FOR HEAT ISSATISFIED.NONENONENONENONENONENONEHWRHWSSEQUENCE OF CONTROL:SEQUENCE OF CONTROL:HWRHWSHWRHWSAIAOBIBOCPAFMSCOCO2CSDPSDPTFRZFSFHEMSDMRLYSSMKTETSTATVFDTEMPSENSORPEMEPOEVOANALOG INPUT TO BCSCONTROLS SYMBOLSANALOG OUTPUT FROM BCSBINARY INPUT TO BCSBINARY OUTPUT FROM BCSCARBON MONOXIDE SENSORCARBON DIOXIDE SENSORCURRENT SWITCHFLOW SWITCHHUMIDITY SENSORMOTOR STARTERDAMPER MOTORRELAYSMOKE DETECTORTEMPERATURE SENSORVARIABLE FREQUENCY DRIVEFREEZSTATSENSORTHERMOSTATSWITCHSPACE MOUNTED STATEQUIPMENT MANUFACTURER'SCONTROL PANELDIFFERENTIAL PRESSURE SWITCHDIFFERENTIAL PRESSURE TRANSDUCERFLOW SENSORAIRFLOW MEASURING STATIONPRESSURE SENSORMOTOR (FAN, DAMPER OR OTHER)EMERGENCY POWER OFFEMERGENCY VENTILATION ONALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:24 PMM5.1MECHANICALCONTROLSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOCity of Aspen Received 5/2/17Building Department
ACEBD123456789KITCHEN109ENTRY100MEETING RM102MEETING RM103MEETING RM104MEETING RM105HALLWAY111VEST.120MEETING RM101OFFICE122MEETING RM107KITCHEN & ALL FIXTURES& PIPING TO REMAIN.(E) W TO KITCHEN.(E) FLOOR CO UNDERACCESS PANEL TOREMAIN.(E) W EXIT. PROVIDEPRICING TO DEMO &REPLACE WITH 4" WFROM UTILITYCONNECTION TOBATHROOM GROUPS,AS SHOWN.(E) W TO SINK. DEMOTO MAIN.REMOVE ALL (E) PLUMBIGFIXTURES & PIPING INBATHROOM GROUPS &APARTMENTS.REMOVE (E) 3" W TOBATROOM GROUPS.(E) WATER FROMUTILITY.(E) GAS METERAND ENTRY.MALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:28 PMP2.2MAIN LEVELDEMOLITIONPLUMBINGPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"MAIN LEVEL DEMOLITION PLUMBING PLANADDITIONAL STORM, HYDRONIC,DOMESTIC, WASTE AND VENT PIPING MAYBE ROUTED IN SPACE THAT IS NOTREPRESENTED, BUT IS TO REMAIN.OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ONTHESE DRAWINGS; MODIFICATIONS TOTHESE SYSTEMS ARE NOT ANTICIPATED.FIELD VERIFY ALL COMPONENTS PRIORTO DEMOLITION. THE INFORMATION ONTHIS SHEET WAS OBTAINED, IN PART,FROM HISTORIC DESIGN DRAWINGS. ONLYPORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATIONDURING DESIGN PROCESS.PROVIDE PRELIMINARY TESTING OFEXISTING HYDRONIC SYSTEMS. MEASURECURRENT FLUID FLOW RATE THROUGHALL EXISTING COILS, RADIANT, ANDSNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OFMEASURED VALUES TO ENGINEER FORREVIEW AND CONFIRMATION OF SYSTEMDESIGN ASSUMPTIONS PRIOR TODEMOLITION.(E) WASTE SYSTEM SERVING SPACE ISLOCATED IN THE CEILING OF THE SPACEBELOW.REMOVE ALL MECHANICAL ITEMSINDICATED.TEMPORARILY SEAL OR CAP PIPING TO BERE-USED FOR LATER CONNECTION.SEAL ALL OPEN DUCTS DURINGCONSTRUCTION TO MITIGATE DUST ANDDEBRIS FROM SYSTEM. CAP DUCTWORKIN LOCATIONS THAT ARE NOT BEINGRECONNECTED.REMOVE ALL DEMOLISHED COLD WATER,HOT WATER AND HOT WATERRECIRCULATION PIPING BACK TO BRANCHFROM MAIN TO ELIMINATE ALL DEADENDS IN DOMESTIC WATER PIPING.NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATIONREPRESENTED IN THE DOCUMENTSVERSUS WHAT IS FOUND IN THE FIELD.COORDINATE PATCHING AND REPAIRS OFWALLS, CEILINGS AND FLOORS WITHARCHITECT.PATCH STRUCTURAL OPENINGS INFLOORS, WALLS AND ROOFS THAT WEREPREVIOUSLY OCCUPIED BY SYSTEMSAND EQUIPMENT DEMOLISHED UNDERTHIS CONTRACT IN ACCORDANCE WITHSTRUCTURAL ENGINEER'SREQUIREMENTS.1.2.3.4.5.6.7.8.9.10.11.DEMOLITION NOTES:City of Aspen Received 5/2/17Building Department
ACEBD123456789STAIR201STOR202STAIR203NARTHEX204VEST205NAVE206SANCTUARY207VESTING /SACRISTY208ALTARSERVERVESTING209REMOVE (E) SINKS, DEMO PIPINGTO WALL AND PROTECT FORCONNECTION TO (N) SINKS.REMOVE (E) SINKS, DEMO PIPINGTO WALL AND PROTECT FORCONNECTION TO (N) SINKS.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:32 PMP2.3SANCTUARYLEVELDEMOLITIONPLUMBINGPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"SANCTUARY LEVEL DEMOLITION PLUMBINGPLANADDITIONAL STORM, HYDRONIC,DOMESTIC, WASTE AND VENT PIPING MAYBE ROUTED IN SPACE THAT IS NOTREPRESENTED, BUT IS TO REMAIN.OTHER SYSTEMS MAY EXIST WITHIN THESPACE THAT ARE NOT REPRESENTED ONTHESE DRAWINGS; MODIFICATIONS TOTHESE SYSTEMS ARE NOT ANTICIPATED.FIELD VERIFY ALL COMPONENTS PRIORTO DEMOLITION. THE INFORMATION ONTHIS SHEET WAS OBTAINED, IN PART,FROM HISTORIC DESIGN DRAWINGS. ONLYPORTIONS OF THE SYSTEMS WEREACCESSIBLE FOR VISUAL CONFIRMATIONDURING DESIGN PROCESS.PROVIDE PRELIMINARY TESTING OFEXISTING HYDRONIC SYSTEMS. MEASURECURRENT FLUID FLOW RATE THROUGHALL EXISTING COILS, RADIANT, ANDSNOWMELT ZONES FOR THE CURRENTLYINSTALLED SYSTEMS. SUBMIT REPORT OFMEASURED VALUES TO ENGINEER FORREVIEW AND CONFIRMATION OF SYSTEMDESIGN ASSUMPTIONS PRIOR TODEMOLITION.(E) WASTE SYSTEM SERVING SPACE ISLOCATED IN THE CEILING OF THE SPACEBELOW.REMOVE ALL MECHANICAL ITEMSINDICATED.TEMPORARILY SEAL OR CAP PIPING TO BERE-USED FOR LATER CONNECTION.SEAL ALL OPEN DUCTS DURINGCONSTRUCTION TO MITIGATE DUST ANDDEBRIS FROM SYSTEM. CAP DUCTWORKIN LOCATIONS THAT ARE NOT BEINGRECONNECTED.REMOVE ALL DEMOLISHED COLD WATER,HOT WATER AND HOT WATERRECIRCULATION PIPING BACK TO BRANCHFROM MAIN TO ELIMINATE ALL DEADENDS IN DOMESTIC WATER PIPING.NOTIFY ENGINEER IMMEDIATELY OF ANYDISCREPANCIES OF INFORMATIONREPRESENTED IN THE DOCUMENTSVERSUS WHAT IS FOUND IN THE FIELD.COORDINATE PATCHING AND REPAIRS OFWALLS, CEILINGS AND FLOORS WITHARCHITECT.PATCH STRUCTURAL OPENINGS INFLOORS, WALLS AND ROOFS THAT WEREPREVIOUSLY OCCUPIED BY SYSTEMSAND EQUIPMENT DEMOLISHED UNDERTHIS CONTRACT IN ACCORDANCE WITHSTRUCTURAL ENGINEER'SREQUIREMENTS.1.2.3.4.5.6.7.8.9.10.11.DEMOLITION NOTES:City of Aspen Received 5/2/17Building Department
ACEBD123456789ELEV EQUIP002STORAGESTORAGEBOILERROOMCRAWLSPACECRAWLSPACECRAWLSPACE2 1/2" HWS2 1/2" HWR2 1/2" CHS2 1/2" CHRCWHWHWC2 1/2" HWS2 1/2" HWR2 1/2" CHS2 1/2" CHRPIPE RACK FROMMECH ROOM. RE: M5.0FCT AND SIZING.2-1/2" HWS/R,2-1/2" CHS/R UP.HWSHWR1" HWR1" HWS1" HWR1" HWS1" HWS1" HWR222222222222221"HWS/R,1"CHS/R UP.WW(E) WATER ENTRYTO REMAIN.(N) 4" W EXIT TOUTILITY MAIN.22 1/2"2 1/2"2 1/2"2 1/2"3/4"3/4"3/4" HWS/R UP.CHSCHRCHS/R TO CHILLER.RE: M2.0 FCT.CHS/R TO MECH.RM. RE: M5.0 FFI.AND FCT.1 1/2"1 1/2"3/4"RECONNECT (E)CW/HW/HWC SERVINGKITCHEN TO (N) PIPING.1 1/2" SMS1 1/2" SMR1 1/2" SMS1 1/2" SMR(N) SM-2 MANIFOLD INSTALLED PER DIAGRAM RQTS,RE: M4.0 FFI. RECONNECT (E) LOOPS TO (N) MANIFOLD.(E) SMS/R PIPE ROUTING AND SIZE TO (E) SM-1 UNKNOWN.CONTRACTOR OPTION TO RE-USE (E) PIPE IF CONDITION ISACCEPTABLE AND SIZE MEETS OR EXCEEDS THAT SHOWN.1-1/2" SMS/R TO MECH RM,RE: M5.0 FCT.1-1/2" SMS/R TO (N) SM-1 INEXTERIOR LANDSCAPE. RE:M2.0 FFI.(E)WCONNNECT (E)WTO (N) 4"W.333ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:46 PMP2.4BASEMENTLEVEL PIPINGPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"BASEMENT LEVEL PIPING PLANFLAG NOTES:13/4" HWS/R TO CUH ABOVE.2RE: 94.0 FOR ALL PLUMBING DIAGRAMS.REFER TO THE PLUMBING FIXTURECONNECTION SCHEDULE FOR PIPE SIZESTO INDIVIDUAL FIXTURES.NOT ALL REQUIRED CLEANOUTS ARENECESSARILY SHOWN ON THESE PLANS.PROVIDE CLEANOUTS ON WASTE, VENTAND STORM PIPING AS REQUIRED BYCODE AND FOR REASONABLEMAINTENANCE BASED ON ACTUAL FIELDINSTALLATION. COORDINATE LOCATIONSWITH ARCHITECT/ENGINEER.COORDINATE ROUTING OF CONDENSATEDRAIN LINES WITH ARCHITECT PRIOR TOINSTALLATION.PIPING ON EXTERIOR WALLS OR PRE-CAST CONCRETE WALLS TO BE ROUTEDIN FRAMED WALL ON INTERIOR SIDE OFINSULATION.ST AND ST(OF) PIPING 3", UNOINSTALL THERMOSTATIC MIXING VALVES,ASSE 1070 LISTED, AT EACH PUBLICHANDWASHING LAVATORY/SINK. SIZE TOMATCH HW PIPE SIZE.ROOF OVERFLOW DRAINAGE STRATEGYTO BE DETERMINED OR VIAARCHITECTURAL SCUPPERS UNOTERMINATE PLUMBING VENTS NOT LESSTHAN 12" ABOVE ROOF.AVOID ROUTING PIPING OVERELECTRICAL ROOMS OR ELECTRICALPANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITHELECTRICAL CONTRACTOR.CONTRACTOR TO MAINTAIN 8'-6" CLEARHEAD HEIGHT IN GARAGE AND INFORMTHE ENGINEER AND ARCHITECT OF ANYAREAS THAT MAY NOT MEET 8'-6" PRIORTO INSTALLATION, MINIMUM 8'-2" CLEARHEAD HEIGHT MUST BE MAINTAINED INACCESSIBLE VEHICLE AREAS.PROVIDE FLEXIBLE PIPE CONNECTIONSTO ALL MOTORIZED EQUIPMENT.ROUTE DOMESTIC HOT WATER RECIRCTO WITHIN 10 FEET OF ALL HOT WATERFIXTURES. CONNECT WITHIN 5 FEET OF0.5 GPM AND LOWER FAUCETS.VERIFY ALL EQUIPMENT ACCESS PANELSWITH MANUFACTURER AND ARCHITECT.PROTECT PIPING ROUTED ALONGCOLUMNS, WALLS, ETC. FROM DAMAGEAS NECESSARY WITH CAGES.COORDINATE WITH ARCHITECT.PEX PIPING SHALL NOT BE ALLOWED TOPENETRATE FIRE BARRIERS WHERE FIRECAULKING IS REQUIRED.ALL VALVES SHALL BE INSTALLED ABOVEDROP-IN CEILINGS IN ACCESSIBLELOCATIONS, OR WITH ACCESS PANELS INHARD-LID CEILINGS.ALL PIPING SHALL BE ROUTED AS HIGHAS POSSIBLE IN THE CEILING SPACE.UTILIZE JOIST SPACE WHEN POSSIBLE,ESPECIALLY WHERE CROSSING OTHERPIPES, DUCTS, AND ELECTRICAL.ACCESS PANELS SHALL BE 24x24, UNOLOCATIONS SHOWN ARE APPROXIMATE,EXACT LOCATIONS SHALL BECOORDINATED WITH THE ARCHITECTSDRAWINGS AND WITH THE LOCATIONS OFTHE EQUIPMENT OR APPARATUS THATTHEY SERVE.1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.PLUMBING NOTES:City of Aspen Received 5/2/17Building Department
W H WHACEBD123456789KITCHEN109ENTRY100MEETING RM102MEETING RM103MEETING RM104MEETING RM105HALLWAY111WOMEN110OFFICE113MEN116HALL115OFFICE114OFFICE119HALL117RECEPT118VEST.120MEETING RM101OFFICE122MEETING RM107CONF RM112P5P5P5P5P4P4P4P6P6P4P4P3P1P1HWS/R, CHS/RRISERS.(N) 4" FLOOR CO IN (E)FLOOR BOX & ACCESSPANEL.1" HWS/R, 1"CHS/R TO FC-7.13/4" HWS/R TOFC-8.HWRHWS1P2P2REF: 1/P4.0FOR DOMESTICPIPING ANDSIZING.M(E) GAS TO UTILITY MAIN.(E) GAS TO MECH. RM.FCOFCOHWSHWRALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:48:54 PMP2.5MAIN LEVELPLUMBINGPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"MAIN LEVEL PLUMBING PLANRE: 94.0 FOR ALL PLUMBING DIAGRAMS.REFER TO THE PLUMBING FIXTURECONNECTION SCHEDULE FOR PIPE SIZESTO INDIVIDUAL FIXTURES.NOT ALL REQUIRED CLEANOUTS ARENECESSARILY SHOWN ON THESE PLANS.PROVIDE CLEANOUTS ON WASTE, VENTAND STORM PIPING AS REQUIRED BYCODE AND FOR REASONABLEMAINTENANCE BASED ON ACTUAL FIELDINSTALLATION. COORDINATE LOCATIONSWITH ARCHITECT/ENGINEER.COORDINATE ROUTING OF CONDENSATEDRAIN LINES WITH ARCHITECT PRIOR TOINSTALLATION.PIPING ON EXTERIOR WALLS OR PRE-CAST CONCRETE WALLS TO BE ROUTEDIN FRAMED WALL ON INTERIOR SIDE OFINSULATION.ST AND ST(OF) PIPING 3", UNOINSTALL THERMOSTATIC MIXING VALVES,ASSE 1070 LISTED, AT EACH PUBLICHANDWASHING LAVATORY/SINK. SIZE TOMATCH HW PIPE SIZE.ROOF OVERFLOW DRAINAGE STRATEGYTO BE DETERMINED OR VIAARCHITECTURAL SCUPPERS UNOTERMINATE PLUMBING VENTS NOT LESSTHAN 12" ABOVE ROOF.AVOID ROUTING PIPING OVERELECTRICAL ROOMS OR ELECTRICALPANELS; MAINTAIN N.E.C. CLEARANCES.COORDINATE ROUTINGS WITHELECTRICAL CONTRACTOR.CONTRACTOR TO MAINTAIN 8'-6" CLEARHEAD HEIGHT IN GARAGE AND INFORMTHE ENGINEER AND ARCHITECT OF ANYAREAS THAT MAY NOT MEET 8'-6" PRIORTO INSTALLATION, MINIMUM 8'-2" CLEARHEAD HEIGHT MUST BE MAINTAINED INACCESSIBLE VEHICLE AREAS.PROVIDE FLEXIBLE PIPE CONNECTIONSTO ALL MOTORIZED EQUIPMENT.ROUTE DOMESTIC HOT WATER RECIRCTO WITHIN 10 FEET OF ALL HOT WATERFIXTURES. CONNECT WITHIN 5 FEET OF0.5 GPM AND LOWER FAUCETS.VERIFY ALL EQUIPMENT ACCESS PANELSWITH MANUFACTURER AND ARCHITECT.PROTECT PIPING ROUTED ALONGCOLUMNS, WALLS, ETC. FROM DAMAGEAS NECESSARY WITH CAGES.COORDINATE WITH ARCHITECT.PEX PIPING SHALL NOT BE ALLOWED TOPENETRATE FIRE BARRIERS WHERE FIRECAULKING IS REQUIRED.ALL VALVES SHALL BE INSTALLED ABOVEDROP-IN CEILINGS IN ACCESSIBLELOCATIONS, OR WITH ACCESS PANELS INHARD-LID CEILINGS.ALL PIPING SHALL BE ROUTED AS HIGHAS POSSIBLE IN THE CEILING SPACE.UTILIZE JOIST SPACE WHEN POSSIBLE,ESPECIALLY WHERE CROSSING OTHERPIPES, DUCTS, AND ELECTRICAL.ACCESS PANELS SHALL BE 24x24, UNOLOCATIONS SHOWN ARE APPROXIMATE,EXACT LOCATIONS SHALL BECOORDINATED WITH THE ARCHITECTSDRAWINGS AND WITH THE LOCATIONS OFTHE EQUIPMENT OR APPARATUS THATTHEY SERVE.1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.PLUMBING NOTES:FLAG NOTES:13/4" HWS/R TO RADIANT MANIFOLDABOVE.City of Aspen Received 5/2/17Building Department
ACEBD123456789STAIR201STOR202STAIR203NARTHEX204VEST205NAVE206SANCTUARY207VESTING /SACRISTY208ALTARSERVERVESTING209HWS/R, CHS/R RISERSIN WALL.RE - CONNECT SACRARIUMBASIN DRAIN TO (E) PIPINGWHICH DISCHARGES TOCRAWLSPACE.STORM/DAYLIGHT. REGULAR BASIN RE-CONNECTED TO (E) TO SANITARYWASTE.P8P72" HWS/R, 2-1/2" CHS/RUP TO AHU-2.2" HWS2" HWR2 1/2" CHS2 1/2" CHRHWSHWRCHSCHR2" HWS/R, 2-1/2" CHS/RTO AHU-1.CHRCHSHWRHWS3ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:49:00 PMP2.6SANCTUARYLEVELPLUMBINGPLANST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: 3/16" = 1'-0"SANCTUARY LEVEL PLUMBING PLANCity of Aspen Received 5/2/17Building Department
TYPICAL HANGER DIAGRAMNO SCALEANCHOR,REFER TOSTRUCTURAL.THREADEDROD.HANGER.PIPE &INSULATION.CONCRETESTRUCTURE.NOTE:ALL PIPING WITHINSULATION TO HAVEINSULATION RUN FULLSIZE THROUGHHANGER WITH SHIELDAND INSERT.CMIN. HEIGHTPER MFR.1/2"FLOORTRAP PRIMER CONNECTIONDIAGRAMNO SCALEBALL VALVE.TAKE-OFF FROMTOP OF CW PIPE.TRAP PRIMER VALVE,SIOUX CHIEF PRIMEPERFECT OR EQUAL.DISTRIBUTION UNIT(FOR MULTIPLEDRAINS).1/2" TYPE KSOFT COPPERLINE(S) TOFLOORDRAIN(S).QUANTITY ASREQUIRED. NOJOINTS BELOWGRADE.DCLEANOUT DIAGRAMSNO SCALE6"SLOPE DN @ 1/4"/L.F.WASTE LINEFINISHED GRADEADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSURE WITH ANCHORFLANGE, HEAVY DUTY TOP, AND VANDAL PROOF FASTENERS, ZURN,Z-1400-HD-KBRASS CLEANOUT PLUG W/COUNTER SUNK HEAD.ADJUSTABLE CLEANOUTAND ACCESS COVER ZURNZB-1400. TOP OF COVER TOBE FLUSH W/ TOP OF FLOOR.16" CONC. PAD TROWELSMOOTH & EDGE.1/8 C.I. BENDBALANCE OF PIPING SAMEAS CLEANOUT TO GRADE.FLOOR LINE1/8 C.I. BENDC.I. WASTE LINE.LGTH TO SUIT.1/8 BEND IF CLEANOUTOCCURS AT END OF LINE.PROVIDE FOLLOWING OPTIONS AS APPROPRIATE:1. CARPET MARKER - FOR CARPETED AREAS.2. SQUARE TOP - FOR CERAMIC TILE OR SIMILARSQUARE PATTERN FLOOR.3. FLASHING CLAMP - FOR ABOVE GRADE WATERPROOFED AREAS.FLOOR CLEANOUT (FCO)CLEANOUT TO GRADE (COTG)BWALL CLEANOUT DIAGRAMNO SCALE1'-0"MAY EXTEND AS AWASTE OR VENT.CHROME WALLCOVERAND SCREW.PLUGGED TEE WITHCLEANOUT.WALL.FLOOR LINE.1/8 C.I. BEND.BALANCE OF PIPINGSAME AS CLEANOUTTO GRADE.HTWO-WAY CLEANOUT TO GRADE DIAGRAMSNO SCALEFINISHED GRADEWASTE LINESLOPE DN @ 1/4"/L.F.6"ADJUSTABLE GRADE CLEANOUT AND ACCESSENCLOSURE WITH ANCHOR FLANGE, HEAVY DUTYTOP, AND VANDAL PROOF FASTENERS, ZURN,Z-1400-HD-KBRASS CLEANOUT PLUG W/COUNTERSUNK HEAD.24" X 16" DIA. CONC. PADTROWELSMOOTH & EDGE.C.I. WASTE LINE.LGTH TO SUIT.1/8 C.I. BENDASANITARY OR STORM BLDG.DRAIN THRU WALL DIAGRAMNO SCALESLOPE 1/4"/L.F.C.O.T.G SEE DIAGRAM.BASEMENT WALL.COORDINATE WALL OPENING SIZEWITH PIPE MATERIAL AND SIZEAND MANUFACTURERREQUIREMENTS.STORM OR SANITARYBLDG. DRAIN.LINK-SEAL OR EQUIVALENT.GRADEEFDIAGRAM & ISOMETRICDRINKING FOUNTAIN MOUNTINGNO SCALEVWV"34"ISOMETRICW1(E)(E)11"212WALLMANUFACTURER'S WALLHANGER & TRIMPLATEP-TRAPS FLATAGAINST WALLCONCEALWALL DAMAGEW/ S.S. PLATEREPLACE (E) SINGLEINLET W/ (N) DOUBLEINLET FITTINGFABRICATE 16 GA S.S.BACK-UP PLATESECURE WALL HANGERW/ THROUGH BOLTSTYPICAL PIPE SIZE CHANGEFOR WATER DIAGRAMNO SCALETOP OF PIPEPIPEPIPEINVERTED ECCENTRICREDUCER.CLCLGHWCHWCWW(E) PIPING TOKITCHEN.1 1/4" CW1" HW3/4" HWC1 1/4" CW1" HW3/4" HWCTO MECH RM.ALBUQUERQUE|AVON|DENVER|FORT COLLINS303.278.3820www˛bgbuildingworks˛comProject No. 9727.00Copyright 2016CHARLESCUNNIFFEARCHITECTS COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC610 EAST HYMAN AVE.ASPEN, CO 81611TEL: 970.925.5590FAX: 970.920.4557cunniffe.comSHEET NO.JOB NO.50% DD 10.11.16100% DD 11.14.1650% CD 12.20.16PERMIT DRAWINGS 01.12.17100% CD 02.15.17ADD-1 03.07.17ISSUE:DATE:PERMIT RESUBMIT 05.01.175/1/2017 4:49:10 PMP4.0PLUMBINGDIAGRAMSAND ISOMETRICST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE:1BASEMENT DOMESTIC, WASTE & VENTISOMETRIC1.2.NOTES:CONNECT (N) VENTS FROM FIXTURES TO(E) VENT SYSTEM, TYP.PROVIDE CLEANOUTS PER 2015 IPC.City of Aspen Received 5/2/17Building Department
LAN
LAN
AV
AV
AV
M
M
M
M
M
LA
MIC
S14/2
RS232
HDMI
R18/2
CAT6
1. INSTALLERS SHALL HOLD CURRENT CERTIFICATION
BY INFOCOMM INTERNATIONAL AS CTS AND/OR
CTS-I AND HOLD MANUFACTURER CERTIFICATIONS
FOR PRODUCTS BEING INSTALLED.
2. CONTRACTOR TO PROVIDE ALL NECESSARY
APPURTENANCES TO ENSURE A FULLY
FUNCTIONING SYSTEM.
3. CONTRACTOR TO PROVIDE WIRELESS
MICROPHONE ANTENNA EXTENSIONS AND ALL
NECESSARY APPURTENANCES TO ACHIEVE
WIRELESS COVERAGE IN THE MEETING ROOMS.
4. ALL NETWORK EQUIPMENT TO BE PROVIDED BY
OWNER UNLESS NOTED OTHERWISE.
5. CONTRACTOR SHALL PROVIDE EQUIPMENT RACK
RACKING, RACK MOUNT POWER, MOUNTING
ACCESSORIES AND VENTILATION EQUIPMENT FOR
AV SYSTEM.
6. LIGHT LINE WEIGHT INDICATES EXISTING OR OFCI
EQUIPMENT.
NOTES:
1. THE SANCTUARY AUDIOVISUAL SYSTEM CONSISTS
OF AN IP-BASED 4K VIDEO MATRIX SWITCHING
SYSTEM AND AN AUDIO SYSTEM WITH INPUTS THAT
INCLUDE AUDIO-FROM-VIDEO VIA DANTE,
LINE-LEVEL SOURCES, AND MICROPHONES.
2. THE SYSTEM INCLUDES:
2.1. TOUCH SCREENS FOR CONTROL.
2.2. AV FLOOR BOXES AND WALL PLATES WITH
HDMI INPUTS.
2.3. A BLU-RAY PLAYER.
2.4. MICROPHONES IN THE CHOIR LOFT AND ALTAR.
2.5. EXISTING 12x8 AUDIO DSP.
2.6. A DANTE BRIDGE TO TAKE AUDIO FROM VIDEO
SOURCES INTO THE DSP.
2.7. VIDEO RECEIVER ROOM BOXES TO CONTROL
PROJECTORS AND PROJECTION SCREENS.
2.8. FOLDBACK VIDEO DISPLAY AT LECTERN.
2.9. OFE PC FOR RECORDING/STREAMING.
2.10. A USB AUDIO BRIDGE TO SEND AUDIO TO THE
PC FROM THE DSP.
2.11. STEERABLE LINEAR COLUMN LOUDSPEAKERS
AND POWERED SUBWOOFERS.
2.12. DISTRIBUTED CEILING LOUDSPEAKERS.
3. THE CONTROL SYSTEM SHALL AUTOMATE
AUDIOVISUAL FUNCTIONS WITH ONE-TOUCH
COMMANDS ISSUED FROM THE TOUCH PANELS.
4. THE AV SYSTEM SHALL BE CONTROLLED VIA WALL
MOUNT TOUCH SCREEN. TOUCH SCREEN SHALL
PROVIDE THE USER THE ABILITY TO:
4.1. POWER ON/OFF ALL DEVICES W/ ONE PRESS.
4.1.1. AUDIO SYSTEM
4.1.2. PROJECTORS AND PROJECTION SCREENS.
4.1.3. VIDEO SYSTEM COMPONENTS
4.2. SWITCH VIDEO SOURCES.
4.3. ADJUST AUDIO LEVEL UP/DOWN AND MUTE.
AV SYSTEM NOTES:
FLOORBOX 1
ACE BACKSTAGE
122SLBK
FULL FLOOR POCKET
HDMI
MIC/LINE 1
MIC/LINE 2
HDMI
OUT
OUT
ROOM BOX
AURORA MULTIMEDIA
VLX-TC1-C
4K TRANCEIVER
LAN HDMI
RS232
PROJECTION SCREEN 1
DA-LITE
TENS COSMO ELECTROL 34492
130" DIAG IN-CEILING
RLY UP
RLY DOWN
PROJECTOR 1
EPSON
G7905U
4K WUXGA W/ LONG THROW LENS
HDMI
RS232
HDMI
POE SWITCH
NETGEAR
GS108PE
8-PORT POE SWITCH
LAN
LAN
LAN
LAN
LAN
LAN
LAN
LANPTZ CAMERA
VADDIO
ROBOSHOT 30-HD-SDI
VIDEO RECORDING
POE
HDMI
LS3
16Ω
2
LS3
16Ω
STAIRSTEPLOUDSPEAKERS COLUMN ARRAY
LOUDSPEAKER
RENKUS-HEINZ
IC16-R-II
POWERED COLUMN ARRAY
IN
SUBWOOFER
RENKUS-HEINZ
CF12S-5
POWERED SUBWOOFER
IN
BLU-RAY PLAYER
SONY
HDMI
HDMI
LA
LA
LA
HDMI
RS232
CAT6
TOUCH SCREEN
CONTROL PANEL
AURORA MULTIMEDIA
QXT-500
CHOIR LOFT
POE
MIC
MIC
MIC
MIC
MIC
MIC
MIC
MIC
MIC
MIC
VIDEO FOLDBACK DISPLAY
TOTEVISION
LED-709HD
7" LED/LCD MONITOR
HDMI
POE SWITCH
CISCO
WS-C2960S-24PS-L
24-PORT POE SWITCH
LAN
LAN
LAN
LAN
LAN
LAN
LAN
LAN
LAN
LAN
CAT6
HDMI
RS232
FLOORBOX 2
ACE BACKSTAGE
122SLBK
FULL FLOOR POCKET
HDMI
MIC/LINE 3
MIC/LINE 4
HDMI
OUT
OUT
FLOORBOX 3
ACE BACKSTAGE
122SLBK
FULL FLOOR POCKET
HDMI
MIC/LINE 5
MIC/LINE 6
HDMI
OUT
OUT
HDMI
HDMI
CAT6
AT AMBO / LECTERN.
HDMI
PC
EXISTING
HDMI
USB
LAN
7.5W
LS1
6
7.5W
LS1 NARTHEXS14/2
S14/2
MIC WALL PLATE 1
CUSTOM
DUAL XLR INPUT
MIC 11
MIC 12
OUT
OUT
MIC WALL PLATE 2
CUSTOM
DUAL XLR INPUT
MIC 13
MIC 14
OUT
OUT
MIC WALL PLATE 3
CUSTOM
DUAL XLR INPUT
MIC 15
MIC 16
OUT
OUT
MIC STAIR PLATE
CUSTOM
DUAL XLR INPUT
MIC 7
MIC 8
OUT
OUT
MIC STAIR PLATE
CUSTOM
DUAL XLR INPUT
MIC 9
MIC 10
OUT
OUT
CAT6
CAT6
COLUMN ARRAY
LOUDSPEAKER
RENKUS-HEINZ
IC16-R-II
POWERED COLUMN ARRAY
IN
SUBWOOFER
RENKUS-HEINZ
CF12S-5
POWERED SUBWOOFER
IN
CAT6
LS3
16Ω
2
LS3
16Ω
STAIRSTEPLOUDSPEAKERSS14/2
AMPLIFIER
CROWN
CTs 3000
EXISTING
IN1
IN2
1250W
8Ω
1250W
8Ω
AMPLIFIER
ASHLY
NX 752
POWER AMPLIFIER
IN1
IN2
75W
70V
75W
70V
LA
LA
1
1
BREAK-IN BOX
BSS
BLU-BIB
INPUT EXPANDER
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
BLU LINK
BLU LINK
AUDIO DSP
CRESTRON
BLU-100
EXISTING
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
BLU LINK
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
LAN
LA
LA
LA
LA
LA
LA
1
2
3
1
2
3
4
5
HDMI
LA
LA
LA
LA
LA
LA
ASSISTED LISTENING TX
LISTEN TECHNOLOGIES
LT-803-072
RF AUDIO TRANSMITTER
LINE IN
LA
PROJECTION SCREEN 2
DA-LITE
TENS COSMO ELECTROL 34492
130" DIAG IN-CEILING
RLY UP
RLY DOWN
BLU LINK
R18/2
R18/2
CAT6
USB INTERFACE
BSS
BLU-USB
BLU-LINK > USB
BLU LINK
BLU LINK USB
CAT6
CAT6
CAT6
PROJECTOR 2
EPSON
G7905U
4K WUXGA W/ LONG THROW LENS
HDMI
RS232
ROOM BOX
AURORA MULTIMEDIA
VLX-TC1-C
4K TRANCEIVER
LAN HDMI
RS232
WALL PLATE
AURORA MULTIMEDIA
VLX-TCW2V-C-B
4K TRANCEIVER
HDMI
HDMI
POE
HDMI
ROOM BOX
AURORA MULTIMEDIA
VLX-TC1-C
4K TRANCEIVER
HDMI POE
TOUCH SCREEN
CONTROL PANEL
AURORA MULTIMEDIA
QXT-500
ALTAR
POE LAN
TRANSCEIVER
AURORA MULTIMEDIA
VLX-TCW2V-C-B
4K TRANCEIVER
HDMI LAN
TRANSCEIVER
AURORA MULTIMEDIA
VLX-TCW2V-C-B
4K TRANCEIVER
HDMI LAN
TRANSCEIVER
AURORA MULTIMEDIA
VLX-TCW2V-C-B
4K TRANCEIVER
HDMI LAN
TRANSCEIVER
AURORA MULTIMEDIA
VLX-TCW2V-C-B
4K TRANCEIVER
HDMI LAN
CAT6
CAT6
CAT6
CAT6
ROOM BOX
AURORA MULTIMEDIA
VLX-TC1-C
4K TRANCEIVER
LAN HDMI
ROOM BOX
AURORA MULTIMEDIA
VLX-TC1-C
4K TRANCEIVER
LAN HDMI
CAT6
CAT6
CAT6
CAT6
R18/2
R18/2
USB
DANTE BRIDGE
BSS
BLU-DAN
AUDIO TRANSCEIVER
BLU-LINK
BLU-LINK
DANTE
CTRL PROCESSOR
AURORA
QXP-2
QUAD-CORE
LAN RLY 1
RLY 2
RS232
CAT6 CAT6CAT6CAT6
CAT6
CAT6 CAT6R18/2
R18/2
RS232
RS232 RS232
CAT6TO RACK SWITCH
TO RACK SWITCH LEFTRIGHTLEFTRIGHTLOCATE IN 35RU AV EQUIPMENT RACK
IN SANCTUARY. PROVIDE MIDDLE
ATLANTIC ERK-3525KD OR EQUAL.
LOCATE EQUIPMENT IN 8RU AV
EQUIPMENT RACK AT CHOIR LOFT.
PROVIDE MIDDLE ATLANTIC OBRK8
OR EQUAL.
TO RACK SWITCH
TO RACK SWITCH
TO RACK SWITCH
LINE LEVEL AUDIO
MIC LEVEL AUDIO
CONTROL (SERIAL)
SPEAKER LEVEL AUDIO (GAUGE/QTY)
PREFAB HDMI CABLE
CATEGORY 6 - 4PR UTP
CONTROL (LV RELAY; GAUGE/QTY)
TO DSP
TO DSP
TO DSP
TO DSP
TO DSP
TO DSP
FROM FLOORBOX 1
FROM FLOORBOX 1
FROM FLOORBOX 2
FROM FLOORBOX 2
FROM FLOORBOX 3
FROM FLOORBOX 3
TO BLU-USB
FROM DSP
TO BLU-BIB
FROM BLU-USBCHOIR LOFTSANCTUARYTO CTRL PROC
TO CTRL PROC
TO CTRL PROC
TO CTRL PROC
TO RACK SWITCH
PROJ
SCRN UP
PROJ
SCRN
DOWN
TO DSP
TO CTRL PROC
LINETYPE LEGEND:
ALBUQUERQUE |AVON |DENVER |FORT COLLINS
303.278.3820 www ˛bgbuildingworks ˛com
Project No. 9727.00 Copyright 2016
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
610 EAST HYMAN AVE.
ASPEN, CO 81611
TEL: 970.925.5590
FAX: 970.920.4557
cunniffe.com
SHEET NO.
JOB NO.
50% DD 10.11.16
100% DD 11.14.16
50% CD 12.20.16
PERMIT DRAWINGS 01.12.17
100% CD 02.15.17
2/10/2017 10:33:37 AMT3.0
TECHNOLOGY
FUNCTIONAL
DIAGRAMSST. MARY CATHOLIC CHURCH533 E. MAIN STREETASPEN, COLORADOSCALE: NONE1
AUDIOVISUAL FUNCTIONAL DIAGRAM -
SANCTUARY
ISSUE: DATE:
City of Aspen
Received
5/2/17
Building Department
Dan Cokley, P.E. 0029799
Project Engineer
Vicinity Map
St. Mary Catholic Church
533 Main Street
Aspen, CO 81611
Parcel #273707331801
Sheet Index
Owner / Applicant
Revision#Date By
Job #.File:
TS-01 Cover Sheet
GN-01 Legend, Notes, and Abbreviations
EX-01 Existing Conditions
CDM-01 Demolition Plan
CGE-01 Geometry Plan
CRD-01 Hunter Street Sidewalk Plan & Profile
CRD-02 Highway-82 Sidewalk Plan & Profile
CEC-01 Erosion Control Plan
CSW-01 Stormwater Management Plan
CDT-01 City of Aspen Standard Details
CDT-02 Project Details
CDT-03 Curb Ramp Cross Sections
CDT-04 Striping Plan
Permit Resub. Set
April 2017
118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
St. Mary Catholic Church
Aspen, CO
Project
Location
Site Plan
Scale: 1" = 40'
Project Contacts:
Project Engineer: Dan Cokley, 970-384-9009
Site Superintendent: Josh Miller, 970-261-5389
Safety Specialist: Stuart Dalpiaz, 970-640-7284
Traffic Control Supervisor: Dick Perkins, 970-216-8603
Erosion Control Supervisor: Josh Miller, 970-261-5389
City of Aspen Engineering: 970-920-5080
City of Aspen Electric: 970-920-5148
Gas: Black Hills Energy 970-927-0482
City of Aspen Water Department: 970-920-5110
Aspen Consolidated Sanitation District: 970-429-5415
Lot: A-I Saint Marys Catholic Church
Subdivision: City and Townsite of Aspen
Block: 93
4/17/2017
City of Aspen
Received
5/2/17
Building Department
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Legend Notes and
Abbreviations
2016.195.001
DCS
8/11/2016
DCS
Admin
XX
GN-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
Additional Abbreviations Additional Line Types & Symbols
4/17/2017
City of Aspen
Received
5/2/17
Building Department
15"4"
8"
11"
5"
5"
15"
13"
13"
17"
20"
20"
18"
6"
28"
26"
26"
30"
30"24"26"24"3"3"33"21"
8"
6"
18"
2"
2"2"4"4"3"4"
3"
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = ##'
0 #####
Existing Conditions
2016.195.001
AMC
8/11/2016
DCS
DemoPlan
XX
EX-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
15"4"8"11"5"5"15"13"13"17"20"20"18"6"28"26"26"30"30"24"26"24"3"3"33"21"8"6"18"2"2"2"4"4"3"4"3"Job No.Drawn by:Date:OfFile:PE:QC:Revision#DateByGraphic ScaleIn Feet: 1" = 15'081530Demolition Plan2016.195.001AMC/DCS8/11/2016DCSDemoPlanXXCDM-0114St. Mary Catholic ChurchAspen, COForConstruction118 West Sixth Street, Suite 200Glenwood Springs, CO 81601970.945.1004 www.sgm-inc.com 4/17/2017City of Aspen Received 5/2/17Building Department
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = 20'
0 10 20 40
Geometry Plan
2016.195.001
AMC/DCS
8/11/2016
DCS
GeometryPlan
XX
CGE-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
15"13"
13"17"
24"
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = 5'
0 3 5 10
Hunter Street Sidewalk Plan
& Profile
2016.195.001
DCS
8/11/2016
DCS
PlanProfile
XX
CRD-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
15"
13"
20"
20"
30"
30"24"26"24"3"3"33"21"
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = 10'
0 5 10 20
Highway-82 Sidewalk Plan
& Profile
2016.195.001
DCS
8/11/2016
DCS
PlanProfile
XX
CRD-02
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = 20'
0 10 20 40
Erosion Control Plan
2016.195.001
AMC/DCS
8/11/2016
DCS
ErosionControlPlan
XX
CEC-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Stormwater
Managment Plan
2016.195.001
DCS
8/11/2016
DCS
Admin
XX
CSW-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
City of Aspen
Standard Details
2016.195.001
DCS
8/11/2016
DCS
Admin
XX
CDT-01
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
Job No.Drawn by:Date:OfFile:PE:QC:Revision#DateByProject Details2016.195.001DCS8/11/2016DCSAdminXXCDT-0214St. Mary Catholic ChurchAspen, COForConstruction118 West Sixth Street, Suite 200Glenwood Springs, CO 81601970.945.1004 www.sgm-inc.com 04/17/2017City of Aspen Received 5/2/17Building Department
13"
13"
3"
15"
4"
8"
17"
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = 5'
0 2 5 10
Curb Ramp Cross Sections
2016.195.001
DCS
8/11/2016
DCS
PlanProfile
XX
CDT-03
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department
15"13"
13"17"
24"
Job No.
Drawn by:
Date:
Of
File:
PE:QC:
Revision#Date By
Graphic Scale
In Feet: 1" = 5'
0 3 5 10
Striping Plan
2016.195.001
AMC/DCS
8/11/2016
DCS
PlanProfile
XX
CDT-04
14
St. Mary Catholic Church
Aspen, CO
For
Construction 118 West Sixth Street, Suite 200
Glenwood Springs, CO 81601
970.945.1004 www.sgm-inc.com
4/17/2017
City of Aspen
Received
5/2/17
Building Department